8/12/2019 Design of Rectangular Water Tank (1)

Design of Rectangular water tank CASE-1 ( L / B < 2 )


Capacity 80000 Litres (given)
Material M20 Grade Concrete (given)
Fe 415 Grade HYSD reinforcement (given)
Solution :-
Provide 6 m x 4 m x 3.5 m tank with free board of 150 mm.
3
Volume = 6 x 4 x 3.35 x 10 = 80400 Litres
L/B= 6/4= 1.5 <2.
The top portion of side walls will be designed as a continuous frame.
bottom 1 m or H / 4 whichever is more is designed as cantilever.
H/4= 3.5 / 4 = 0.875 m
bottom 1 m will be designed as cantilever.
Water pressure at 3.5 - 1 = 2.5 m height from top = 2.5 x YW = 2.5 x 9.8
2
= 24.5 KN / m
3
where Yw is unit weight of water = 9.8 KN / m
To find moment in side walls, moment distribution or kani's method is used. As the
frame is symmetrical about both the axes, only one joint is solved
6m
6m A E

2.5 m F
2
3.5 m 24.5 KN / m

1m

D
2
34.3 KN / m
Elevation Plan

Fixed end moments :-


2
MAB = w x l / 12 =
2
= 24.5 x 6 / 12 = 73.5 KNm

2
MAD = w x l / 12 =
2
= 24.5 x 4 / 12 = -32.66 KNm

Kani's Method :-

- 32.66 73.5
-3/10 40.84 -2/10
0 -12.25 -8.17 0
0 -12.25 -8.17 0
D 0 A 0 B
-57.16 57.16
Rotation factor at Joint A

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 1/242
8/12/2019 Design of Rectangular Water Tank (1)

Relative Rotation Factor


Joint Member ∑K u =(-1/2) k / ∑ K
Stiffness( K )
AB I/6 - 2 / 10
A 5 * I / 12
AD I/4 - 3 / 10

Sum of FEM
MAF = 73.5-32.66
40.84 KNm

F
MAB = MAB + 2 MAB' + MBA'
= 73.5 + 2 x (- 8.17 ) + 0
= 57.16

F
MAD = MAD + 2 MAD' + MDA'
= (- 32.66 ) + 2 x (- 12.25 ) + 0
= -57.16

2
B.M. at centre of long span = w x l / 8 - 57.16
2
= 24.5 x 6 / 8 - 57.16
53.09 KNm

2
B.M. at centre of short span = w x l / 8 - 57.16
2
= 24.5 x 4 / 8 - 57.16
-8.16 KNm

Direct tension in long wall = Yw ( H - h ) x B / 2


= 24.5 x 4 / 2 = 49 KN

Direct tension in short wall = Yw ( H - h ) x L / 2


= 24.5 x 6 / 2 = 73.5 KN

Design of Long Walls :-


At support
M= 57.16 KNm
T= 49 KN Tension on liquid face.
From Table 9-6 Q = 0.306 Assuming d / D = 0.9
D= M/Qxb
6
= 57.16 x 10 / 0.306 x 1000
= 432.2 mm, Assuming d / D = 0.9

Take D = 450 mm d = 450 - 25 - 8


= 417 mm
From Table 9-5

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 2/242
8/12/2019 Design of Rectangular Water Tank (1)

Ast1 for moment = M / σst x j x d


6
= 57.16 x 10 / 150 x 0.872 x 417
2
= 1048 mm

Ast2 for direct tension = T / σ st


3
= 49 x 10 / 150
2
= 327 mm
Total Ast1 + Ast2 = 1048 + 327
2
= 1375 mm
Provide 16 mm O bar
2
spacing of bar = Area of one bar x 1000 / required area in m / m
= 200.96 x 1000 / 1375
= 146.15273 mm
2
Provide 16 mm O bar @ 130 mm C/C…marked(a) = 1546 mm / m.
Larger steel area is provided to match with the steel of short walls.
At centre
M= 53.09 KNm
T= 49 KN tension on remote face
e= M/T= 53.09 / 49
= 1.08 m Line of action of forces lies outsi
i.e.tension is small
E= e+D/2-d b
= 1080 + 450 / 2 - 417
= 888 mm
D
modified moment d
= = 4943.51
x 0.888 KNm
d'
Ast1 for moment = M / σst x j x d E=e+D/2-d
6
= 43.51 x 10 / 190 x 0.89 x 417
2
= 617 mm

Ast2 for direct tension = T / σ st


3
= 49 x 10 / 150
2
= 327 mm

Total Ast1 + Ast2 = 617 + 327 2


= 944 mm
Provide 16 mm O bar
2
spacing of bar = Area of one bar x 1000 / required area in m / m
= 200.96 x 1000 / 944
= 212.88136 mm

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 3/242
8/12/2019 Design of Rectangular Water Tank (1)

2
Provide 16 mm O bar @ 200 mm C/C…marked(b) = 1005 mm
From Table 9-3 minimum reinforcement 0.16 %
Distribution steel = 0.16 / 100 x 1000 x 450
2
= 720 mm
2
On each face = 360 mm
Provide 8 mm O bar
2
spacing of bar = Area of one bar x 1000 / required area in m / m
= 50.24 x 1000 /360
= 139.55556 mm
2
Provide 8 mm O bar @ 130 mm C/C…marked(d) = 385 mm
Vertical Steel ( c)
Provide 10 mm O bar
2
spacing of bar = Area of one bar x 1000 / required area in m / m
= 78.50 x 1000 /360
= 218.05556 mm
2
Provide 10 mm O bar @ 200 mm C/C…marked(c) = 392 mm
Horizontal steel :-
2
Remote face ( b) - Provide 16 mm O @ 200 mm C/C = 1005 mm
2
Liquid face ( d) - Provide 8 mm O @ 130 mm C/C = 385 mm
2
Vertical Steel ( c) - Provide 10 mm O @ 200 mm C/C both faces = 392 mm

Design of short walls :-


At support M= 57.16 KNm
T= 73.5 KN tension on liquid face
From Table 9-5
Ast1 for moment = M / σst x j x d
6
= 57.16 x 10 / 150 2x 0.872 x 417
= 1048 mm

Ast2 for direct tension = T / σ st


3
= 73.5 x 10 / 150
2
= 490 mm
Total Ast1 + Ast2 = 1048 + 490
2
= 1538 mm
Provide 16 mm O bar
2
spacing of bar = Area of one bar x 1000 / required area in m / m
= 200.96 x 1000 / 1538
= 130.6632 mm
2
Provide 16 mm O bar @ 130 mm C/C…marked(b) = 1546 mm / m.

At centre
M= 8.16 KNm
T= 73.5 KN tension on liquid face

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 4/242
8/12/2019 Design of Rectangular Water Tank (1)

From Table 9-5


Ast1 for moment = M / σst x j x d
6
= 8.16 x 10 / 150 x 0.872 x 417
2
= 150 mm

Ast2 for direct tension = T / σ st


3
= 73.5 x 10 / 150
2
= 490 mm
Total Ast1 + Ast2 = 150 + 490
2
= 640 mm
Provide 12 mm O bar
2
spacing of bar = Area of one bar x 1000 / required area in m / m
= 113.04 x 1000 / 640
= 176.625 mm
2
Provide 12 mm O bar @ 130 mm C/C…marked(e) = 869 mm / m.

From Table 9-3 minimum reinforcement 0.16 %


Distribution steel = 0.16 / 100 x 1000 x 450
2
= 720 mm
2
On each face = 360 mm
Provide 8 mm O bar
2
spacing of bar = Area of one bar x 1000 / required area in m / m
= 50.24 x 1000 /360
= 139.55556 mm
2
Provide 8 mm O bar @ 130 mm C/C…marked(d) = 385 mm
Vertical Steel ( c)
Provide 10 mm O bar
2
spacing of bar = Area of one bar x 1000 / required area in m / m
= 78.50 x 1000 /360
= 218.05556 mm
2
Provide 10 mm O bar @ 200 mm C/C…marked(c) = 392 mm .

Horizontal steel :-
2
Remote face ( e) - Provide 12 mm O @ 130 mm C/C = 869 mm
2
Liquid face ( d) - Provide 8 mm O @ 130 mm C/C = 385 mm
2
Vertical Steel ( c) - Provide 10 mm O @ 200 mm C/C both faces = 392 mm

Bottom 1 m will be designed as cantilever


Cantilever moment : -
2
M= Yw x H x h / 6 OR Yw x H / 6 , whichever is greater.
= 9.8 x 3.5 x 1 / 6 = 9.8 x 3.5 / 6
= 5.72 KNm = 5.72 ,tension on liquid face.

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 5/242
8/12/2019 Design of Rectangular Water Tank (1)

From Table 9-5


Ast for moment = M / σst x j x d
6
= 5.72 x 10 / 150 x 0.872 x 417
2
= 105 mm
From Table 9-3 minimum reinforcement 0.16 %
Distribution steel = 0.16 / 100 x 1000 x 450
2
= 720 mm
2
On each face = 360 mm
Provide 10 mm O bar
2
spacing of bar = Area of one bar x 1000 / required area in m /m
= 78.50 x 1000 /360
= 218 mm
2
Provide 10 mm O bar @ 200 mm C/C…marked(c) = 392 mm .
each face
Base slab :-
Base slab is resting on ground. For a water head 3.5 m, provide 150 mm thick slab.
From table 9-3
Minimum steel = 0.229%
= 0.229 / 100 x 1000 x 150
2 2
= 344 mm ,172 mm bothway
Provide 8 mm O bar
2
spacing of bar = Area of one bar x 1000 / required area in m / m
= 50.24 x 1000 /172
= 292 mm
Provide 8 mm O bar @ 290 mm C/C both ways, top and bottom.
2
Ast = 346 mm
Designed section,Elevation etc. are shown in fig.
2
Top slab may be designed as two-way slab as usual for a live load of 1.5 KN / m
Top slab : -
consider 1 m wide strip. Assume 150 mm thick slab.
lx = 4 + 0.15 = 4.15 say 4.5 m
ly = 6 + 0.15 = 6.15 say 6.5 m
2
Dead Load : self 0.15 x 25 = 3.75 KN / m
2
floor finish = 1.0 KN / m
2
Live load = 1.5 KN / m
2
6.25 KN / m

For 1 m wide strip PU = 1.5 x 6.25


= 9.38 KN / m
ly / lx =
6.5 / 4.5
= 1.4
AS Per IS-456-2000,Four Edges Discontinuous,positive moment at mid-span.

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 6/242
8/12/2019 Design of Rectangular Water Tank (1)

Table 26 αx = 0.085
αy = 0.056
2
Mx = αx x w x lx My = αy x w x lx2
2 2
= 0.085 x 9.38 x 4.5 = 0.056 x 9.38 x 4.5

= 16.15
From Table KNm
6-3 ,Q = 2.76 = 10.64 KNm

drequired = M/Qxb
6
= 16.15 x 10 / 2.76 x 1000
= 76.50 mm
dshort = 150 - 15(cover) - 5
= 130 > 76.50 mm …………(O.K.)
dlong = 130 - 10 = 120 mm
Larger depth is provided due to deflection check.
2 6
Mu / b x d (short) = 16.15 x 10 / 1000 x 130 x 130
= 0.96
Pt = 50 1-√1-(4.6 / fck) x (Mu / b x d2)
fy / fck

= 50 1-√1-(4.6 / 20) x (0.96)


415 / 20

= 50 [(1-0.88) x 20 / 415 ]
= 0.29%

Ast (short) = 0.29 x 1000 x 130 / 100


2
= 377 mm
Provide 10 mm O bar
2
spacing of bar = Area of one bar x 1000 / required area in m /m
= 78.50 x 1000 /377
= 208 mm
2
Provide 10 mm O bar @ 210 mm c/c = 374 mm .

2 6
Mu / b x d (long) = 10.64 x 10 / 1000 x 120 x 120
= 0.74
2
Pt

= 50 1- 1-(4.6 / fck) x (Mu / b x d )
fy / fck

= 50 1-√1-(4.6 / 20) x (0.74)


415 / 20

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 7/242
8/12/2019 Design of Rectangular Water Tank (1)

= 50 [(1-0.91) x 20 / 415 ]
= 0.22%

Ast (long) = 0.22 x 1000 x 120 / 100


2
= 264 mm

Provide 8 mm O bar
2
spacing of bar = Area of one bar x 1000 / required area in m / m
= 50.24 x 1000 /264
= 190 mm
2
Provide 8 mm O bar @ 190 mm c/c = 264 mm .

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 8/242
8/12/2019 Design of Rectangular Water Tank (1)

4m

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 9/242
8/12/2019 Design of Rectangular Water Tank (1)

TABLE 9-6
Balanced Design Factors for members in bending
For M20 Grade Concrete Mix
Mild steel HYSD bars
d/D 2 2
Q = M / bD Pt Q = M / bD Pt
0.75 0.3 0.4 0.295 0.289
0.8 0.305 0.37 0.299 0.272

0.85 0.31 0.355 0.302 0.258


0.9 0.314 0.335 0.306 0.246

TABLE 9-5
Members in bending ( Cracked condition )
Coefficients for balanced design

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 10/242
8/12/2019 Design of Rectangular Water Tank (1)

Grade of Grade of σcbc σst


concrete steel 2 2 k j Q
N / mm N / mm
For members less than 225mm thickness and tension on liquid face
M20 Fe250 7 115 0.445 0.851 1.33
Fe415 7 150 0.384 0.872 1.17
For members more than 225mm thickness and tension away from liquid face
M20 Fe250 7 125 0.427 0.858 1.28
Fe415 7 190 0.329 0.89 1.03

ide the section

D/2

e=M/T

TABLE 9-3
Minimum Reinforcement for Liquid Retaining Structures
% of reinforcement
Thickness, mm
Mild Steel HYSD bars
100 0.3 0.24

150 0.286 0.229


200 0.271 0.217
250 0.257 0.206
300 0.243 0.194
350 0.229 0.183
400 0.214 0.171

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 11/242
8/12/2019 Design of Rectangular Water Tank (1)

450 or more 0.2 0.16

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 12/242
8/12/2019 Design of Rectangular Water Tank (1)

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 13/242
8/12/2019 Design of Rectangular Water Tank (1)

10 O @ 210 c/c 8 O @ 190 c/c


150
150 Free board

10 O @ 200 c/c - shape

3500 10 O @ 200 c/c - shape

8 O @ 290 c/c both ways top and bottom


1500 A
1500
150
150
1 : 4 : 8 P.C.C.
150 450 6000 450 150

Elevation
1500
450
1000 16 O @ 130 c/c (a)

16 O @ 200 c/c (b) (c)


10 O @ 200 c/c both faces (c)
(d)
4000 8 O @ 130 c/c (d)
12 O @ 130 c/c (e)

(a) ( a ) 1000
(b) (d)
1000

450

1500 1500

6000

450 450

Section A-A

Table 6-3

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 14/242
8/12/2019 Design of Rectangular Water Tank (1)

2
Limiting Moment of resistance factor Q lim, N / mm
2
2 fy, N / mm
fck N / mm
250 415 500 550
15 2.22 2.07 2.00 1.94

20
25 2.96
3.70 2.76
3.45 2.66
3.33 2.58
3.23
30 4.44 4.14 3.99 3.87

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 15/242
8/12/2019 Design of Rectangular Water Tank (1)

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 16/242
8/12/2019 Design of Rectangular Water Tank (1)

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 17/242
8/12/2019 Design of Rectangular Water Tank (1)

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 18/242
8/12/2019 Design of Rectangular Water Tank (1)

Pt,bal

1.36
0.98

1.2
0.61

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 19/242
8/12/2019 Design of Rectangular Water Tank (1)

Design of Rectangular water tank CASE-2 ( L / B ≥ 2 )


Size of tank : 3.6 m x 8.0 m x 3.0 m high (given)
Material M20 Grade Concrete (given)
Fe 415 Grade HYSD reinforcement (given)
Solution :-
Size of tank : 3.6 m x 8.0 m x 3.0 m high
3
Volume = 3.6 x 8 x 3.0 x 10 = 86400 Litres
L/B= 8 / 3.6 = 2.22 >2.
The long walls are designed as vertical cantilevers from the base.
The short walls are designed as supported on long walls.
If thickness of long walls is 400 mm, the span of the short wall = 3.6 + 0.4 = 4.0 m.
bottom 1 m or H / 4 whichever is more is designed as cantilever.
H/4= 3.0 / 4 = 0.75 m
bottom h = 1 m will be designed as cantilever.

Moments and tensions :


Maximum B.M. in long walls at the base
= (1 / 6 ) x Y w x H3
3
= ( 1 / 6 ) x 9.8 x 3
= 44.1 KNm.

Maximum ( - ve ) B.M. in short walls at support


2
= Yw x ( H - h ) x B / 12
2
= 9.8 x ( 3 - 1 ) x 4 / 12
= 26.13 KNm.

Maximum ( + ve ) B.M. in short walls at centre


2
= Yw x ( H - h ) x B / 16
2
= 9.8 x ( 3 - 1 ) x 4 / 16
= 19.60 KNm.

For bottom portion


2
M= Yw x H x h / 6 OR Yw x H / 6 , whichever is greater
= 9.8 x 3.0 x 1 / 6 = 9.8 x 3.0 / 6
= 4.90 KNm = 4.90 KNm

Direct tension in long wall = Yw x ( H - h ) x B / 2


= 9.8 x ( 3 - 1 ) x 3.6 / 2
= 35.28 KN

Direct tension in short wall= Yw ( H - h ) x 1


= 9.8 x ( 3 - 1 ) x 1
= 19.6 KN
It is assumed that end one metre width of long wall gives direct tension to short walls.

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 20/242
8/12/2019 Design of Rectangular Water Tank (1)

Design of long walls : -


M(-)= 44.1 KNm ( water face )
T= 35.28 KN ( perpendicular to moment steel )
From Table 9-6 Assume d / D = 0.9 Q = 0.306

D= M/Qxb
= √44.1 x 10 6
/ 0.306 x 1000
= 379.6 mm,

Take D = 400 mm d = 400 - 25 - 8


= 367 mm
From Table 9-5 , Ast for Moment
Ast = M / σst x j x d
6
= 44.1 x 10 / 150 x 0.872 x 367
2
= 918.68 mm
Provide 16 mm O bar
2
spacing of bar = Area of one bar x 1000 / required area in m / m
= 200.96 x 1000 / 918.68
= 218.75 mm
2
Provide 16 mm O bar @ 200 mm c/c = 1005 mm .
Note : The design is made at the base. The moment reduces from base to top.For ec
reinforcement can be curtailed or the thickness of wall can also be reduced as we hav
cantilever retaining wall.
From Table 9-3
Distribution steel = 0.171 % for 400 mm depth
As = ( 0.171 / 100 ) x 1000 x 400
2
= 684 mm .
2
on each face = 342 mm . …………………… ( 1 )

Steel required for direct tension


= T / σst
3
= 35.28 x 10 / 150
2
= 235 mm . …………………… ( 2 )
From ( 1 ) and ( 2 ) , minimum steel is sufficient for resisting direct tension.
Provide 8 mm O bar
2
spacing of bar = Area of one bar x 1000 / required area in m / m
= 50.24 x 1000 / 342
= 146.9 mm
2
Provide 8 mm O bar @ 140 mm c/c on each face = 357 mm
on each face

Design of short walls :-

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 21/242
8/12/2019 Design of Rectangular Water Tank (1)

At support M= 26.13 KNm


T= 19.6 KN
From Table 9-5
Ast1 for moment = M / σst x j x d
6
= 26.13 x 10 / 150 x 0.872 x 367
= 544 mm2

Ast2 for direct tension = T / σst


3
= 19.6 x 10 / 150
2
= 131 mm
Total Ast1 + Ast2 = 544 + 131
2
= 675 mm
Provide 12 mm O bar
2
spacing of bar = Area of one bar x 1000 / required area in m / m
= 113.04 x 1000 / 675
= 167.47 mm
2
Provide 12 mm O bar@160 mm c/c = 706 mm .

1000

203.56
400 367
163.44

checking :
modular ratio m = 280 / 3 x σcbc
= 13.33
2
b x D / 2 + Ast ( m - 1 ) x d
x=
b x D + ( m - 1 ) x Ast

2
= ( 1000 x 400 / 2 ) + ( 706 x ( 13.33 - 1 ) x 367 )
( 1000 x 400 ) + ( ( 13.33 - 1 ) x 706 )

= 203.56 mm

D-x= 196.44 mm
d-x= 163.44 mm
AT = b x D + ( m - 1 ) x Ast
= 1000 x 400 + (13.33 - 1 ) x 706
2
= 408705 mm

Ixx = ( 1 / 3 ) x b x ( x3 + ( D - x )3 ) + ( m - 1 ) x Ast x ( d - x )2

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 22/242
8/12/2019 Design of Rectangular Water Tank (1)

3 3 2
= ( 1 / 3 ) x 1000 x ( 203.56 + 196.44 ) + ( 13.33 - 1 ) x 706 x 163.44
= 5.34E+09 + 2.33E+08
4
= 5.57E+09 mm

fct = T / AT
= 19.6 x 10 3 / 408705
2
= 0.048 N / mm

fcbt = M x ( d - x ) / Ixx
6 9
= 26.13 x 10 x 163.44 / 5.57 x 10
2
= 0.767 N / mm
check :
≤1
( fct / σct ) + ( f cbt / σcbt )
( 0.048 / 1.2 ) + ( 0.767 / 1.7 ) ≤ 1 From Table 9-2
0.04 + 0.4512 ≤ 1
0.4912 ≤ 1 ………………….. ( O. K. )
At centre :
M= 19.6 KNm
T= 19.6 KN
From Table 9-5
Ast1 for moment = M / σst x j x d
6
= 19.6 x 10 / 150 x 0.872 x 367
2
= 408 mm

A for direct tension = T / σst


st2
3
= 19.6 x 10 / 150
2
= 131 mm
Total Ast1 + Ast2 = 408 + 131
2
= 539 mm
Provide 12 mm O bar
2
spacing of bar = Area of one bar x 1000 / required area in m / m
= 113.04 x 1000 / 539
= 209.72 mm
2
Provide 12 mm O bar @ 200 mm c/c = 565 mm .

From Table 9-3


Distribution steel = 0.171 % for 400 mm depth
As = ( 0.171 / 100 ) x 1000 x 400
2
= 684 mm .
2
on each face = 342 mm . …………………… ( 1 )

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 23/242
8/12/2019 Design of Rectangular Water Tank (1)

Steel required for direct tension


= T / σst
3
= 19.6 x 10 / 150
2
= 131 mm . …………………… ( 2 )
From ( 1 ) and ( 2 ) , minimum steel is sufficient for resisting direct tension.
Provide 8 mm O bar
2
spacing of bar = Area of one bar x 1000 / required area in m / m
= 50.24 x 1000 / 342
= 146.9 mm
2
Provide 8 mm O bar @ 140 mm c/c on each face = 357 mm
on each face
Bottom cantilever
M = 4.9 KNm
From Table 9-5
Ast = M / σst x j x d
6
= 4.9 x 10 / 150 x 0.872 x 367
2
= 102 mm
2
Minimum steel = 342 mm on each face.
2
Provide 8 mm O bar @ 140 mm c/c on each faces = 357 mm
on each face

Base slab :-
Base slab is resting on ground. For a water head 3 m, provide 150 mm thick slab.
From table 9-3
Minimum steel = 0.229%
= 0.229 / 100 x 1000 x 150
2 2

Provide 8 mm O bar = 344 mm ,172 mm bothway


2
spacing of bar = Area of one bar x 1000 / required area in m / m
= 50.24 x 1000 /172
= 292 mm
Provide 8 mm O bar @ 290 mm C/C both ways, top and bottom.
2
Ast = 346 mm
Designed section,Elevation etc. are shown in fig.
2
Top slab may be designed as a one-way slab as usual for a live load of 1.5 KN / m
Top slab : -
consider 1 m wide strip. Assume 150 mm thick slab.
lx = 3.6 + 0.4 = 4 say 4 m
ly = 8 + 0.15 = 8.15 say 8.5 m
2
Dead Load : self 0.15 x 25 = 3.75 KN / m
2
floor finish = 1.0 KN / m
2
Live load = 1.5 KN / m
2
6.25 KN / m

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 24/242
8/12/2019 Design of Rectangular Water Tank (1)

For 1 m wide strip


PU = 1.5 x 6.25
= 9.38 KN / m

2
Maximum moment = 9.38 x 4 / 8
= 18.76 KNm

Maximum shear = 9.38 x 3.6 / 2


= 16.88 KN
From Table 6-3 ,Q = 2.76
drequired = M/Qxb

= √18.76 x 10 6
/ 2.76 x 1000
= 82.44 mm
dprovided = 150 - 15(cover) - 6
= 129 > 82.44 …………(O.K.)
Larger depth is provided due to deflection check.
Design for flexure :
2 6
Mu / b x d = 18.76 x 10 / 1000 x 129 x 129
= 1.13
Pt = 50 1-√1-(4.6 / fck) x (Mu / b x d2)
fy / fck

= 50 1-√1-(4.6 / 20) x (1.13)


415 / 20

= 50 [(1-0.86) x 20 / 415 ]
= 0.34%

Ast = 0.34 x 1000 x 129 / 100


2
= 439 mm
Provide 8 mm O bar
2
spacing of bar = Area of one bar x 1000 / required area in m /m
= 50.24 x 1000 /439
= 114 mm
2
Provide 8 mm O bar @ 110 mm c/c = 457 mm .
Minimum steel is 0.15 % for mild steel and 0.12 % for HYSD Fe415 reinforcement
Distribution steel = ( 0.12 / 100 ) x 1000 x 150
2
= 180 mm

Provide 6 mm O bar
2
spacing of bar = Area of one bar x 1000 / required area in m / m
= 28.26 x 1000 /180

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 25/242
8/12/2019 Design of Rectangular Water Tank (1)

= 157 mm
2
Provide 6 mm O bar @ 150 mm c/c = 188 mm .

