OPERATION INSTRUCTION TIME SETTING: In the thermostat on states press and for 5 seconds,

VALVE CONTROL : Thermostat acquires the room temperature via its integrated the time area will be flashing, press to select minutes, hours or week,
sensor and maintains the set-point by ON-OFF/modulating output. then press or to adjust the relevant time, press to confirm.
CAPACITIVE TOUCH SERIES
POWER ON OR OFF : TO SELECT MANUAL AND PROGRAMMABLE : In the thermostat ON status, Press
MODEL status. and hold and for more than 5 seconds, the icon of or will be flashing,
INCREASE / DECREASE : In the ON state, press UP or DOWN to increase or press to select manual or programmable and press to confirm.
TX1000EC220-V2 TX1000EC024-V2
decrease the setting parameters.
ADJUSTING OF WEEKLY PROGRAMMABLE : After selected programmable mode,
TX1000EC220-V2M TX1000EC024-V2M HEAT/COOL/VENT : Pressing the MODE button to select heat cool or press for more than 5 seconds enter into program schedule setting then press
ventilation mode. to select setting item of periods, time and temp. Press or to adjust the
APPLICATIONS TEMPERATURE DISPLAY : Temperature display mode can be changed via ISU mode relevant value, press to confirm. The program schedule is a weekly (7days) cycle,
the temperature display mode available for set-point display only, room temperature display it can be selected for 5+2 days, 6+1 days or 7 days. 5+2 is 5 workdays plus 2 days
TX1000 Series is touch pad thermostat with many variants suitable for only, and both room temperature and set-point are displayed. Default is both room temperature holiday a week, 6+1 is for 6 workdays plus 1 day holiday a week, 7 is for 7 workdays
and set-point are displayed.
2-pipe cooling & heating fan coil units and EC motor units. Available in a week. There’s 6 periods for workdays and 2 periods for holidays.
FAN OPERATION : Fan operation available for manual mode and automatic
basic standalone and Modbus communication variants. 3-speed mode and the fan control types can be configured as Ao = Automatic Setting sequence when enter program setting
fan only, CO = Constant (Manual) fan only, BO= Both auto &manual in ISU code #3 Workdays 1st period time adjusting -> temperature adjusting -> 2nd period time
SPECIFICATION In Automatic 3-Speed mode : The fan will be switched upon the differences between adjusting -> temperature adjusting……6th period time adjusting -> temperature
adjusting -> holidays 1st period time adjusting -> temperature adjusting -> 2nd
♦ Power Supply: 85-240VAC / 24VAC• Frequency: 50~60Hz room temperature and the set-point as per following logic :
period time adjusting -> temperature adjusting
In the Cooling Mode :
♦ Function: Cooling/Heating, Valve Control : When the room temperature is 2.5˚C/5˚F higher than set point, the fan will be switched to Auto high. Note : 1. The single period can be switched off by turning off the temperature setting
ON-OFF output for 220VAC and 0-10VDC Modulating for 24VAC When the room temperature is 1.5˚C/3˚F higher than set-point, the fan will be switched to Auto medium.
by pressing POWER button, Modbus 40005 will show 00260.
2. The time adjusting 1-6 periods of working days & 1-2 periods of holiday should be
♦ Relay Life: 220±10% VAC, 3(5)A, 100,000 times When the room temperature is 1 ˚C/1˚F higher than set-point, the fan will be switched to Auto low.
moved like clockwise (counterclockwise setting is not available, Example : 00:00 am
♦ Wiring Max: 16AWG In the Heating Mode : is not available on 6th period )
When the room temperature is 2.5˚C/5˚F lower than set point, the fan will be switched to Auto high. 3. In the weekly programmable setting, the parameters of cooling mode and heating
♦ Sensing Element: 10K(@25°C) NTC When the room temperature is 1.5˚C/3˚F lower than set-point, the fan will be switched to Auto medium. mode can be set seperately. If the thermostat enters into programmable mode in
♦ Display Accuracy: 0.5°C, Set-point accuracy: 0.5°C/step When the room temperature is 1 ˚C/1˚F lower than set-point, the fan will be switched to Auto low. cooling mode states, the period time and temperature are set for cooling mode.
Deadzone temperature is 0.5˚C / 1 ˚F
If the thermostat enters into programmable mode in heating mode states, the period
♦ Set-point range: 10-32°C(50-90°F) • Display range: 0-50°C time and temperature are set for heating mode.
If ISU code #3 is set to AO ( Automatic mode only ),the fan speed will be switched upon the differences 4. If the Energy saving mode is activated during programmable mode by button press
♦ Protection Glass: IP 20 • Operation Temperature: -18~49°C of room temperature &setpoint only,it can not change the fan speed by pressing FAN button. , the thermostat will keep running as per the energy saving mode settings, press POWER
♦ Shipping Temperature: -35~65°C • Suitable System: 2-pipe If ISU code #3 is set to CO (Manual mode only ) , the fan can be switched to the selected button to stop energy saving mode.
FCU cooling&heating, ON-OFF/Modulating speed via control output Fh,Fm, FI by pressing FAN button.
If ISU code #3 is set BO (both Manual and automatic mode), the fan can be switched to manual
♦ Suitable Valve: 2-line/3-line valve • Relative Humidity: 10~90% FRI FRI

