Eb Recommended Practice For Electrical Preventative Maintenance

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 10

image here

Recommended practice for


electrical preventative maintenance
Equipment care bulletin

HSB Canada, part of Munich Re, The HSB Recommended Practice for CLEAN: Electrical apparatus and
is a technology-driven company built Electrical Preventive Maintenance is equipment rooms should be kept clean
on a foundation of specialty insurance, based on prevention of the most and free of excessive dust and dirt
engineering, and technology, all common and frequent problems accumulations. Obviously,
working to drive innovation in a leading to electrical equipment failure. consideration is given to the normal
modern world, to keep you ahead While drawing from several sources, environment for the location and the
of risk. as noted in the standard itself, it type of equipment installed. Equipment
addresses four basis points regarding rooms are not to be used for storage
electrical maintenance. Electrical and access should be limited to only
apparatus must be kept CLEAN, authorized operations and maintenance
COOL, DRY, and TIGHT. personnel. Proper lighting should be
maintained in order to ensure that
operations and maintenance can be
accomplished correctly and safely.
Recommended practice for Page 2/10
electrical preventive maintenance
Equipment care bulletin

COOL: Excessive heat buildup in As with any standards regarding preventive maintenance program.
electrical apparatus enclosures and equipment maintenance, HSB All work associated with electric
equipment rooms can be detrimental recommends that applicable power systems and equipment should
to the equipment. Conductors and jurisdictional requirements be be performed in accordance with
apparatus are designed for specific followed first, followed next by appropriate manufacturers
maximum heat loads. Exceeding specific manufacturers’ instructions and guidelines and
these maximums will result in recommendations. As a minimum, accepted industry practices. In all
improper operation and shortened HSB recommends that electrical cases, appropriate safe work practices
equipment life expectancy. Equipment preventive maintenance be performed should be employed for the protection
rooms should be kept cool to prevent at three year intervals. More frequent of all involved personnel. Please see
excessive heat buildup. Where intervals should be followed where the list of referenced standards at the
installed, cooling fans or blowers on conditions warrant. An effective end of this guide.
equipment must be properly maintenance program is one that can
maintained to provide adequate demonstrate that appropriate Frequency of EPM
cooling. As well, ventilation openings maintenance is done on a regular and In general, HSB recommends a
in equipment enclosures should be routine basis. Finally, proper minimum frequency of once every
kept clean and free from obstruction. maintenance can only be done by three years for conducting regular
If filters are installed they should be qualified and competent maintenance preventive maintenance on electrical
changed or cleaned regularly, as personnel. equipment. Where applicable, this
recommended by the manufacturer. standard will note components that
Introduction require a more frequent EPM program
DRY: Persistent exposure to moisture Electrical equipment failures account to help ensure reliability and
as well as direct contact with water for millions of dollars in damage and operation.
can result in equipment failures or lost business every year. As this
shortened life expectancy. Equipment country’s electrical infrastructure It is recognized that individual
rooms should be kept dry and the continues to age, this problem is only locations may require more frequent
equipment protected from moisture. going to worsen unless active steps maintenance due to the physical
When evidence of moisture are taken to counter the trend. environment or operational nature of
contamination is noted, equipment Ironically, more than two-thirds of the equipment. For example, harsh
should be examined for damage electrical system failures can be environments where excessive
and necessary repairs made, and the prevented by a routine preventive moisture or dust may be present
source of the moisture identified maintenance program. Studies show should have a more frequent EPM
and eliminated. that the failure rate of electrical program. Similarly, equipment that
equipment is three times higher for is used intermittently or equipment
TIGHT: The most common source of components that are not part of a critical to a key process should
electrical equipment failure is loose scheduled preventive maintenance be considered for a more frequent
connections. The single most program as compared with those that program. Sound engineering
important part of any electrical are. In addition, a planned Electrical judgment should be used in
equipment maintenance program is Preventive Maintenance (EPM) determining if more frequent
action to ensure all connections are program allows the equipment owner maintenance is appropriate.
properly maintained and kept tight. to schedule the system outage at a
Care should be taken to follow any time of their choosing rather than Recommended
applicable manufacturer’s instructions having to correct major problems maintenance practices
for tightening connections. As resulting from an always untimely The following sections are segmented
effective means of testing for loose failure. by equipment type. For each
connections is infrared imaging. An component, a recommended
infrared imaging survey should be a The purpose of this standard is to minimum practice for preventive
regular part of a comprehensive provide the insured with maintenance is provided. Where
electrical maintenance program. recommended practices and applicable, additional suggested
frequencies that would form the core practices are presented for a more
of a regularly scheduled electrical thorough EPM Program.
Recommended practice for Page 3/10
electrical preventive maintenance
Equipment care bulletin