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 26/242
8/12/2019 Design of Rectangular Water Tank (1)

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 27/242
8/12/2019 Design of Rectangular Water Tank (1)

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 28/242
8/12/2019 Design of Rectangular Water Tank (1)

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 29/242
8/12/2019 Design of Rectangular Water Tank (1)

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 30/242
8/12/2019 Design of Rectangular Water Tank (1)

nomy, the
e done for

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 31/242
8/12/2019 Design of Rectangular Water Tank (1)

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 32/242
8/12/2019 Design of Rectangular Water Tank (1)

Table 9-2
Permissible concrete stresses in calculations relating
to resistance to cracking
2
Grade of Permissible stresses in N / mm
Direct Tension due to Shear stress
concrete
tension σct bending σcbt v= V / b j d

M15 1.1 1.5 1.5


M20 1.2 1.7 1.7
M25 1.3 1.8 1.9
M30 1.5 2.0 2.2
M35 1.6 2.2 2.5
M40 1.7 2.4 2.7

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 33/242
8/12/2019 Design of Rectangular Water Tank (1)

8 O @ 110 c/c 6 O @ 150 c/c

150

12 O @ 200 c/c

8 O @ 140 c/c - shape


3000
8 O @ 140 c/c
8 O @ 290 c/c both ways top and bottom
2000
2000
150
150
1 : 4 : 8 P.C.C. 150
150 400 8000 400

Section A-A
2000 B 8 O @ 140 mm c/c
400
900 16 O @ 200 c/c ( chipiya )
12 O @ 160 c/c(chipiya)

8 O @ 140 c/c (chipiya)


3600 8 O @ 140 c/c
12 O @ 200 c/c

900
900
400

2000 2000
B
8000

400 Sectional plan 400

8 O @ 110 c/c 6 O @ 150 c/c

150

16 O @ 200 c/c ( chipiya )

8 O @ 140 c/c
3000

Base details not

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 34/242
8/12/2019 Design of Rectangular Water Tank (1)

900 900 shown for clarity


150
150
150 400 3600 400 150

Section B- B

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 35/242
8/12/2019 Design of Rectangular Water Tank (1)

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 36/242
8/12/2019 Design of Rectangular Water Tank (1)

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 37/242
8/12/2019 Design of Rectangular Water Tank (1)

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 38/242
8/12/2019 Design of Rectangular Water Tank (1)

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 39/242
8/12/2019 Design of Rectangular Water Tank (1)

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 40/242
8/12/2019 Design of Rectangular Water Tank (1)

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 41/242
8/12/2019 Design of Rectangular Water Tank (1)

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 42/242
8/12/2019 Design of Rectangular Water Tank (1)

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 43/242
8/12/2019 Design of Rectangular Water Tank (1)

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 44/242
8/12/2019 Design of Rectangular Water Tank (1)

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 45/242
8/12/2019 Design of Rectangular Water Tank (1)

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 46/242
8/12/2019 Design of Rectangular Water Tank (1)

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 47/242
8/12/2019 Design of Rectangular Water Tank (1)

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 48/242
8/12/2019 Design of Rectangular Water Tank (1)

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 49/242
8/12/2019 Design of Rectangular Water Tank (1)

Design of simply supported one way slab


effective span = 4 m supported on masonry wall of 230 mm thickness ( given )
Live load = 2.5 KN / m2 ( given )
Floor finish = 1 KN / m2 ( given )
material M15 grade concrete ( given )
HYSD reinforcement grade Fe415 ( given )
solution : -
Assume 0.4 % steel , a trial depth by deflection criteria
IS 456-2000 clause 23.2.1 fig-4 ,for tension reinforcement
modification factor = 1.26
for simply supported, basic span / effective depth ratio = 20
( span / d ) ratio permissible = 1.26 x 20
= 25.2
drequired = 4000 / 25.2
= 158.7 mm
D = 158.7 + 15 ( cover ) + 5 ( assume 10 O bar )
= 178.7 mm
Assume an overall depth = 180 mm
2
DL = 0.18 x 25 = 4.5 KN / m
2
Floor finish = 1.0 KN / m
2
Live load = 2.5 KN / m
2
Total 8.0 KN / m
Factored load = 1.5 x 8 = 12 KN / m
Consider 1 m length of slab
Maximum moment = w x l2 / 8
= 12 x 42 / 8
= 24 KNm
Maximum shear = w x l / 2
= 12 x 4 / 2
= 24 KN
Design for flexure : -
d = 180 - 15 - 5
= 160 mm

2 6 2
Mu / b x d = 24 x 10 / 1000 x (160)
= 0.94
Pt = 50 1 -√1-(4.6 / fck) x (Mu / b x d )
2

fy / fck

= 50 1-√1-(4.6 / 15) x (0.94)


415 / 15

= 50 [(1-0.84) x 15 / 415 ]
= 0.289%

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 50/242
8/12/2019 Design of Rectangular Water Tank (1)

Ast = 0.289 x 1000 x 160 / 100


2
= 462 mm
Provide 10 mm O bar
2
spacing of bar = Area of one bar x 1000 / required area in m / m
= 78.50 x 1000 /462
= 170 mm
2
Provide 10 mm O bar @ 170 mm c/c = 462 mm .
Half the bars are bent at 0.1 l = 400 mm , and
2
remaining bars provide 231 mm area
100 x As / ( b x D ) = 100 x 231 / ( 1000 x 180 )
= 0.128 > 0.12 % ( minimum steel for Fe415)
i.e. remaining bars provide minimum steel. Thus, half the bars may be bent up.
Distribution steel = ( 0.12 /100 ) x 1000 x 180
2
= 216 mm
Maximum spacing = 5 x 160 = 800 or 450 mm i.e. 450 mm
Provide 8 mm O bar
2
spacing of bar = Area of one bar x 1000 / required area in m /m
= 50.24 x 1000 /216
= 233 mm
2
Provide 8 mm O bar @ 230 mm c/c = 218 mm .
Check for shear : -
Vu = 24 KN
Actual Shear stress = Vu / b x d
3
= 24 x 10 / 1000 x 160
2
= 0.150 N / mm <( C ) N / mm
2
( too small )
For bars at support
d = 160 mm
As = 231 mm .
100 x As / b x d = 100 x 231 / 1000 x 160
= 0.144
Design shear strength c = 0.85 √ 0.8 x fck ( √ 1 + 5 x β - 1 )
6xβ
β = 0.8 x fck / 6.89 Pt , but not less than 1.0
= 0.8 x 15 / 6.89 x 0.144

= 12.1
Design shear strength = 0.85 √ 0.8 x 15 ( √ 1 + 5 x 12.1 - 1 )
c
6 x 12.1
= 0.277
IS 456-2000 Table 19 from table 7-1
2
for Pt = 0.144 c = 0.28
N / mm

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 51/242
8/12/2019 Design of Rectangular Water Tank (1)

IS 456-2000 clause 40.2.1.1 25 difference -0.05


k = 1.24 for 180 mm slab depth 20 difference ? -0.04
Design shear strength = 1.24 x 0.28
2
= 0.347 N / mm ……………….( O.K.)
Check for development length : -

Assuming L0 = 8 O (HYSD Fe415 steel ) For continuing bars


As = 231 mm
Mu1 = 0.87 x fy x Ast x d { 1 - ( fy x Ast / fck x b x d ) } OR
= 0.87 x 415 x 231 x 160 { 1 - (415 x 231 / 15 x 1000 x 160 ) }
= 13.34 { 1- 0.0399 }
= 12.812 KNm

Vu = 24 KN
Development length of bars Ld = O σs / 4 x bd = 56 O ( from Table 7-6 )
1.3 x ( Mu1 / Vu ) + L0 ≥ Ld
6 3
1.3 x ( 12.81 x 10 / 24 x 10 ) + 8 O ≥ 56 O
693.875 + 8 O ≥ 56 O
48 O ≤ 693.88
which gives O ≤ 14.46 mm ……………….( O.K.)
Check for deflection : -
Basic ( span / d ) ratio = 20
Pt = 100 x Ast / b x d = 100 x 462 / 1000 x 160
= 0.289
IS 456-2000 clause 23.2.1 fig-4 ,for tension reinforcement
modification factor = 1.42
( span / d ) ratio permissible = 1.42 x 20
= 28.4
Actual (span / d ) ratio = 4000 / 160
= 25.00 < 28.4 ……………….( O.K.)
The depth could be reduced
Check for cracking : -
IS 456-2000 , clause 26.3.3
Main bars : maximum spacing permitted = 3 x effective depth of slab or 300 mm

spacing provided = 170 mm =3<x 160mm= 480


300 mm
……………….( or 300O.m
Distribution bars : maximum spacing permitted = 5 x effective depth of slab or
= 5 x 160 = 800 mm
spacing provided = 230 mm < 450 mm ……………….( O.
For tying the bent bars at top , provide 8 mm O @ 230 mm c/c

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 52/242
8/12/2019 Design of Rectangular Water Tank (1)

NOTE : -
If clear span = 3.77 m , effective span = 3.77 + 0.23 = 4 m OR
effective span = 3.77 + 0.16 ( effective depth ) = 3.93 m

0.6 % for mild steel reinforcement and 0.3 to 0.4 % for HYSD Fe415 grade
reinforcement
NOTE : -

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 53/242
8/12/2019 Design of Rectangular Water Tank (1)

For mild steel minimum reinforcement 0.15 %

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 54/242
8/12/2019 Design of Rectangular Water Tank (1)

For checking development l


may be assumed as 8 O for
Pt = 100 x As / b x d bars ( usually end anchorag
provided ) and 12 O for mild
= 100 x 231 / 1000 x 160
U hook is provided usually
= 0.14
anchorage length is 16 O.
From equation
Pt = 50 1 -√1-(4.6 / fck) x (Mu / b x d )
2

fy / fck
2
we get , Mu1 / b x d = 0.49
2 -6
Mu1 = 0.49x 1000 x 160 x 10
= 12.54 KNm

160
180

8 O @ 230 c/c
400 10 O @ 170 c/c 400
( alternate bent )
4000

whichever is small

.) i.e. 300 mm
450 mm whichever is small
or 450 mm i.e. 450 mm
.)

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 55/242
8/12/2019 Design of Rectangular Water Tank (1)

If ly / lx ≥ 2 ,called one way slab provided that


it is supported on all four edges . Note that , if
all four edge is not supported and l y / lx < 2 ,
then also it is one-way slab,If ly / lx < 2 , called
two-way slab.provided that it is supported on
all four edges.

IS 456-2000 clause 22.2


Effective Span
( a ) Simply Supported Beam or Slab -
The effective span of a member that is not built integrally with its
supports shall be taken as clear span plus the effective depth of
slab or beam or centre to centre of supports , whichever is less.
( b )Continuous Beam or Slab - In the case of
continuous beam or slab, if the width of the

support is less than l/12 of the clear span, the


effective span shall be as in (a). If the
supports are wider than I/12 of the clear span
or 600 mm whichever is less, the effective span
shall be taken as under:
1) For end span with one end fixed and the
other continuous or for intermediate spans,
the effective span shall be the clear span
between supports;
2) For end span with one end free and the other
continuous, the effective span shall be equal
to the clear span plus half the effective depth
of the beam or slab or the clear span plus
half the width of the discontinuous support,
whichever is less;
3) In the case of spans with roller or rocket
bearings, the effective span shall always be
the distance between the centres of bearings.
( c )Cantilever-The effective length of a cantilever
shall be taken as its length to the face of the
support plus half the effective depth except

where it forms the end of a continuous beam


where the length to the centre of support shall
be taken.
( d )Frames-In the analysis of a continuous frame,
centre to centre distance shall be used.

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 56/242
8/12/2019 Design of Rectangular Water Tank (1)

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 57/242
8/12/2019 Design of Rectangular Water Tank (1)

ngth , l0
HYSD
is not
steel (
hose

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 58/242
8/12/2019 Design of Rectangular Water Tank (1)

Design of Cantilever one way slab


used for residential purpose
at the free end of slab S 1 ,concrete parapet of 75 mm thick and 1 m high.
material M15 grade concrete ( given )
mild steel grade Fe250 ( given )
Live Load As per IS 875
Solution : -
2
For slab S2 live load = 2 KN /m
2
For slab S1 live load = 3 KN /m ( Balcony slab )
Assume 120 mm thick slab DL LL ly =
2
For S2 self load = 0.12 x 25 = 3 0 KN / m
2
floor finish = 1 0 KN / m
2
live load = 0 2 KN / m
2
Total 4 2 KN / m
2
Pu = 1.5 ( 4 + 2 ) = ( 6 + 3 ) KN / m
DL LL
2
For S1 self load = 0.12 x 25 = 3 0 KN / m
2
floor finish = 1 0 KN / m
2
live load = 0 3 KN / m
2
Total 4 3 KN / m
2
Pu = 1.5 ( 4 + 3 ) = (6 + 4.5) KN / m
Weight of parapet 0.075 x 25 x 1 = 1.875 KN / m
Pu = 1.5 x 1.875 = 2.8 KN / m
Consider 1 m long strip
(1) To get maximum positive moment in slab S 2 only dead load on slab
S1 and total load on slab S2 shall be considered
9 KN/m 6 KN/m

S
S2 S1

A 3m B 1.2m C

(a) Loads for maximum positive moment


9 KN/m 10.5 KN/m 2.8 KN

S2 S1

A 3m B 1.2m C

(b) Loads for maximum negative


moment,maximum shear for cantilever span
and maximum reaction at support B
considering fig (a)
cantilever moment = wx l2 / 2
2
= 6 x 1.2 / 2

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 59/242
8/12/2019 Design of Rectangular Water Tank (1)

= 4.32 KNm
shear = Reaction at A = w x l / 2 - Moment @ B at distance 3 m
= 9 x 3 / 2 - 4.32 / 3
= 12.06 KN
Point of zero shear from A = 12.06 ( KN ) / 9 ( KN / m )
= 1.34 m
2
Maximum positive moment = 12.06 x 1.34 - W x l / 2
2
= 12.06 x 1.34 - 9 x 1.34 / 2
= 8.08 KNm
(2) To get maximum negative moment and maximum shear at B,
the slab is loaded with full loads as shown in fig (b)
2
Maximum negative moment = w x l + w x l / 2
2
= 2.8 x 1.2 + 10.5 x 1.2 / 2
= 10.92 KNm
Maximum shear at B
Vu,BA = w x l / 2 + Moment @ B at distance 3 m
= 9 x 3 / 2 + 10.92 / 3
= 17.14 KN
Vu,BC = w x l + 2.8
= 10.5 x 1.2 + 2.8
= 15.4 KN
Moment steel :
Maximum moment = 10.92 KNm
From Table 6-3 Q = 2.22
drequired = √M / Q x b
= √10.92 x 10
6
/ 2.22 x 1000
= 70.14 mm,
dprovided = 120 - 15 - 6 ( assume 12 O bar )
= 99 mm, ……………….( O.K.)
2 6 2
Mu / b x d ( + ) = 8.08 x 10 / 1000 x (99)
= 0.82
Pt = 50 1 -√1-(4.6 / fck) x (Mu / b x d )
2

fy / fck

= 50 1-√1-(4.6 / 15) x (0.82)


250 / 15

= 50 [(1-0.865) x 15 / 250 ]
= 0.405%

Ast ( + ) = 0.405 x 1000 x 99 / 100


2
= 401 mm

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 60/242
8/12/2019 Design of Rectangular Water Tank (1)

Provide 10 mm O bar
2
spacing of bar = Area of one bar x 1000 / required area in m / m
= 78.5 x 1000 / 401
= 195.76 mm
2
Provide 10 mm O bar@170 mm c/c = 462 mm . ( alternate bent up )
6 2
Mu / b x d2 ( - ) = 10.92 x 10 / 1000 x (99)
= 1.11
Pt = 50 1 -√1-(4.6 / fck) x (Mu / b x d )
2

fy / fck

= 50 1-√1-(4.6 / 15) x (1.11)


250 / 15

= 50 [(1-0.812) x 15 / 250 ]
= 0.564%

Ast ( - ) = 0.564 x 1000 x 99 / 100


2
= 558 mm
Provide 10 mm O bar
2
Provide 10 mm O bar@340 mm c/c = 231 mm . ( bent bars extended )
Area provided = Area of one bar x 1000 / spacing of bar in m
= 78.5 x 1000 / 340
2
= 231 mm
remaining area = 558 - 231
2
= 327 mm
Provide 12 mm O bar
spacing of bar = Area of one bar x 1000 / required area in m 2 / m
= 113.04 x 1000 / 327
= 346 mm
2
Provide 12 mm O bar@340 mm c/c = 332 mm . ( Extra )
2 2
Total 231 + 332 mm = 563 mm steel provided
Note that at simple support , the bars are bent at 0.1 l whereas at continuity of slab it
is bent at 0.2 l
For mild steel minimum reinforcement 0.15 %
Distribution steel = ( 0.15 /100 ) x 1000 x 120
2
= 180 mm .
Provide 6 mm O bar
2
spacing of bar = Area of one bar x 1000 / required area in m / m
= 28.26 x 1000 / 180
= 157 mm
2
Provide 6 mm O bar@150 mm c/c = 188 mm .
For negative moment reinforcement
Development length of bars L d = O σs / 4 x bd ( from Table 7-6 )

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 61/242
8/12/2019 Design of Rectangular Water Tank (1)

= O x 0.87 x 250 / 4 x 1
= 54.4 O
Ld = 54.4 x ( 10 + 12 ) / 2
= 598 mm. say 600 mm
As a thumb rule, a bar shall be given an anchorage equal to the length of

the cantilever.
Check for development length : -
Assuming L0 = 12 O (mild steel )
2
At A , Pt = 100 x As / b x d Half bars bent = 462 / 2 = 231 mm )
= 100 x 231 / 1000 x 99
= 0.233
From equation OR
Pt = 50 1 -√1-(4.6 / fck) x (Mu / b x d )
2
Mu1 = 0.87 x fy
fy / fck = 0.87 x 25
2
we get , Mu1 / b x d = 0.487 = 4.974
2 -6
Mu1 = 0.487 x 1000 x 99 x 10 = 4.78
= 4.77 KNm
Vu = 12.06 KN
Development length of bars L d = O σs / 4 x bd = O x 0.87 x 250 / 4 x 1 =54.4 O
1.3 x ( Mu1 / Vu ) + L0 ≥ Ld
6 3
1.3 x ( 4.77 x 10 / 12.06 x 10 ) + 12 O ≥ 54.4 O
514.18 + 12 O ≥ 54.4 O
42.4 O ≤ 514.18
which gives O ≤ 12.13 mm ……………….( O.K.)
2
At B , Pt = 100 x As / b x d Half bars bent = 462 / 2 = 231 mm )
= 100 x 231 / 1000 x 99
= 0.233
From equation OR
Pt = 50 1 -√1-(4.6 / fck) x (Mu / b x d )
2
Mu1 = 0.87 x fy
fy / fck = 0.87 x 25
2
we get , Mu1 / b x d = 0.487 = 4.974
2 -6
Mu1 = 0.487 x 1000 x 99 x 10 = 4.78
= 4.77 KNm
Near point of contraflexure i.e. 0.15 x l from B
Vu = 17.14 - ( 0.15 x 3 ) x 9 = 13.09 KN
Development length of bars L d = O σs / 4 x bd = O x 0.87 x 250 / 4 x 1 =54.4 O
1.3 x ( Mu1 / Vu ) + L0 ≥ Ld
6 3
1.3 x ( 4.77 x 10 / 13.09 x 10 ) + 12 O ≥ 54.4 O
473.72 + 12 O ≥ 54.4 O
42.4 O ≤ 473.72
which gives O ≤ 11.2 mm ……………….( O.K.)

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 62/242
8/12/2019 Design of Rectangular Water Tank (1)

Check for shear : -


Span AB :
At A , Vu,AB = 12.06 KN ( for maximum loading )
At B , shear at point of contraflexure = 13.09 KN
Use Vu = 13.09 KN
Shear stress v = Vu / b x d
3
= 13.09 x 10 / 1000 x 99
= 0.132 N / mm < c ……………….( O.K.)
Pt = 100 x As / b x d = 100 x 231 / 1000 x 99
= 0.233
Design shear strength c = 0.85 √ 0.8 x fck ( √ 1 + 5 x β - 1 )
6xβ
β = 0.8 x fck / 6.89 Pt , but not less than 1.0
= 0.8 x 15 / 6.89 x 0.233
= 7.47
Design shear strength c = 0.85 √ 0.8 x 15 ( √ 1 + 5 x 7.47 - 1 )
6 x 7.47
= 0.34
IS 456-2000 Table 19 from table 7-1
2
for Pt = 0.233 c = 0.34
N / mm
IS 456-2000 clause 40.2.1.1 0.1 difference 0.07
k = 1.3 for 120 mm slab depth 0.02 difference ? 0.014
Design shear strength = 1.3 x 0.34
2
= 0.442 N / mm > v ……………….( O.K.)
Span BC :

Vu = 17.14 KN
Shear stress v = Vu / b x d
3
= 17.14 x 10 / 1000 x 99
2
= 0.173 N / mm < c ……………….( O.K.)
Pt = 100 x As / b x d = 100 x 563 / 1000 x 99
= 0.569
Design shear strength c = 0.85 √ 0.8 x fck ( √ 1 + 5 x β - 1 )
6xβ
β = 0.8 x fck / 6.89 Pt , but not less than 1.0
= 0.8 x 15 / 6.89 x 0.569
= 3.06
Design shear strength = 0.85 √ 0.8 x 15 ( √ 1 + 5 x 3.06 - 1 )
c
6 x 3.06
= 0.487
IS 456-2000 Table 19 from table 7-1
2
for Pt = 0.569 c = 0.48
N / mm

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 63/242
8/12/2019 Design of Rectangular Water Tank (1)

IS 456-2000 clause 40.2.1.1 0.25 difference 0.08


k = 1.3 for 120 mm slab depth 0.181 difference ? 0.0579
Design shear strength = 1.3 x 0.48
2
= 0.624 N / mm > v ……………….( O.K.)
Check for deflection : -
For span AB :
Basic ( span / d ) ratio = 20
Pt = 100 x Ast / b x d = 100 x 462 / 1000 x 99
= 0.467
IS 456-2000 clause 23.2.1 fig-4 ,for tension reinforcement
modification factor = 2
( span / d ) ratio permissible = 2 x 20
= 40
Actual (span / d ) ratio = 3000 / 99
= 30.30 < 40 ……………….( O.K.)
For span BC :
Basic ( span / d ) ratio = 7
Pt = 100 x Ast / b x d = 100 x 563 / 1000 x 99
= 0.569
IS 456-2000 clause 23.2.1 fig-4 ,for tension reinforcement
modification factor = 1.8
( span / d ) ratio permissible = 1.8 x 7
= 12.6
Actual (span / d ) ratio = 1200 / 99
= 12.12 < 12.6 ……………….( O.K.)
Check for cracking : -
IS 456-2000 , clause 26.3.3
(1) Main bars : maximum spacing permitted = 3 x effective depth of slab or 300 mm
= 3 x 99 = 297 mm or 300 m
spacing provided = 170 mm < 297 mm ……………….( O.K
(2 )Distribution bars : maximum spacing permitted = 5 x effective depth of slab or
= 5 x 99 = 495 mm
spacing provided = 150 mm < 450 mm ……………….( O.K

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 64/242
8/12/2019 Design of Rectangular Water Tank (1)

S3 Column 300 x 300


1.2m

0.15m B3

B2 B1
1m high parapet
6m S2 S1

B4
0.15m

0.15m 0.15m
lx = 3m 1.2m

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 65/242
8/12/2019 Design of Rectangular Water Tank (1)

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 66/242
8/12/2019 Design of Rectangular Water Tank (1)

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 67/242
8/12/2019 Design of Rectangular Water Tank (1)

Ast x d ( 1 - f y x Ast / b x d x fck )


-6
0 x 231 x 99 ( 1 - 250 x 231 / 1000 x 99 x 15 ) x 10
( 1 - 0.0389 )

KNm

Ast x d ( 1 - f y x Ast / b x d x fck )


-6
0 x 231 x 99 ( 1 - 250 x 231 / 1000 x 99 x 15 ) x 10
( 1 - 0.0389 )
KNm

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 68/242
8/12/2019 Design of Rectangular Water Tank (1)

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 69/242
8/12/2019 Design of Rectangular Water Tank (1)

10 O @ 340 c/c (bent)


+ 12 O @ 340 c/c (extra)

1200 1200

120 125

10 O @ 170 c/c
6 O @ 150 c/c
6 O @ 150 c/c

300 600
150 3000 150 1200

hichever is small
i.e. 297 mm
.)
450 mm whichever is small
or 450 mm i.e. 450 mm
.)