high, medium and low speed or automatic 3-speed by pressing FAN button.
♦ Installed on 75mm x 75mm box TEMPORARY MODE : When thermostat is working under program schedule, the set-point
can be changed by pressing UP or DOWN buttons. will be displayed.
LCD DISPLAY & KEYS DESCRIPTION The different applications include cool only, heat only and manual heat/cool changeover.
The temporary mode will not be stopped until next period starts.
Rea l Time C l ock Cooling Heating & Ventilation ADJUSTING OF WEEKLY ADJUSTING OF WEEKLY
KEY LOCK : The default status of “Key lock” is all buttons available and it can be changed PROGRAMMABLE IN COOLING MODE PROGRAMMABLE IN HEATING MODE
in ISU mode. Key lock function includes the following settings: All buttons are available PERIODS SYMPOLS DEFAULT TIME
DEFAULT TEMP. DEFAULT TEMP.
COOLING MODE HEATING MODE SYMPOLS DESCRIPTION
(Default) Mode button is locked out. Fan and Mode button are locked out. All buttons
are locked. 1 06:00AM 26 C 18 C 1 ST PERIOD, WAKE UP
2 08:00AM 26 C 18 C 2 ND PERIOD , LEAVE
Weekdays FRI Periods ENERGY SAVING MODE : A dry contact(such as hotel key card) or button press(By WORKDAYS 3 11:30AM 26 C 18 C 3 RD PERIOD,
Room Temp. Program/Manual Mode pressing MODE button for 3 seconds can activate the energy saving mode with
Key lock 4 12:30PM 26 C 18 C BACK FOR LUNCH
Set Temp. icon appearing on the screen). The dry contact can be selected as normal open or
normal close in ISU code#5. 5 17:00PM 26 C 18 C 4 TH PERIOD, LEAVE
Key Card Valve Open/Modbus ID If activated by dry contact, all buttons will be locked except the multi-key for ISU, if 6 22:00PM 26 C 18 C 5 TH PERIOD,
Fan Speed activated by button press, press POWER button can stop energy saving mode. 1 08:00AM 26 C 18 C BACK FOR DINNER
If energy saving mode is activated, the set-point will be changed to remote setback WEEKEND
2 23:00PM 26 C 18 C 6 TH PERIOD, SLEEP
heating set-point and cooling set-point in ISU code#8&9 or via remote BMS Modbus
points. For heating mode, the range of remote setback heating set-point is from 10˚C IN PROGRAMMABLE MODE, SET -POINT PERIODS
to 21 ˚C and default value is 18˚C .The value can be changed with step of 0.5 ˚C. AND TIME COULD BE ADJUSTED DESCRIPTION
Mode Fan Power Up Down
For cooling mode, the range of remote setback cooling set-point is from 22 ˚C to 32 ˚C
SETUP FUNCTION SETTINGS AND OPTIONS
FUNCTION and default value is 26 ˚C. The value can be changed with step of 0.5 ˚C.
The memory function will not keep energy saving mode, when thermostat power cut-off a. Press and key for 5 seconds to enter ISU setting mode, the ISU code will
7 Days 6 Periods and re-powered on, the energy saving mode will be cancelled. be flashing.
2-pipe FCU cooling&heating,
ON-OFF/0-10VDC Modulating Programmable Function FREEZE PROTECTION MODE: Freeze protection can be disable(default) or enabled b. Press or to select the setting items from 1 - 31
Key Pad Lock via ISU mode. If freeze protection is enabled (it is not available in cooling only c. Press and the values of selected item will be flashing with icon on,
