INTRODUCTION
This is the report of visual inspection that was conducted on the structural components of the
residential house as described below.
In response to Grace Ojil (client) request, the team on the 30th of March, 2022, undertook an
assessment by Visual inspection only on this building. This document reports on the
structural integrity assessment of the facility is based on Physical Observations conducted on
the building. The analysis, however, does not include any gravity and lateral loads Analysis
or tests
The structure which is analyzed and assessed is a two-storey load bearing natural masonry
building with solid RCC first flor slab on its top. The structure has been strengthened with
different vertical and horizontal RC beams and columns so as to improve the gravity loads
performance of the structure.
Based on the visual inspection carried out, the building is primarily designed as a residential
apartment. This means the suspended floor is expected to serve mainly as bedrooms.
kitchens, living rooms and bathrooms. At the time of this investigation, the building was
loaded since it had occupants in it and it is partially under repairs which are yet to be fully
completed.
There is indication of alteration to the building structure at the garage space which deviates
from its initial intended purpose to a room area as a residential apartment. The other
alteration to the building structure is at the living room front section load bearing walls is
temporarily removed to allow for foundation repairs.
~ 3 out of 16 ~
PURPOSE AND SCOPE
The main purpose of this structural condition assessment is to observe and note down
the items of distress or design deficiency and the method of construction,
Utmost effort has been utilized in this respect to become as much objective possible in
observing, visualizing, analyzing, interpreting, evaluating and assessing, instead of
being subjective. A checklist based field data sheet, as being prepared by MERGE
ASSOCIATES LIMITED. personnel from their previous experience in this field, is
fully utilized in order to optimize the outcome of the field inspection phase in this
regard.
The objective of this report is to check the building whether they are technically fit for
operating as residential building or not according to the Building Codes & other
required codes.
~ 4 out of 16 ~
AVAILABLE BUILDING AND SUBSURFACE INFORMATION
~ 5 out of 16 ~
CLIENT INFORMATION/HISTORICAL DATA
~ 6 out of 16 ~
VISUAL INSPECTION/PHYSICAL OBSERVATIONS
Established upon the physical observations made during this inspection, the following
items were noted:
~ 7 out of 16 ~
Evidence of structural cracks in the northeast bedroom balcony exhibiting
walls and columns dethatched from each other. Visible damage between the
guard rails from their support structures.
All other rooms located at the rear section of the house are in good shape
because of non-structural cracks observed on them.
~ 8 out of 16 ~
RECOMMENDATIONS
Visual inspection is required for proper assessment and analysis on the effect of the
current construction on the existing structure. The Site visit is in order so that
appropriate survey can be conducted to determine the structural characteristics of the
existing building through
Modeling of the existing building using the data for the residential Building.
Structural analysis of the modeled building.
Reinforced concrete design of the structural elements considering STAAD
results.
Compare the obtained & existing design of structural elements of the
residential building.
Recommend whether buildings are settlement safer or not for the building
uses.
Availability of the architectural drawings, structural drawings and technical
specifications of the building structural layout plans from the building owner will
assist the structural engineers to:
Understand the structural system and layout of the building;
Identify critical areas for inspection;
Identify the allowable imposed loads, in order to assess the usage and
possibility of overloading; and
Verify if unauthorized addition or alteration works that affect the structure of
the building have been carried out
Hence, it is concluded that the existing building is use as a residential Building is Non
Engineered Building based on the requirements of Building Codes, construction
quality and architectural design. Retrofitting is recommended for the building.
After the analysis of the residential building, we conclude that the existing building
has no sufficient capacity to resist additional force during the construction activities.
So the retrofitting works are essential to this building during the repair of the
foundations.
~ 9 out of 16 ~
The structure may have experience differential settlement between its foundation
systems underground due to the high shrink/swell potentials because of the high
percentage of expansive clays present. This type of soil is known to be one of the
most expansive clay soils so classified in the area.
The stairs and landings leading to the upper stories of the structure appear to be
performing their intended functions. The stair step geometry generally appears to be
within the allowable amounts and there were no excessive height changes in the steps.
The existence of the diagonal crack on the ground floor, in our opinion, is more of a
function of the foundation movement due to frequent swell and shrink of the clay soil
below the structure. This should immediately be resolved.
Lack of proper support of the props at the top and bottom may lead to collapse of the
slab – beam, this issue is critical to the safety of the house. It is an important safety
consideration for the occupants. Therefore, the quality of repair workmanship
exhibited on the site is quite non satisfactory with poor support systems.
Existence of cracks repair at the walls is an indication of continuous renovation of the
persistence problem overtime. Also, cyclic excavation of the foundation can decrease
masonry strength considerably. It is worth mentioning that for initiation and
propagation of cracks due to settlement of the foundation and excavation.
RECOMMENDED TESTS
The aim of these tests are to show that the structural integrity of the structure and
foundation to carry loads of the two-floor house is adequate:
a) Scan tests
The purpose of this test is to determine the bar size, bar spacing and bar
cover in order to ascertain the serviceability and ultimate limit state
confirming to the designed characteristic compressive strength and steel
reinforcement amount if they are adequate. Since no drawings are available,
and some honeycombing has been observed, we would need to know the as-
built condition of the structure and the location and quantity of the
reinforcement which will help in the evaluation of the structure strength and
capacity.
b) Rebound hammer
~ 10 out of 16 ~
To assess the capacity of the structure, the material properties of the relevant
elements must be known. Since the client has not provided any drawings or
project documentation, a way to determine the mechanical properties of the
elements is necessary. The Elcometer concrete rebound (Schmidt) hammer
test is a recognized non-destructive test to assess the homogeneity and
integrity of concrete strength.
Characteristic compressive strength for concrete is the ability of material or
structure to carry the loads on its surface without any crack or deflection.
This ability is highly required to be analyzed whether external loading is
properly applied to be resisted by internal load involving by compressive
strength of concrete member in combination with steel reinforcement.
Rebound hammer test establish the current the compressive strength of the
structure.
c) Trial pits
To determine the depth of exaction and soil characteristics.
d) Soil tests
There are no information regarding geotechnical perimeters to be utilized for
assessments of ultimate limit state and serviceability limit state based on
codes of practices. But, the foundation is evidently thought to be constructed
on black cotton soil layer. Soil tests are necessary to affirm the condition of
the supporting ground.
e) Soil bearing capacity
The ground conditions are postulated by visual inspection and experience of
the structural engineers. No geotechnical tests were carried out on the site
hence a conservative soil bearing capacity tests should be carried out.
~ 11 out of 16 ~
CONCLUSION
Proper inspection and the recommended tests as indicated in the report of the existing
components can help reduce the possibility of structural failures.
Overall, this house is in not in good shape because of the unfinished repair works and
partially incomplete prop support system.
Based upon the observations made during this inspection, it is our opinion that the
following structural components of the residence either defective in performance or
are in need of attention.
~ 12 out of 16 ~
d) During construction, the contractor shall be responsible for maintaining
the structure in a stable condition and ensuring no part shall be
damaged under construction activities.