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 70/242
8/12/2019 Design of Rectangular Water Tank (1)

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 71/242
8/12/2019 Design of Rectangular Water Tank (1)

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 72/242
8/12/2019 Design of Rectangular Water Tank (1)

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 73/242
8/12/2019 Design of Rectangular Water Tank (1)

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 74/242
8/12/2019 Design of Rectangular Water Tank (1)

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 75/242
8/12/2019 Design of Rectangular Water Tank (1)

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 76/242
8/12/2019 Design of Rectangular Water Tank (1)

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 77/242
8/12/2019 Design of Rectangular Water Tank (1)

Ast = 0.208 x 1000 x 120 / 100


2
= 250 mm
Provide 8 mm O bar
2
spacing of bar = Area of one bar x 1000 / required area in m / m
= 50.24 x 1000 / 250
= 200.96 mm
2
Provide 8 mm O bar@ 200 mm c/c = 251 mm .
2 6 2
Mu / b x d ( - ) = 13.66 x 10 / 1000 x (130)
= 0.81
Pt = 50 1 -√1-(4.6 / fck) x (Mu / b x d )
2

fy / fck

= 50 1-√1-(4.6 / 15) x (0.81)


415 / 15

= 50 [(1-0.867) x 15 / 415 ]
= 0.240%

Ast = 0.24 x 1000 x 130 / 100


2
= 312 mm
Provide 8 mm O bar
2
spacing of bar = Area of one bar x 1000 / required area in m / m
= 50.24 x 1000 / 312
= 161 mm
2
Provide 8 mm O bar@ 150 mm c/c = 335 mm .
For HYSD Fe415
Minimum steel = ( 0.12 / 100 ) x 1000 x 150
2
= 180 mm
At discontinuous edges 4 and 5 , 50 % of the positive steel is required at top
= ( 1 / 2 ) x 251
2
= 126 mm
This is less than minimum , therefore , use minimum steel at location 4 and 5 .
Provide 8 mm O bar
2
spacing of bar = Area of one bar x 1000 / required area in m / m
= 50.24 x 1000 / 180
= 279.11 mm
2
Provide
More steel8 is
mm O bar@
provided to260 mmwith
match c/c the
= 193 mm .
torsion reinforcement.
In edge strip , minimum reinforcement is provided equal to 8 mm O @ 260 mm c/c.
Torsion steel :-
At corner A , steel required = ( 3/4 ) x 250
2
= 188 mm .
Provide 8 mm O bar

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 78/242
8/12/2019 Design of Rectangular Water Tank (1)

2
spacing of bar = Area of one bar x 1000 / required area in m / m
= 50.24 x 1000 / 188
= 267.23 mm
2
Provide 8 mm O bar@ 260 mm c/c = 193 mm .
This will be provided by minimum steel of edge strip,
At corner B , steel required = ( 1/2 ) x 188
2
= 94 mm .
Provide 8 mm O bar
2
spacing of bar = Area of one bar x 1000 / required area in m / m
= 50.24 x 1000 / 180
= 279.11 mm
2
Provide 8 mm O bar@ 260 mm c/c = 193 mm .
This will be provided by minimum steel .
Note that positive reinforcements are not curtailed because if they are curtailed , the
remaining bars do not provide minimum steel.
Check for shear : -
At point 1 or 3
S.F. = w x l / 2 + Moment @ point 1 or 3 in that span
= 11.625 x 5 / 2 + 13.66 / 5
= 31.795 KN
100 x As / b x d = 100 x 335 / ( 1000 x 130 )
= 0.258
from table 7-1
2
for Pt = 0.258 , c = 0.354 N / mm 0.25 differen 0.11
IS 456-2000 clause 40.2.1.1 0.242 differe ? -0.1065
k = 1.3 for 150 mm slab depth
Design shear strength = 1.3 x 0.354
= 0.460 N / mm2 ……………….( O.K.)
OR
Design shear strength c = 0.85 √ 0.8 x fck ( √ 1 + 5 x β - 1 )
6xβ
β = 0.8 x fck / 6.89 Pt , but not less than 1.0
= 6.75
Design shear strength c = 0.85 √ 0.8 x 15 ( √ 1 + 5 x 6.75 - 1 )
6 x 6.75
= 0.356
IS 456-2000 clause 40.2.1.1
k = 1.3 for 150 mm slab depth
Design shear strength = 1.3 x 0.356
2
= 0.463 N / mm ……………….( O.K.)
Actual shear stress = Vu / b x d
3
= 31.795 x 10 / ( 1000 x 130 )
2
= 0.245 N / mm < c ……………….( O.K.)

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 79/242
8/12/2019 Design of Rectangular Water Tank (1)

At point 4 or 5
S.F. = w x l / 2
= 11.625 x 5 / 2
= 29.06 KN
100 x As / b x d = 100 x 251 / ( 1000 x 120 )

= 0.209
from table 7-1
2
for Pt = 0.209 , c = 0.321 N / mm 0.1 differenc 0.07
IS 456-2000 clause 40.2.1.1 0.041 differe ? -0.0287
k = 1.3 for 150 mm slab depth
Design shear strength = 1.3 x 0.321
2
= 0.417 N / mm
OR
Design shear strength c = 0.85 √ 0.8 x fck ( √ 1 + 5 x β - 1 )
6xβ
β = 0.8 x fck / 6.89 Pt , but not less than 1.0
= 8.33
Design shear strength = 0.85 √ 0.8 x 15 ( √ 1 + 5 x 8.33 - 1 )
c
6 x 8.33
= 0.326
IS 456-2000 clause 40.2.1.1
k = 1.3 for 150 mm slab depth
Design shear strength = 1.3 x 0.326
2
= 0.424 N / mm
Actual shear stress = Vu / b x d
3
= 29.06 x 10 / ( 1000 x 120 )

= 0.242 N / mm < c
……………….( O.K.)
Check for development length : -
This is critical at point 4 or 5.
At point 4 or 5 , Vu = 29.06 KN No bar is curtailed or bent up.
Assuming L0 = 8 O (HYSD Fe415 steel )
Pt = 100 x As / b x d
= 100 x 251 / 1000 x 120
= 0.209
From equation OR
Pt = 50 1 -√1-(4.6 / fck) x (Mu / b x d )
2
Mu1 = 0.87 x fy

fy / fck = 0.87 x 41
2
we get , Mu1 / b x d = 0.711 = 10.875
2 -6
Mu1 = 0.711 x 1000 x 120 x 10 = 10.246
= 10.24 KNm
Development length of bars L d = O σs / 4 x bd =54.3 O (From Table 7-6 )

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 80/242
8/12/2019 Design of Rectangular Water Tank (1)

1.3 x ( Mu1 / Vu ) + L0 ≥ Ld
6 3
1.3 x ( 10.246 x 10 / 29.06 x 10 ) + 8 O ≥ 54.3 O
458.36 + 8 O ≥ 54.3 O
46.3 O ≤ 458.36
which gives O ≤ 9.90 mm ……………….( O.K.)
Short span Vu = 11.25 x ( 4.5 / 2 ) = 25.31 KN
Assuming L0 = 8 O (HYSD Fe415 steel )
Pt = 100 x As / b x d
= 100 x 462 / 1000 x 160
= 0.289
From equation OR
Pt = 50 1 -√1-(4.6 / fck) x (Mu / b x d )
2
Mu1 = 0.87 x fy
fy / fck = 0.87 x 41
2
we get , Mu1 / b x d = 0.9595 = 26.689
2 -6
M = 0.9595 x 1000 x 160 x 10 = 24.554
u1
= 24.56 KNm
Development length of bars L d = O σs / 4 x bd =56 O (From Table 7-6 )
1.3 x ( Mu1 / Vu ) + L0 ≥ Ld
6 3
1.3 x ( 24.56 x 10 / 25.31 x 10 ) + 8 O ≥ 56 O
1261.5 + 8 O ≥ 56 O
48 O ≤ 1261.5
which gives O ≤ 26.28 mm ……………….( O.K.)
Note that the bond is usually critical along long direction.
Check for deflection : -
Basic ( span / d ) ratio = 26
positive moment steel = 251 mm2.
actual d = 150 - 15 -8 - 4
= 123 mm.
Pt = 100 x Ast / b x d = 100 x 251 / 1000 x 123 240.7
= 0.204
IS 456-2000 clause 23.2.1 fig-4 ,for tension reinforcement
modification factor = 1.65
( span / d ) ratio permissible = 1.65 x 26
= 42.9
Actual (span / d ) ratio = 5000 / 123
= 40.65 < 42.9 ……………….( O.K.)
Check for cracking : -
IS 456-2000 , clause 26.3.3
(1) Main bars : maximum spacing permitted = 3 x effective depth of slab or 3
= 3 x 130 = 390 mm
spacing provided = 200 mm < 300 mm ……………….( O.
(2) Distribu. bars : maximum spacing permitted = 5 x effective depth of slab or 4
= 5 x 120 = 600 mm

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 81/242
8/12/2019 Design of Rectangular Water Tank (1)

spacing provided = 260 mm < 450 mm ……………….( O.


Note that the bottom reinforcements are both ways and therefore there is no
necessity of secondary reinforcements.However , top reinforcement in edge strip
requires the secondary steel for tying the bars.
2
This is minimum (0.12 / 100) x 150 x 1000 = 180 mm

Provide 8 mm O bar 2
spacing of bar = Area of one bar x 1000 / required area in m / m
= 50.24 x 1000 / 180
= 279.11 mm
2
Provide 8 mm O bar@ 260 mm c/c = 193 mm . for uniformity in spacing.
For clarity , top and bottom reinforcements are shown separately.
B c
/
c
0
625 3750 625 ip
rt 6
2
s
e @
g O c
d
8 /c
625 E
ip
rt 0
A 0 A
S 2
3750 S1 le @
d
id O
M 8
p
ir c
/c
625
t
s 0
e 6
g 2
d
E @
O
8

Edge strip Middle Strip Edge strip


8 O @ 260 c/c 8 O @ 260 c/c
8 O @ 200 c/c

B 8 O @ 150 c/c
500 8 O @ 200 c/c 8 O @ 260 c/c
150

8 O @ 260 c/c
1500 1500
625 3750 625
Section A-A

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 82/242
8/12/2019 Design of Rectangular Water Tank (1)

5m

5m S1
7
4
.0
0
- 1
B

5 -
3
0
.
ip p
ir 0 3
tr ts 5
5m s S1
e e 2 0.035
g g
d Middle Strip d
E E
A 4 B

625 3750 625 5m


ly/8 (3/4)ly ly/8

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 83/242
8/12/2019 Design of Rectangular Water Tank (1)

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 84/242
8/12/2019 Design of Rectangular Water Tank (1)

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 85/242
8/12/2019 Design of Rectangular Water Tank (1)

Ast x d ( 1 - f y x Ast / b x d x fck )


-6
5 x 251 x 120 ( 1 - 415 x 251 / 1000 x 120 x 15 ) x 10
( 1 - 0.0579 )
KNm

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 86/242
8/12/2019 Design of Rectangular Water Tank (1)

Ast x d ( 1 - f y x Ast / b x d x fck )


5 x 462 x 160 ( 1 - 415 x 46
( 1 - 0.0799 )
KNm

00 mm whichever is small
or 300 mm i.e. 300 mm
.)
50 mm whichever is small
or 450 mm i.e. 450 mm

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 87/242
8/12/2019 Design of Rectangular Water Tank (1)

.)

1000
c
/
c
0
625 3750 625 ip
rt 4
2
s
e @
g O /c
1000 625 d
1500 1500 E 8 c
ip
rt 0
4
500 S 1
3750 S1 le @
d
0 id O
0 M 8
5 c
625 1 p
ir /c
t
s 0
e 4
0 g 2
0 d
5 E @
1 O
8

Edge strip Middle Strip Edge strip


8 O @ 240 c/c 8 O @ 240 c/c
8 O @ 140 c/c

8 O @ 140 c/c
8 O @ 240 c/c 500 8 O @ 240 c/c
150

8 O @ 180 c/c
8 O @ 240 c/c
1500 1500
625 3750 625

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 88/242
8/12/2019 Design of Rectangular Water Tank (1)

0.047

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 89/242
8/12/2019 Design of Rectangular Water Tank (1)

Design of Continuous One-way slab


A five span continuous one-way slab used as an office floor.
The centre-to-centre distance of supporting beams is 3 m
2 2
Live load 3 KN / m and floor finish 1 KN / m given
Material M15 grade concrete

Solution :HYSD
- reinforcement of grade Fe415
Try 120 mm thick slab DL LL
2
Dead load 0.12 x 25 = 3 0 KN / m
2
floor finish = 1 0 KN / m
2
live load = 0 3 KN / m
2
Total 4 3 KN / m
factored load = 1.5 ( 4 + 3 )
2
= ( 6 + 4.5 ) KN / m
Consider 1 m wide strip of the slab.
( 6 + 4.5 ) KN / m

1 2 2 2 1
A 3m B 3m C 3m D 3m E 3m F

The factored moments at different points using the coefficients are as follows :
2 2
Mu1 ( + ) = ( 1 / 12 ) x w ( DL ) x l + ( 1 / 10 ) x w ( LL ) x l
2 2
= ( 1 / 12 ) x 6 x 3 + ( 1 / 10 ) x 4.5 x 3
= 4.5 + 4.05
= 8.55 KNm
2 2
Mu2 ( + ) = ( 1 / 16 ) x w ( DL ) x l + ( 1 / 12 ) x w ( LL ) x l
2 2
= ( 1 / 16 ) x 6 x 3 + ( 1 / 12 ) x 4.5 x 3
= 3.38 + 3.38
= 6.75 KNm
2 2
Mu3 ( - ) = ( 1 / 10 ) x w ( DL ) x l + ( 1 / 9 ) x w ( LL ) x l
2 2
= ( 1 / 10 ) x 6 x 3 + ( 1 / 9 ) x 4.5 x 3
= 5.4 + 4.5
= 9.9 KNm
2 2
Mu4 ( - ) = ( 1 / 12 ) x w ( DL ) x l + ( 1 / 9 ) x w ( LL ) x l
2 2
= ( 1 / 12 ) x 6 x 3 + ( 1 / 9 ) x 4.5 x 3
= 4.50 + 4.50
=9 KNm
Maximum shear is Vu(BA) = 0.6 x w x l + 0.6 x w x l
= 0.6 x 6 x 3 + 0.6 x 4.5 x 3
= 18.9 KN
Maximum moment is Mu3 ( - ) = 9.9 KNm
From Table 6-3 Q = 2.07

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 90/242
8/12/2019 Design of Rectangular Water Tank (1)

drequired =√M / Q x b
= √9.9 x 10
6
/ 2.07 x 1000
= 69.2 mm,
Try 110 mm overall depth
dprovided = 110 - 15 - 5 ( assume 10 O bar )
= 90 mm, ……………….( O.K.)
Pt = 50 1 -√1-(4.6 / fck) x (Mu / b x d )
2

fy / fck
Ast = Pt x b x d / 100
2
spacing of bar = Area of one bar x 1000 / required area in m / m
Table
Factored Ast
point moment 2
Mu/(b x d ) Pt 2
Steel Provided
KNm mm
10 mm O @ 440 c/c + 8 mm O @ 440 c/c
1(+) 8.55 1.06 0.322 290 = 178 +114 = 292 mm 2 (Half 10 O+half 8 O)
8 mm O @ 220 c/c
2(+) 6.75 0.83 0.248 223 2
= 228 mm
10 mm O @ 220 c/c
3(-) 9.9 1.22 0.38 342 2
= 357 mm
10 mm O @ 220 c/c
4(-) 9.0 1.11 0.34 306 2
= 357 mm
For Main steel ,HYSD Fe415 reinforcement
minimum steel area = ( 0.12 / 100 ) x 1000 x 110
2
= 132 mm
For Distribution steel , mild steel Fe250 reinforcement
minimum steel area = ( 0.15 / 100 ) x 1000 x 110
2
= 165 mm
Use 6 mm O
2
spacing of bar = Area of one bar x 1000 / required area in m / m
= 28.26 x 1000 /165
= 171
2
Use 6 mm O @ 160 mm c/c = 177 mm .
Note that the positive bars cannot be curtailed as the remaining bars in the internal
spans ( + ve moment ) will not provide minimum area.
2
Provide 50 % Ast at end support top bars i.e. 292 / 2 = 146 mm .

Use 8 mm O 2
spacing of bar = Area of one bar x 1000 / required area in m / m
= 50.24 x 1000 /146
= 344
2
Use 8 mm O @ 340 mm c/c = 148 mm .
Check for shear : -
Maximum shear = 18.9 KN

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 91/242
8/12/2019 Design of Rectangular Water Tank (1)

Actual Shear stress = Vu / b x d


3
= 18.9 x 10 / 1000 x 90
2
= 0.210 N / mm <( C ) N / mm
2
( too small )
For bars at support
d = 90 mm
2
As = 357 mm .
100 x As / b x d = 100 x 357 / 1000 x 90
= 0.397
Design shear strength c = 0.85 √ 0.8 x fck ( √ 1 + 5 x β - 1 )
6xβ
β = 0.8 x fck / 6.89 Pt , but not less than 1.0
= 0.8 x 15 / 6.89 x 0.397
= 4.4
0.85 √ 0.8 x 15 ( √ 1 + 5 x 4.4 - 1 )
Design shear strength c =
6 x 4.4
= 0.42
IS 456-2000 Table 19 from table 7-1
2
for Pt = 0.397 c = 0.42
N / mm
IS 456-2000 clause 40.2.1.1 0.25 difference 0.11
k = 1.3 for 110 mm slab depth 0.103 difference ? 0.0453
Design shear strength = 1.3 x 0.42
2
= 0.546 N / mm ……………….( O.K.)
At point of contraflexure i.e. 0.15 x l from B with positive moment reinforcement ( 29
Vu = 18.9 - 0.15 x 3 x 10.5
= 14.18 KN
Actual Shear stress = Vu / b x d
3
= 14.18 x 10 / 1000 x 90
2
= 0.158 N / mm <( C ) N / mm
2
( too small )
For bars at support
d = 90 mm
2
As = 292 mm .
100 x As / b x d = 100 x 292 / 1000 x 90
= 0.324
Design shear strength c = 0.85 √ 0.8 x fck ( √ 1 + 5 x β - 1 )
6xβ
β = 0.8 x fck / 6.89 Pt , but not less than 1.0
= 0.8 x 15 / 6.89 x 0.324
= 5.4

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 92/242
8/12/2019 Design of Rectangular Water Tank (1)

Design shear strength = 0.85 √ 0.8 x 15 ( √ 1 + 5 x 5.4 - 1 )


c
6 x 5.4
OR = 0.39
IS 456-2000 Table 19 from table 7-1
2
for Pt = 0.324 c = 0.38
N / mm
IS 456-2000 clause 40.2.1.1 0.25 difference 0.11
k = 1.3 for 110 mm slab depth 0.176 difference ? 0.0774
Design shear strength = 1.3 x 0.38
2
= 0.494 N / mm ……………….( O.K.)
Check for development length : -
Span AB is critical for checking this requirement
At support A
Vu = 0.4 x w x l + 0.45 x w x l
= 0.4 x 6 x 3 + 0.45 x 4.5 x 3 = 13.28 KN
At A , Pt = 100 x As / b x d
= 100 x 292 / 1000 x 90
= 0.324
From equation OR
Pt = 50 1 -√1-(4.6 / fck) x (Mu / b x d )
2
Mu1 = 0.87 x fy
fy / fck = 0.87 x 41
2
we get , Mu1 / b x d = 1.064 = 9.4884
2 -6
Mu1 = 1.064 x 1000 x 90 x 10 = 8.64
= 8.62 KNm
Assuming L0 = 8 O (HYSD Fe415 steel )
Development length of bars L d = O σs / 4 x bd = O x 0.67 x 415 / 4 x 1 =56.4 O

1.3 x ( Mu1 / Vu ) + L0 ≥ Ld
6 3
1.3 x ( 8.64 x 10 / 13.28 x 10 ) + 8 O ≥ 56.4 O
845.783 + 8 O ≥ 56.4 O
48.4 O ≤ 845.78
which gives O ≤ 17.47 mm ……………….( O.K.)
At support B, point of contraflexure is assumed at 0.15 x l from B
Vu = 18.9 - 0.15 x 3 x 10.5
= 14.18 KN
Mu1 = 8.64 KNm as before
L0 = 12 O ( actual anchorage is more than 12 O but L 0 is limited to 12 O or d
, i.e. 90 mm whichever is greater )
1.3 x ( Mu1 / Vu ) + L0 ≥ Ld
6 3
1.3 x ( 8.64 x 10 / 14.18 x 10 ) + 12 O ≥ 56.4 O
792.102 + 12 O ≥ 56.4 O
44.4 O ≤ 792.1
which gives O ≤ 17.84 mm ……………….( O.K.)
Check for deflection : -

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 93/242
8/12/2019 Design of Rectangular Water Tank (1)

Maximum positive moment occurs in span AB. Therefore, this check is critical in span
Basic ( span / d ) ratio = 26
Pt = 100 x Ast / b x d = 100 x 292 / 1000 x 90
= 0.324
IS 456-2000 clause 23.2.1 fig-4 ,for tension reinforcement

modification factor = 1.34


( span / d ) ratio permissible = 1.34 x 26
= 34.84
Actual (span / d ) ratio = 3000 / 90
= 33.33 < 34.84 ……………….( O.K.)
For span BC :
Basic ( span / d ) ratio = 26
Pt = 100 x Ast / b x d = 100 x 228 / 1000 x 90
= 0.253
IS 456-2000 clause 23.2.1 fig-4 ,for tension reinforcement
modification factor = 1.6
( span / d ) ratio permissible = 1.6 x 26
= 41.6
Actual (span / d ) ratio = 3000 / 90
= 33.33 < 41.6 ……………….( O.K.)
Check for cracking : -
IS 456-2000 , clause 26.3.3
(1) Main bars : maximum spacing permitted = 3 x effective depth of slab or 300 mm
= 3 x 90 = 270 mm or 300 m
spacing provided = 220 mm < 270 mm ……………….( O.
(2 )Distribution bars : maximum spacing permitted = 5 x effective depth of slab or
= 5 x 90 = 450 mm
spacing provided = 160 mm < 450 mm ……………….( O.

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 94/242
8/12/2019 Design of Rectangular Water Tank (1)

IS 456-2000 Clause -22.5


( 22.5.1 ) Unless more exact estimates are made, for
beams of uniform cross-section which support
substantially uniformly distributed loads over three or
more spans which do not differ by more than 15 percent

of theinlongest,
used design the
maybending moments
be obtained usingand
theshear forces
coefficients
given in Table 12 and Table 13 respectively.
For moments at supports where two unequal spans
meet or in case where the spans are not equally loaded,
the average of the two values for the negative moment
at the support may be taken for design.
Where coefficients given in Table 12 are used for
calculation of bending moments, redistribution referred
to in 22.7 shall not be permitted.
(22.5.2 ) Beams and Slabs Over Free End Supports
Where a member is built into a masonry wall which
develops only partial restraint, the member shall be
designed to resist a negative moment at the face of the
support of Wl / 24 where W is the total design load
and I is the effective span, or such other restraining
moment as may be shown to be applicable. For such a
condition shear coefficient given in Table 13 at the
end support may be increased by 0.05.
Table 12 Bending Moment coefficients
Span moments Support m
Type of load Near middle At middle of At support next to
of end span interior span the end support
Dead load and imposed + 1 / 12 + 1 / 16 -1 / 10
load ( fixed )

imposed load ( + 1 / 10 + 1 / 12 -1 / 9
not fixed )
NOTE -For obtaining the bending moment, the coefficient shall be multiplie
design load and effective span.
Table 13 Shear Force coefficients

At end At support next to the end support


Type of load
support Outer side Inner side
Dead load and imposed
0.4 0.6 0.55
load ( fixed )

imposed load ( 0.45 0.6 0.6


not fixed )

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 95/242
8/12/2019 Design of Rectangular Water Tank (1)

( 0.15 l1 ) ( 0.3 l1 ) ( 0.3 l1 ) ( 0.3 l1 )


450 900 900 900
8 O @ 340 c/c 10 O @ 220 c/c

110 90

6 O @ 160 c/c
8 O @ 440 c/c 8 O @ 220 c/c
+ 10 O @ 440 c/c

3000 3000

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 96/242
8/12/2019 Design of Rectangular Water Tank (1)

2
2 mm )

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 97/242
8/12/2019 Design of Rectangular Water Tank (1)

Ast x d ( 1 - f y x Ast / b x d x fck )


-6
5 x 292 x 90 ( 1 - 415 x 292 / 1000 x 90 x 15 ) x 10
( 1 - 0.0898 )
KNm

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 98/242
8/12/2019 Design of Rectangular Water Tank (1)

hichever is small
i.e. 270 mm
.)
450 mm whichever is small
or 450 mm i.e. 450 mm
.)

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 99/242
8/12/2019 Design of Rectangular Water Tank (1)

oments
At other interior
supports

-1 / 12

-1 / 9

by the total

At all other
interior
supports

0.5

0.6

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 100/242
8/12/2019 Design of Rectangular Water Tank (1)

( 0.3 l1 )
900
10 O @ 220 c/c

3000

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 101/242
8/12/2019 Design of Rectangular Water Tank (1)

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 102/242
8/12/2019 Design of Rectangular Water Tank (1)

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 103/242
8/12/2019 Design of Rectangular Water Tank (1)

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 104/242
8/12/2019 Design of Rectangular Water Tank (1)

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 105/242
8/12/2019 Design of Rectangular Water Tank (1)

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 106/242
8/12/2019 Design of Rectangular Water Tank (1)

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 107/242
8/12/2019 Design of Rectangular Water Tank (1)

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 108/242
8/12/2019 Design of Rectangular Water Tank (1)

Design of Simply supported two way slab


residential building drawing room 4.3 m x 6.55 m
It is supported on 350 mm thick walls on all four sides.
given
material M15 grade concrete

HYSD reinforcement of grade Fe415


Solution :
Consider 1 m wide strip. Assume 180 mm thick slab.
lx = 4.3 + 0.18 = 4.48 say 4.5 m
ly = 6.55+0.18 = 6.73 say 6.75 m
2
Dead load : self 0.18 x 25 = 4.5 KN / m
2
floor finish = 1.0 KN / m
2
Live load ( residence ) = 2.0 KN / m
2
Total 7.5 KN / m
For 1 m wide strip
Pu = 1.5 x 7.5
= 11.25 KN / m
ly / lx = 6.75 / 4.5
= 1.5
IS 456-2000 Table -27
2
Mux = αx x w x l x2 = 0.104 x 11.25 x 4.5 = 23.7 KNm
2
Muy = αy x w x lx2 = 0.046 x 11.25 x 4.5 = 10.48 KNm

From Table 6-3 Q = 2.07


drequired = √ M/Qxb

= √23.7 x 10
6
/ 2.07 x 1000
= 107 mm,
dshort provided = 180 - 15 - 5 ( assume 10 O bar )
= 160 mm, > 107 mm ……………….( O.K.)
dlong provided = 160 - 10
= 150 mm, > 107 mm
Larger depth is provided due to deflection check.
2 6 2
Mu / b x d ( short ) = 23.7 x 10 / 1000 x (160)
= 0.926
2
Pt = 50 1- 1-(4.6 / fck) x (Mu / b x d )
fy / fck

= 50 1-√1-(4.6 / 15) x (0.926)

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 109/242
8/12/2019 Design of Rectangular Water Tank (1)

415 / 15

= 50 [(1-0.846) x 15 / 415 ]
= 0.28%

Ast ( short ) = 0.28 x 1000 x 160 / 100


2
= 448 mm
Provide 10 mm O bar
2
spacing of bar = Area of one bar x 1000 / required area in m / m
= 78.5 x 1000 / 448
= 175.22 mm
2
Provide 10 mm O bar@170 mm c/c = 462 mm . ( short span )
2 6 2
Mu / b x d ( long ) = 10.48 x 10 / 1000 x (150)
= 0.466
Pt = 50 1- 1-(4.6 / fck) x (Mu / b x d 2)
fy / fck

= 50 1-√1-(4.6 / 15) x (0.466


415 / 15

= 50 [(1-0.926) x 15 / 415 ]
= 0.134%

Ast ( long ) = 0.134 x 1000 x 150 / 100


2
= 201 mm
For HYSD Fe415 minimum reinforcement 0.12 %
Minimum steel = ( 0.12 /100 ) x 1000 x 180
2
= 216 mm .
Provide 8 mm O bar
2
spacing of bar = Area of one bar x 1000 / required area in m / m
= 50.24 x 1000 / 216
= 232.59 mm
2
Provide 8 mm O bar@ 230 mm c/c = 218 mm . ( long span )
The bars cannot be bent or curtailed because if 50 % of long span bars are curtailed ,
the remaining bars will be less than minimum
At top on support , provide 50 % of bars of respective span to take into account
negative moment due to slab nature.
Check for development length : -
Long span Vu = 11.25 x ( 4.5 / 2 ) = 25.31 KN
Assuming L0 = 8 O (HYSD Fe415 steel )

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 110/242
8/12/2019 Design of Rectangular Water Tank (1)

Pt = 100 x As / b x d
= 100 x 218 / 1000 x 150
= 0.145
From equation OR
2
P = 50 1- 1-(4.6 / fck) x (M / b x d ) M = 0.87 x f
t u u1 y
fy / fck = 0.87 x 41
2
we get , Mu1 / b x d = 0.5023 = 11.806
2 -6
Mu1 = 0.5023 x 1000 x 150 x 10 = 11.331
= 11.30 KNm
Development length of bars Ld = O σs / 4 x bd =56 O (From Table 7-6 )
1.3 x ( Mu1 / Vu ) + L0 ≥ Ld
6 3
1.3 x ( 11.30 x 10 / 25.31 x 10 ) + 8 O ≥ 56 O
580.4 + 8 O ≥ 56 O
48 O ≤ 580.403
which gives O ≤ 12.09 mm ……………….( O.K.)
Short span Vu = 11.25 x ( 4.5 / 2 ) = 25.31 KN
Assuming L0 = 8 O (HYSD Fe415 steel )
Pt = 100 x As / b x d
= 100 x 462 / 1000 x 160
= 0.289
From equation OR
2
Pt = 50 1- 1-(4.6 / fck) x (Mu / b x d ) Mu1 = 0.87 x fy

fy / fck = 0.87 x 41
2
we get , Mu1 / b x d = 0.9595 = 26.689
2 -6
Mu1 = 0.9595 x 1000 x 160 x 10 = 24.554
= 24.56 KNm
Development length of bars Ld = O σs / 4 x bd =56 O (From Table 7-6 )
1.3 x ( Mu1 / Vu ) + L0 ≥ Ld
6 3
1.3 x ( 24.56 x 10 / 25.31 x 10 ) + 8 O ≥ 56 O
1261.5 + 8 O ≥ 56 O
48 O ≤ 1261.48
which gives O ≤ 26.28 mm ……………….( O.K.)
Note that the bond is usually critical along long direction.
Check for shear : -
This is critical along long span
Vu = 25.31 KN
Shear stress = Vu / b x d
3
= 25.31 x 10 / 1000 x 150

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 111/242
8/12/2019 Design of Rectangular Water Tank (1)

2
= 0.169 N / mm <( C ) N / mm
2
( too small )
100 x As / b x d = 100 x 218 / 1000 x 150
= 0.145
from table 7-1
for Pt = 0.145 c = 0.28 N / mm 25 difference -0.05
IS 456-2000 clause 40.2.1.1 20 difference ? -0.04
k = 1.24 for 180 mm slab depth
Design shear strength = 1.24 x 0.28
2
= 0.347 N / mm ……………….( O.K.)
OR
Design shear strength c = 0.85 √ 0.8 x fck ( √ 1 + 5 x β - 1 )
6xβ
β = 0.8 x fck / 6.89 Pt , but not less than 1.0
= 12.011
Design shear strength c = 0.85 √ 0.8 x 15 ( √ 1 + 5 x 12.01 - 1 )
6 x 12.011
= 0.278
IS 456-2000 clause 40.2.1.1 25 difference -0.05
k = 1.24 for 180 mm slab depth 20 difference ? -0.04
Design shear strength = 1.24 x 0.278
2
= 0.345 N / mm ……………….( O.K.)
Check for deflection : -
This check shall be done along short span
Basic ( span / d ) ratio = 20
Pt = 100 x Ast / b x d = 100 x 462 / 1000 x 160
= 0.289
IS 456-2000 clause 23.2.1 fig-4 ,for tension reinforcement
modification factor = 1.44
( span / d ) ratio permissible = 1.44 x 20
= 28.8
Actual (span / d ) ratio = 4480 / 160
= 28.00 < 28.8 ……………….( O.K.)
Check for cracking : -
IS 456-2000 , clause 26.3.3
(1) Main bars : maximum spacing permitted for short span steel = 3 x effective depth
= 3 x 160 = 480
spacing provided = 170 mm < 300 mm ……………….( O.
(2) Distribu. bars : maximum spacing permitted for long span steel = 5 x effective depth
= 5 x 150 = 750
spacing provided = 230 mm < 450 mm ……………….( O.

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 112/242
8/12/2019 Design of Rectangular Water Tank (1)

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 113/242
8/12/2019 Design of Rectangular Water Tank (1)

Table - 26 Bending moment coefficients for rectangular panels supported on four sid

short span c
Type of Panel and Moments
Case No. ( Values
considered

1 Interior Panels: 1.0 1.1 1.2 1.3


Negative moment at continuous edge 0.032 0.037 0.043 0.047
Positive moment at mid-span 0.024 0.028 0.032 0.036
2 One Short Edge Discontinuous:
Negative moment at continuous edge 0.037 0.043 0.048 0.051
Positive moment at mid-span 0.028 0.032 0.036 0.039
3 One long Edge Discontinuous:
Negative moment at continuous edge 0.037 0.044 0.052 0.057

Positive moment at mid-span 0.028 0.033 0.039 0.044


4 Two Adjacent Edges Discontinuous:
Negative moment at continuous edge 0.047 0.053 0.060 0.065
Positive moment at mid-span 0.035 0.040 0.045 0.049
5 Two Short Edges Discontinuous:
Negative moment at continuous edge 0.045 0.049 0.052 0.056
Positive moment at mid-span 0.035 0.037 0.040 0.043
6 Two Long Edges Discontinuous:
Negative moment at continuous edge - - - -

Positive moment at mid-span 0.035 0.043 0.051 0.057


7
Three Edges Discontinuous

(One Long Edge Continuous):


Negative moment at continuous edge 0.057 0.064 0.071 0.076
Positive moment at mid-span 0.043 0.048 0.053 0.057
8 Three Edges Discrmntinuous
(One Short Edge Continuous) :
Negative moment at continuous edge - - - -
Positive moment at mid-span 0.043 0.051 0.059 0.065
9 Four-Edges Discontinuous:
Positive moment at mid-span 0.056 0.064 0.072 0.079

Table - 27 Bending moment coefficients for slabs spanning in two directions at right a

ly / lx 1.0 1.1 1.2 1.3 1.4

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 114/242
8/12/2019 Design of Rectangular Water Tank (1)

αx 0.062 0.074 0.084 0.093 0.099


αy 0.062 0.061 0.059 0.055 0.051

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 115/242
8/12/2019 Design of Rectangular Water Tank (1)

A xd(1-f xA /bxdxf )
st y st ck -6
5 x 218 x 150 ( 1 - 415 x 218 / 1000 x 150 x 15 ) x 10
( 1 - 0.0402 )
KNm

Ast x d ( 1 - fy x Ast / b x d x f ck )
-6
5 x 462 x 160 ( 1 - 415 x 462 / 1000 x 160 x 15 ) x 10
( 1 - 0.0799 )
KNm

350 6550 350

350
460 10 O @ 340 c/c

10 O @ 170 c/c

690 8 O @ 230 c/c 690


4300 4650

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 116/242
8/12/2019 Design of Rectangular Water Tank (1)

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 117/242
8/12/2019 Design of Rectangular Water Tank (1)

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 118/242
8/12/2019 Design of Rectangular Water Tank (1)

s with provision for torsion at corners

oefficient αx Long span


of ly / lx ) coefficient αy for
all values of l y / lx
1.4 1.5 1.75 2.0
0.051 0.053 0.060 0.065 0.032
0.039 0.041 0.045 0.049 0.024

0.055 0.057 0.064 0.068 0.037


0.041 0.044 0.048 0.052 0.028

0.063 0.067 0.077 0.085 0.037

0.047 0.051 0.059 0.065 0.028

0.071 0.075 0.084 0.091 0.047


0.053 0.056 0.063 0.069 0.035

0.059 0.060 0.065 0.069 -


0.044 0.045 0.049 0.052 0.035

- - - - 0.045

0.063 0.068 0.080 0.088 0.035

0.080 0.084 0.091 0.097 -


0.060 0.064 0.069 0.073 0.043

- - - - 0.057
0.071 0.076 0.087 0.096 0.043

0.085 0.089 0.100 0.107 0.056

ngles , simply supported on Four sides

1.5 1.75 2.0 2.5 3.0

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 119/242
8/12/2019 Design of Rectangular Water Tank (1)

0.104 0.113 0.118 0.122 0.124


0.046 0.037 0.029 0.020 0.014

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 120/242
8/12/2019 Design of Rectangular Water Tank (1)

Design of Continuous Beam


An R.C.C. floor is used as a banking hall
Design the beams B 10-B11-B12.
The Slab thickness is 120 mm .
2 B10
Live load = 3 KN / m 6m
Floor finish = 1 KN / m2 (Given )
Rib size = 230 mm x 450 mm
Column = 300 mm x 300 mm
Main beams = 300 mm x 570 mm overall .
Material M15 grade concrete 6m
HYSD reinforcement of grade Fe415 .
Solution : -
( a ) Load calculations and analysis :
2
Slab 120 mm thick 0.12 x 25 = 3 + 0 KN / m
2
Floor finish = 1 + 0 KN /m
2
Live load = 0 + 3 KN / m
Total 4 + 3 KN / m2
Load on beam = 3 ( 4 + 3 ) = 12 + 9 KN / m
Self wt. = 0.23 x 0.45 x 25 = 2.58 + 0 KN / m
Total 14.58 + 9 KN / m
Factored Load = 1.5 ( 14.58 + 9 )
= 21.87 + 13.5
say ( 22 + 14 ) KN /m .
Case ( a ) Maximum moment at B
36 KN / m 36 KN / m 22 KN / m

6m 6m 6m
A B C D
Using three moment equation for span ABC
MA ( L1 / I1 ) + 2MB ( L1 / I1 + L2 / I2 ) + MC ( L2 / I2 ) = - 6 A1a1 / ( I1 L1 ) -6 A2a2 / ( I2L2)
36 KN / m 36 KN / m

A B B C
162 162

A1 = ( 2 / 3 ) x Base x h1 A2 = ( 2 / 3 ) x Base x h1
= ( 2 / 3 ) x 6 x 162 = ( 2 / 3 ) x 6 x 162
= 648 = 648
a1 = 3 m a2 = 3 m
MA ( 6 / I ) + 2MB ( 6 / I + 6 / I ) + MC ( 6 / I ) = - [ 6 x 648 x 3 / ( I x 6 ) ] - [ 6 x 648 x 3 / ( I x
6MA + 24MB + 6MC = - [ 1944 ] - [ 1944 ]
4MB + MC = - 648 As MA = 0 …………………….( 1 )

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 121/242
8/12/2019 Design of Rectangular Water Tank (1)

Using three moment equation for span BCD


MB ( L2 / I2 ) + 2MC ( L2 / I2 + L3 / I3 ) + MD ( L3 / I3 ) = - 6 A 2a2 / ( I2 L2 ) -6 A3a3 / ( I3L3)
36 KN / m 22 KN / m

C
B C D
162 99

A2 = ( 2 / 3 ) x Base x h2 A3 = ( 2 / 3 ) x Base x h3
= ( 2 / 3 ) x 6 x 162 = ( 2 / 3 ) x 6 x 99
= 648 = 396
a2 = 3 m a3 = 3 m
MB ( 6 / I ) + 2MC ( 6 / I + 6 / I ) + MD ( 6 / I ) = - [ 6 x 648 x 3 / ( I x 6 ) ] - [ 6 x 396 x 3 / ( I x
6MB + 24MC + 6MD = - [ 1944 ] - [ 1188 ]
MB + 4MC = - 522 As MD = 0 …………………….( 2 )
4MB + MC = - 648 …………………….( 1 )
MB + 4MC = - 522 …………………….( 2 )
By putting Value of M B from Equation ( 2 ) into Equation ( 1 )
4(- 522 - 4MC ) + MC = - 648
- 2088 - 16 MC + MC = - 648
15 MC = - 1440
MC = - 96 KNm
By putting Value of M C into Equation ( 1 )
4MB + ( - 96 ) = - 648

4 MB = - 552
MB = - 138 KNm
36 KN / m 36 KN / m 22 KN / m

6m 6m 6m
A B C D
138
162 (-) 96
(+) 162 99
(-) (+)

93 51 6 m Distance 138 KNm


45 3 m Distance (?) 69
(+) (+) (+) 6 m Distance 96 KNm
(-) (-) 3 m Distance (?) 48
6 m Distance 42 KNm
96
3 m Distance (?) 21
138

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 122/242
8/12/2019 Design of Rectangular Water Tank (1)

115 MB = - 138 KNm


85
82 VA x 6 -36 x 6 x 3 = -138 X dist.
VA = 85 KN 6 - X dist.

2.36 m VA + VB = 36 x 6 131 X =8
50
VB = 216 - 85 216 X =
101 VB = 131 KN X = 2.36
131

MC = - 96 KNm MB = - 138 KNm


VD x 6 -22 x 6 x 3 = -96 50 x 12 + VC x 6 - 36 x 6 x 3 - 22 x 6 x 9 = -138
VD = 50 KN Vc = 183 KN
VC + VD = 22 x 6 VC + 82 = 183
VC = 132 - 50 VC = 101 KN
VC = 82 KN MC = - 96 KNm

85 x 12 + VB x 6 - 36 x 6 x 9 - 36 x 6 x 3 = - 96
VB = 246 KN
VB + 131 = 246
VB = 115 KN
Three cases are considered for getting maximum values of moments. Case ( a ) gives ma
negative moment at B.The same moment shall be used at C also because of symmetry. C
gives the maximum positive moment in span BC while the case ( c ) gives maximum positi
moments in span AB and CD.
Factored maximum moments :
B or C , negative moment = 138 KNm
AB ( + ) = CD ( + ) = 110 KNm
BC ( + ) = 58 KNm
BC ( minimum - ve ) = 5 KNm
The moment redistribution shall be now carried out. Maximum negative moment = 138 KN
reduce it by 20 % . Then Mu = 0.8 x 138 = 110.4 KNm. For all the cases , redistribute ( inc
decrease ) the moment at B or C = 110.4 KNm ( Hogging ).
Maximum design moments :
Support B or C = 110.4 KNm > 0.7 x 138 KNm ………………( O.K.) ( As per I
AB or CD ( + ) = 111.6 KNm > 0.7 x 110 KNm
BC ( - ) = 11.6 KNm
BC ( + ) = 51.6 KNm > 0.7 x 58 KNm.
Note that after redistribution , the design positive moments also have been reduced.
( b ) Design for flexure :
Span AB or CD
Mu ( + ) = 111.6 KNm.
The beam acts as a flanged beam
For T-beams , b f = ( l0 / 6 ) + bw + 6 Df
bf = ( 0.7 x 6000 / 6 ) + 230 + 6 x 120 ( As per IS456-2000 ,Clause 23.1.2 , Note
= 1650 mm > 3000 mm

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 123/242
8/12/2019 Design of Rectangular Water Tank (1)

Assuming one layer of 20 mm diameter bars


d = 450 + 120 -25 - 10 = 535 mm .
2
Minimum Ast = ( 0.205 / 100 ) x 230 x 535 = 252 mm ( As per IS456-2000 ,Cl
bf / bw = 1650 / 230 = 7.17 For bf /bw = 7 For bf /
Df / d = 120 / 535 = 0.224 0.01 diff. 0.014 0.016
2
Mu,lim / fck bw d = 0.671 ( As per SP:16 ,Table 58 ) 0.006 diff. ? ?
2 -6
Mu.lim = 0.671 x 15 x 230 x 535 x 10 -0.0084 -0.0096
= 662.6 KNm > 111.6 KNm For 0.224 0.6566 0.743
1 diff 0.0864
0.83 diff ? 0.0717
If Mu < Mu,lim : design as under-reinforced section (singly reinforced beam) as explaine
Ast = Mu / 0.87 x fy x lever arm
where lever arm = d - D f / 2 = 535 - 120 / 2 = 535 - 60
6
Ast = 111.6 x 10 / 0.87 x 415 x ( 535 - 60 )
= 651 mm2 .
2
Provide 6 - 12 mm O = 678 mm .
Span BC :
Mu ( + ) = 51.6 KNm
6
Ast = 51.6 x 10 / 0.87 x 415 x ( 535 - 60 )
= 301 mm .
2
Provide 3 - 12 mm O = 339 mm .
In span AB , curtail 3 - 12 O at 300 mm ( 0.05 ℓ ) from A and at 900 mm ( 0.15 ℓ ) from B.
Continue 3 - 12 O in span BC as required for flexure.
Support B or C :
Mu ( - ) = 110.4 KNm
2 6 2
Mu / bd = 110.4 x 10 / 230 x 535 = 1.68 < 2.07. ( From Table 6-3 )
The section is under-reinforced.