3 Speed Fan + Auto Fan Control application) and thermostat is in OFF mode while the room temperature is below 6 Press and revise the values of the setting items, press to confirm.
Both Room temperature and °C , the thermostat will open heating device until the temperature rises to 8 °C.
Energy Saving Mode and Comfort If you want to revise the other setting items, please repeat above step b. and c. while
set-point are displayed RS-485 ID SETTING : When ISU mode code #10 is set to ON, in the thermostat OFF
Mode Settings (Temperature display mode status, press MODE and DOWN together for 5 seconds, the ID number will setting, press to exit, the setting items and values are as below form shown.
can be changed via ISU) be flashing, you can press UP or DOWN to adjust the ID range from 1-64.
ECV2_VN0121
ISU OF: USER SETTING WILL BE KEPT, BUT ONCE RE-ELECTRIFIED NO TERMINALS DESCRIPTION
DESCRIPTION POSSIBLE OPTIONS THE THERMOSTAT WILL BE IN OFF STATES AND WHEN THE
CODE
THERMOSTAT TURNS ON AGAIN, IT WILL RUN AS PER THE L
SETTINGS BEFORE POWER CUT-OFF. 1 LIVE LINE IN
0 HEAT + VENTILATION CHANGEOVER ON/OFF MEMORY
19 SU: USER SETTING WILL BE KEPT, ONCE RE-ELECTRIFIED,
1 SYSTEM TYPE 1 COOL + VENTILATION CHANGEOVER SETTING THE THERMOSTAT WILL BE RUN AS PER THE STATES BEFORE 2
2 TWO PIPES 1H1C (HEAT,COOL&VENTILATION POWER CUT-OFF (DEFAULT IS SU)
3 AO ANALOG OUTPUT 0-10V FOR FAN
CHANGEOVER) DEFAULT 2 10-60 SECONDS(DEFAULT 30 SEC.,USER CAN ADJUST
20 BACK-LIGHT SETTINGS
F : °F B ACK-LIGHT TIME ACCORDING TO ACTUALDEMANDS) 4
2 TEMPERATURE UNIT C : ° C(DEFAULT) ON: ON, THE VALVE OPEN VALUE WILL BE DISPLAYED ON LCD 5 NO VALVE OPEN
AO : AUTO ONLY VALVE OPEN (ONLY AVAILABLE FOR MODULATING TYPE THERMOSTAT)
21 6 NC VALVE CLOSE
3 FAN CONTROL TYPE CO : CONSTANT(MANUAL) ONLY PERCENTAGE OF: OFF, THE VALVE OPEN VALUE WILL NOT BE DISPLAYED
BO : BOTH(DEFAULT) ON THE LCD, DEFAULT IS OF 7 N NEUTRAL LINE IN
22 LOW SPEED FAN SETTINGS SETTING RANGE: 0.5V-3V (O.5V PER STEP), DEFAULT IS 2V
0: ALL BUTTON S ARE AVAILABLE (DEFAULT)
1 : MODE BUTTON IS LOCKED OUT 23 MEDIUM SPEED FAN SETTINGS SETTING RANGE: 3.5V-7V(0.5V PER STEP), DEFAULT IS 5V 8 COM COM FOR UI
4 KEYPAD LOCK OUT 2: FAN AND MODE BUTTONS ARE LOCKED OUT
24 HIGH SPEED FAN SETTINGS SETTING RANGE: 7.5V-10V(0.5V PER STEP), DEFAULT IS 10V
3: ALL BUTTONS ARE LOCKED 9 UI RS (EXTERNAL SENSOR)&KC(KEY CARD)
NO : HOTEL CARD NO
480=4800, 960=9600, 192=19200, 384=38400,
BAUD RATE 576=57600, 115=115200 (DEFAULT:960)
REMOTE SETBACK 25 SELECTION
5 NC : HOTEL CARD NC AFTER CHANGED THE BAUD RATE, PLEASE CUT-OFF POWER AC24V
ENABLE METHOD AC24V
BU : BUTTON (DEFAULT) AND RE-ELECTRIFIED THE THERMOSTAT
OF : DISABLED(DEFAULT) 0 : NO PARITY, DATA 8 BITS, 1 STOP BITS (DEFAULT)
6 FREEZE PROTECTION
ON : ENABLED 1 : NO PARITY, DATA 8 BITS, 2 STOP BITS 0-10V
0-10V
Fan
Fan
RANGE : -9°C~+9°C (-9°F~+9°F) DEFAULT IS 0°C/0°F RS-485 COMMUNICATION 2 : EVEN PARITY, DATA 8 BITS, 1 STOP BITS 0-10V

IF ISU CODE# 30 TEMPERATURE DISPLAY MODE IS


26 3 : ODD PARITY, DATA 8 BITS, 1 STOP BITS
0-10V
Valve
Valve

ROOM TEMP. DISPLAY PORT SETTING


7 ADJUSTMENT SET TO 0&2, THERMOSTAT CAN ADJUST THE AFTER CHANGED THE BAUD RATE, PLEASE CUT-OFF POWER
ROOM TEMPERATURE BASED AS PER ABOVE VALUE AND RE-ELECTRIFIED THE THERMOSTAT
REMOTE SETBACK RANGE 10-21°C DEFAULT IS 18 ° C (RANGE 50-71°F THERMOSTAT OR 00: BOTH THERMOSTAT & REMOTE BMS (DEFAULT)
8 27 REMOTE CONTROL
HEATING SET-POINT DEFAULT IS 64°F) 01: REMOTE BMS ONLY (THERMOSTAT CONTROL IS DISABLE)
SETTING

9
REMOTE SETBACK RANGE 22-32°C DEFAULT IS 26 ° C (RANGE 72-90°F 28 HEATING RANGE STOP 10-32℃,DEFAULT 32℃(50-90℉Default 90℉)
COOLING SET-POINT DEFAULT IS 79°F) 29 COOLING RANGE STOP 10-32℃,DEFAULT 10℃(50-90℉Default 50℉)
MODBUS ID DISPLAY OF: NO MODBUS ID ADDRESS DISPLAY, ON: DISPLAY 0 : DIS PLAY ROOM TEMPERATURE(WHEN PRESSING
10 Rs485
Rs485
SETTING WITH MODBUS ID ADDRESS, DEFAULT IS OF UP OR DOWN BUTTON, IT WILL DISPLAY SET-POINT A:Red
A:Red
B: Black
WITH ICON , WHEN NO KEY PRESS, IT WILL DISPLAY B: Black
RANGE: 1-20 FOR PROPORTIONAL OUTPUT
ROOM TEMP. WITH ICON
11 P: ADJUSTMENT OF ADJUSTMENT, IT SHOULD BE ADJUSTED BASES TEMPERATURE
VALVE CONTROL 30 1 : DISPLAY SET-POINT WITH ICON IN COOLING& TX1000EC024-V2M TX1000EC024-V2
ON THE ACTUAL CONDITION, DEFAULT IS 10 DISPLAY MODE
HEATING MODE (IN PROGRAM MODE, IF PERIOD IS SET
RANGE: 1-100 FOR INTEGRAL OUTPUT ADJUSTMENT,
TO OFF, IT WILL DISPLAY ROOM TEMP INSTEARD), IN
I : ADJUSTMENT OF VENTILATION MODE IT WILL DISPLAY ROOM TEMP WITH ICON
12 IT SHOULD BE ADJUSTED BASES ON THE ACTUAL 2 : DISPLAY BOTH(DEFAULT 2)
VALVE CONTROL
CONDITION, DEFAULT IS 60 THIS FUNCTION IS RESETTING ALL ISU SETTINGS TO FACTORY
IN : INTERNAL SENSOR, OU: EXTERNAL SENSOR, 31 DEFAULTS, OPERATION: PRESS “ ” 0>1>2>3>4, THEN PRESS NO TERMINALS DESCRIPTION
RESET TO DEFAULTS
IF CHOOSING EXTERNAL SENSOR, THE HOTEL KEY CARD “ ”4>3>2 AND PRESS “ ” TO CONFIRM DEFAULT: 0
13 SENSOR SELECTION 1 R 24V ACTIVE
FUNCTION WILL NOT BE AVAILABLE, DEFAULT IS IN IN PROGRAM MODE, WHEN THE PERIOD IS OFF, IT WILL
DISPLAY ROOM TEMP INSTEAD OF SET-POINT.
14 BEE SOUND SETTING ON: ON, OF: OFF, DEFAULT IS OF 2 C 24V NEUTRAL&COM FOR AO