Switchgear properly secured during operation. immediately identified and


Where heater elements are installed, corrective measures taken to
Enclosures these should be cleaned, examined for permanently correct the condition.
Ensure that all enclosure panels, damage and/or deterioration, and
doors, and structures are well- tested. Repair or replace heater Insulators, supports, and
maintained in accordance with the elements as necessary. connectors
manufacturer’s specifications. During Inspect insulators and conductor
de-energized maintenance, In environments where there is supports for signs of cracking,
enclosures are to be vacuum cleaned an extreme exposure to adverse broken pieces, and other physical
of all loose dirt and debris. Use of conditions, the frequency of damage or deterioration. Clean all
compressed air is not recommended maintenance for enclosures should be loose dirt with lint free rags. For
since this may cause foreign particles increased as conditions warrant. contaminates that will not remove
to become embedded in the insulation easily, solvents approved by the
or damage insulators. Any buildup of Most types of outdoor high voltage manufacturer may be used. Examine
dirt or other contaminates that will switchgear are provided with moisture for evidence of moisture that may
not come off with vacuuming should /condensation reducing heater lead to tracking or flashover while in
be cleaned with lint free rags using modules. Maintenance should include operation. Examine surrounding
cleaning solvents recommended by a check that the heater modules are areas for signs of tracking, arcing, or
the manufacturer. operating satisfactorily. overheating. Repair or replace
damaged insulators and supports as
All vents and fan grills are to be Electrical equipment rooms or vaults necessary.
cleaned of all dust and/or dirt should be kept cleaned of dirt and/or
accumulations. Ensure that ventilation dust accumulations on a regular basis. Examine all bolts and connecting
openings are not obstructed. Where Doors and windows should be devices for signs of deterioration,
seals and/or gaskets are installed, maintained in proper working order corrosion, or overheating. Ensure
these should be examined and and kept closed during routine that bolts and connecting devices are
repaired or replaced as necessary. All operation. Access doors should be tight, according to manufacturer’s
doors and access panels should be clearly marked to alert personnel that specifications. Be careful not to over-
live electrical equipment is in use. torque bolts and connecting devices
Where ventilation and/or air since insulators are easy to damage
conditioning are used, all fan motors and difficult to replace. Where
should be cleaned and examined for copper and aluminum conductors
signs of wear and deterioration. and/or connectors are used together,
examine connections for signs of
Fan blades should be cleaned of dirt galvanic action. Ensure that the
and dust and bearings should be connectors are property used and
properly lubricated. Vent openings installed in accordance with
should be cleaned of all dust and dirt manufacturer’s specifications. Apply
accumulations. Filters should be an antioxidant compound to all
cleaned and/or changed as aluminum-to-copper connections.
recommended by the manufacturer;
or more often if conditions warrant. Conductors
Electrical equipment rooms should Examine insulation for signs
never be used as storage areas. of deterioration, cracking, flaking,
or overheating. Examine all
Electrical equipment rooms or vaults connections for signs of overheating,
should be examined for evidence of cracked or broken connectors, and
water seepage. The tops of electrical signs of tracking or arcing. Ensure
equipment enclosures should be that conductors are clean and dry.
examined for evidence of water since Examine and clean all connections,
this is a common entryway that often and torque to manufacturer’s
goes undetected until a failure occurs. recommendations.
The source of the water should be
Recommended practice for Page 4/10
electrical preventive maintenance
Equipment care bulletin