Pt = 50
1- √ 1 - ( 4.6 / f ck) x ( Mu / bd )
2

fy / fck

Pt = 50 1 - √ 1 - ( 4.6 / 15 ) x ( 1.68 )
415 / 15
= 0.549
2
Ast
= ( 0.549 / 100 ) x 230 x 535 = 676 mm 2
603 135
20 % of steel should be carried through the span = 0.2 x 676 = 135 mm
2
Provide 2- 10 mm O anchor bars = 157 mm . At support , provide 3 - 16 mm O extra at to
one of which may be curtailed at 0.15 ℓ = 900 mm from centre of support B and remaining
at 0.25 ℓ = 1500 mm from B .

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 124/242
8/12/2019 Design of Rectangular Water Tank (1)

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 125/242
8/12/2019 Design of Rectangular Water Tank (1)

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 126/242
8/12/2019 Design of Rectangular Water Tank (1)

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 127/242
8/12/2019 Design of Rectangular Water Tank (1)

3m
B11 B12

3m

6m 6m

Case ( b ) Maximum positive moment in span B


22 KN / m 36 KN / m 22 KN / m

6m 6m 6m
A B C D
Using three moment equation for span ABC
MA ( L1 / I1 ) + 2MB ( L1 / I1 + L2 / I2 ) + MC ( L2 / I
22 KN / m 36 K

A B B
99 162

A1 = ( 2 / 3 ) x Base x h1 A2 = ( 2 / 3 ) x Bas
= ( 2 / 3 ) x 6 x 99 = (2/3)x
= 396 = 648
a1 = 3 m a2 = 3 m
6) ] MA ( 6 / I ) + 2MB ( 6 / I + 6 / I ) + MC ( 6 / I ) = -
6MA + 24MB + 6MC = - [ 1188 ] - [ 1944 ]
4MB + MC = - 522 As MA = 0

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 128/242
8/12/2019 Design of Rectangular Water Tank (1)

Using three moment equation for span BCD


MB ( L2 / I2 ) + 2MC ( L2 / I2 + L3 / I3 ) + MD ( L3 / I
36 KN / m 22 K

C
B C
162 99

A2 = ( 2 / 3 ) x Base x h2 A3 = ( 2 / 3 ) x Bas
= ( 2 / 3 ) x 6 x 162 = (2/3)x
= 648 = 396
a2 = 3 m a3 = 3 m
6) ] MB ( 6 / I ) + 2MC ( 6 / I + 6 / I ) + MD ( 6 / I ) = -
6MB + 24MC + 6MD = - [ 1944 ] - [ 1188 ]
MB + 4MC = - 522 As MD = 0

4MB + MC = - 522 …………………….


MB + 4MC = - 522 …………………….
By putting Value of M B from Equation ( 2 ) into
4(- 522 - 4MC ) + MC = - 522
- 2088 - 16 M C + MC = - 522
15 MC = - 1566
MC = - 104 KNm
By putting Value of M C into Equation ( 1 )
4MB + ( - 104 ) = - 522

4 MB = - 418
MB = - 104 KNm
22 KN / m 36 KN / m 22 KN / m

6m 6m 6m
A B C104 D
104
99 (-) 99
162 (-) (+)

47 58 47
( 162 - 69 = 93 KNm )
(+) (+) (+)
( 99 - 48 = 51 KNm ) (-) (-)

( 162 - ( 96 + 21 ) = 45 KNm )
104 104

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 129/242
8/12/2019 Design of Rectangular Water Tank (1)

108
48.67
85 83.33

131
5(6-X) 2.21 m
48.67
10
m 108
83.33

MC = - 104 KNm MB = - 104 KNm


VD x 6 -22 x 6 x 3 = -104 48.67 x 12 + VC x
VD = 48.67 KN Vc = 191.33 KN
VC + VD = 22 x 6 VC + 83.33 = 191.
VC = 132 - 48.67 VC = 108 KN
VC = 83.33 KN MC = - 104 KNm

48.67 x 12 + VB x
VB = 191.33 KN
VB + 83.33 = 191.3
VB = 108 KN
imum
ase ( b )
ve

m.
rease or
IS 456-2000 ,Clause 37.1.1 Redistri
Continuous Beams and Frames -
S 456-2000 , Clause 37.1.1 ) ( b ) The ultimate moment of resistan
member is not less than 70 percent of
obtained from an elastic maximum m
appropriate combinations of loads.
( c ) The elastic moment at any sec

particular
than 30 %combination of loads
of the numerically shall
largest
the elastic maximum moments di
member , covering all appropriate co
IS 456-2000 ,Clause 23.1.2 Effective
) In the absence of more accurate dete
width of flange may be taken as the f

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 130/242
8/12/2019 Design of Rectangular Water Tank (1)

greater than the breadth of the web pl


distances to the adjacent beams on ei
lause 26.5( a ) ) ( a ) For T-beams , b f = ( l0 / 6 ) + bw +
bw = 8 ( b ) For L-beams , bf = ( l0 / 12 ) + bw
Where ,
bf = effective width of flange ,
l0 = distance between points of zero
bw = breadth of the web ,
Df = thickness of flange , and
0.671 b = actual width of the flange.
below. NOTE - For continuous beams and fr
assumed as 0.7 times the effective sp

IS 456-2000 Clause 26.5 Requireme


Structural Members
26.5.1 Beams
26.5.1.1 Tension Reinforcement
a ) Minimum reinforcement - The mi
shall not be less than that given by th
As / b d = 0.85 / f y
where ,
As = minimum area of tension reinforc
b = breadth of the beam or the breadt
d = effective depth , and
fy = characteristic strength of reinforce
b ) Maximum reinforcement - The m
reinforcement shall not exceed 0.04 b
Minimum steel %
For mild steel
100 As / b d = 100 x 0.85 / 250 = 0.34
For HYSD steel , Fe415 grade
100 As / b d = 100 x 0.85 / 415 = 0.20

For HYSD steel , Fe500 grade


100 As / b d = 100 x 0.85 / 500 = 0.17
2
p = 603 mm ,
2 - 16 mm O Table 6-3
Limiting Moment of resistance factor Q lim, N /
For singly reinforced rectangular sections

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 131/242
8/12/2019 Design of Rectangular Water Tank (1)

fck 2
fy, N / mm
2
N / mm 250 415 500
15 2.22 2.07 2.00
20 2.96 2.76 2.66
25 3.70 3.45 3.33
30 4.44 4.14 3.99

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 132/242
8/12/2019 Design of Rectangular Water Tank (1)

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 133/242
8/12/2019 Design of Rectangular Water Tank (1)

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 134/242
8/12/2019 Design of Rectangular Water Tank (1)

C Case ( c ) Maximu
36 KN / m

6m
A B
Using three mome
2 ) = - 6 A1a1 / ( I1 L1 ) -6 A2a2 / ( I2L2) MA ( L1 / I1 ) + 2MB
N/m 36 K

C A
162

x h1 A1 = ( 2 / 3 ) x Bas
6 x 162 = (2/3)x
= 648
a1 = 3 m
[ 6 x 396 x 3 / ( I x 6 ) ] - [ 6 x 648 x 3 / ( I x 6) ] MA ( 6 / I ) + 2MB (
6MA + 24MB + 6MC
…………………….( 1 ) 4MB + MC = - 522

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 135/242
8/12/2019 Design of Rectangular Water Tank (1)

Using three mome


3 ) = - 6 A2a2 / ( I2 L2 ) -6 A3a3 / ( I3L3) MB ( L2 / I2 ) + 2MC
N/m 22 K

D B
99

x h3 A2 = ( 2 / 3 ) x Bas
6 x 99 = (2/3)x
= 396
a2 = 3 m
[ 6 x 648 x 3 / ( I x 6 ) ] - [ 6 x 396 x 3 / ( I x 6) ] MB ( 6 / I ) + 2MC (
6MB + 24MC + 6MD
…………………….( 2 ) MB + 4MC = - 522

(1) 4MB + MC = - 522


(2) MB + 4MC = - 522
quation ( 1 ) By putting Value of
4(- 522 - 4MC ) +
- 2088 - 16 MC +
15 MC = - 1566
MC = - 104.4 KNm
By putting Value of
4MB + ( - 104.4 ) =

4 MB = - 417.6
MB = - 104.4 KNm
36 KN / m

6m
A B
10
162
(-)
(+)

6 m Distance 104 KNm 110


3 m Distance (?) 52 ( 99 - 52 = 47 KNm )
Moment in span BC = ( 162 - 104 ) = 58 KNm (+)

(-)

104

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 136/242
8/12/2019 Design of Rectangular Water Tank (1)

MB = - 104 KNm
90.67
VA x 6 -22 x 6 x 3 = -104 X dist. 48.67 66
VA = 48.67 KN 6 - X dist. 83.33
VA + VB = 22 x 6 83.33 X = 48.67 ( 6 - X ) 2.52 m

VB = 132 - 48.67 132 X = 292.02


VB = 83.33 KN X = 2.21 m
125.

MC = - 104 KNm
- 36 x 6 x 3 - 22 x 6 x 9 = -104 VD x 6 -36 x 6 x 3
VD = 90.67 KN
3 VC + VD = 36 x 6
VC = 216 - 90.67
VC = 125.33 KN

- 36 x 6 x 3 - 22 x 6 x 9 = - 104

ution of moments in

e provided at any section of a


the moment at that section
ment diagram covering all

ion in a member due to a

not be given
oment reduced by more
anywhere by
gram for the particular
bination of loads.
width of flange -
rmination , the effective
llowing but in no case

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 137/242
8/12/2019 Design of Rectangular Water Tank (1)

us half the sum of the clear


ither side :
6 Df
+ 3 Df

oments in the beam ,

mes , ' l0 ' may be


an.

nts of Reinforcement for

nimum area of tension reinforcement


following :

ement ,
h of the web of T- beam ,

2
ment in N / mm .
aximum area of tension
D.

2
m

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 138/242
8/12/2019 Design of Rectangular Water Tank (1)

550
1.94
2.58
3.23
3.87

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 139/242
8/12/2019 Design of Rectangular Water Tank (1)

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 140/242
8/12/2019 Design of Rectangular Water Tank (1)

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 141/242
8/12/2019 Design of Rectangular Water Tank (1)

positive moment in span AB and CD


22 KN / m 36 KN / m

6m 6m
C D
nt equation for span ABC
( L1 / I1 + L2 / I2 ) + MC ( L2 / I2 ) = - 6 A 1a1 / ( I1 L1 ) -6 A2a2 / ( I2L2)
N/m 22 KN / m

B B C
99

x h1 A2 = ( 2 / 3 ) x Base x h1
6 x 162 = ( 2 / 3 ) x 6 x 99
= 396
a2 = 3 m
6 / I + 6 / I ) + MC ( 6 / I ) = - [ 6 x 648 x 3 / ( I x 6 ) ] - [ 6 x 396 x 3 / ( I x 6) ]
= - [ 1944 ] - [ 1188 ]
As MA = 0 …………………….( 1 )

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 142/242
8/12/2019 Design of Rectangular Water Tank (1)

nt equation for span BCD


( L2 / I2 + L3 / I3 ) + MD ( L3 / I3 ) = - 6 A2a2 / ( I2 L2 ) -6 A3a3 / ( I3L3)
N/m 36 KN / m

C
C D
162

x h2 A3 = ( 2 / 3 ) x Base x h3
6 x 99 = ( 2 / 3 ) x 6 x 162
= 648
a3 = 3 m
6 / I + 6 / I ) + MD ( 6 / I ) = - [ 6 x 396 x 3 / ( I x 6 ) ] - [ 6 x 648 x 3 / ( I x 6) ]
= - [ 1188 ] - [ 1944 ]
As MD = 0 …………………….( 2 )

…………………….( 1 )
…………………….( 2 )
MB from Equation ( 2 ) into Equation ( 1 )
C = - 522
C = - 522

MC into Equation ( 1 )
- 522

22 KN / m 36 KN / m

6m 6m
C 162 D
104
(+)
99 (-)

110 6 m Distance 104 KNm


3 m Distance (?) 52 ( 162 - 52 = 110 K
(+) Moment in span BC = ( 104 - 99 ) = 5 KNm
(-)
5.0

104

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 143/242
8/12/2019 Design of Rectangular Water Tank (1)

125.33 MB = - 104 KNm


VA x 6 -36 x 6 x 3 = -104 X dist. 90.67
VA = 90.67 KN 6 - X dist. 125.33
VA + VB = 36 x 6 125.33 X =90.67 ( 6 - X )
66
90.67 VB = 216 - 90.67 216 X = 544.02
VB = 125.33 KN X = 2.52 m
33

MB = - 104 KNm
-104 90.67 x 12 + VC x 6 - 22 x 6 x 3 - 36 x 6 x 9 = -104
Vc = 191.33 KN
VC + 125.33 = 191.33
VC = 66 KN
MC = - 104 KNm

90.67 x 12 + VB x 6 - 36 x 6 x 9 - 22 x 6 x 3 = - 104
VB = 191.33 KN
VB + 125.33 = 191.33
VB = 66 KN

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 144/242
8/12/2019 Design of Rectangular Water Tank (1)

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 145/242
8/12/2019 Design of Rectangular Water Tank (1)

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 146/242
8/12/2019 Design of Rectangular Water Tank (1)

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 147/242
8/12/2019 Design of Rectangular Water Tank (1)

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 148/242
8/12/2019 Design of Rectangular Water Tank (1)

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 149/242
8/12/2019 Design of Rectangular Water Tank (1)

m)

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 150/242
8/12/2019 Design of Rectangular Water Tank (1)

Design of Cantilever Beam


Span = 3 m
Characteristic U.D.L. = 12 KN /m
Assume that sufficient safety against overturning is there
( Given )
and reinforcement anchorages are also available.
Material M15 grade concrete
mild steel reinforcement.
Solution : -
Assume an initial trial section of 230 mm x 600 mm overall depth to consider self-wei
The self-weight = 0.23 x 0.6 x 25 = 3.45 KN / m
Total load = 12 + 3.45 = 15.45 KN / m
Factored load = 1.5 x 15.45 = 23.2 KN / m
Factored S.F. = w x ℓ = 23.2 x 3 = 69.6 KN
2 2
Factored B.M. = w x ℓ / 2 = 23.2 x 3 / 2 = 104.4 KNm
Depth required = √M / Q b = √( 104.4 x 10 6 ) / ( 2.22 x 230 ) ( From Table 6-3 )
= 452 mm
Using one layer of 20 mm O bars and overall depth of 550 mm
d = 550 - 25 - 10 = 515 mm OR 1
2 6 2
Mu / b d = 104.4 x 10 / ( 230 x 515 ) Mu,lim = 2.22 x 230 x 515
= 1.71 < 2.22 ( Table 6-3 ) = 135.42 KNm
The section is singly reinforced ( under-reinforced ) Mu < Mu,lim

Pt = 50
1- √ 1 - ( 4.6 / f ck)
2
x ( Mu / bd )
fy / fck

Pt = 50 1 - √ 1 - ( 4.6 / 15 ) x ( 1.71 )
250 / 15
= 0.93
Ast = ( 0.93 / 100 ) x 230 x 515 = 1102 mm2
2
Provide 4 - 20 mm O giving A st = 4 x 314 = 1256 mm .
Check for development length :
Ld = 1102 / 1256 = 55 O ( From Table 7-6 )
IS 456-2000 clause 26.2.1 ( From Table 7-5 )
Development length of bars L d = O σs / 4 x bd
= O ( 0.87 x 250 x 1102 ) / ( 1256 x 4 x 1.0 )
= 47.71 O
= 47.71 x 20
= 954 mm

The bar shall


anchorage of extend
1200 mminto. Ifthe
in support for athe
some case straight length
bars are of bent
to be 954 mm
e.g. .anchored
Provide in
column , the bearing stress around the bend has to be checked as discussed
in the next example .
Check for shear :
Vu = 69.6 KN

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 151/242
8/12/2019 Design of Rectangular Water Tank (1)

Actual shear strength v = Vu / bd


3
= 69.6 x 10 / ( 230 x 515 )
2
= 0.588 N / mm
100 x As / b d = ( 100 x 1256 ) / ( 230 x 515 ) ( From IS 456-2000 , table 19 table 7-
= 1.06 0.25 difference
2
design ( permissible ) shear strength 0.61
c = N / mm > v 0.19 difference
Provide minimum shear reinforcement . For 230 mm wide beam ,
From IS 456-2000 clause 26.5.1.6
Spacing of minimum shear reinforcement using 6 O stirrups
= 0.87 Asv fy / 0.4 b
= 0.87 x 56 x 250 / 0.4 x 230
= 132.4 mm
spacing should not exceed
( i ) 450 mm
( ii ) 0.75 d = 0.75 x 515 = 386 mm

( iii ) ≤132.4 mm ( minimum )


( iv ) 569.2 mm ( designed )
Provide 6 mm O two-legged stirrups @ 130 mm c/c
Check for deflection :
Basic span / d ratio = 7
100 Ast / b d = 100 x 1256 / 230 x 515 = 1.06
modification factor = 1.4 IS 456-2000 clause 23.2.1 fig-4 ,for tension reinforcemen
Span / d permissible = 7 x 1.4 = 9.8
Actual span / d = 3000 / 515 = 5.83 < 9.8 ………………………( safe )
Check for cracking (spacing of bars ) :
Clear distance between bars
= ( 230 - 50 - 4 x 20 ) / 3 = 10 mm
Maximum clear distance permitted
= 300 mm ( cracking - table 8-1 , IS 456-2000 , table 15 ) ……………………
The design beam is shown in fig.

4 -20 O

550
Fixed end 2-12 O
support
1200 3000
230
6 O @ 130 c/c Stirrups 6 O @ 130 c/c

Design of Cantilever Beam


A cantilever rectangular bracket projects from a column of size 230 mm x 500 mm

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 152/242
8/12/2019 Design of Rectangular Water Tank (1)

in the direction of 500 mm for a length of 3 m


Factored load of 20 KN / m inclusive of self - weight
Material M15 grade concrete
HYSD reinforcement of grade Fe415 .
Solution : -

Vu = w x ℓ2= 20 x 3 = 60
2 KN
Mu = w x ℓ / 2 = 20 x 3 / 2 = 90 KNm
( a ) Moment steel :
Take size of Beam 230 mm x 550 mm overall.
Assuming 16 mm diameter bars in one layer
d = 550 - 25 ( Cover ) -8 OR
= 517 mm Mu,lim = 2.07 x 230 x 517
2 6 2
Mu / b d 90 x 10 / ( 230 x 517 ) = 127.26 KNm
= 1.46 < 2.07 ( Table 6-3 ) Mu < Mu,lim
The section is singly reinforced ( under-reinforced ) Beam
2
Pt = 50 1 -
√ 1 - ( 4.6 / fck) x ( Mu / bd )
fy / fck

P = 50 1 - √ 1 - ( 4.6 / 15 ) x ( 1.46 )
t
415 / 15
= 0.464
2
Ast = ( 0.464 / 100 ) x 230 x 517 = 552 mm
2.
Provide 16 mm O - 3 No. = 603 mm
Use 2- 10 mm O as bottom anchor bars .
( b ) Check for development length :
IS 456-2000 clause 26.2.1
Development length of bars L d = O σs / 4 x bd
2
Stress in bar σs = 0.87 x fy = 0.87 x 415 x 552 / 603 = 330.5 N / mm
2
( bd = 1.6 x 1 = 1.6 N / mm
IS 456-2000 clause 26.2.1 ( From Table 7-5 )
Development length of bars L d = O σs / 4 x bd
= O 330.5 / ( 4 x 1.6 )
= 51.64 O
= 51.64 x 16
= 826 mm
The arrangement of anchoring the bars is shown in fig. and is equivalent to an ancho
of 1127 mm. The bearing stress inside the bend is now checked .
O = 16 mm
a = 82 mm for internal bar ( centre to centre distance between bar ) ( = ( 230
= 25 + 16 = 41 mm for external bar . ( = cover + dia of bar )
3
The bearing stress is critical in external bar . Check for this stress for a = 41 mm.
Design bearing stress = 1.5 x f ck / [1 + ( 2O/a ) ]
= 1.5 x 15 / [ 1 + ( 2 x 16 / 41 ) ]

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 153/242
8/12/2019 Design of Rectangular Water Tank (1)

= 22.5 / 1.78 550


2
= 12.64 N / mm
At the centre of bend , the anchorage available = 279 + 147 = 426 mm
Stress in bar at centre of the bend = 330.5 x ( 826 - 426 ) / 826
2
= 160 N / mm
-3
Fbt = 160 x 201 x 10 = 32.16 KN ( area of 16 O bar = 201 mm2 )
Bearing stress = Fbt / r O
3
= 32.16 x 10 / 180 x 16
2 2
= 11.16 N / mm < 12.64 N /mm ……………………..( safe )
The arrangement is thus satisfactory.
( c )Check for she
Vu = 60 KN
Actual shear strength v = Vu / bd
3
= 60 x 10 / ( 230 x 517 )
2
= 0.505 N / mm
100 x As / b d = ( 100 x 603 ) / ( 230 x 517 ) ( From IS 456-2000 , table 19 table 7-
= 0.507 0.25 difference
2
design ( permissible ) shear strength c = 0.46 N / mm < v 0.243 difference
shear design is necessary .
At support , Vus = Vu - c bd OR Vus = ( 0.505 - 0.46
-3
= 60 - 0.46 x 230 x 517 x 10 = 5.35
= 60 - 54.699
= 5.3 KN
2
Using 6 mm O ( mild steel ) Two legged stirrups , A sv = 28 x 2 = 56 mm .
2
fy = 250 N / mm
Sv = 0.87 fy Asv d / Vus
3
= 0.87 x 250 x 56 x 517 / 5.3 x 10
= 1188 mm
Provide minimum shear reinforcement . For 230 mm wide beam ,
From IS 456-2000 clause 26.5.1.6
Spacing of minimum shear reinforcement using 6 O stirrups
= 0.87 Asv fy / 0.4 b
= 0.87 x 56 x 250 / 0.4 x 230
= 132.4 mm
spacing should not exceed
( i ) 450 mm
( ii ) 0.75 d = 0.75 x 517 = 388 mm
( iii ) ≤132.4 mm ( minimum )
( iv ) 1188 mm ( designed )
Provide 6 mm O two-legged stirrups @ 130 mm c/c
( d ) Check for deflection :

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 154/242
8/12/2019 Design of Rectangular Water Tank (1)

Basic span / d ratio = 7


100 Ast / b d = 100 x 603 / 230 x 517 = 0.507
modification factor = 1.2 IS 456-2000 clause 23.2.1 fig-4 ,for tension reinforcemen
Span / d permissible = 7 x 1.2 = 8.4
Actual span / d = 3000 / 517 = 5.8 < 8.4 ………………………( safe )
( e ) Check for cracking (spacing of bars ) :
Clear distance between bars
= ( 230 - 50 - 3 x 16 ) / 2 = 66 mm
Minimum clear distance permitted
= hagg + 5 mm = 20 + 5 = 25 mm or 16 mm ( O of bar ) i.e. 25 mm .
Maximum clear distance permitted
= 180 mm ( cracking - table 8-1 , IS 456-2000 , table 15 ) ……………………
The design beam is shown in fig.

50
279 3-16 O
295

108 r internal radius


r = 180
r 550
295
150 2-10 O

500 3000 mm

Stirrups 6 mm O @ 130 mm c/c

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 155/242
8/12/2019 Design of Rectangular Water Tank (1)

ht.
23.2 KN /m

3m

69.6 KN

04.4 KNm -
2 -6
x 10

IS 456-2000 , Table 19
Table 7-1
Design shear strength of concrete , C, N/m
100 x Concrete grade
As M15 M20 M25 M30 M35

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 156/242
8/12/2019 Design of Rectangular Water Tank (1)

≤ 0.15 0.28 0.28 0.29 0.29 0.29


0.25 0.35 0.36 0.36 0.37 0.37
0.50 0.46 0.48 0.49 0.50 0.50
1) 0.75 0.54 0.56 0.57 0.59 0.59
0.04 1.00 0.60 0.62 0.64 0.66 0.67
? -0.0304 1.25 0.64 0.67 0.70 0.71 0.73
1.50 0.68 0.72 0.74 0.76 0.78
1.75 0.71 0.75 0.78 0.80 0.82
2.00 0.71 0.79 0.82 0.84 0.86
2.25 0.71 0.81 0.85 0.88 0.90
2.50 0.71 0.82 0.88 0.91 0.93
2.75 0.71 0.82 0.90 0.94 0.96
3.00 0.71 0.82 0.92 0.96 0.99
The above given table is based on the following formula
Design shear strength c = 0.85 √ 0.8 x fck ( √ 1 + 5 x β -

6xβ
β = 0.8 x fck / 6.89 Pt , but not less than 1.

