1. Total Load:
Floor area of the x Volt-Ampere/sq. meter = Volt-ampere
Building (based on PEC table 2.20.23)
81 sq. meter x 24 VA/sq. meter = 1,944 Volt-Ampere
4. Service Equipment:
a. Maximum Current Rating of Protection Device, with:
1. Non-time Delay Fuse.
= 3000 VA +1,218 VA + 300% (1,840 VA) ÷ 230 V = 42 Amperes
2. Inverse Time Circuit Breaker
= 3000 VA +1,218 VA + 250% (1,840 VA) ÷ 230 V = 38 Amperes
Use 60AT/100AF or 70AT/100AF 2-pole, 250 volts.
Molded Case Circuit Breaker.
5. Daigram: