0612DB1702

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 20

Data Bulletin 0612DB1702 03/2017

PowerPact™ P-Frame Circuit Breaker Data Sheets

What’s in This Document


PowerPact P-Frame General Information ....................................................2
PowerPact P-Frame Codes/Standards .........................................................2
PowerPact P-Frame Interrupting Ratings .....................................................3
PowerPact P-Frame Continuous Current Rating.........................................3
PowerPact P-Frame Automatic Molded Case Switches ............................4
PowerPact P-Frame Motor Circuit Protectors ..............................................5
PowerPact P-Frame Electrically-Operated Circuit Breakers .....................5
PowerPact P-Frame Application Information ...............................................6
PowerPact P-Frame Operation Ratings........................................................7
PowerPact P-Frame Trip Unit Details............................................................7
PowerPact P-Frame Trip Curves .................................................................13
PowerPact P-Frame Common Accessories ...............................................14

Schneider Electric As standards, specifications, and design change


from time to time, please ask for confirmation of
800 Federal Street the information given in this publication.
Andover, MA 01810 USA © 2017 – Schneider Electric. All rights reserved.
888-778-2733
www.schneider-electric.us
PowerPact™ P-Frame Circuit Breaker Data Sheets PowerPact P-Frame General Information

PowerPact P-Frame General Information


PowerPact™ P-frame electronic trip molded case circuit breakers are designed to
protect electrical systems from damage caused by overloads, short circuits, and
ground faults. All circuit breakers are designed to open and close a circuit by
nonautomatic means and to open the circuit automatically on a predetermined
overcurrent. Electronic trip molded case circuit breakers use an electronic trip system
to signal the circuit breaker to open automatically.
The PowerPact P-frame (1200 A frame size) circuit breakers are dual rated to UL489
and IEC 60947-2.
P-frame molded case circuit breakers are available with either a basic ET 1.0I
electronic trip system or with a more advanced Micrologic™ trip system. Electronic trip
motor circuit protectors (trip system ET 1.0M), which trip on short circuit only, and
automatic molded case switches, which trip at a predetermined self-protection level
only, are also available for special applications. All of these circuit breakers are
available labeled as Square D™ or Schneider Electric™ (formerly Merlin Gerin™,
Federal Pioneer™, or Federal Pacific™).
• Both standard (80%) and 100% rated construction circuit breakers are available in
1200 A with a sensor size range of 250–1200 A.
• Interrupting ratings (AIR):

Voltage G J K L

240 Vac 65 kA 100 kA 65 kA 125 kA


480 Vac 35 kA 65 kA 50 kA 100 kA
600 Vac 18 kA 25 kA 50 kA 25 kA

P-Frame Termination Options

F = No Lugs (Includes terminal nut kit on both ends) For factory-installed termination, place
L = Lugs both ends termination letter in the third block of the circuit
M = Lugs I/ON end, terminal nut kit O/OFF end breaker catalog number.
P = Lugs O/OFF end, terminal nut kit I/ON end
D = Drawout PGL36040U 4 1 A
A = I-Line Terminatio n Le tte r

PowerPact P-Frame Codes/Standards


P-frame electronic trip circuit breakers and switches are manufactured and tested in
accordance with the following standards:

Standards

P-Frame Circuit Breakers P-Frame Switches


UL 4891 UL 4892
IEC Standard 60947-2 IEC Standard 60947-3
CSA C22.2 No 5 CSA C22.2 No 5
Federal Specification W-C-375B/GEN Federal Specification W-C-375B/GEN
NEMA AB1 NEMA AB1
NMX J-266 NMX J-266
UTE, VDE, BS, CEI, UNE, CCC UTE, VDE, BS, CEI, UNE

Circuit breakers should be applied according to guidelines detailed in the NEC and
other local wiring codes.

1. PowerPact P-frame circuit breaker is in UL File E63335.


2. PowerPact P-frame switch is in UL File E103740.

2 0612DB1702
PowerPact P-Frame Interrupting Ratings PowerPact™ P-Frame Circuit Breaker Data Sheets

PowerPact P-Frame Interrupting Ratings


Interrupting Ratings

Ampere Rating (A) Interrupting Ratings

Circuit IEC 60947-2


Mounting Basic UL/CSA/NMX
Breaker Micrologic™
Electronic 240 Vac 380/415 Vac
Trip Units
Trip Units
240 Vac 480 Vac 600 Vac Icu Ics Icu Ics
PG 65 kA 35 kA 18 kA 50 kA 25 kA 35 kA 20 kA

Individually- PJ 600, 800, 250, 400, 600, 100 kA 65 kA 25 kA 65 kA 35 kA 50 kA 25 kA