( safe )

4-20 O

2-12 O

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 157/242
8/12/2019 Design of Rectangular Water Tank (1)

( given )

2 -6
x 10

age

50 - 3 x 16 ) / 2 + 16 = 82 mm )
82 82 33
IS 456-2000 Clause 26.2.2.5 Bearing stresses at bend
The bearing stress in concrete for bends and hooks desc
16 25 need not be checked . The bearing stress inside a bend i

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 158/242
8/12/2019 Design of Rectangular Water Tank (1)

calculated as given below :


Bearing stress = Fbt / r O
Where ,
230
Fbt = tensile force due to design loads in a bar or group o
r = internal radius of the bend , and
O = size of the bar or , in bundle , the size of bar of equiv
For Limit state method of design , this stress shall not ex
Where,
fck is the characteristic strength of concrete and
a is the centre to centre distance between bars or group
of bars adjacent to the face of the member a shall be tak
bar ( O )

1)
0.08
? -0.0778

-3
) x 230 x 517 x10

KN

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 159/242
8/12/2019 Design of Rectangular Water Tank (1)

( safe )

3-16 O

2-10 O

230

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 160/242
8/12/2019 Design of Rectangular Water Tank (1)

M40

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 161/242
8/12/2019 Design of Rectangular Water Tank (1)

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 162/242
8/12/2019 Design of Rectangular Water Tank (1)

s
ribed in IS : 2502-1963
n any other bend shall be

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 163/242
8/12/2019 Design of Rectangular Water Tank (1)

f bars,

alent area
eed 1.5 f ck / [ ( 1+ 2O/a ) ]

of bars , for a bar or group


en as the cover plus size of

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 164/242
8/12/2019 Design of Rectangular Water Tank (1)

Design of Simply supported Doubly reinforced Beam


Span = 5 m ( simply supported rectangular beam )
super-imposed load = 40 KN / m
Beam section = 230 mm x 600 mm ( Given )
Material M15 grade concrete
HYSD reinforcement of grade Fe415
Solution : -
DL of beam 0.23 x 0.60 x 25 = 3.45 KN / m
super-imposed load = 40 KN / m
Total 43.45 KN / m
Factored load = 1.5 x 43.45 = 65.18 KN / m
2
Mu = w x ℓ / 8
2
= 65.18 x 5 / 8
= 203.688 KNm
Vu = w x ℓ / 2
= 65.18 x 5 / 2
= 162.95 KN
( a ) Moment steel :
Assuming 20 mm diameter bars in two layer
d = 600 - 25 ( Cover ) - 20 - 10 OR
= 545 mm Mu,lim = 2.07 x 230 x 545
2 6 2
Mu / b d = 203.69 x 10 / ( 230 x 545 ) = 141.41 KNm
= 2.98 > 2.07 ( Table 6-3 ) Mu > Mu,lim
The section is Doubly reinforced ( over-reinforced )
Mu,lim = 2.07 x 230 x 5452 x 10-6 = 141.41 KNm
Mu2 = Mu - Mu,lim = 203.69 - 141.41 = 62.28 KNm
Let the compression reinforcement be provided at an effective cover of 40 mm .
d' / d = 40 / 545
= 0.07 consider d' / d = 0.1 .
2
Stress in compression steel , f sc = 353 N / mm ( refer to table 6-6 )
Asc = Mu2 / ( fsc x ( d - d' ) )
6
= 62.28 x 10 / 353 ( 545 - 40 )
2
= 349 mm
Corresponding tension steel
Ast2 = Asc fsc / 0.87 fy
= 349 x 353 / ( 0.87 x 415 )
= 341.2 mm2
Ast,lim = Mu,lim / ( 0.87 fy ( d - 0.42 Xu,max ) )
6
= 141.41 x 10 / ( 0.87 x 415 ( 545 - 0.42 x 0.48 x 545 ) )
6
= 141.46 x 10 / 361.05 ( 435.13 )
2
= 900 mm

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 165/242
8/12/2019 Design of Rectangular Water Tank (1)

Ast = Ast,lim + Ast2 .


2
= 900 + 341.2 mm
2
= 1241.2 mm
Provide
Asc = 2-16 O = 402 mm
Ast = 4-20 O = 1256 mm2 ( all straight )
( b ) Check for development length :
As all the bars are taken into support , M u1 may be taken as Mu .
Assume L0 = 12 O Ld = 56 O ( From Table 7-6 )
1.3 x M1 / V + L0 ≥ Ld
6 3
1.3 x 203.69 x 10 / 162.95 x 10 +12 O ≥ 56 O
1625.02 ≥ 44 O
O ≤ 36.93 mm
Oprovided = 20 mm ……………………..( safe )
( c ) Check for shear
Vu = 162.95 KN
Actual shear strength v = Vu / bd
3
= 162.95 x 10 / ( 230 x 545 )
2
= 1.3 N / mm
100 x As / b d = ( 100 x 1256 ) / ( 230 x 545 ) ( From IS 456-2000 , table 19 table 7-
= 1.0
2
0.6
design ( permissible ) shear strength N / mm
c = < v
As the ends are confined with compressive reaction , shear at distance d will be used
checking shear at support . At 545 mm , shear is equal to

Vu = 162.95 - 0.545 x 43.45 = 139.27 KN


Vus = Vu - c b d
-3
= 139.27 - 0.6 x 230 x 545 x 10 = 64.06 KN
2 2
Assuming 8 mm O two - legged stirrups , A sv = 100 mm , fy = 415 N / mm .
Sv = 0.87 fy Asv d / Vus
3
= 0.87 x 415 x 100 x 545 / 64.06 x 10
= 307 mm
From IS 456-2000 clause 26.5.1.6
Spacing of minimum shear reinforcement using 8 mm O stirrups
= 0.87 Asv fy / 0.4 b
= 0.87 x 100 x 415 / 0.4 x 230
= 392.4 mm
spacing should not exceed
( i ) 450 mm
( ii ) 0.75 d = 0.75 x 545 = 408 mm
( iii ) ≤392.4 mm ( minimum )
( iv ) 307 mm ( designed )

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 166/242
8/12/2019 Design of Rectangular Water Tank (1)

Minimum shear reinforcement of 8 mm O @ 390 mm c/c will be used .


At support provide 8 mm O @ 300 mm c/c .
Shear resistance of beam with minimum shear reinforcement
= ( 0.87 fy Asv d / Sv )+ c b d
-3 -3
= (0.87 x 415 x 100 x 545 x 10 / 390 ) + 0.6 x 230 x 545 x 10
= 50.45 + 75.21
= 125.66 KN
Designed shear reinforcement is required from face of the support upto the
distance equal to
162.95 - 125.66 / 43.45 = 0.858 m
No. of stirrups = ( 858 / 300 ) + 1 = 3.86 say 4
Provide 8 mm O two-legged stirrups @ 300 mm c/c upto 4 no. from face of the suppor
and 8 mm O @ 390 mm c/c in remaining central portion .
( d ) Check for deflection :
Basic span / d ratio = 20
100 Ast / b d = 100 x 1256 / 230 x 545 = 1.0

modification factor = 0.97 IS 456-2000 clause 23.2.1 fig-4 ,for tension reinforcemen
100 Asc / b d = 100 x 402 / 230 x 545 = 0.32
modification factor = 1.08 IS 456-2000 clause 23.2.1 fig-5 ,for compression reinforc
Span / d permissible = 20 x 0.97 x 1.08 = 20.95
Actual span / d = 5000 / 545 = 9.17 ………………………( safe )
( d ) Check for cracking (spacing of bars ) :
Clear distance between bars
= ( 230 - 50 - 4 x 20 ) / 3 = 10 mm
Minimum clear distance permitted
= hagg + 5 mm = 20 + 5 = 25 mm or 20 mm ( O of bar ) i.e. 25 mm .
Maximum clear distance permitted

= 180
The design mm is( shown
beam cracking table 8-1 , IS 456-2000 , table 15 ) ……………………
in -fig.

2-16 O 2-16 O

545 600

600 4- 20 O ( straight ) 600


bearing
230 4- 20 O
5000 c/c

DIA 8O 8O 8O
NO. 4 rest 4
SPA. 300 390 300

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 167/242
8/12/2019 Design of Rectangular Water Tank (1)

Table 6-6
STRESS IN COMPRESSION REINFORCEMENT fsc ,
2
N / mm IN DOUBLY REINFORCED BEAMS
2 d'/d
fy N / mm
0.05 0.1 0.15 0.2
250 217 217 217 217
415 355 353 342 329
500 424 412 395 370
2 -6
x 10 550 458 441 419 380

If Mu > Mu,lim : design the section either increasing the


Over reinforced section ( doubly-reinforced beam ).The a
needed is obtained by providing compression( top ) reinf
reinforcement. Mu2 = Mu - Mu,lim as explained below .

Ast,lim = Mu,lim / ( 0.87 fy ( d - 0.42 Xu,max ) )


Asc = Mu2 / ( fsc x ( d - d' ) )
Ast2 = Asc fsc / 0.87 fy
Ast = Ast,lim + Ast2 .
If Xu < Xu,max the section is under-reinforced ( singly reinf
If Xu = Xu,max the section is balanced
If Xu > Xu,max the section is over-reinforced ( doubly reinfo
where ,
Xu,max = 0.53 x d ( for Fe250 mild steel )
Xu,max = 0.48 x d ( for Fe415 HYSD steel )
Xu,max = 0.46 x d ( for Fe500 HYSD steel )
Xu,max = 0.44 x d ( for Fe550 HYSD steel )
Xu =( 0.87 fy Ast ) / ( 0.36 fck b )

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 168/242
8/12/2019 Design of Rectangular Water Tank (1)

1)

for

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 169/242
8/12/2019 Design of Rectangular Water Tank (1)

ement

( safe )

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 170/242
8/12/2019 Design of Rectangular Water Tank (1)

dimensions of section or deign as


dditional moment of resistance M u2
rcement and additional tensile

rced )

rced )

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 171/242
8/12/2019 Design of Rectangular Water Tank (1)

Design of Simply supported Singly reinforced Beam


Span = 6 m ( simply supported rectangular beam )
characteristic load = 20 KN / m inclusive of its self-weight
Beam section = 230 mm x 600 mm
Material M15 grade concrete ( Given )

HYSD reinforcement of grade Fe415


The beam is resting on R.C.C. columns.
Solution : -
Factored load = 1.5 x 20 = 30 KN /m.
2
Mu = w x ℓ / 8
2
= 30 x 6 / 8
= 135 KNm
Vu = w x ℓ / 2

= 30 x 6 / 2

= 90 KN
( a ) Moment steel :
Assuming 20 mm diameter bars in one layer
d = 600 - 25 ( Cover ) -10 OR
= 565 mm Mu,lim = 2.07 x 230 x 565
2 6 2
Mu / b d = 135 x 10 / ( 230 x 565 ) = 151.983 KNm
= 1.84 < 2.07 ( Table 6-3 ) Mu < Mu,lim
The section is singly reinforced ( under-reinforced )

1- √ 1 - ( 4.6 / f ck)
2
x ( Mu / bd )
Pt = 50 fy / fck

Pt = 50
1- √ 1 - ( 4.6 / 15 ) x ( 1.84 )
415 / 15
= 0.614
2
Ast = ( 0.614 / 100 ) x 230 x 565 = 798 mm
As per IS 456-2000 clause 26.5.1.1 ( a )
2
Minimum steel , As = ( 0.205 / 100 ) x 230 x 565 = 266 mm
From Table 6-4
2
Ast,lim
= 0.72 / 100 x 230 x 565 = 9362.mm .
Provide 16 mm O - 4 No. = 804 mm
Let 2 bars are bent at 1.25 D = 1.25 x 600 = 750 mm , from the face of the support .
( b ) Check for development length :
( 1 ) A bar can be bent up at a distance greater than L d = 56 O ( Table 7-6 )
From the centre of the support , i.e. 56 x 16 = 896 mm .

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 172/242
8/12/2019 Design of Rectangular Water Tank (1)

in this case , the distance is ( 3000 - 750 ) = 2250 mm ……………….( safe )


2
( 2 ) For the remaining bars , A st = 402 mm
Mu1 = 0.87 fy Ast d ( 1 - [( fy Ast ) / ( fck b d ) ] )
-6
= 0.87 x 415 x 402 x 565 ( 1 - [ ( 415 x 402 ) / ( 15 x 230 x 565 ) ] ) x 10

=
= 82.01
74.99 x
KNm 0.91
Vu = 90 KN , L0 = 12 O ( assume )
As the reinforcement is confined by compressive reaction
1.3 x M1 / V + L0 ≥ Ld
6 3
1.3 x 74.99 x 10 / 90 x 10 +12 O ≥ 56 O
1083.19 ≥ 44 O
O ≤ 24.62 mm
Oprovided = 16 mm ……………………..( safe )
( c ) Check for shear :

At support , Vu = 90 KN
As the ends of the reinforcement are confined with compressive reaction , shear at distan
will be used for checking shear at support.
Vu = 90 - 0.565 x w = 90 - 0.565 x 30 = 73.05 KN
Actual shear strength v = Vu / bd
3
= 73.05 x 10 / ( 230 x 565 )
2
= 0.562 N / mm
100 x As / b d = ( 100 x 402 ) / ( 230 x 565 ) ( From IS 456-2000 , table 19 table 7-
= 0.309 0.25 difference
2
design ( permissible ) shear strength c = 0.376 N / mm < v 0.191 difference
shear design is necessary .
At support , Vus = Vu - c bd OR Vus = ( 0.562 - 0.376
-3
= 73.05 - 0.376 x 230 x 565 x 10 = 24.17
= 73.05 - 48.86
= 24.19 KN
Capacity of bent bars to resist shear
-3
= 2 x 201 x 0.87 x 415 x sin 45º x 10 ( 0.87 fy Asv sin α )
= 102.6 KN
Bent bars share 50 % = 12.09 KN
Stirrups share 50 % = 12.09 KN
Using 6 mm O ( mild steel ) Two legged stirrups , A sv = 28 x 2 = 56 mm2 .
Sv = 0.87 fy Asv d / Vus
3
= 0.87 x 250 x 56 x 565 / 12.09 x 10
= 569.2 mm
From IS 456-2000 clause 26.5.1.6
Spacing of minimum shear reinforcement using 6 O stirrups

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 173/242
8/12/2019 Design of Rectangular Water Tank (1)

= 0.87 Asv fy / 0.4 b


= 0.87 x 56 x 250 / 0.4 x 230
= 132.4 mm
spacing should not exceed
( i ) 450 mm
( ii ) 0.75 d = 0.75 x 565 = 423 mm
( iii ) ≤132.4 mm ( minimum )
( iv ) 569.2 mm ( designed )
Provide 6 mm O two-legged stirrups @ 130 mm c/c
At 1.25 D = 750 mm from face of the support where contribution of bent bars is not availab
Vu = 90 - 0.75 x w = 90 - 0.75 x 30 = 67.5 KN
Vus = Vu - c bd
-3
= 67.5 - 0.376 x 230 x 565 x 10
= 67.5 - 48.86
= 18.64 KN

Provide minimum
( d ) Check 6 mm O: M.S. two -legged stirrups @ 130 mm c/c throught the beam.
for deflection
Basic span / d ratio = 20
100 Ast / b d = 100 x 804 / 230 x 565 = 0.62
modification factor = 1.1 IS 456-2000 clause 23.2.1 fig-4 ,for tension reinforcement

Span / d permissible = 20 x 1.1 = 22


Actual span / d = 6000 / 565 = 10.62 ………………………( safe )
( d ) Check for cracking (spacing of bars ) :
Clear distance between bars
= 230 - 50 - 2 x 16 = 148 mm
Minimum clear distance permitted
= hagg + 5 mm = 20 + 5 = 25 mm or 16 mm ( O of bar ) i.e. 25 mm .
Maximum clear distance permitted
= 180 mm ( cracking - table 8-1 , IS 456-200 , table 15 ) ……………………
The design beam is shown in fig.
2-10 O 2-10 O

565 600

750 4- 16 O ( 2 straight +
2 bent )
230 4- 16 O
6000 c/c

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 174/242
8/12/2019 Design of Rectangular Water Tank (1)

mm mm c c

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 175/242
8/12/2019 Design of Rectangular Water Tank (1)

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 176/242
8/12/2019 Design of Rectangular Water Tank (1)

Consider width of the beam equal to 230 mm. The depth may be a
as 1 / 10 to 1 / 8 of the span.
To find steel area
( 1 ) For a given ultimate moment ( also known as factored momen
and assumed width of section , find out d from equation


d = Mu / Qlim b
This is a balanced section and steel area may be found out from t

( 2 ) For a given factored moment ,width and depth of section .


2
Obtain Mu,lim = Qlim bd .
If Mu < Mu,lim : design as under-reinforced section (singly reinfor

Pt = 50
1- √ 1 - ( 4.6 / f ck)
2
x ( Mu / bd )

fy / fck
If Mu = Mu,lim : design as balanced section as explained in ( 1 ).
If Mu > Mu,lim : design the section either increasing the dimensio
Over reinforced section ( doubly-reinforced beam ).The additional
2 -6
x 10 needed is obtained by providing compression( top ) reinforcement
reinforcement. Mu2 = Mu - Mu,lim as explained below .

Ast,lim = Mu,lim / ( 0.87 fy ( d - 0.42 Xu,max ) )


Asc = Mu2 / ( fsc x ( d - d' ) )
Ast2 = Asc fsc / 0.87 fy
Ast = Ast,lim + Ast2 .

If Xu < Xu,max the section is under-reinforced ( singly reinforced )


If Xu = Xu,max the section is balanced
If Xu > Xu,max the section is over-reinforced ( doubly reinforced )
where ,
Xu,max = 0.53 x d ( for Fe250 mild steel )
Xu,max = 0.48 x d ( for Fe415 HYSD steel )
Xu,max = 0.46 x d ( for Fe500 HYSD steel )

Xu,max = 0.44 x d ( for Fe550 HYSD steel )


Xu =( 0.87 f y Ast ) / ( 0.36 fck b )

Table 6-2
Limiting Moment of Resistance and Reinforcement
Index for Singly Reinforced Rectangular Sections

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 177/242
8/12/2019 Design of Rectangular Water Tank (1)

2
fy , N / mm 250 415 500 550
2
Mu,lim / fck b d 0.148 0.138 0.133 0.129
Pt,lim fy / fck 21.93 19.86 19.03 18.2

Table 6-3
Limiting Moment of resistance factor Q lim, N / mm
2

For singly reinforced rectangular sections


2
fck fy, N / mm
2
N / mm 250 415 500 550
15 2.22 2.07 2.00 1.94
20 2.96 2.76 2.66 2.58
25 3.70 3.45 3.33 3.23
30 4.44 4.14 3.99 3.87

Table 6-4
ed Limiting Percentage of Reinforcement P t,lim
For singly reinforced rectangular sections
2
fck fy, N / mm
2
N / mm 250 415 500 550
15 1.32 0.72 0.57 0.50
20 1.75 0.96 0.76 0.66
) 25 2.19 1.20 0.95 0.83
0.11 30 2.63 1.44 1.14 0.99
? -0.084
IS 456-2000 Clause 26.5 Requirements of Reinforcement for
-3
) x 230 x 565 x10 Structural Members
KN 26.5.1 Beams
26.5.1.1 Tension Reinforcement
a ) Minimum reinforcement - The minimum area of tension reinfo
shall not be less than that given by the following :
As / b d = 0.85 / fy
where ,
As = minimum area of tension reinforcement ,
b = breadth of the beam or the breadth of the web of T- beam ,
d = effective depth , and
2
fy = characteristic strength of reinforcement in N / mm .
b ) Maximum reinforcement - The maximum area of tension
reinforcement shall not exceed 0.04 b D.
Minimum steel %
For mild steel

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 178/242
8/12/2019 Design of Rectangular Water Tank (1)

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 179/242
8/12/2019 Design of Rectangular Water Tank (1)

IS 456-2000 , Table 19
Table 7-1
2
Design shear strength of concrete , C, N / mm
Pt = 100 x As Concrete grade
bxd M15 M20 M25 M30 M35 M40
≤ 0.15 0.28 0.28 0.29 0.29 0.29 0.30
0.25 0.35 0.36 0.36 0.37 0.37 0.38
0.50 0.46 0.48 0.49 0.50 0.50 0.51
0.75 0.54 0.56 0.57 0.59 0.59 0.60
1.00 0.60 0.62 0.64 0.66 0.67 0.68
1.25 0.64 0.67 0.70 0.71 0.73 0.74
1.50 0.68 0.72 0.74 0.76 0.78 0.79
1.75 0.71 0.75 0.78 0.80 0.82 0.84
2.00 0.71 0.79 0.82 0.84 0.86 0.88
2.25 0.71 0.81 0.85 0.88 0.90 0.92
2.50 0.71 0.82 0.88 0.91 0.93 0.95

2.75
3.00 0.71
0.71 0.82
0.82 0.90
0.92 0.94
0.96 0.96
0.99 0.98
1.01
The above given table is based on the following formula
Design shear strength c = 0.85 √ 0.8 x fck ( √ 1 + 5 x β - 1 )
6xβ
β = 0.8 x fck / 6.89 Pt , but not less than 1.0

IS 456-2000 , Table 20
Table 7-2
Maximum shear stress , C, N / mm2
Concrete
grade M15 M20 M25 M30 M35 M40
2
( c )max N/mm 2.5 2.8 3.1 3.5 3.7 4.0

IS 456-2000 Clause 26.5.1.6 Minimum shear reinforcement


Minimum shear reinforcement in the form of stirrups shall be provi
such that : Asv / b sv ≥ 0.4 / 0.87 f y
where,
Asv = total cross-sectional area of stirrup legs effective in shea
Sv = stirrup spacing along the length of the member ,
b = breadth of the beam or breadth of the web of flanged be

fy = characteristic strength of the stirrup reinforcement in N /


2
which shall not be taken greater than 415 N / mm .

check for deflection


Basic values of span to effective depth ratios for spans upto 10 m
cantilever 7
simply supported 20

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 180/242
8/12/2019 Design of Rectangular Water Tank (1)

continuous 26
For spans above 10 m, the values in (a) may be multiplied by
10 / span in metres , except for cantilever in which case
deflection calculations should be made.
check for cracking
IS 456-2000 26.3.3 Maximum distance between bars in tension
Table 15 Clear distance Between Bars ( Clause
26.3.3 )
% redistribution to or from section considered
fy -30 -15 0 +15 +30
Clear distance between bars
2
N / mm mm mm mm mm mm
250 215 260 300 300 300
415 125 155 180 210 235
500 105 130 150 175 195

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 181/242
8/12/2019 Design of Rectangular Water Tank (1)

ssumed

t)

ble P t,lim , SP : 16 ,2.3

ced beam) as explained below.

ns of section or deign as
oment of resistance M u2
and additional tensile

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 182/242
8/12/2019 Design of Rectangular Water Tank (1)

rcement

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 183/242
8/12/2019 Design of Rectangular Water Tank (1)

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 184/242
8/12/2019 Design of Rectangular Water Tank (1)

ed

m , and
2
m

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 185/242
8/12/2019 Design of Rectangular Water Tank (1)

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 186/242
8/12/2019 Design of Rectangular Water Tank (1)