0: 5 WORKING DAYS AND 2 DAYS HOLIDAY A WEEK,


3 AO1 ANALOG OUTPUT 0-10V FOR VALVE
WIRING DIAGRAM
1: 6 WORKING DAYS AND 1 DAY HOLIDAY A WEEK, AC85-240V AC85-240V 4
15 PROGRAM SETTING
2: 7 WORKING DAYS A WEEK, 3: CLOSE PROGRAM
SCHEDULE ,DEFAULT IS 0 5
0-4 MINUTES, EXAMPLE, WHEN SETTING IS 1 WITH 0-10V
Fan
0-10V
Fan 6 AO2 ANALOG OUTPUT 0-10V FOR FAN
COMPRESSOR ON-OFF 1 MINUTE DELAY WITH BOTH ON OR OFF COMPRESSOR On-Off
16 0 FOR ON-OFF VALVE CONTROL, 1-4 MINUTES
On-Off
Valve 7
TIME DELAY Valve
FOR COMPRESSOR CONTROL, DEFAULT IS 0
LO: FAN WILL BE SWITCHED TO LOW SPEED WHEN 8 COM COM FOR 0-10FAN & UI
ROOM TEMP. REACHES TO SET-POINT & VALVE TURNS OFF
17 FAN STOP/RUN
OF: FAN WILL BE SWITCHED OFF WHEN ROOM TEMP. 9 UI RS (EXTERNAL SENSOR)&KC(KEY CARD)
SETTINGS
REACHES TO SET-POINT & VALVE TURNS OFF.
DEFAULT IS OF
Note :
OF: OFF, THE BACK-LIGHT WILL BE OFF AFTER 1. Please do wiring with professional technician.
ON/OFF BACK LIGHT 30 SECONDS IF NONE KEY PRESSED. ON: ON, THE Rs485
18 A:Red 2. If the thermostat was burned by accidently, please don’t wiring it again by yourself, try to check
SETTING BACK-LIGHT WILL BE ALWAYS ON EVEN NONE KEY B: Black
it with a professional technician or contact with our manufacturer.
PRESSED, DEFAULT IS OF
9 TERMINAL POWER BOX
TX1000EC220-V2M TX1000EC220-V2
*wiring is subject to change without notice based on addons
ECV2_VN0121
MODBUS DATA ADDENDUM The upload data is actual value
PRODUCT DIMENSION
multiplied by 10, actual value
0.5 per step, Example: 10.5 >
The TX1000EC-communication series has integrated Modbus RS485 RTU Space Set Temperature:
105 In ECO mode, the set-point 40005 F=03, item #4 26 R/W
1 0 - 3 2 °C (50-90°F)
communications.Using a Modbus master controller Thermostat can be is set by ISU mode code#8&9 or
set via Modbus point(Reg
controlled centrally and Monitored. Modbus is a simple communication 40007&40008)
protocol which is widely popular. Correct wiring practises should be followed Occupancy Enable
(Key Card) :
If enabled thermostat operation shall
be based on occupied set- point,
in order to attain maximum reliability. See page of WIRING DIAGRAM for the 0 : Disable else works on unoccupied set-point 40006 F=03, item #5 1 R/W
1 : NO (refer below point for set-points)
detailed wiring Modbus connection. 2: NC NO & NC both are ENBLE
The upload data is actual value
Our Modbus protocol has 4 ranges-Coil status,input status.holding registers Remote cooling
temperature 22-32°C
multiplied by 10,
actual value 0.5 per step
40007 F=03, item #6 26 R/W
and input registers. Modbus data is within the “00XXX/10XXX/40XXX/30XXX Example: 10.5 > 105
”range, this is been holding registers.Depending on your choice of Modbus Remote heating
The upload data is actual value
multiplied by 10,
F=03, item #7 18 R/W
master you may need to write using full address such us “40025” or by temperature 10-21°C actual value 0.5 per step
40008
Example: 10.5 > 105
selecting holding register simply write” 25”
The upload data is actual value
Remote cooling multiplied by 10,
temperature 22-32°C 40009 F=03, item #8 0
actual value 0.5 per step
DATA FORMAT Example: 10.5 > 105
Protocol : Modbus RTU(Slave) The upload data is actual value
Remote heating multiplied by 10,
Byte Format : 1 start bit,8 Data bit,1 stop bit,NO parity temperature 10-21°C actual value 0.5 per step 40010 F=03, item #9 10
Address : 1 to 64 Example: 10.5 > 105
INSTALLATION AND COMMISSIONING
Baud rate : 4800/9600/19200/38400/57600/115200 Holding Output (0-10V):
When 00005 is set to 1, this
address is writable
Register 0-100 percent 0: off, 1 : on 40011 F=03, item #10 60
The modbus slave have supported the following : address : 1 When 00005 is set to 0, this
address is read only
length : 20
♦ Read Coils ♦ Write Single Coil Lock mode:
♦ Read Discrete Inputs ♦ Write Single Register 0: All buttons are available
1: Mode button is locked
♦ Read Holding Registers ♦ Write Multiple Coils out
40012 F=03, item #11 0 R/W
2: Fan and mode button
♦ Read Input Registers ♦ Write Multiple Registers are locked out
3: All button are locked
out.