Air circuit breakers Older breakers equipped with carbon Operating mechanism
contactors generally require very little Inspect for loose, broken, worn, or
Insulation maintenance. Examine for proper missing parts (consult manufacturer’s
Remove and clean interphase barriers. pressure, deterioration, or excessive schematics for required parts). Examine
Clean all insulating materials with dressing which may interfere with for excessive wear of moving parts.
vacuum and/or clean lint free rags. their proper operation. Observe that operating mechanisms
If it is necessary to use cleaning function properly without binding,
solvents, use only solvents Draw-out contacts on the circuit hanging, or without delayed action.
recommended by the manufacturer. breaker and the stationary contacts in Ensure any lubrication is done
Inspect for signs of corona, tracking, the cubicle should be cleaned according to the manufacturer’s
arcing, or thermal or physical damage. and inspected for overheating, specifications. Ensure mechanisms are
Ensure that insulation is left clean alignment, and broken or weak clean, properly lubricated, and all bolts
and dry. springs. Coat contact surfaces with and screws are properly secured. Repair
contact lubricant to ease mating (see or replace as necessary.
Contacts manufacturer’s recommendations).
Ensure that all contacts are clean, Auxiliary devices
smooth, and in proper alignment. Arc interrupters Inspect operating devices for proper
Ensure that spring pressures are Clean all ceramic materials of loose operation and general condition. Ensure
maintained according to dirt and examine for signs of moisture, all indicating devices are fully functional
manufacturer’s specifications. On make sure the assemblies are clean and property set. Protective relays
silver contacts, discoloration is not and dry. Examine for cracked or and circuit breaker trip devices should
be inspected and tested according to
manufacturers’ specifications and
applicable industry standards.

Vacuum circuit breakers


All maintenance is similar to that
performed on air circuit breakers. As
always, it is recommended that the
manufacturer be consulted for specific
maintenance and testing procedures.

The integrity of the vacuum chamber


is often tested by applying a test
voltage across the open contacts of
the breaker. However, this can be a
destructive test and is therefore not
recommended by HSB.

usually harmful unless caused by broken pieces. Dirt and arcing Caution: This procedure can produce
insulating deposits. Clean silver deposits may be removed by light X-ray emissions, so personnel should
contacts with alcohol or silver cleaner sanding – do not use emery cloth or maintain a safe distance from
using nonabrasive cloths. wire brushes which may leave the breaker if this test is performed.
conductive residue behind. Repair or It is important to closely follow
Manually close breaker to check for replace as necessary. manufacturer’s recommended
proper wipe, contact pressure, contact procedures if conducting this test in
alignment, and to ensure that all Examine arc chutes for dirt and/or order to ensure that proper results are
contacts make at approximately the duct accumulations and clean as obtained. The breaker vapor shield can
same time. If possible, a contact necessary. Dielectric testing of arc accumulate an electrostatic charge
resistance test should be performed shields may be recommended by the during this test. Ensure that it is
to determine the quality of the manufacturer. Check air puffer for discharged immediately following
contacts. proper operation. the test.
Recommended practice for Page 5/10
electrical preventive maintenance
Equipment care bulletin

