Professional Documents
Culture Documents
Jockey Fire Pump 25 GPM @110m (Xylem)
Jockey Fire Pump 25 GPM @110m (Xylem)
Company name
Contact
Technical data Phone number
e-mail address
Operating data
Pumpe ty pe Single head pump Fluid Water
Av ailable sy stem NPSH m 0 Operating temperature t A °C 4
Nominal f low US g.p.m. 25 pH-v alue at t A 7
Nominal head m 110 Density at t A kg/m³ 1000
Static head m 0 Kin. v iscosity at t A mm²/s 1.569
Inlet pressure kPa 0 Vapor pressure at t A kPa 100
Env ironmental temperature °C 20 Solids 0
Altitude m 0
Pump data
Make Lowara Nominal US g.p.m. 25.8 ( 25.8 )
Speed rpm 2900 Flow Max- US g.p.m. 37.4
Number of stages 21 Min- US g.p.m.
Max. casing pressure kPa Nominal m 117.1
Max. working pressure kPa 1548.8 Head at Qmax m 66.7
Head H(Q=0) m 160 at Qmin m 157.9
Weight kg 47 Shaf t power kW 2.7 ( 2.7 )
Max. mm 76 Max. shaf t power kW 2.9
Impeller R designed mm 76 Ef f iciency % 68.64
Min. mm 76 NPSH 3% m 1.7
Motor data
Manuf acturer Lowara Electric v oltage 400 V Speed 2865 rpm Insulation class F
Specif ic design IE3 3ph Flange Motor Frame size 100 L Colour RAL 5010
Ty pe PLM 100R B14 3 kW
Rated power 3 kW Degree of protection IP55
Electric current 6.33 A
Remarks:
Hydraulic data
Operating Data Specification Hydraulic data (duty point) Impeller design
Flow 25 US g.p.m. Flow 25.8 US g.p.m. Impeller R 76 mm
Head 110 m Head 117 m Frequency 50 H z
Static head 0m MEI >=0,7 Speed 2900 rpm
Drawing
Dimensions mm