Mounted 1000, 1200 800, 1000, 1200
PK 65 kA 50 kA 50 kA 50 kA 25 kA 50 kA 25 kA
PL 125 kA 100 kA 25 kA3 125 kA 65 kA 85 kA 45kA
PG 65 kA 35 kA 18 kA 50 kA 25 kA 35 kA 20 kA
PJ 600, 800, 250, 400, 600, 100 kA 65 kA 25 kA 65 kA 35 kA 50 kA 25 kA
I-Line™ 1000, 1200 800, 1000, 1200
PK 65 kA 50 kA 50 kA 50 kA 25 kA 50 kA 25 kA
PL 125 kA 100 kA 25 kA3 125 kA 65 kA 85 kA 45 kA

PowerPact P-Frame Continuous Current Rating


All circuit breakers marked as 100% rated can be continuously loaded to 100% of their
rating.
Because of additional heat generated when applying circuit breakers at 100% of
continuous current rating, the use of specially-designed enclosures and 90°C (194°F)
wire is required. The 90°C (194°F) wire must be sized according to the ampacity of the
75°C (167°F) wire column in the NEC. Minimum enclosure size and ventilation
specifications are indicated on the circuit breaker and in PowerPact P-Frame
Enclosure Sizes, page 6.
Circuit breakers with 100% rating can also be used in applications requiring only 80%
continuous loading.

3. Non-standard AIR.

0612DB1702 3
PowerPact™ P-Frame Circuit Breaker Data Sheets PowerPact P-Frame Automatic Molded Case Switches

PowerPact P-Frame Automatic Molded Case Switches


Automatic molded case switches are available in individually-mounted and I-Line
constructions from 600–1200 A. Automatic switches are similar in construction to
electronic trip circuit breakers except that long-time tripping is not present. The
switches open instantaneously at a non-adjustable magnetic trip point calibrated to
protect only the molded case switch itself. They must be used in conjunction with a
circuit breaker or fuse of equivalent rating.

Automatic Switch Information

Withstand Rating Trip


Circuit Ampere Voltage Catalog Point
Breaker Rating Rating Number
240 Vac 480 Vac 600 Vac (±10%)

600 600 Vac PJL36000S60 100 kA 65 kA 25 kA 10 kA

PJ 800 600 Vac PJL36000S80 100 kA 65 kA 25 kA 10 kA


2P4, 3P
1000 600 Vac PJL36000S10 100 kA 65 kA 25 kA 10 kA
1200 600 Vac PJL36000S12 100 kA 65 kA 25 kA 10 kA
600 600 Vac PKL36000S60 65 kA 50 kA 50 kA 24 kA

PK 800 600 Vac PKL36000S80 65 kA 50 kA 50 kA 24 kA


2P, 3P, 4P5
1000 600 Vac PKL36000S10 65 kA 50 kA 50 kA 24 kA
1200 600 Vac PKL36000S12 65 kA 50 kA 50 kA 24 kA
600 480 Vac PLL34000S60 125 kA 100 kA — 10 kA

PL 800 480 Vac PLL34000S80 125 kA 100 kA — 10 kA


2P, 3P —
1000 480 Vac PLL34000S10 125 kA 100 kA 10 kA
1200 480 Vac PLL34000S12 125 kA 100 kA — 10 kA

4. For 2P, replace the leading 3 in the catalog number following the prefix with a 2 (PJL36000S60 becomes PJL26000S60). Add the suffix 2 for
AC phasing (standard offer), or use 5 for CA phasing (option).
5. For 4P, replace the leading 3 in the catalog number following the prefix with a 4 (PKL36000S60 becomes PKL46000S60).

4 0612DB1702
PowerPact P-Frame Motor Circuit Protectors PowerPact™ P-Frame Circuit Breaker Data Sheets

PowerPact P-Frame Motor Circuit Protectors


Motor circuit protectors are similar in construction to thermal-magnetic circuit breakers,
but have only instantaneous trip functions provided by the ET1.0M trip unit. These
motor circuit protectors comply with NEC requirements for providing short-circuit
protection when installed as part of a listed combination controller having motor
overload protection. Interrupting ratings are determined by testing the motor circuit
protector in combination with a contactor and overload relay.
Motor circuit protectors are available in PJ and PL individually-mounted and I-Line™
construction. According to the NEC, the instantaneous trip of the motor circuit protector
may be set to a maximum of 8 to 17 times motor Full Load Amps (FLA), but a setting
as close as possible to inrush current (without nuisance tripping) results in the best
protection. The instantaneous trip pickup level is adjustable within the ranges shown
below.

