Load List - OCDR - Intake
Load List - OCDR - Intake
EXECUTION OF MEGA PWS TO ALL VILLAGES OF ATHAGARH BLOCK & TIGIRIA BLOCK AND 07 GP'S OF BANKI BLOCK OF CUTTACK DISTRICT DOCUMENT NO. DATE
PROJECT
INCLUDING FIVE YEARS OPERATION & MAINTENANCE UNDER ONE PACKAGE 10-03-2023
PREPARED CHECKED APPROVED SHEET 1 OF 1
SUBJECT LOAD LIST - INTAKE
SK SGS SGS REV 0
TOTAL
EQUIPMENT VOLTAGE DUTY POINT WORKING STAND BY WORKING EFFICIENCY POWER LOAD KW
SL NO DESCRIPTION TYPE OF LOAD QUANTITY
RATING(KW) (v)ph (Bkw) (NOS) (NOS) LOAD(KW) (%) FACTOR (KVAR) (INPUT SIDE)
(NOS)
F= C * TAN
A B C=A*B D E G=C/D
(COS‐1 E)
A RAW WATER PUMPS
1 VT Pump-802.78 m3/Hr @43 m C 160 415V/3ph 134.38 2 2 4 268.76 95.00% 0.82 187.60 282.91
LOAD KW EFFICIENCY
KVAR PF
(KW) (INPUT SIDE) %
LOAD DESCRIPTION
E=COS
X Y Z M=X/Y
(TAN-1(Z/X))
RAW WATER PUMPS (L1) 268.76 282.91 187.60 95% 0.82
Total continous Load(Except Raw Water Pump)
3.95 4.69 2.92 84% 0.85
(L2)
Total intermittent Load (L3) 10.09 12.07 7.45 84% 0.85
Auxiliary load (L2+L3*0.4) 7.99 9.52 5.90 83.9% 0.85
Total load (L1+L2+L3*0.4) 276.75 292.42 193.50 87.6% 0.83
Connected Load 748.98 KW C Continuous Load
I Intermittent Load
Maximum Deamand 292.42 KW
*Note: 1. Efficiency & Starting power factor of motors is as per motor catalogue.
2. The loads mentioned in this list is based on the catalogue of manufacturers. There may be a variation of +/‐ 5% after finalization of manufacturer.
3. Type of Load : "C" for Continuous & "I" for Intermediate.