Submit Tal

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

A-C FIRE PUMP SYSTEMS FP 2.

5
Dimensions – Series 1580 Inline Fire Pumps Page 205
1.5x1.5x7F, 2.5x2.5x7F, 2.5x2.5x9.5F, 3x3x7F, 3x3x9.5F,
4x4x7F, 4x4x9.5F, 6x6x9.5F, 6x6x11F, 8x8x9.5F
March, 2017

Supersedes all previous issues


Submit t al

Jo b/Pro je ct : Re pre se nt at ive :


ESP-Syst e mwize : WIZE-7 14BFA1B Cre at e d O n: 03/06 /2 02 4 Pho ne :
Lo cat io n/Tag: Email:
Engine e r: Submit t e d By: Dat e :
Co nt ract o r: Appro ve d By: Dat e :

In-Line Fire Pump Selection Criteria NFPA Limits


Pump Mo de l: 6 x6 x9.5F-L Rat e d Flo w 500 US gpm 140% He ad o f Rat e d He ad 17 5 psi
No m. Spe e d: 3550 rpm Rat e d He ad 12 5 psi 6 5% He ad at 150% Flo w 81.3 psi
Marke t : List e d Fire Pump Imp. Dia 9.082 in Flo w at 150% 7 50 US gpm
Appro val/List ing: FM/UL Po we r Re quire d at Dut y 7 3.4 hp He ad at 150% 119 psi
Rat e d Efficie ncy 49.5 % Po we r Re q at 150% 82 .6 hp
Fluid Wat e r Efficie ncy at 150% 6 3.1 %
T e mpe rat ure 85 ºF Max BHP 98 hp
Sp. Gravit y 1.000 Clo se d Valve He ad 138 psi

140% He ad o f Rat e d He ad 175PSI

Typical Performance Curve is shown. Fire Pumps are tested to ANSI/HI 14.6 acceptance grade 1U.
Rated Duty Point is guaranteed within the following tolerances: Flow 0% to + 10%, Head 0% to + 6%.
NO OTHER POINTS ARE GUARANTEED. PLEASE CONSULT FACTORY IF NEEDED.

Pe rfo rmance Curve Dat a


Flo w (US gpm) He ad (psi) Efficie ncy (%) Po we r Re quire d (hp) NPSHr (ft )
0 138 0 0 9
12 5 135 2 2 .2 57 .3 9
2 50 131 31.5 6 2 .7 9
37 5 12 7 40.8 6 8.2 9
500 12 5 49.5 7 3.4 8.99
7 50 119 6 3.1 82 .6 10.4
1592 77 7 5.8 94.3 2 7 .1
PERFORMANCE CURVES FP 2.0

500 GPM
OCTOBER 2012

SUPERSEDES ALL PREVIOUS ISSUES

Curves show performance with clear water at 85°F. If specific gravity is other than 1.0, BHP must be corrected.

© 2012 Xylem Inc. A-C Fire Pump is a trademark of Xylem Inc. or one of its subsidiaries.