Motor Circuit Protector Trip Range

Catalog Number
Ampere Rating Adjustable Trip Range
J-Interrupting—600 Vac L-Interrupting—480 Vac

600 A 1200–10,000 A PJL36060M68 PLL34060M68

800 A 1200–10,000 A PJL36080M68 PLL34080M68

1000 A 1500–10,000 A PJL36100M69 PLL34100M69

1200 A 1800–10,000 A PJL36120M70 PLL34120M70

NOTE: Continuous currents larger than the ampere rating can damage the motor
circuit protector.

PowerPact P-Frame Electrically-Operated Circuit


Breakers
Electrically-operated P-frame circuit breakers are available in I-Line and unit-mount
construction up to 1200 A and are denoted in the catalog number by an “M” suffix.
These come equipped with a two-step stored energy mechanism and come standard
with a motor assembly. These are available factory-installed only.
Motor assemblies provide on and off control from remote locations. The assemblies
contain a spring-charging motor (MCH), a shunt trip (MX) and a shunt close (XF) and
are available in standard or communicating versions. An SDE overcurrent trip switch is
also included for trip indication. When remote indication of the circuit breaker status is
required, use of a circuit breaker with an OF auxiliary switch for on-off indication.

Motors Assembly Voltage Ratings (Vn)

Voltage Type Voltage Ratings (Vn)

Vac 50/60 Hz 48, 100–130, 220–240, 380–415

Vdc 24–30, 48–60, 110–130, 200–250

0612DB1702 5
PowerPact™ P-Frame Circuit Breaker Data Sheets PowerPact P-Frame Application Information

PowerPact P-Frame Application Information


PowerPact P-Frame Voltage, Frequency and Withstand Ratings
The voltage rating is the highest voltage for the electrical system on which the circuit
breaker can be applied. The frequency rating indicates the system frequency for which
the circuit breaker is intended. The withstand rating is used to improve system
coordination by maximizing the current level at which the circuit breaker trips with no
intentional delay. The withstand rating is the level of RMS symmetrical current that a
circuit breaker can carry in a closed position for a stated period of time.

Voltage, Frequency and Withstand Ratings

Circuit Breaker Voltage Rating Frequency Rating Withstand Rating at 480 Vac6

PG, PK 600 Vac 50/60 Hz (UL and IEC) 25 kA (0.5 sec)

PJ 600 Vac 50/60 Hz (UL and IEC) 10 kA (0.5 sec)

PL 480 Vac 50/60 Hz (UL and IEC) 10 kA (0.5 sec)

PowerPact P-Frame Enclosure Sizes


All type ET electronic trip UL/IEC M-frame, P-frame and R-frame circuit breakers are
available as standard rated circuit breakers. Micrologic electronic trip UL/IEC circuit
breakers are also available in 100% rated constructions. Because the additional heat
generated when applying circuit breakers at 100% of continuous current rating, the use
of specially designed enclosures and 90°C (194°F) rated wire sized per the 75°C (167°
F) NEC chart is required.
Circuit breakers with 100% rating can also be used in applications requiring only 80%
continuous loading.

Minimum Enclosure Sizes for Fixed-Mounted Circuit Breakers

Enclosure Dimensions (h x w x d) Ventilation Area


Circuit Breaker Rating
3P Circuit Breaker 4P Circuit Breaker Top Bottom

P-Frame,
51.9 x 20.25 x 7.75 in. 51.9 x 23.01 x 7.75 in.
≤ 800 A, 100% Rated P-Frame, — —
(1318.3 x 514.4 x 196.9 mm) (1318.3 x 584.4 x 196.9 mm)
≤ 1200 A, Standard Rated

P-Frame, ≤ 1200 A, 62.25 x 23 x 14.75 in. 62.25 x 25.76 x 14.75 in. 16.5 in. 16.5 in.
100% Rated (1581.2 x 584.2 x 374.7 mm) (1581.2 x 654.2 x 374.7 mm) 10,645 mm 10,645 mm

6. A system coordination study should be done for optimum circuit breaker coordination.

6 0612DB1702
PowerPact P-Frame Operation Ratings PowerPact™ P-Frame Circuit Breaker Data Sheets

PowerPact P-Frame Operation Ratings


Temperature Re-Rating Values
To meet the requirements of the UL489 Standard, molded case circuit breakers are
designed, built and calibrated for use on 50/60 Hz ac systems in a 40°C (104°F)
ambient environment. Electronic trip circuit breakers, however, are designed to react
only to the magnitude of the current flowing through the circuit breaker and are
inherently ambient insensitive. Both UL/IEC and IEC-only circuit breakers may be
operated at temperatures between -25°C and +70°C (-13°F and 158°F). For
temperatures other than 40°C (104°F), the circuit breakers must be re-rated as shown.