MODBUS REGISTER Space temperature


The upload data is actual value
multiplied by 10, Wiring on the terminals of the back plate
40013 F=03, item #12 RO To take the front panel and back plate
ADDRESS Read:R
: 0 - 5 0 (C/F) actual value 0.5 per step
apart by screw driver according to above wiring diagram,then fix the
Example: 10.5 > 105
Type Name Description Default Write:W back plate on the junction box by screw driver
Modscan Modbus Poll Read Only: RO MAC address : 0-9999 40014 F=03, item #13

In Remote BMS only, all controls Baud Rate :


(temperature set-point&fan control 0 : 4800 , 1 : 9600 After changed the baud rate,
points)are from remote BMS via please cut-off power and 40015 F=03, item #14 1 R/W
Control Type: 2 : 19200 , 3: 38400 re-electrified the thermostat.
Modbus points as per below 4 : 57600, 5 : 115200
0 : Both Thermostat settings, thermostat control will be
&Remote BMS 00001 F= 01, item #0 0 R/W
disabled; In both thermostat&
1 : Remote BMS only remote BMS mode, all controls
Communication port
are from both thermostat controls configuration:
&Remote BMS 0: No parity, 1 stop bits; After changed the baud rate,
Coil Output please cut-off power and 40016 F=03, item #15 0 R/W
Register 1: No parity, 2 stop bits;
Low speed: fan will be switched re-electrified the thermostat.
COIL STATUS 2: Even parity, 1 stop bits;
to low speed when room 3: Odd parity, 1 stop bits;
address:1
temperature reaches to the
length:5 Fan run/stop Mode :
set-point&valve turns off
0: Low speed 00002 F= 01, item #1 1 R/W
OFF: fan will be switched
1: OFF 10-32°C Default 32°C
off when room temperature Heating Range Stop 40017 F=03, item #16 32°C/90°F R/W
50-90°F Default 90°F
reaches to the set-point&valve
turns off.
Recombine the front panel and back plate
ECO enable: 0:off , 1:on 00003 F= 01, item #2 0 R/W by contact pins
10-32°C Default 10 °C 40018 F=03, item #17 10 °C/50°F R/W
Thermostat status: Cooling Range Stop 50-90°F Default 50°F
0: off, 1: on 00004 F=01, item #3 0 R/W