Kb = 1.5 x Ib / l
3
= 1.5 x ( ( 1 / 12 ) x 230 x 420 ) / 5000
3
= 426006 mm
Column stiffness
3
Kc = Ic / l = 1/12 x 400 x 230 / 7000
3
= 57938.095 mm
β1 = β2 = ∑ Kc / ( ∑Kc + ∑Kb )
= 2 x 57938.1 / 2 ( 57938.1 + 426006 )
= 0.1197
as per IS 456-2000 fig. 27
lef / l = 1.06 < 1.2 ……………….consider 1.2
ley = 1.2 x unsupported length
= 1.2 ( 7000 -420 )
= 7896 mm
ley / b = 7896/300
= 26.32 > 12
The column is long about Y direction.
The column is bent in double curvature. Reinforcement will be distributed equally on four
ℓex / D = 6000 / 400
= 15.0 > 12
ℓey / b = 5000 / 300
= 16.7 > 12
Therefore the column is slender about both the axes.
Additional moments
Max = ( Pu D / 2000 ) x ( ℓex / D )2
2 -3
= ( 1500 x 400 / 2000 ) x (15) x 10
= 67.5 KNm
May = ( Pu b / 2000 ) x ( ℓey / b )2
2 -3
= ( 1500 x 300 / 2000 ) x (16.7) x 10
= 62.75 KNm
The above moments will have to be reduced in accordance with clause 39.7.1.1 of the IS
but multiplication factors can be evaluated only if the reinforcement is known.
For first trial , assume p = 3.0 ( with reinforcement equally on all the four sides ).
Ag = 400 x 300 Puz = 0.45 fck Ac + 0.75 f
2
= 120000 mm Ac = 400 x 300 - 1200
2 2
mm
From chart 63 , puz / Ag = 22.5
-3 N/mm OR = 116400
Puz = 22.5 x 120000 x 10 Puz = 0.45 x 30 x 116400 x 1
= 2700 KN = 1571.4 +
Calculation of Pb : = 2692 KN
Assuming 25 mm dia bars with 40 mm cover
d' / D ( about xx-axis ) = 52.5 / 400 = 0.13 ……………use d' / D = 0.15

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 187/242
8/12/2019 Design of Rectangular Water Tank (1)

d' / D ( about yy-axis ) = 52.5 / 300 = 0.18 ……………use d' / D = 0.2


From Table 60 , SP 16
Pb ( about xx-axis ) = ( k 1 + k2 p / fck ) fck b D
-3
Pbx = ( 0.196 + 0.203 x 3 /30 ) 30 x 300 x 400 x10

= 779 KN
Pb ( about yy-axis ) = ( k 1 + k2 p / fck ) fck b D
-3
Pby = ( 0.184 + 0.028 x 3 /30 ) 30 x 300 x 400 x10
= 672 KN
Kx = ( Puz - Pu ) / ( Puz - Pbx )
= ( 2700 - 1500 ) / ( 2700 - 779 )
= 1200 / 1921
= 0.625
Ky = ( Puz - Pu ) / ( Puz - Pby )
= ( 2700 - 1500 ) / ( 2700 - 672 )
= 1200 / 2028
= 0.592
The additional moments calculated earlier , will now be multiplied by the above values of
Max = 67.5 x 0.625 = 42.2 KNm
May = 62.75 x 0.592 = 37.15 KNm
The additional moments due to slenderness effects should be added to the initial momen
after modifying the initial moments as follows ( see note 1 under 39.7.1 of the code IS 45
Mux = ( 0.6 x 40 - 0.4 x 22.5 ) = 15.0 KNm
Muy = ( 0.6 x 30 - 0.4 x 20 ) = 10.0 KNm
The above actual moments should be compared with those calculated from minimum ecc
consideration ( see 25.4 of the code ) and greater value is to be taken as the initial mome
adding the additional moments.
ex = ( ℓ / 500 ) + ( D / 30 ) = ( 7000 / 500 ) + ( 400 / 30) = 27.333
ey = ( ℓ / 500 ) + ( b / 30 ) = ( 7000 / 500 ) + ( 300 / 30) = 24
Moments due to minimum eccentricity :
-3
Mux = 1500 x 27.33 x 10 = 41.0 KNm > 15.0 KNm
-3
Muy = 1500 x 24 x 10 = 36.0 KNm > 10.0 KNm
Total moments for which the column is to be designed are :
Mux = 41.0 + 42.2 = 83.2 KNm

Muy = 36.0 + 37.15 = 73.15 KNm


The section is to be checked for biaxial bending
3
Pu / fck b D = 1500 x 10 / ( 30 x 300 x 400 )
= 0.417
p / fck = 3 / 30 = 0.10
referring to chart 45 (d' / D = 0.15 ) ,

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 188/242
8/12/2019 Design of Rectangular Water Tank (1)

2
Mu / fck b D = 0.104
2
Mux1 = 0.104 x 30 x 300 x 400
= 149.8 KNm
referring to chart 46 (d' / D = 0.2 ) ,
2
Mu / fck b D = 0.096
2
Muy1 = 0.096 x 30 x 400 x 300
= 103.7 KNm
Mux / Mux1 = 83.2 / 149.8 = 0.56
Muy / Muy1 = 73.15 / 103.7 = 0.71
Pu / Puz = 1500 / 2700 = 0.56
referring to chart 64 , the maximum allowable value of Mux / Mux1 corresponding to the
above values of Muy / Muy1 and Pu / Puz is 0.58 which is slightly higher than the actual
value of 0.56 . The assumed reinforcement of 3.0 % is therefore satisfactory.
for Pu / Puz = 0.56 , αn = 1.602
From , IS 456-2000 , Clause 39.6
αn = 1.602 0.2 difference 0.34
check : α α 0.04 difference ?
Mux Muy
Mux1
+ Muy1
≤1
1.602
( 0.56 ) + 1.602
( 0.71 )

0.395 + 0.577

= 0.972 ≤1 ……………………..( O.K.)

As = p x b x D / 100 = 3.0 x 300 x 400 / 100


2
= 3600 mm
2
Provide 25 mm diameter bar ( 3600 / 491 ) = 8 no. = 3928 mm
Ties : -
O min = 25 / 4
= 6.25
Provide 8 mm O M.S. ties. 500
Spacing should not exceed lesser of
( i ) 300 mm
( ii ) 16 x 25 = 400 mm 300
( iii ) 48 x 8 = 384 mm
Provide 8 mm O M.S. ties @ 300 mm c/c

Note that the distance between corner bars in one face is more than 48 O tr

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 189/242
8/12/2019 Design of Rectangular Water Tank (1)

( 500 - 80 -25 = 395 > 48 x 8 = 384 ). Therefore two sets of closed ties shall be used .
Note that if this distance would be less than ( 48 x 8 ) mm , open ties for internal bars wo
sufficient.

Design of slender ( Long ) columns ( with Uniaxial bending )


Size of column 230 x 450 mm Column of a braced frame
Concrete grade M 20
2
Characteristic strength of reinforcement 415 N/mm HYSD reinforcement
Unsupported length in both the direction = 5.0 m
Factored load Pu = 1000 kN
Factored.moment in the direction of larger dimension M uxx = 80 kNm at top and 60 KNm
bottom.
Factored.moment in the direction of shorter dimension M uyy = 40 kNm at top and 30 KNm
bottom.
The column is bent in double curvature and is slender about both the axis.
The slenderness ratios ℓex / Ixx and ℓey / Iyy are respectively 13.2 and 15.6
Assume that the moments due to minimum eccentricities about both the axes are less th
applied moments.
Solution : -
Assume adjustment factor k = 0.8 for the first trial .
Additional moments
Max = ( Pu D / 2000 ) x ( ℓex / D )2
2 -3
= ( 1000 x 450 / 2000 ) x (13.2 ) x 10
= 39.2 KNm
May = ( Pu b / 2000 ) x ( ℓey / b )2
2 -3
= ( 1000 x 230 / 2000 ) x (15.6 ) x 10
= 28 KNm
About XX
Pu = 1000 KN
Muxx = Mi + k x Max
Mi = 0.6 Mu2 + 0.4 Mu1
= 0.6 x 80 - 0.4 x 60
= 48 - 24
= 24 KNm < 0.4 x 80 = 32 KNm
Take , Mi = 32 KNm
Note that Mu1 is considered negative as the column bends in double curvature .
Mu,xx = 32 + 0.8 x 39.2
= 63.36 KNm. < 80 KNm
Take , Mu,xx = 80 KNm
About YY
Pu = 1000 KN
Muyy = Mi + k x May

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 190/242
8/12/2019 Design of Rectangular Water Tank (1)

Mi = 0.6 Mu2 + 0.4 Mu1


= 0.6 x 40 - 0.4 x 30
= 24 - 12
= 12 KNm < 0.4 x 40 = 16 KNm
Take , Mi = 16 KNm
Mu,yy = 16 + 0.8 x 28
= 38.4 KNm. < 40 KNm
Take , Mu,yy = 40 KNm
Finally design the column for
Pu = 1000 KN
Mu,xx = 80 KNm
Mu,yy = 40 KNm
For the first trial , assume uniaxial bending about y axis for the following values .
P'u = 1000 KN
M'uy = ( 230 / 450 ) ( 80 + 40 ) = 61.33 KNm
d' / D = 50 / 230 = 0.22 Say 0.2
3
P'u / fck b D = 1000 x 10 / 20 x 230 x 450 = 0.48
2 6 2
M'uy / fck b D = 61.33 x 10 / 20 x 450 x 230 = 0.129
p / fck = from chart 46 , SP : 16 = 0.162
p = 0.162 x 20
= 3.24
Asc = ( 3.24 /100 ) x 230 x 450
2
= 3353 mm
Assumptions made above for k = 0.8 and for uniaxial moment to find out first trial steel ar
2

usually conservative
Now check the assumed. Letsection
us try 4as
- 25 O + 4: - 20 O = 3220 mm
follows
Puz = 0.45 fck Ac + 0.75 fy Asc
Ac = 230 x 450 - 3220
2
= 100280 mm
-3 -3
Puz = 0.45 x 20 x 100280 x 10 + 0.75 x 415 x 3220 x 10
= 902.52 + 1002.23
= 1904.7 KN
Pb = ( k1 + k2 p / fck ) fck b D
Asc = ( p / 100 ) x b x D

p / fck = ( 3220 x 100 ) / ( 230 x 450 x 20 )


= 0.156
For d' / D = 0.2 , k1 = 0.184 and k2 = -0.022 from table 60 ,SP : 16
-3
Pb = ( 0.184 - 0.022 x 0.156 ) x 20 x 230 x 450 x 10
= 0.181 x 2070
= 373.8 KN

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 191/242
8/12/2019 Design of Rectangular Water Tank (1)

k = ( Puz - Pu ) / ( Puz - Pb )
= ( 1904.7 - 1000 ) / ( 1904.7 - 373.8 )
= 904.7 / 1530.9
= 0.59
Design for

Pu = 1000 KN
Mux = 32 + 0.59 x 39.2 = 55.13 KNm < 80 Take , Mux = 80 KNm
Muy = 16 + 0.59 x 28 = 32.52 KNm < 40 Take , Muy = 40 KNm
For p / fck = 0.162 and Pu / fck b D = 0.48 , the reinforcement being equally distributed ,
the moment capacities can be found out as follows :
About XX
d' / D = 50 / 450 = 0.11 ≈ 0.15
From chart 45 , SP : 16
2
Mux1 / fck b D = 0.145
2 -6
Mux1 = 0.145 x 20 x 230 x 450 x 10
= 135.07 KNm
About YY
d' / D = 50 / 230 = 0.22 ≈ 0.2
From chart 46 , SP : 16
2
Muy1 / fck b D = 0.13
2 -6
Muy1 = 0.13 x 20 x 450 x 230 x 10
= 61.89 KNm
Check :
Pu / Puz = 1000 / 1904.7 = 0.525
From , IS 456-2000 , Clause 39.6

α:
check
n = 1.542 0.2 difference
0.075 difference
0.34
?
α α
Mux Muy
Mux1
+ Muy1
≤1
1.542 1.542
80 + 40
135.07 61.89

0.446 + 0.51

0.956 ≤1 …………….( O.K.)


Provide 4 - 25 O + 4 - 20 O equally distributed. 230

Ties : Minimum diameter Otr = 25 / 4 = 6.25 mm


Use 8 mm diameter M.S. ties.
Spacing should not exceed lesser of
( i ) 230 mm ( least lateral dimension )
( ii ) 16 x 25 = 400 mm ( 16 times least longitudinal diameter

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 192/242
8/12/2019 Design of Rectangular Water Tank (1)

( iii ) 48 x 8 = 384 mm ( 48 times diameter of tie )


Provide 8 mm O M.S. ties @ 230 mm c/c
Note that the distance between corner bars in one face is less than 48 O tr
( 450 - 80 -25 = 345 < 48 x 8 = 384 ). Therefore two sets of Opened ties shall be used .
Note that if this distance would be more than ( 48 x 8 ) mm , closed ties for internal bars

sufficient.

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 193/242
8/12/2019 Design of Rectangular Water Tank (1)

IS 456-2000 clause 25

Note :- A column may be considered as short w


ratios lex / D and ley / b ≤ 12 OR lex / ixx < 40 wh
/ D ≤ 10 .

lex = effective length in respect of the major axis


( Given ) D = depth in respect of the major axis
ley = effective length in respect of the minor axis
b = width of the member
ottom.
ixx = radius of gyration in respect of the major a
iyy = radius of gyration in respect of the minor a
ttom.

IS 456 : 2000
Table 28 Effective Length of Com
Degree of End Restraint of
Sy
Compression members
Effectively held in position and
restrained against rotation in
both ends

Effectively held in position at


both ends , restrained against
rotation at one ends

Effectively held in position at


both ends , but not restrained
against rotation .

Effectively held in position and


restrained against rotation at one end ,
and at the other end restrained against
rotation but not held in position

Effectively held in position and


restrained against rotation at one end ,
and at the other partially restrained
against rotation but not held in position

Effectively held in position at one end


but not restrained against rotation and at
the other end restrained against rotation
but not held in position

Effectively held in position and


restrained a ainst rotation at one end

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 194/242
8/12/2019 Design of Rectangular Water Tank (1)

but not held in position nor restrained


against rotation at the other end.

NOTE - ℓ is the unsupported length of compres

( i + 1 ) th floor sla

Bea

( i ) th floor

sides.

Effective length of column ( ℓef ) : It is the distance betwe


column height .

456-2000

y Asc
0*3/100

-3 -3
0 + 0.75 x 415 x 3600 x 10
1120.5

SP : 16 ,Table 60
Slender compression members- Values

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 195/242
8/12/2019 Design of Rectangular Water Tank (1)

Rectangular sections : P b / fck b D = k1 + k2 .


2
Circular sections : Pb / fck D = k1 + k2 . p
Values of k1
Section d' / D

0.05 0.10 0.15


Rectangular 0.219 0.207 0.196
Circular 0.172 0.160 0.149
Values of k2
Section d' / D
2
fy N/ mm 0.05 0.10
Rectangular ; equal 250 -0.045 -0.045
reinforcement on two 415 0.096 0.082
opposite sides 500 0.213 0.173
Rectangular ; equal 250 0.215 0.146
reinforcement on four 415 0.424 0.328
sides 500 0.545 0.425
k. 250 0.193 0.148
Circular 415 0.410 0.323
500 0.543 0.443
ts IS 456-2000 clause 39.7.1
-2000 ) The additional moments M ax and May shall be calculated
Max = ( Pu D / 2000 ) x ( ℓex / D )2
May = ( Pu b / 2000 ) x ( ℓey / b )2
entricity Where ,
nt for Pu = axial load on the member,
ℓex = effective length in respect of the majo
mm > 20 mm ℓey = effective length in respect of the mino
mm > 20 mm D = depth of the cross - section at right an
the major axis , and
b = width of the member
NOTES : -
1) A column may be considered braced in a given plane i
stability to the structure as a whole is provided by walls o

bracing or buttressing designed to resist all lateral forces


that plane. It should otherwise be considered unbraced.
2 ) In the case of a braced column without any transvers
occurring in its height, the additional moment shall be ad
to an initial moment equal to sum of 0.4 M u1, and 0.6 Mu2
where Mu2 is the larger end moment and Mu1 is the small

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 196/242
8/12/2019 Design of Rectangular Water Tank (1)

end moment (assumed negative if the column is bent in


curvature). In no case shall the initial moment be less tha
0.4 Mu2 nor the total moment including the initial moment
less than Mu2. For unbraced columns, the additional mo

shall be added to the end moments.


3 ) Unbraced compression members, at any given level
subject to lateral load are usually constrained to deflect
equally. In such cases slenderness ratio for each column
be taken as the average for all columns acting in the sa
direction.
IS 456-2000 clause 39.7.1.1
The values given by equation 39.7.1 may be multiplied b
K = ( Puz - Pu ) / ( Puz - Pb ) ≤1
where ,
Pu = axial load on compression member,
Puz = as defined in 39.6, Puz = 0.45 fck Ac +
-0.068 Pb = axial load corresponding to the condition
of maximum compressive strain of
0.0035 in concrete and tensile strain of
0.002 in outer most layer of tension steel.

8-25 O

8O@
300 c/c

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 197/242
8/12/2019 Design of Rectangular Water Tank (1)

ld be

t
( Given )
at

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 198/242
8/12/2019 Design of Rectangular Water Tank (1)

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 199/242
8/12/2019 Design of Rectangular Water Tank (1)

-0.1275

4-25 O
+ 4 -20 O
450

8 O @ 230 mm c/c
( three sets )

of bar )

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 200/242
8/12/2019 Design of Rectangular Water Tank (1)

ould be

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 201/242
8/12/2019 Design of Rectangular Water Tank (1)

hen both slenderness


re, For Circular column lex

is.
is.

pression Members ( Clause E-3 )


Theoretical Value Recommended Value
bol of effective length of effective length

0.5 ℓ 0.65 ℓ

0.7 ℓ 0.8 ℓ

1.0 ℓ 1.0 ℓ

1.0 ℓ 1.2 ℓ

- 1.5 ℓ

2.0 ℓ 2.0 ℓ

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 202/242
8/12/2019 Design of Rectangular Water Tank (1)

. .

ion member.

n the points of zero moment (contraflexure ) along the

of P b

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 203/242
8/12/2019 Design of Rectangular Water Tank (1)

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 204/242
8/12/2019 Design of Rectangular Water Tank (1)

ouble
n
be
ent

r storey,

may
e

the following factor :

.75 fy Asc

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 205/242
8/12/2019 Design of Rectangular Water Tank (1)

Design of short eccentrically loaded square columns - Biaxial bending.


Size 500 mm x 500 mm
Axial factored load 1500 KN
Factored moment Mux = 90 KNm
Muy = 120 Knm ( Given )

moment due to minimum eccentricity is less than the applied moment.


Material M15 grade concrete
HYSD reinforcement of grade Fe415
Solution :-
Assume an axial load P'u of 1500 KN and a uniaxial moment M' ux = 90 + 120 = 210 K
3
P'u / ( fck x b x D ) = 1500 x 10 / ( 15 x 500 x 500 )
= 0.4
2 6 2
M'ux / ( fck x b x D ) = 210 x 10 / ( 15 x 500 x 500 )
= 0.112
d' = 40 + 10 = 50 mm

d' / D =
From 50 /32
chart 500 = 0.1
, SP-16
p / fck = 0.078
p = 0.078 x 15 = 1.17
As = 1.17 x b x D = 1.17 x 500 x 500 / 100
2
= 2925 mm
2
Provide 4-25 mm O + 4-20 mm O = 3220 mm , equally distributed
p = 3220 x 100 / ( 500 x 500 )
p = 1.288
p / fck = 1.288 / 15
= 0.086
The assumed section is now checked.
For p / fck = 0.086 and Pu / ( fck x b x D ) = 0.4 ,
The reinforcement being equally distributed , the moment capacities from
Chart - 44 , SP-16
2 2
Mux1 / ( fck x b x D ) = Muy1 / ( fck x b x D ) = 0.108
2 -6
Mux1 = Muy1 = 0.108 x 15 x 500 x 500 x 10
= 202.5 KNm
Puz = 0.45 fck Ac + 0.75 fy Asc
Ac = 500 x 500 - 3220
2
= 246780 mm
-3 -3
Puz = 0.45 x 15 x 246780 x 10 + 0.75 x 415 x 3220 x 10
= 1665.8 + 1002.2
= 2668 KN
Pu / Puz = 1500 / 2668

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 206/242
8/12/2019 Design of Rectangular Water Tank (1)

= 0.56
From , IS 456-2000 , Clause 39.6
αn = 1.602 0.2 difference 0.34
check : 0.04 difference ? -0.068
αn αn
Mux Muy
Mux1
+ Muy1
≤1
1.602 1.602
90 120
202.5 + 202.5

0.273 + 0.433

0.706 ≤1
Ties : Minimum diameter Otr = 25 / 4 = 6.25 mm
Use 8 mm diameter M.S. ties. 500
Spacing should not exceed lesser of
( i ) 500 mm 4-25
( ii ) 16 x 25 = 400 mm 500 4-20
( iii ) 48 x 8 = 384 mm
Provide 8 mm O M.S. ties @ 350 mm c/c
8O
350

Design of short eccentrically loaded rectangle columns - Biaxial bending.


Size 300 mm x 500 mm
Axial factored load 1500 KN
Factored moment Mux = 60 KNm

Muy = 60 KNm ( Given )


moment due to minimum eccentricity is less than the applied moment.
Material M15 grade concrete
HYSD reinforcement of grade Fe415
Solution :-
Assume an axial load P'u of 1500 KN and a uniaxial moment M' uy = 300 / 500 ( 60 + 6
3
P'u / ( fck x b x D ) = 1500 x 10 / ( 15 x 300 x 500 )
= 0.67
2 6 2
M'u / ( fck x b x D ) = 72 x 10 / ( 15 x 500 x 300 )
= 0.107

d'
d' =
/ D40= +5010/ 300
= 50=mm
0.167 ………………..use 0.2
From chart 34 , SP-16
p / fck = 0.167
p = 0.167 x 15 = 2.5
As = 2.5 x b x D = 2.5 x 300 x 500 / 100

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 207/242
8/12/2019 Design of Rectangular Water Tank (1)

2
= 3750 mm
2
Provide 8-25 mm O = 3928 mm , equally distributed
p = 3928 x 100 / ( 300 x 500 )
p = 2.62
p / fck = 2.62 / 15
= 0.175
The assumed section is now checked.
About X
d' / D = 50 / 500 = 0.1 , For p / f ck = 0.175 and Pu / ( fck x b x D ) = 0.67 ,
Chart - 44 , SP-16
2
Mux1 / ( fck x b x D ) = 0.13
2 -6
Mux1 = 0.13 x 15 x 300 x 500 x 10
= 146.25 KNm
About Y
d' / D = 50 / 300 = 0.167 say 0.2 , For p / f ck = 0.175 and Pu / ( fck x b x D ) = 0.67 ,

Chart - 46 , SP-162
Muy1 / ( fck x b x D ) = 0.103
2 -6
Muy1 = 0.103 x 15 x 500 x 300 x 10
= 69.53 KNm
Pure axial load capacity
Puz = 0.45 fck Ac + 0.75 fy Asc
Ac = 300 x 500 - 3928
2
= 146072 mm
-3 -3
Puz = 0.45 x 15 x 146072 x 10 + 0.75 x 415 x 3928 x 10
= 985.99 + 1222.6
= 2208.6 KN
Pu / Puz = 1500 / 2208.6
= 0.68
From , IS 456-2000 , Clause 39.6
αn = 1.802 0.2 difference 0.33
check : 0.12 difference ? -0.198
αn αn
Mux Muy
Mux1
+ Muy1
≤1
1.802 1.802
60 60
146.25 + 69.53

0.2 + 0.77

0.97 ≤1
Ties : Minimum diameter Otr = 25 / 4 = 6.25 mm

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 208/242
8/12/2019 Design of Rectangular Water Tank (1)

Use 8 mm diameter M.S. ties. 500


Spacing should not exceed lesser of
( i ) 300 mm
( ii ) 16 x 25 = 400 mm
300
( iii ) 48 x 8 = 384 mm
Provide 8 mm O M.S. ties @ 300 mm c/c

Note that the distance between corner bars in one face is more than 48 O tr
( 500 - 80 -25 = 395 > 48 x 8 = 384 ). Therefore two sets of closed ties shall be used .
Note that if this distance would be less than ( 48 x 8 ) mm , open ties for internal
bars would be sufficient.