Air disconnect switches Insulating oil test the surrounding of the breaker, the
Inspect and clean insulators and Conduct a dielectric screen test of the heat build-up may not be permitted to
conductors as with circuit breakers. insulating fluid. Based on the results dissipate properly and result in
Tighten connections in accordance of this test, filter or replace oil as nuisance tripping.
with manufacturer’s specifications. required. Heavy carbon content can
Do not over tighten as this may result indicate potential contact wear and Clean the breaker housing and inspect
in damage to connectors. should be investigated further. it for cracks or signs of overheating.
Tighten all connections. Exercise the
If cleaning solvents are used, ensure Internal breaker several times to ensure the
that they are as recommended by the Since the contacts for oil circuit mechanism has freedom of movement
manufacturer. Where abnormal breakers are not readily accessible for and to allow contact wiping.
environmental conditions exist, more inspection, the contact resistance
frequent inspection and cleaning may should be tested as a minimum. In addition, larger duty circuit
be required. breakers (225 amps or above) should
More extensive maintenance on the be electrically trip tested to ensure
Check the operation of the arc blades, contacts might be require draining the proper operation of the trip elements
if applicable, and ensure proper wipe oil and dropping the tank, and is and trip linkages. Refer to the latest
of the main contacts. Interphase therefore performed less frequently. edition of the National Electrical
linkages and operating rods should Follow manufacturer’s recommended Manufacturer’s Association (NEMA)
be inspected to make sure that the schedule for examination of internal Standard AB4, Procedures for
linkage has not been bent or distorted components such as contact Verifying Field Inspections and
and that all fastenings are secure. inspections. Open breaker and Performance Verification of Molded-
The position of the toggle latch to the examine contacts for wear and/or Case Circuit Breakers. If possible, test
switch operating linkage should be excessive deterioration. Examine contact resistance to ensure quality of
observed on all closed switches to linkages for loose, broken, or missing breaker contacts.
verify the switch is mechanically parts; repair or replace as necessary.
locked in a closed position. Operate All molded-case circuit breaker panels
switch manually several times to Auxiliary devices should be cleaned of all dirt, dust, and
ensure proper operation, and then Operating mechanisms should be debris using a vacuum.
by motor if power- operated. Ensure maintained as with air circuit
that all moving parts are properly breakers. Where applicable, examine Battery stations / chargers
secured and lubricated as specified oil level indicators, sight glasses, oil
by the manufacturer. lines, gaskets, and tank lifters for Batteries
proper conditions. Repair or replace as Following should be done monthly:
Contact resistance testing of each necessary and in accordance with
phase contact should be performed. manufacturer’s recommendations. − T horoughly clean all battery
The results should be recorded and surfaces of dust and/or dirt
analyzed to ensure proper contact is Examine arc-quenching assemblies accumulations. Clean and tighten
being made. If the contact resistance for carbon deposits or other all terminal connections. Remove
of the switch exceeds recommended contaminates. Follow manufacturer’s any corrosion on battery terminals
minimums, repair or replace the recommendations for cleaning. with bicarbonate of soda.
switch immediately. − Clean battery studs and cable ends.
Molded-case circuit breakers On stranded cable, if ends are
Oil circuit breakers Molded-case circuit breakers should corroded, cut off ends or separate
be kept clean for proper ventilation of strands and clean internally.
External the breakers. These types of breakers − Check electrolyte levels and specific
Inspect the enclosure for signs of oil are usually tripped by a thermal gravity, where applicable. Variations
leakage. Clean external bushings element that senses an increase in of more than fifty (50) points
assemblies and examine for signs of temperature due to excessive current between cells may indicate a
deterioration, tracking, and loose or draw. However, if dirt accumulates on bad cell.
broken parts. Observe oil gauge to
ensure device is operating properly
and measuring the oil level accurately.
Recommended practice for Page 6/10
electrical preventive maintenance
Equipment care bulletin