Temperature Re-Rating Values

Maximum Ambient Temperature

°F 158 140 122 104 86 77 68 50 32 14 -4 -13


°C 70 60 50 40 30 25 20 10 0 -10 -3 -25
Current 0.75 0.83 0.92 1 1.07 1.11 1.14 1.21 1.27 1.33 1.39 1.42

Altitude Derating Values


Circuit breakers are suitable for use at altitudes up to 13,100 ft. (4000 m). For altitudes
higher than 6560 ft. (2000 m), circuit breakers must be derated as shown.

Altitude Derating Values Per ANSI C37.20.1

≤ 6,600 ft. 8,500 ft. 13,000 ft.


Altitude (≤ 2,000 m) (2,600 m) (3,900 m)

Voltage 1 0.95 0.8

Current 1 0.99 0.96

PowerPact P-Frame Trip Unit Details


Micrologic Electronic Trip Systems
The P-frame electronic trip circuit breakers can be equipped with the optional
Micrologic trip systems listed below:

Micrologic Trip Systems

(LSIG) Long-time +
(LS0) (LI)
(LSI) Long-time + Short-time +
Long-time + Long-time +
Short-time + Instantaneous Protection +
Model Short-time + Instantaneous
Instantaneous Protection Equipment Ground-Fault
Zero delay Protection
(UL LIsted, IEC Rated) Protection
(IEC Rated Only) (UL Listed, IEC Rated)
(UL LIsted, IEC Rated)

Micrologic Basic Trip Unit 2 3 5 —

Micrologic A Trip Unit 2.0A 3.0A 5.0A 6.0A

Micrologic P Trip Unit — — 5.0P 6.0P

Micrologic H Trip Unit — — 5.0H 6.0H

0612DB1702 7
PowerPact™ P-Frame Circuit Breaker Data Sheets PowerPact P-Frame Trip Unit Details

Micrologic™ Trip Unit Features

Micrologic Trip Unit (X = Standard Feature O = Available Option)

Feature Standard Ammeter Power Harmonics


2 3 5 2.0A 3.0A 5.0A 6.0A 5.0P 6.0P 5.0H 6.0H
Field-Installable X X X X X X X X X X X
LI X X
LS0 X X
LSI X X X X
LSIG/Ground-Fault Trip7 X X X

Ground-Fault Alarm/No Trip7,8 X X

Ground-Fault Alarm and Trip7, 8 X X

Adjustable Rating Plugs X X X X X X X X X X X

True RMS Sensing X X X X X X X X X X X

UL Listed X X X X X X X X X
Thermal Imaging X X X X X X X X X X X

Phase-Loading Bar Graph X X X X X X X X

LED for Long-Time Pick-Up X X X X X X X X X X X

LED for Trip Indication X X X X X X X X

Digital Ammeter X X X X X X X X

Zone-Selective Interlocking9 X X X X X X X

Communications O O O O X X X X
LCD Dot Matrix Display X X X X

Advanced User Interface X X X X


Protective Relay Functions X X X X

Neutral Protection1 X X X X
Contact Wear Indication X X X X
Incremental Fine Tuning of Settings X X X X

Selectable Long-Time Delay Bands X X X X

Power Measurement X X X X
Power Quality Measurements X X

Waveform Capture X X

7. 3Ø, 4W circuits require either a neutral current transformer or a 4-pole circuit breaker.
8. Requires M6C Programmable Contact Module.
9. Not available for 2.0A trip units as upstream devices.

8 0612DB1702
PowerPact P-Frame Trip Unit Details PowerPact™ P-Frame Circuit Breaker Data Sheets

Micrologic Control Wiring


Control wiring for unit-mount and I-Line construction is connected to terminals located
under the circuit breaker accessory cover. Control wiring for drawout construction is
connected to terminals located on the cradle.

Accessory Control Wiring Diagrams for Manually-Operated Circuit Breakers

Power Trip Unit Remote Operation Alarm Contacts

Tripped
Closed
Upstream Downstream

Open

Fault
N A C
5
1
2
3
4

C2
D2
N
1
2
3
1

5
2
3
4

32
34
22
24
12
14

82
84

92
94
A

MN MX
OF3 OF2 OF1 SDE SD
TripUnit
or

B
T4/F1-
M1
M2

T1/M3
T2
T3

D1

C1
F2

31

21

11

81

91
C 24 D
T1

T3
T4
T2

NOTE: All diagrams show circuit breaker in open position.

A–Do not remove factory-installed jumpers between Z3, Z4 and Z5 unless ZSI is connected.
B–Do not remove factory-installed jumper between T1 and T2 unless neutral CT is connected. Do not install jumper between T3 and T4.
C–For proper wiring of neutral CT, refer to Instruction Bulletin 48041-082-01 shipped with it.
D–24 Vdc power supply for trip unit must be separate and isolated from 24 Vdc power supply for communication modules.

