CONCRETE COMPRESSIVE STRENGTH TEST REPORT NF EN

12390-3
Number of Test Report 143
Project CONGO – BIOFUEL 1st AGRI HUB - INDUSTRIAL START-UP
Contractor ZEROCK CONSTRUCTION CONGO
Origin of Concrete Zerock Concrete Batching Plant in Loudima

Temperature - Size of specimen (75 x 75 mm) x 3

Pouring date 11/21/2023 Slump test at 0' -


Mix Design Code Micro-concrete
Composition Cement Water Sand Gravel 1 Gravel 2 Admixture
Type Tec 311 MC - 0/1 6/14
Quantity(Kg/m3) 25 3 7 7
Part of Structure

Production line shed / Vertical Pressure Leaf Filter; Drum Sieve And Soya Cracker / F29(4pces); F11(1pce)
(micro concrete WEBERTEC 311 MC) Complet Kit

30A100_RFI_275 EXT
Number notification Date of receipt 11/24/2023
30A100_RFI_3317 EXT

Curing by Density Strength (Mpa)


Spec. Tag Crushing date Weight (Kg) Load (kN)
days (T/m3) Unit Average
MC-079 1.12 2.65 252.07 44.81
MC-080 8 11/29/2023 1.12 2.65 211.79 37.65 40.60
MC-081 1.05 2.49 221.30 39.34
MC-082 1.07 2.54 291.54 51.83
MC-083 28 12/19/2023 1.07 2.53 254.08 45.17 47.80
MC-084 1.04 2.47 261.08 46.41

Inspection execution result


ACCEPTED ⃣ REJECTED ⃣ POSTPONED ⃣ CANCELLED ⃣
Remarks :

Inspectors for : GEOLAB ENI CONGO ZEROCK

Name

Signature

Date