Charger Inspect for sharp bends, physical Raceways


Following should be done monthly: damage, excessive tension, oil Check raceways for proper
leaks, pits, cable movement, soft mechanical support of raceway and
− C lean all dust and/or dirt spots, cracked jackets, damaged cables as well as check insulation for
accumulations from charger. Clean fireproofing, poor ground connections, abrasion or cracks at support points.
all vent openings and ensure that deteriorated and corroded or Examine raceway joints for clean and
they are free from obstructions. weakened cable supports. Inspect for tight connections.
− Check terminals and connections wear at entrance point and at
for tightness. Check all relays, supports. Inspect manhole for spilled Bus duct
lights, and other indicating devices concrete, proper ventilation and Bus duct joint covers should be
for proper operation. excessive leakage and for cracked / removed to allow access for a
− If all cells consistently read low, chipped porcelain. thermographic survey of the
check charger for proper operation. energized bus under load. After
If electrolyte levels are low, check de-energizing and grounding the bus
charger rate settings against the duct, connections should be checked
manufacturer’s specifications. for proper tightness as well as
Consistently low levels may indicate evidence of overheating, corrosion,
the charge rate is too fast. arcing, or other forms of
deterioration. All loose or dirty
Capacity tests connections should be cleaned and
In addition to the aforementioned properly torqued. Be careful not to
battery inspections, certain tests over-torqued the bolts. Consult the
should be performed to assess manufacturer for recommended
whether or not the battery meets maintenance practices and torque
the manufacturer’s specifications, values. The tops of the bus duct
or whether the battery is performing enclosure should be inspected for
adequately, or even to determine evidence of water or other foreign
whether the battery is performing up matter that may contaminate the
to the requirements of the system. bust duct.
In general, a performance test of a
battery should be conducted within Testing
the first two years from the initial Suggested cable or bus tests include
installation, and every five years insulation resistance testing and
thereafter. polarization index testing. These
tests should be recorded to track
Safety Examine the manhole and cable trends that may indicate a
Caution – While charging, some grounding system to ensure its deterioration of the cable’s insulation.
batteries emit explosive gases. Allow integrity. If cathodic protection has
no open flames or sparks permitted been installed in the manhole, it too Transformers
near charging batteries. Battery should be evaluated. Corrective action Transformer data (such as, voltage,
rooms should be well ventilated and should be taken as appropriate to current, and temperature readings)
smoking should not be permitted. maintain the integrity of these should be recorded on a regular basis
systems. in order to determine operating
Cables and Bus conditions of the transformer. Peak,
Cables must be de-energized if they Aerial cables or redline, indicators should be
are to be touched or moved during Check supports for excessive wear or recorded and reset. Readings taken
maintenance. deterioration, check cables for wear at on a weekly basis can provide
support points, inspect for mechanical important information about the
Cables in manholes damage from vibration. At dead-ends, loading of the transformer that is
Caution: Check for dangerous check cable for worn insulation, sharp needed before additional loads can
gases using a properly calibrated test bends, or cracks. be added to the transformer.
meter before entering an confined
space such as a manhole.
Recommended practice for Page 7/10
electrical preventive maintenance
Equipment care bulletin

Dry type transformers connections in accordance with condition of the spiral spring, disc
After de-energizing and grounding manufacturer’s recommendations. clearances, contacts, and case
the transformer, clean all coils, shorting contacts (if present). Check
connections, and insulators of loose If applicable, perform a ground mechanism for freedom of movement,
dust or dirt deposits with a vacuum resistance test to ensure a value of proper travel and alignment, and
cleaner. Examine the transformer for 25 ohms or less. tightness of counting hardware
signs of overheating, deterioration, and plugs.
arcing, loose or broken parts, or other Surge arrestors
abnormal conditions. Ensure all Clean and inspect porcelain for signs Electrical testing
connections are tightened according of damage or deterioration. Repair or Using an appropriate testing
to manufacturer’s specifications. replace as necessary. Examine instrument, suitable for the relays
Clean enclosure of any dust and dirt arrestor leads for damage and/or being tested, conduct electrical testing
accumulations and ensure that vent deterioration. Any gap-type silicone of the relays in accordance with
openings are free from obstruction. If carbide arrestors should be replaced manufacturer’s recommendations
cooling fans are installed, examine for with modern metal oxide arrestors. and IEEE testing standards. For over
proper operations and lubricate as current relays, test the following
necessary. Other suggested tests are watts-loss functions of the relay at the
and leakage current tests, insulation established settings specified by the
Additional suggested testing includes resistance tests, and grounding system engineer or manufacturer.
an insulation resistance test, and a electrode circuit resistance tests.
winding resistance test. These are These should be conducted according − P ickup contacts should close when
non-destructive tests which can be to manufacturer’s recommendations. a current equal to the relay tap
performed to track the condition of setting is applied to the induction
the insulation over time. Detailed Protective relays coil. Adjust the spring as needed to
records should be maintained and Inspection, maintenance and testing allow for proper operation.
analyzed to identify undesirable of protective relays should be done − Timing tests should be performed
trends that may indicate the onset of on an annual basis in order to ensure corresponding to two (2) or more
an insulation failure. proper and reliable operation. All points on the relay’s time-current
necessary precautions should be curves. One of the tests should be
Liquid-filled transformer taken while working with protective done at the specified time dial
Insulating liquid samples should devices to ensure personnel safety setting.
be taken annually and screen tested and to avoid any unplanned − Instantaneous pickup test should
for dielectric breakdown, acidity, color, interruption of service. In particular, be performed for the specified
power factor, and interfacial tension. when working on control circuits, instantaneous setting, if applicable.
A Dissolved-Gas-in-Oil (DGA) test all current transformer (CT) − Seal-in units should be tested to
conducted by a qualified testing secondaries should be shorted to ensure that the contacts hold closed
laboratory should be performed ground and never left open-circuited with the minimum specified current
annually. The results should be in order to avoid serious injury to applied.
trended to track conditions and maintenance personnel. − Relay target should indicate when
schedule maintenance as necessary. the relay has operated. If possible,
Visual and mechanical inspection the relays should be tested to ensure
Examine the transformer tank and Inspect relays for physical damage that operation of the relay will in fact
bushings for evidence of leakage. and deterioration. Inspect gaskets and cause a tripping action of the
Inspect the bushings, insulators, covers for damage and /or excessive respective circuit breaker.
and surge arrestors for broken or wear, and repair or replace as
damaged parts, signs of overheating necessary. Examine and clean the Relays that do not test satisfactorily or
or arcing, or tracking. Clean all relay and enclosure of foreign are found to be defective should be
bushings, insulators, and surge materials, such as dust, dirt, and replaced immediately to maintain the
arrestors of any dirt or dust moisture contamination. Examine the integrity of the protection systems.
accumulation. Tighten all conductor
Recommended practice for Page 8/10
electrical preventive maintenance
Equipment care bulletin

UPS systems Check inverters for fluid leaks from Most electrical breakdowns occur as a
This section provides general wave-forming capacitors. Check result of the motor’s environment – too
recommended maintenance capacitors for signs of bulging or dirty or wet, too warm, or too much
guidelines for Uninterruptible Power discoloration. Examine transformers movement.
Supply (UPS) systems. Since there and heat sinks for signs of
is a wide variety of systems and overheating. Maintain batteries as Contamination – Failures often occur
equipment available, the prescribed in section 3.7 of this when elements in the environment
manufacturer’s instructions and standard and as specified by the such as moisture, abrasive or
recommendations should be manufacturer. conducting dust, or chemicals react
consulted for more complete and with the insulation system to lower
detailed maintenance requirements. Motors the resistance between phases, or
phase to ground. Contamination can
UPS systems are categorized in two Why do motors fail? be high humidity, oil leaking from the
basic ways: static and rotary. For the Virtually every kind of facility or bearings, aggressive chemicals or
purposes of this standard, only static business relies on electric motors to many other common occurrences.
systems will be addressed. drive something. Many large
manufacturing plants have thousands Heat – Motor windings are designed
When performing any maintenance of motors and their “critical” motors by the manufacturer to operate at or
and/or testing of UPS systems, follow number in the hundreds. below a certain temperature. If the
all recommended safety procedures as Unfortunately, motors are so reliable winding is operated hotter than
indicated by the manufacturer and and efficient, that many receive little design, thermal aging of the insulation
required by Canadian Health & Safety attention, until they fail. occurs at a more rapid rate and
Legislation and/or WHMIS. Only fully machine life expectancy is reduced.
trained and qualified persons with A general rule is that for each 10°C
proper test equipment should perform over rated temperature that the motor
UPS maintenance. is operated, the insulation life is cut
in half.
Clean interior and exterior of cabinets
and enclosures, ensuring that any Movement – The major cause of
areas of corrosion and/or deterioration electrical failures is movement of the
are repaired as necessary. Clean all coils during start-up and operation.
vent and air circulation openings and This includes motion between coils or
ensure freedom from obstructions. conductors and the core iron, between
If installed, clean cooling fan blades conductors within the coils
and motor housings. Ensure that themselves, and between conductors
motor bearings are properly lubricated and their supporting structure or
and that fan blades are properly bracing. The mechanical stresses
secured to drive shafts. Examine for caused by starting under heavy load,
signs of moisture contamination and as well as the natural magnetic
correct if necessary. stresses cause a flexing of the coils,
forcing them to move outward and
Clean and examine all electrical sideways. This movement usually
connections for signs of corrosion or Electric motor failures can be put into results in a short to ground, in the end
deterioration, repair or replace as two major categories: mechanical turns, where the coil leaves the slot of
necessary. Ensure all connections are breakdowns and electrical the stator iron. Shorts also occur
tightened according to manufacturer’s breakdowns. Causes for mechanical between strands of wire in random
specifications. As applicable, clean breakdowns include loss of wound motors and between turns
and test all breakers, disconnects, and lubrication, worn-out bearings, within a coil in form-wound motors.
relays as prescribed elsewhere in coupling misalignment, rotor
these standards and as specified by unbalance, etc. Periodic vibration A turn-to-turn short circuit creates a
the manufacturer. Check all system monitoring, and lubrication analysis decrease in the equivalent number of
alarms and indicating lights for proper can often help to detect these faults winding turns, which increases the
operation. early enough to avoid failure. stator winding current, and thus
Recommended practice for Page 9/10
electrical preventive maintenance
Equipment care bulletin

increases the heat loss. The increased Electrical test methods The High-Potential (hi-pot) test is an
heating accelerates the thermal Even with today’s advanced industry accepted, pass/fail test that
degradation of the surrounding technology, there is still no single is ideally suited for new or recently
insulation, which results in additional electrical test that can positively rewound motors. An AC or DC voltage
shorted turns and further increases determine the remaining useful life is applied to the windings at twice
in temperature. of a motor’s insulation. At best, we the operating voltage plus 1000v.
can assess the insulation integrity (A 4160v motor is tested at 9000
Maintenance inspections from the knowledge of the insulation volts!) Both the AC and DC “hi-pot”
A well-balanced maintenance characteristics, the stresses tests are considered destructive tests,
program for motors is based on experienced by the machine, because marginal equipment can fail
diagnostic testing and visual experience with similar machines, a prematurely while undergoing this
inspection, performed by qualified, physical examination, and a trend of test. Therefore, hi-pot testing is not
knowledgeable personnel. There are diagnostic tests over time. recommended by HSB.
no test methods available which can
replace the need for a good visual There are a number of electrical test Motor Current Signature Analysis
inspection. A visual inspection methods which are widely used in is a relatively new technique that
program should concentrate on industry today. Some of the best have can help detect broken rotor bars,
those areas most prone to damage only become practical in the field cracked rotor end ring, loose rotor
or degradation. Observation of the within the last few years. Each of the joints, bent shafts, and worn bearings.
external condition of the motor following methods works well for its This inexpensive test measures side-
should include: intended use. band frequency spectra from the line
current while the motor is running.
− E vidence of damage Two of the older, traditional methods Sophisticated software then process
caused by dirt, loose parts, that are still commonly used are the the raw signal and analyzes the
or foreign objects. insulation resistance and the high signature in both time and frequency
− Verification that air inlets potential (hi-pot) test. Both of these domains.
are not blocked. tests concentrate on the integrity of
− Evidence of moisture the phase to ground insulation – they Surge Comparison Testing uses
and/or dirt buildup. cannot check the condition of coil-to- a charged capacitor to pulse a voltage
− Unusual noises, leaking coil, or phase-to-phase insulation. into two windings of a motor
oil seals, or high vibration. simultaneously. The voltage is set low
− Oil level gages (if present) Insulation Resistance Test: The frame to begin and raised slowly while the
should be checked. of the motor is grounded, and a DC operator watches the wave forms on
− Evidence of oil leakage voltage (typically 500 or 1000 volts an oscilloscope. The voltage pulse is
at the bearings. for a 480v motor) is applied to the eventually raised to twice the
− Degradation of foundation, windings. If the insulation is in good operating voltage, plus 1000 volts.
bed plates, anchor bolts. condition, the resistance reading may Since the windings are supposed to
be hundreds of megohms. The IEEE be identical, the wave forms should be
Inspection of the end winding minimum acceptable standard is identical – a difference in wave forms
conditions with a borescope or 1 megohm plus 1 megohm for each indicates a problem. A skilled operator
directly, may reveal conditions of 1000v of motor rating. (A minimum can determine the exact type of fault
winding ties and evidence of acceptable reading for a 4160v motor (turn to turn, phase to phase etc.) by
loose coils, such as dusting or is 5.16 megohms). As a minimum, studying the wave form patterns.
greasing at the coil support points. HSB recommends an insulation This test can also be considered a
Not all motors need annual resistance test on a three year basis; potentially destructive test, because
maintenance, but the service life the test results should be recorded marginal motors can fail under test, if
will be increased if a prudent annual and trended to identify potential the test is not done properly.
inspection program is followed. insulation degradation over time.
Recommended practice for Page 10/10
electrical preventive maintenance
Equipment care bulletin

Infrared inspection Infrared surveys are done on of routine testing for trending
An infrared, or thermographic, energized equipment and should be purposes. Document all repair and/or
inspection should be performed at conducted during peak demand replacement of electrical components.
least once every three years on all periods if possible. This will reveal the When changes are made to the
switchgear, distribution panels, cable most serious problems and those that electrical distribution system, update
and bus connections, motor control would otherwise go undetected. At a all applicable drawings and
centers and starters, and other critical minimum, the loading should be at maintenance schedules to reflect
equipment. Infrared inspections are least 40% of the rated load of the the changes. Ensure that spare parts
equipment being inspected. inventories are updated for any new
equipment added based on the
Effective infrared surveys require manufacturer’s recommendations.
specialized equipment and should
be performed only by qualified Standards
technicians. Experience and training Any electrical preventive maintenance
is required to accurately identify program should be performed in
problem conditions and possible accordance with accepted industry
causes so that specific standards and work / safety practices.
recommendations can be made to This includes, but is not limited to, the
correct the situation. It is imperative latest releases of the following:
that these recommendations be
implemented in a timely manner to − C anadian Electrical Code Part I –
benefit from an infrared inspection. Electrical Installations
extremely beneficial in reducing Knowing a problem exists does not − Canadian Electrical Code Part II –
electrical failures by identifying help avoid an electrical failure unless Consumer and Commercial
potentially dangerous conditions; corrective actions are employed. Products
such as loose or dirty connections, − Canadian Electrical Code Part II –
overloaded or imbalanced circuits, or General Requirements
improperly installed equipment. By − Canadian Electrical Code Part II –
measuring the heat imbalance relative Industrial Products
to the environment and to surrounding − Canadian Electrical Code Part II –
equipment, abnormal or adverse Wiring Products
conditions can be uncovered that if − Canadian Electrical Code Part III
left unattended would worsen to − Electricity Distribution and
the point of failure. Transmission
− Electrical Engineering Standards
Infrared (IR) surveys are very helpful − Electromagnetic Compatibility
in planning the work scope of an (EMC)
upcoming scheduled outage. Prior to − H armonized Electrical Standards
the planned maintenance, an IR
survey should be conducted to help Record keeping Note: Upgrades or expansion
identify areas that need specific and The electrical preventive maintenance of electrical systems should be
immediate attention. Resources can program should be well-documented designed by a competent professional
then be allocated to address these as to scope and frequency of engineer and installed by qualified
specific problems during the maintenance. Record all routine electricians.
deenergized period. maintenance activities and the results

HSB Canada These recommendations are general guidelines and are not intended to be exhaustive or complete,
390 Bay Street, Suite 2000 nor are they designed to replace information or instructions from the manufacturer of your equipment.
Toronto, ON M5H 2Y2 © 2020 The Boiler Inspection and Insurance Company of Canada. All rights reserved.
Tel.: (416) 363-5491
hsb.ca Follow us

You might also like