0612DB1702 9
PowerPact™ P-Frame Circuit Breaker Data Sheets PowerPact P-Frame Trip Unit Details

Accessory Control Wiring for Manually-Operated P-Frame Circuit Breaker

Trip Unit Type


E1 E2 E3 E4 E5 E6 MN/MX
24 Vdc OF1 Basic A P H Connector Description
11 12 14
- + D1/C1
M1 M2 M3 F1 F2 — • • • Com: E1- Circuit breaker communication module
Z1 Z2 Z3 Z4 Z5 T1 T2 T3 T4 C3 OF2
21 22 24 E6 E1 = +24 Vdc
D2/C2 E2 = Common
VN OF3 E3 = A/Tx- D0
31 32 34
E4 = B/Tx+ D1
SD E5 = A/Rx- D0
91 92 94 E6 = B/Rx+ D1
— • • • Z Zone-selective interlocking (ZSI)
V1 Z1 = ZSI OUT signal
Z2 = ZSI OUT
V2
Z3 = ZSI IN signal |
81 Z4 = ZSI IN short-time delay
V3
82 Z5 = ZSI IN ground fault
84 — • • • T External neutral sensor
SDE
— • • • F 24 Vdc external power supply

Connector Recommended Wire Size — — • • Vn External neutral voltage takeoff

V1, V2, V3, Vn 22–16 AWG (0.3–1.5 mm2) — — • • V1, V2, V3 External phase voltage takeoff

22 AWG (0.3 mm2) MIN shielded pair cable M6C10: Q1, 6 programmable contacts
E1–E2 or twisted pair copper wires — — • • 24 Vdc external power supply required
Q2, Q3

T 22 AWG (0.3 mm2) stranded shielded cable Function Connector Description

M Refer to MDGF instructions Open/Closed circuit breaker or switch


OF position contacts
E3–E6, Q1, Q2, 22 AWG (0.3 mm2) shielded twisted pairs Auxiliary
Q3 with drain (Belden 8723 or equal)3 Contacts SD Bell alarm
OF, SD, SDE 18–16 AWG (0.8–1.5 mm2) SDE Electrical fault alarm contact

MN, MX 18–14 AWG (0.8–2.5 mm2) MN Undervoltage trip device


Remote
Operation
F Size per aux 24 Vdc power supply MX Shunt trip

Z1–Z5 22–18 AWG (0.3–0.8 mm2)

10. Optional M6C programmable contacts are supplied with flying leads.

10 0612DB1702
PowerPact P-Frame Trip Unit Details PowerPact™ P-Frame Circuit Breaker Data Sheets

Accessory Control Wiring Diagrams for P-Frame Circuit Breakers

Power Trip Unit Alarm Contacts


Remote Operation

Tripped
Closed
Upstream Downstream

Open

Fault
N A C

5
1
2
3
4
N
1
2
3
1

5
2
3
4
Open Close
A

C2
D2

32
34
22
24
12
14

82
84

92
94
A4

A2

4
TripUnit Motor Mechanism
Module
MN M OF3 OF2 OF1 SDE SD
B E
T4/F1-
M1
M2

T1/M3
T2
T3

F2

or
C 24 D
T1

T3
T4
T2

D1

C1

A1

31

21

11

81

91
NOTE: All diagrams show circuit breaker in open position.

A–Do not remove factory-installed jumpers between Z3, Z4 and Z5 unless ZSI is connected.
B–Do not remove factory-installed jumper between T1 and T2 unless neutral CT is connected. Do not install jumper between T3 and T4.
C–For proper wiring of neutral CT, refer to Instruction Bulletin 48041-082-01 shipped with it.
D–24 Vdc power supply for trip unit must be separate and isolated from 24 Vdc power supply for communication modules.
E–Motor mechanism includes opening and closing coils.

0612DB1702 11
PowerPact™ P-Frame Circuit Breaker Data Sheets PowerPact P-Frame Trip Unit Details

Control Wiring for Electrically-Operated P-Frame Circuit Breaker

Trip Unit Type


E1 E2 E3 E4 E5 E6 MN/MX
24 Vdc OF1
11 12 14 Basic A P H Connector Description
- + D1/C1
M1 M2 M3 F1 F2 Circuit breaker communication module
Z1 Z2 Z3 Z4 Z5 T1 T2 T3 T4 C3 OF2
21 22 24 E1 = +24 Vdc
D2/C2 E2 = Common
VN OF3 — • • • Com: E1-E6 E3 = A/Tx- D0
31 32 34
E4 = B/Tx+ D1
SD E5 = A/Rx- D0
91 92 94
E6 = B/Rx+ D1
Zone-selective interlocking (ZSI)
V1 Z1 = ZSI OUT signal
V2 Z2 = ZSI OUT
— • • • Z Z3 = ZSI IN signal |
81
V3 Z4 = ZSI IN short-time delay
82 Z5 = ZSI IN ground fault
84
— • • • T External neutral sensor
SDE
— • • • F 24 Vdc external power supply

Connector Recommended Wire Size — — • • Vn11 External neutral voltage takeoff

V1, V2, V3, Vn 22–16 AWG (0.3–1.5 mm2) — — • • V1, V2, V3 External phase voltage takeoff

22 AWG (0.3 mm2) MIN shielded pair cable M6C: Q1, 6 programmable contacts
E1–E2 or twisted pair copper wires — — • • 24 Vdc external power supply required
Q2, Q3

T 22 AWG (0.3 mm2) stranded shielded cable Function Connector Description

M Refer to MDGF instructions Open/Closed circuit breaker or switch


Auxiliary OF position contacts
E3–E6, Q1, 22 AWG (0.3 mm2) shielded twisted pairs Contacts
Q2, Q3 with drain (Belden 8723 or equal)3 SDE Electrical fault alarm contact

OF, SD, SDE 18–16 AWG (0.8–1.5 mm2) MN Undervoltage trip device
Remote
Operation
MN, MX 18–14 AWG (0.8–2.5 mm2) MX Shunt trip

F Size per aux 24 Vdc power supply A4 Electrical opening

Z1–Z5 22–18 AWG (0.3–0.8 mm2) Motor Mech A2 Electrical closing


Module
Power supply for control devices and
B4, A1
gear motor

11. Optional M6C and external voltage takeoff are supplied with flying leads.

12 0612DB1702
PowerPact P-Frame Trip Curves PowerPact™ P-Frame Circuit Breaker Data Sheets

PowerPact P-Frame Trip Curves


Trip curves are available on the Schneider Electric website:

http://www.digestplus-us.schneider-electric.com/additional_product_infos

0612DB1702 13
PowerPact™ P-Frame Circuit Breaker Data Sheets PowerPact P-Frame Common Accessories

PowerPact P-Frame Common Accessories


PowerPact P-frame circuit breakers can be used with a variety of internal and external
accessories to increase application versatility and meet the demands of modern
electrical distribution systems.
Circuit breaker internal accessories are available either factory installed or field
installable. They can be installed in accessory compartments behind the circuit
breaker accessory cover.
Factory-Installed Accessories
Factory-installed accessories are internally mounted by the factory. Accessories only
available factory installed cannot be removed or repaired in the field. Order factory-
installed accessories by adding the correct two-letter suffix to the standard circuit
breaker catalog number. To build a catalog number, refer to the product selector or
contact a field office.
Field-Installable Accessories
Field-installable accessories can be installed or replaced in the field without affecting
the circuit breaker ratings. Field-installable accessories are shipped separately from
the circuit breakers. Install and wire field-installable accessories according to the
instructions supplied with the circuit breaker and particular accessory. Order field-
installable accessories by the catalog number found in the Schneider Electric Digest.

PowerPact P-Frame Control Wiring


Control wiring is connected to terminals located under the circuit breaker accessory
cover.
NOTE: All diagrams show circuit breaker in open position.

Accessory Control Wiring Diagrams

Function Connector Description Remote Operation Alarm Contacts

Open/Closed Circuit Breaker


OF

Tripped
Auxiliary Position Contacts
Closed
Open

Fault
Contacts
SD Bell Alarm

MN Undervoltage Trip Device


Remote
C2

Operation
D2

MX Shunt Trip
32
34
22
24
12
14

82
84

92
94

OF1
MN/MX 11 12 14

D1/C1 MN MX OF3 OF2 OF1 SDE SD


OF2
21 22 24
D2/C2
OF3 or
31 32 34

SD
91 92 94
D1

C1

31

21

11

81

91

81
82

84
SDE

14 0612DB1702
PowerPact P-Frame Common Accessories PowerPact™ P-Frame Circuit Breaker Data Sheets

Shunt Trip and Shunt Close Characteristics

Characteristics MX1 XF Min Max


24 Vac 17 Vac 26 Vac
48 Vac 34 Vac 52 Vac
120 Vac 60 Vac 132 Vac
Vac
240 Vac 168 Vac 264 Vac
50/60 Hz
277 Vac 194 Vac 304 Vac
380 Vac 266 Vac 418 Vac
Voltage Ratings (Vn)
480 Vac 336 Vac 528 Vac
12 Vdc 8 Vdc 13 Vdc
24 Vdc 17 Vdc 26 Vdc
Vdc 48 Vdc 34 Vdc 52 Vdc
125 Vdc 88 Vdc 137 Vdc
250 Vdc 175 Vdc 275 Vdc
Operating Threshold 0.7 to 1.1 Vn 0.85 to 1.1 Vn