Remote valve(0-10V) 0: Disable, 1: Enable 00005 F=01, item #4 0 R/W


0 Display Room Temperature TROUBLE SHOOTING TIPS
control Temperature Display 1 Display Set-point 40019 F=03, item #18 2 R/W
Mode 2 Display Both
Valve status:
1 : Open 10001 F=02, item #0 RO
(In program mode, when the
period is OFF, it will display
IF... THEN...
0 : Close room temp. instead of set-point)
Set the mode to Heat by pressing the Mode button.
Discrete Inputs When ISU mode code# 13 set to 1, Thermostat Control
0 Manual Mode
0~1 = R/W
Heating system does not turn on Wait five minutes for the heating system to respond.
if thermostat didn't 1 Programmable Mode 40020 F=03, item #19 0
Status External sensor status: Mode 2 = RO
Input Register 0: Connected connect with external sensor, the 2 Temporary Mode
10002 F=02, item #1 RO
address:1 temperature display area will
1: Disconnected Low speed fan setting range Set the mode to Cool by pressing the Mode button.
length:5 display --, and modbus register of EC fan speed settings 0.5V-3V (O.5V per step) 40021 F=03, item #20 0 R/W Cooling system does not turn on
10002 will display 1 Low speed fan Default 2V Wait five minutes for the cooling system to respond.
Occupancy input
status: Low speed fan setting range
0 : None 10003 F=02, item #2 RO EC fan speed settings 3.5V-7V (O.5V per step) 40022 F=03, item #21 R/W
1 : Input Medium speed fan 0
Default 5V Check whether the fan mode is set to Auto.
Compressor Status
10005 F=02, item #4 RO Low speed fan setting range
The fan doesn’t work Check whether the heating or cooling system works well or not.
0: off 1: open EC fan speed settings 7.5V-10V (O.5V per step) 40023 F=03, item #22 0 R/W
High speed fan Default 10V
Status of current
period(Programmable) 0:On 1:Off 10006 F=02, item #5 RO Check whether the Fan mode is set to Auto
Reserved for additional settings 40024 F=03, item #23 0 The Mode button does not work Check whether the heating or cooling system works well.
Device ID: 1-64 40001 F=03, item #0 1 R/W Check whether the keypad is locked out (ISU mode item 4)
Fan Control
( Enum Value) : Compressor delay time 0-4(0 for on-off valve, 40025 F=03, item #24 0
In Cooling or heating mode, Fan Selection R/W Check whether the system is working in energy saving mode.
4 : Auto will be switched to low speed/off 1-4 for compressor delay time)
3 : High when temperature is achieved 40002 F=03, item #1 4 R/W The Fan button does not work
2 : Medium The upload data is actual value
(Reg 00002) and fan
1 : Low command will be disable
Space Temperature multiplied by 10,
30001 F=04, item #1 RO
Check whether the key pad is locked out (ISU mode item 4)
0 : Off : 0 - 5 0 (C/F) actual value 0.5 per step
Holding Example : 10.5 > 105
Register
Operation mode:
Check whether the system is working in energy saving mode.
address : 1 Fan Speed Input Status: The Up or Down button does not work
length : 20 0: Fan
40003 F=03, item #2 0 R/W Low: 1
1: Cool Input Register
2: Heat Medium:2 Check whether the key pad is locked out (ISU mode item 4)
address : 1
length : 3 High: 3
Fan speed input status: Off: 0 30002 F=04, item #0 RO
1: Low Auto off: 4
2: Medium Auto Low: 5
3: High Auto Medium: 6
0: Off 40004 F=03, item #3 RO
Auto High: 7
4: Auto off
5: Auto Low
6: Auto Medium AI value: 0-50 (C/F) 30003 F=04, item #2 RO
7: Auto High

ECV2_VN0121