Power Consumption (VA or W) Steady-State/Inrush 4.5/200

70 ms ±10 (NW ≤ 4000


A)
Circuit Breaker Response Time at Vn 50 ms ±10 80 ms ±10 (NW > 4000
A)
55 ms (NT)

Undervoltage Trip Characteristics

Characteristics MN
24 Vac
48 Vac
120 Vac
Vac
240 Vac
50/60 Hz
277 Vac
380 Vac
Voltage Ratings (Vn)
480 Vac
12 Vdc
24 Vdc
Vdc 48 Vdc
125 Vdc
250 Vdc
Power Consumption (VA or W) Constant/Inrush 4.5/200

Opening 0.35 to 0.70 Vn


Operating Threshold
Closing 0.35 Vn

Circuit Breaker Response Time at Vn 90 ms ±5

0612DB1702 15
PowerPact™ P-Frame Circuit Breaker Data Sheets PowerPact P-Frame Common Accessories

PowerPact P-Frame Accessories


Manually-Operated Circuit Breakers Electrically Operated Circuit Breakers
Accessory
(Y = Yes , N = No, N/A = Not Available
Field Installable Factory Installed Field Installable Factory Installed

Shunt Trip (MX) Y Y Y Y

Undervoltage Trip (MN) Y Y Y Y

Adjustable Time Delay Module for Undervoltage Trip Y N Y N

Auxiliary Switch (OF) Y Y Y Y

Alarm Switch (SD) Y Y N/A N/A

Overcurrent Trip Switch (SDE) Y Y Y Y

Spring-Charging Motor N/A N/A Y Y

Trip Unit Replacement Covers Y N Y N

Neutral Current Transformer Y N Y N


Ground-Fault Interface Module Y Y Y Y
External Sensor for SGR or MDGF Protection Y Y Y Y
Sensor Plugs Y Y Y Y

Rating Plugs Y Y Y Y

M2C and M6C Programmable Contacts Y Y Y Y

Circuit Breaker Communication Module Y Y Y Y


Restraint Interface Module Y N Y N
External Power Supply Module Y Y Y Y

External Battery Backup Module Y Y Y Y

Hand-Held Test Kit Y Y Y Y


Full-Function Test Kit Y Y Y Y
Mechanical Lug Y Y Y Y

Compression Lug Y Y Y Y

Terminal Pad Y Y Y Y
I-Line Jaws N Y N Y
Power Distribution Connectors Y Y Y Y
Control Wire Terminations Y Y Y Y
Phase Barriers Y N Y N
Electric Joint Compound Y N Y N

Door-Mounted Operating Mechanism Y Y Y Y

Rotary Handle N Y N/A N/A

Replacement Handles Y Y Y Y

Long Handle Extension Y Y N/A N/A

Accessory Cover Door Escutcheons Y N Y N

Padlock Attachment Y Y Y Y
Keylock N Y N Y

Keylock Provision N Y N Y

Sub-Feed Lugs Y Y Y Y

16 0612DB1702
PowerPact P-Frame Common Accessories PowerPact™ P-Frame Circuit Breaker Data Sheets

PowerPact P-Frame External Accessories


Phase Barriers
Phase Barriers
Phase barriers are available for unit-mount circuit breakers with bus connections or
with lugs ≤ 800 A.

Phase Barriers

Cat. No. Qty Per Kit

S33646 3

Electric Joint Compound


I-Line circuit breakers, I-Line busway plug-on units and I-Line panelboards and
switchboards are supplied with factory-applied joint compound on the plug-on
connectors. The compound is especially formulated for I-Line connections and
contributes to the overall performance of the connection.
If the joint compound is removed, it must be reapplied. A two-ounce container of the
compound (Cat. No. PJC7201) is available.

PowerPact P-Frame Handle Extension


Handle extensions are available for P-frame circuit breakers. Order catalog number
33195.

PowerPact P-Frame Replacement Handles


Replacement toggle handle extensions, including an optional longer handle extension,
are available for P-frame circuit breakers.

Replacement Handles for PowerPact P-Frame Circuit Breakers

Description Field-Installed Cat. No.

Standard Short S46998


Long S46996

0612DB1702 17
PowerPact™ P-Frame Circuit Breaker Data Sheets PowerPact P-Frame Common Accessories

PowerPact P-Frame Door Mounted Operating Mechanisms


Door-mounted operating mechanisms are available for P-frame circuit breakers. The
Type L door-mounted variable-depth operating mechanism feature heavy-duty, all-
metal constructions. They can be padlocked in the OFF position when the enclosure
door is open. Handle assemblies can be locked OFF with up to three padlocks, which
also locks the door closed. Complete kits include a handle assembly, operating
mechanism, and shaft assembly, and are rated for NEMA Type 1, 3R and 12
enclosures. A door drilling template is supplied for ease of installation.

Shaft Mounting
Description Handle Assembly12 Cat. No.
Depth

7.2–11.625 in.
Painted, 8 inch LW1
(182–295 mm)
Circuit Breaker Type L
Mechanism 7.2–22.25 in.
Painted, 8 inch LW4
(182–565 mm)

Type 3, 4 Painted, 8 inch LHP48


Handle 7.2–11.625 in.
Assembly13 (182–295 mm)
Type 3, 4, 4X Chrome Plated, 8 inch LCP48

Handle Assembly Painted, 8 inch — SLHP8

Operating
— — LW7
Mechanism
Replacement
Parts 7.2–11.625 in.
Standard Shaft — (182–295 mm) LS8

7.2–22.25 in.
Long Shaft — LS10
(182–565 mm)

PowerPact P-Frame Flexible Cable Mechanisms


Flexible cable mechanisms are for use with Class 9422 handle operators specially
designed for tall, deep enclosures where placement flexibility is required.

Cable Mechanism
Flexible Cable
No of Poles Frame Size
Mechanism Length Type

48 in. CMP40
9422CSJ30 3 1200 A 50 in. CMP50
120 in. CMP10

PowerPact P-Frame Door Escutcheons


Accessory cover door escutcheons are available for all M-frame circuit breakers.

Door Escutcheons for P-Frame Circuit Breakers

Description Field-Installed Cat. No.

Accessory Cover S33718

Toggle Handle S33717

12. Painted handles are painted flat black, with the base ring silver.
13. Due to gasketing, NEMA 3 and 4 handle assemblies are NOT trip indicating.

18 0612DB1702
PowerPact P-Frame Common Accessories PowerPact™ P-Frame Circuit Breaker Data Sheets

PowerPact P-Frame Locking Accessories


Locks and Interlocking

Description Factory- Field-


Device
Installed Installed
Cat. No. Suffix Cat. No.
Removable (Lock Off Only) — S44936
Handle
Padlocking Fixed (Lock Off or On) YP S32631
Device
Fixed (Lock Off Only) YQ MPRPAF

Interlocking
(Not UL Mechanical for Circuit Breakers with Rotary Handles14 — S33890
listed)

Provision Only, Vertical Mount,


1 key interlock including padlock provision, Kirk JE1 —
open position only

Provision Only, Vertical Mount, 1 or 2 Locks Kirk JA —

Provision Only, Horizontal Mount Kirk JK —

1 Lock Ronis JB —

Provision and 1 Lock, Vertical Mount Kirk JG —

Kirk JL —
Key Locking Provision and 1 Lock, Horizontal Mount Ronis JC —

Profalux JF —

Provision and 2 Locks Keyed Alike, Vertical


Kirk JN —
Mount
Provision and 2 Locks Keyed Alike,
Kirk — —
Horizontal Mount
Provision and 2 Locks Keyed Differently,
Kirk JP —
Vertical Mount
Provision and 2 Locks Keyed Differently,
Kirk — —
Horizontal Mount

14. Not available on motor-operated or I-Line circuit breakers.

0612DB1702 19
PowerPact™ P-Frame Circuit Breaker Data Sheets PowerPact P-Frame Common Accessories

PowerPact P-Frame Sub-Feed Lugs


Sub-feed lug kits are UL Listed for use on Listed equipment. They have plug-on jaw
construction and plug on to the I-Line bus stack in the same manner as branch circuit
breakers. Lugs on these devices accommodate the same wire sizes as the equivalent
ampere rated circuit breakers.

I-Line Sub-Feed Lug Kit Terminations

Lug
Plug-On Mounting Ampere
Lug Kit Poles Height Rating Conductors
Cat. No. Catalog No. Wire Size Per Lug

3/0 AWG–500 kcmil


SL800M5 3 800 A — (95–240 mm2) 3

3/0 AWG–500 kcmil


SL1200P5 3 1200 A — (95–240 mm2) 4

350–600 kcmil
SL1200P6 3 1200 A — (185–300 mm2) 3

3/0 AWG–750 kcmil


SL1200P7 3 1200 A — (95–400 mm2) 2

3/0 AWG–500 kcmil


S33931 3 9 in. 1200 A AL1200P24K (95–240 mm2) 4

3/0 AWG–600 kcmil


S33930 3 15 in. 1200 A AL1200R53K (95–300 mm2) 4

20 0612DB1702