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 209/242
8/12/2019 Design of Rectangular Water Tank (1)

m.

39.6 Members Subjected to Combined Axial Load


and Biaxial Bending where ,
α α M
Mux Muy
Mux1
+ Muy1
≤1 Mu

αn is related to Pu/Puz
where Puz = 0.45 fck Ac + 0.75 fy Asc
For values of Pu / Puz = 0.2 to 0.8, ( 0.2 , 0.4 , 0.6 , 0.8 )th
linearly from 1 .0 to 2.0.( 1.0 , 1.33 , 1.67 , 2.0 ) For value
1 .O; for values greater than 0.8, α n is 2.0.

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 210/242
8/12/2019 Design of Rectangular Water Tank (1)

+ ( least lateral dimension )


( 16 times least longitudinal diameter of bar )
( 48 times diameter of tie )
@
c/c

0 ) = 72 KNm .

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 211/242
8/12/2019 Design of Rectangular Water Tank (1)

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 212/242
8/12/2019 Design of Rectangular Water Tank (1)

( least lateral dimension )


( 16 times least longitudinal diameter of bar )
( 48 times diameter of tie )

8O@
300 c/c
(two sets )

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 213/242
8/12/2019 Design of Rectangular Water Tank (1)

ux , Muy = moments about x and y axes


due to design loads,
x1, Muy1 = maximum uniaxial moment
capacity for an axial load of Pu,
bending about x and y axes
respectively, and

e values of αn vary
s less than 0.2, α n is

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 214/242
8/12/2019 Design of Rectangular Water Tank (1)

Design of short eccentrically loaded columns - uniaxial bending.


Size 300 mm x 600 mm
Axial factored load 600 KN
Factored moment 300 KNm
( Given )
moment due to minimum eccentricity is less than the applied moment.
Material M15 grade concrete
HYSD reinforcement of grade Fe415
Solution :-
Using 25 mm diameter bars with 40 mm clear cover
d' = 40 + 12.5 = 52.5 mm
d' / D = 52.5 / 600 = 0.088 ,say 0.1
3
Pu / ( fck x b x D ) = 600 x 10 / ( 15 x 300 x 600 )
= 0.222
2 6 2
Mu / ( fck x b x D ) = 300 x 10 / ( 15 x 300 x 600 )
= 0.185
From chart 32 , SP : 16

p / fck = 0.1
p = 0.1 x 15 = 1.5
As = 1.5 x b x D = 1.5 x 300 x 600 / 100
2
= 2700 mm
2
Provide 22 mm O ( 2700 / 380 = 8 no.) = 3041 mm
As the distance between two opposite corner bars is more than 300 mm ,
provide 2- 12 mm O at centre of long sides of the column, which may be tied by open
2
Provide 8- 25 O + 2 - 12 O = 4151 mm
Ties : Minimum diameter Otr = 25 / 4 = 6.25 mm 600

Use 8 mm diameter M.S. ties.

Spacing
( i ) 300 mmshould not exceed lesser of 300
( ii ) 16 x 25 = 400 mm
( iii ) 48 x 8 = 384 mm
Provide 8 mm O M.S. ties @ 300 mm c/c ( two sets )
Note that the distance between corner bars in one face is more than 48 O tr
( 600 - 80 -25 = 495 > 48 x 8 = 384 ). Therefore two sets of closed ties shall be used .
Note that if this distance would be less than ( 48 x 8 ) mm , open ties for internal
bars would be sufficient.

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 215/242
8/12/2019 Design of Rectangular Water Tank (1)

ties.

8-25 O
+ 2-12 O

8 mm O @ ( least lateral dimension )


300 mm c/c ( 16 times least longitudinal diameter of bar )
( two sets ) ( 48 times diameter of tie )

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 216/242
8/12/2019 Design of Rectangular Water Tank (1)

Design of short circular column


Working load = 1200 KN
Assume emin < 0.05 D
( a ) lateral ties & Given
( b ) helical reinforcement
Material M20 grade concrete
HYSD steel Fe415
For Lateral reinforcement mild steel Fe250
Solution : -
Factored load = 1.5 x 1200
= 1800 KN
( a ) lateral ties : -
Pu = 0.4 fck Ac + 0.67 fy Asc
Assume 0.8 % minimum steel.
Then , Asc = 0.008 Ag
Ac = Ag - Asc
= 0.992 Ag
Substituting , we have
3
1800 x 10 = 0.4 x 20 x 0.992 Ag + 0.67 x 415 x 0.008 Ag
3
1800 x 10 = 7.936 Ag + 2.2244 Ag
3
1800 x 10 = 10.1604 Ag
2
177165 mm
Ag =
If D is the diameter of the column
2
( ¶ / 4 ) x D = 177165
D = √ 225688
D = 475 mm
Use 475 mm diameter column.
Asc = 0.008 x 177165
2
= 1417 mm
Minimum 6 bars shall be used.
Provide 16 mm diameter bars ( 1417 / 201 ) = 8 no.
Asc = 8 x 201
2
= 1608 mm
Use 6 mm O lateral ties , Spacing shall be lesser of
( i ) 475 mm ( least lateral dimension )
( ii ) 16 x 16 = 256 mm ( 16 times least longitudinal diameter

( iii ) 48 x 6 = 288 mm ( 48 times diameter of tie )


Provide 6 mm O lateral ties @ 250 mm c/c .
( b ) Helical reinforcement : -
The column with helical reinforcement can support 1.05 times the load of a similar
member with lateral ties. Therefore
Pu = 1.05 [ 0.4 fck Ac + 0.67 fy Asc ]

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 217/242
8/12/2019 Design of Rectangular Water Tank (1)

3
1800 x 10 = 1.05 [0.4 x 20 x 0.992 Ag + 0.67 x 415 x 0.008 Ag ]
3
1800 x 10 = 8.3328 Ag + 2.3356 Ag
3
1800 x 10 = 10.6684 Ag
2
Ag = 168729 mm

If D is the diameter
2 of the column
( ¶ / 4 ) x D = 168729
D = √ 214941
D = 463 mm
Use 450 mm diameter column.
2
Then , Ag = ( ¶ / 4 ) x 450
2
=
158963 mm
3
1800 x 10 = 1.05 [0.4 x 20 x (158963 - Asc ) + 0.67 x 415 x Asc ]
= 1335289 - 8.4 Asc + 291.95 Asc
464711 = 283.55 Asc

Asc = 1638.9 mm
provide 20 mm diameter bars ( 1638.9 / 314 =) 6 No.
Asc = 6 x 314
2
= 1884 mm
Assume 8 mm O M.S. bars for helix at 40 mm clear cover .
Dc = 450 - 40 - 40
= 370 mm
2
asp = ( ¶ / 4 ) x 8
2
= 50 mm
Minimum ρs = 0.36 ( (Ag / Acr) - 1 ) f ck / fy
0.36 ( ( 4502 / 3702 ) - 1 ) x 20 / 250
=
0.36 x 0.4792 x 20 / 250
=
=
0.0138
Now ρs =
4 x asp / p x Dc
0.0138 = 4 x 50 / p x 370
p = 39.17 mm …………………….. ( 1 )
As per IS 456-2000 clause 26.5.3.2 ( d )
The pitch < 75 mm
< Dc / 6 ( = 370 / 6 = 61.67 mm )
> 25 mm
> 3 x dia of helix bar = 3 x 8 = 24 mm ……………( 2 )
From ( 1 ) and ( 2 ) , provide 8 mm O helix @ 35 mm pitch.

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 218/242
8/12/2019 Design of Rectangular Water Tank (1)

of bar )

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 219/242
8/12/2019 Design of Rectangular Water Tank (1)

6 - 20 O

450

6 - 20 O

35

8 mm O @
35 mm c/c

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 220/242
8/12/2019 Design of Rectangular Water Tank (1)

Design of short column


Factored load = 1500 KN
Assume emin < 0.05 D
Given
Material M15 grade concrete
mild steel Fe250
Solution : -
Here , emin < 0.05 D , But emin = 20 mm
Therefore , size of column shall be minimum ( 20 / 0.05 = 400 ) 400 mm x 400 mm
Assume 0.8 % minimum steel.
Then , sc = 0.008 Ag

Ac = Ag - Asc
= 0.992 Ag
Pu = 0.4 fck Ac + 0.67 fy Asc
= 0.4 x 15 x 0.992 Ag + 0.67 x 250 x 0.008 Ag
3 5.952 + 1.34
1500 x 103 = g g
1500 x 10 = 7.292 Ag
2
Ag = 205705 mm
If the column is to be a square , the side of column = √205705 = 453 mm
Adopt 450 mm x 450 mm size column .
Then ,
3
1500 x 10 = 0.4 x 15 x ( 450 x 450 - Asc )+ 0.67 x 250 x Asc
1500 x 10 = 1215000 -
3 + 167.5
sc sc

285000 = 161.5 Asc


2
Asc = 1765 mm
Provide 20 mm diameter bars = ( 1765 / 314 ) = 6 No.
2
giving , Asc = 6 x 314 = 1884 mm
Note that the distance between the bars exceeds 300 mm on two parallel sides .
the arrangement of reinforcement should be changed.
Provide then 4 no. 20 mm diameter bars plus 4 no. 16 mm diameter bars giving
Asc = 4 x 314 + 4 x 201
= 1256 + 804
2
= 2060 mm
Lateral ties :
Use 6 mm O lateral ties.
Spacing should be lesser of :
( i ) 450 mm ( least lateral dimension )
( ii ) 16 x 16 = 256 mm ( 16 times least longitudinal diameter of bar )
(iii) 48 x 6 = 288 mm . ( 48 times diameter of tie )
Provide 6 mm O ties about 250 mm c/c .
Note that the distance between corner bars in one face is more than 48 O tr

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 221/242
8/12/2019 Design of Rectangular Water Tank (1)

( 450 - 80 -20 = 350 > 48 x 6 = 288 ). Therefore two sets of closed ties shall be used .
Note that if this distance would be less than ( 48 x 6 ) mm , open ties for internal bars
would be sufficient.

450 450
6 - 20 O
4 - 20
+4-1

450 450

6 mm
(dou

wrong arrangement correct arrangement

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 222/242
8/12/2019 Design of Rectangular Water Tank (1)

IS 456-2000 clause 25
Note :- A column may be considered as short when both slendern
ratios lex / D and ley / b ≤ 12 OR lex / ixx < 40 where,
lex = effective length in respect of the major axis
D = depth in respect of the major axis
ley = effective length in respect of the minor axis
b = width of the member
ixx = radius of gyration in respect of the major axis.
iyy = radius of gyration in respect of the minor axis.
All columns shall be designed for minimum eccentricity equal to th
unsupported length of column / 500 plus lateral dimension / 30 , su
a minimum of 20 mm. For bi-axial bending this eccentricity exceed
minimum about one axis at a time.
IS 456-2000 clause 39.3

When emin ≤ 0.05 D , the column shall be designed by the followin


equation:
Pu = 0.4 fck Ac + 0.67 fy Asc
Ac = Area of concrete ,
Asc = Area of longitudinal reinforcement for columns.
If emin > 0.05 D , the column shall be designed for moment also.
IS 456-2000 clause 26.5.3.1
The cross-sectional area of longitudinal reinforcement , shall be n
than 0.8 % nor more than 6 % of the gross cross-sectional area of
column.
NOTE - The use of 6 percent reinforcement may involve
practical difficulties in placing and compacting of concrete;
hence lower percentage is recommended. Where bars from
the columns below have to be lapped with those in the
column under consideration, the percentage of steel shall
usually not exceed 4 percent
26.5.3 columns
26.5.3.1 Longitudinal reinforcemen
a) The cross-sectional area of longitudinal
reinforcement, shall be not less than 0.8 percent
nor more than 6 percent of the gross crosssectional
area of the column.
NOTE - The use of 6 percent reinforcement may involve
practical difficulties in placing and compacting of concrete;
hence lower percentage is recommended. Where bars from
the columns below have to be lapped with those in the

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 223/242
8/12/2019 Design of Rectangular Water Tank (1)

column under consideration, the percentage of steel shall


usually not exceed 4 percent.
b) In any column that has a larger cross-sectional
area than that required to support the load,
the minimum percentage of steel shall be
based upon the area of concrete required to
O resist the direct stress and not upon the actual
area.
c)The minimum number of longitudinal bars
O @ 250 mm c/c
le ties ) provided in a column shall be four in rectangular
columns and six in circular columns.
d )The bars shall not be less than 12 mm in
diameter.
e) A reinforced concrete column having helical
reinforcement shall have at least six bars of
longitudinal reinforcement within the helical
reinforcement.
f )In a helically reinforced column, the longitudinal
bars shall be in contact with the helical
reinforcement and equidistant around its inner
circumference.
g )Spacing of longitudinal bars measured along
the periphery of the column shall not exceed
300 mm.
h )In case of pedestals in which the longitudinal
reinforcement is not taken in account in strength
calculations, nominal longitudinal reinforcement
not less than 0.15 percent of the cross-sectional
area shall be provided.

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 224/242
8/12/2019 Design of Rectangular Water Tank (1)

ss

bject to
s the

t less
the

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 225/242
8/12/2019 Design of Rectangular Water Tank (1)

Design of dog-legged staircase

230
1 5 9 10
UP 900

Floor A B 150 1950

20 19 15 11
900

230
300 900 2250 900 230

Rise of step = 160 mm Rise > 200 mm 175 mm to 200 m


Tread = 250 mm Tread < 230 mm 250 mm to 280 m
Nosing is not provided ( given )

Material
mild steelM15 Grade concrete
reinforcement Fe250
Solution : -
Assume 150 mm thick waist slab. Both the landings can span on walls.
Landing A or B
2
Self-load 0.15 x 25 = 3.75 KN / m
2
Floor finish = 1.00 KN / m
2
Live load ( residence ) = 3.00 KN / m
2
Total 7.75 KN / m
PU = 1.5 x 7.75 = 11.63 KN / m
Span = 1950 + 150 = 2100 i.e. 2.1 m
Consider 1 m length of slab
2
M= wxl /8
2
= 11.63 x 2.1 / 8
= 6.41 KNm
Reinforcement will be in second layer, Assuming 12 mm O bars
d = 150 - 15 (cover ) -12 - 6
= 117 mm

2 6 2
Mu / b x d = 6.41 x 10 / 1000 x 117
= 0.468

Pt = 50 1 -√1-(4.6 / fck) x (Mu / b x d )


2

fy / fck

= 50 1-√1-(4.6 / 15) x (0.468)


250 / 15

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 226/242
8/12/2019 Design of Rectangular Water Tank (1)

= 50 [(1-0.93) x 15 / 250 ]
= 0.224%

Ast = 0.224 x 1000 x 117 / 100


2
= 262 mm
According to IS 456-200 clause 26.5.2.1 Minimum steel 0.15 % for Fe250 and 0.12
% for Fe415
Minimum steel = ( 0.15 / 100 ) x 1000 x 150
2
= 225 mm
Provide 10 mm O bar
2
spacing of bar = Area of one bar x 1000 / required area in m /m
= 78.50 x 1000 /262
= 300 mm
2
Provide 10 mm O bar @ 280 mm c/c = 280 mm .
Maximum spacing = 3 x d = 3 x 117
= 351 mm ……………….( O.K.)
Check for shear : -
Vu = w x l / 2
= 11.63 x 2.1 / 2
= 12.21 KN
Shear stress = Vu / b x d
3
= 12.21 x 10 / 1000 x 117
2
= 0.104 N / mm < ( C ) N / mm2 ( too small )
for Pt = 0.224 c = 0.28 < 0.28 ( from table 7-1 )
……………….( O.K.)
Check for development length : -
Assuming L0 = 12 O (mild steel )
Pt = 100 x As / b x d
= 100 x 280 / 1000 x 117
= 0.239
From equation
Pt = 50 1 -√1-(4.6 / fck) x (Mu / b x d )
2

fy / fck
2
Mu1 / b x d = 0.499
Mu1 = 0.499 x 1000 x 1172 x 10-6
= 6.83 KNm
Vu = 12.21 KN
1.3 x ( Mu1 / Vu ) + L0 ≥ Ld
6 3
1.3 x ( 6.83 x 10 / 12.21 x 10 ) + 12 O ≥ 55 O

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 227/242
8/12/2019 Design of Rectangular Water Tank (1)

727.191 + 12 O ≥ 55 O
43 O ≤ 727.19
which gives O ≤ 16.91 mm ……………….( O.K.)
Check for deflection : -
Basic ( span / d ) ratio = 20
Pt = 100 x Ast / b x d = 100 x 280 / 1000 x 117
= 0.239
IS 456-2000 clause 23.2.1 fig-4 ,for tension reinforcement
modification factor = 2
( span / d ) ratio permissible = 2 x 20
= 40
Actual (span / d ) ratio = 2100 / 117
= 17.95 < 40 ……………….( O.K.)

Design of flight : -
Span and loading on both the flights are the same. Therefore same design will be
adopted.
Loads :
2 2
Inclined length of waist slab for one step = √ 250 + 160
= 296.8 mm
Assuming 150 mm thick waist slab
2
self-load in plan = ( 296.8 / 250 ) x 0.15 x 25 = 4.45 KN / m
Floor finish length for one step = 160 + 250
= 410 mm
2
floor finish = ( 410 / 250 ) x 1 = 1.64 KN / m 250
Weight of step ( ( 0 + 160 ) / 2000 ) x 25 = 2.00 2
KN / m 160 296.8
2
Live load = 3.00 KN / m
Total = 4.45 + 1.64 + 2.00 + 3.00
2
= 11.09 KN / m
2
Pu = 1.5 x 11.09 = 16.64 KN / m
IS 456-2000 , clause 33.2
Landing is spanning in transverse direction. The span of stair according to discussion
made in art 13-1 and loading for 1 m width of stair is shown in fig below.

16.64 KN / m

11.63 KN / m 11.63 KN / m

RA = 24.83 KN RB = 24.83 KN
525 2250 525 525 = 900 / 2 +75
3300

RA = RB = 0.525 x 11.63 + 16.64 x 2.25 / 2

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 228/242
8/12/2019 Design of Rectangular Water Tank (1)

= 6.11 + 18.72
= 24.83 KN
2 2
Mu = 24.83 x 3.3/2 - 11.63 x (3.3/2) / 2 - ( ( 16.64 - 11.63 ) x ( 2.25/2 ) ) / 2
= 40.97 - 15.83 - 3.17
= 21.97 KNm
From Table 6-3 Q = 2.22
drequired = √ M/Qxb

= √21.97 x 10
6
/ 2.22 x 1000
= 99.48 mm,
dprovided = 150 - 15 - 6
= 129 mm, ……………….( O.K.)
2 6 2
Mu / b x d = 21.97 x 10 / 1000 x (129)
= 1.32
Pt = 50 1 -√1-(4.6 / fck) x (Mu / b x d )
2

fy / fck

= 50 1-√1-(4.6 / 15) x (1.32)


250 / 15

= 50 [(1-0.77) x 15 / 250 ]
= 0.687%

Ast = 0.687 x 1000 x 129 / 100


2
= 886 mm

Provide 12 mm O bar 2
spacing of bar = Area of one bar x 1000 / required area in m / m
= 113.04 x 1000 / 886
= 127.585 mm
2
Provide 12 mm O bar@125 mm c/c = 904 mm .
Minimum steel is 0.15 % for mild steel and 0.12 % for HYSD Fe415 reinforcement
Distribution steel = ( 0.15 / 100 ) x 1000 x 150
2
= 225 mm
Provide 8 mm O bar
2
spacing of bar = Area of one bar x 1000 / required area in m /m
= 50.24 x 1000 /225
= 223 mm
2
Provide 8 mm O bar @ 220 mm c/c = 228 mm .
Check for shear : -
Vu = 24.83 KN
Shear stress = Vu / b x d
3
= 24.83 x 10 / 1000 x 129

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 229/242
8/12/2019 Design of Rectangular Water Tank (1)

2
= 0.192 N / mm <( C ) N / mm
2
( too small )
100 x As / b x d = 100 x 904 / 1000 x 129
= 0.70
from table 7-1
2

for Pt = 0.7 = 0.524 N / mm


c
IS 456-2000 clause 40.2.1.1
k = 1.3 for 150 mm slab depth
Design shear strength = 1.3 x 0.524
2
= 0.681 N / mm ……………….( O.K.)
Check for development length : -
Assuming L0 = 12 O (mild steel )
Pt = 100 x As / b x d
= 100 x 904 / 1000 x 129
= 0.70
From equation


Pt = 50 1 - 1-(4.6 / fck) x (Mu / b x d2)
fy / fck
2
we get , Mu1 / b x d = 1.344
2 -6
Mu1 = 1.344 x 1000 x 129 x 10
= 22.37 KNm
Vu = 24.83 KN
Development length of bars L d = O σs / 4 x bd = O x 0.87 x 250 / 4 x 1 =54.4 O
1.3 x ( Mu1 / Vu ) + L0 ≥ Ld
6 3
1.3 x ( 22.37 x 10 / 24.83 x 10 ) + 12 O ≥ 54.4 O
1171.2 + 12 O ≥ 54.4 O
42.4 O ≤ 1171.2
which gives O ≤ 27.62 mm ……………….( O.K.)
From Crossing of bars, the bars must extend upto 54.4 x 12 = 653
say 700 mm.
Check for deflection : -
Basic ( span / d ) ratio = 20
Pt = 100 x Ast / b x d = 100 x 904 / 1000 x 129
= 0.70
IS 456-2000 clause 23.2.1 fig-4 ,for tension reinforcement
modification factor = 1.62

( span / d ) ratio permissible = 1.62 x 20


= 32.4
Actual (span / d ) ratio = 3300 / 129
= 25.58 < 32.4 ……………….( O.K.)
The depth could be reduced
Check for cracking : -
IS 456-2000 , clause 26.3.3

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 230/242
8/12/2019 Design of Rectangular Water Tank (1)

Main bars : maximum spacing permitted = 3 x effective depth of slab or 300 mm


= 3 x 129 = 387 mm or 300 m
spacing provided = 125 mm < 300 mm ……………….( O.
Distribution bars : maximum spacing permitted = 5 x effective depth of slab or
= 5 x 129 = 645 mm
spacing provided = 220 mm < 450 mm ……………….( O.

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 231/242
8/12/2019 Design of Rectangular Water Tank (1)

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 232/242
8/12/2019 Design of Rectangular Water Tank (1)

check for shear


IS 456-2000 , Table 19
Table 7-1
Design shear strength of concrete , C, N / mm2
Pt = 100 x As Concrete grade
bxd M15 M20 M25 M30 M35
≤ 0.15 0.28 0.28 0.29 0.29 0.29
0.25 0.35 0.36 0.36 0.37 0.37
0.50 0.46 0.48 0.49 0.50 0.50
0.75 0.54 0.56 0.57 0.59 0.59
1.00 0.60 0.62 0.64 0.66 0.67
1.25 0.64 0.67 0.70 0.71 0.73
1.50 0.68 0.72 0.74 0.76 0.78
1.75 0.71 0.75 0.78 0.80 0.82
2.00 0.71 0.79 0.82 0.84 0.86
2.25 0.71 0.81 0.85 0.88 0.90
2.50 0.71 0.82 0.88 0.91 0.93
2.75 0.71 0.82 0.90 0.94 0.96
3.00 0.71 0.82 0.92 0.96 0.99
The above given table is based on the following formula
Design shear strength c = 0.85 √ 0.8 x fck ( √ 1 + 5 x β -
6xβ
β = 0.8 x fck / 6.89 Pt , but not less than 1.

IS 456-2000 , Table 20
Table 7-2
Maximum shear stress , C, N / mm2

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 233/242
8/12/2019 Design of Rectangular Water Tank (1)

Concrete grade M15 M20 M25 M30 M35


2
( c )max N / mm2.5 2.8 3.1 3.5 3.7
check for development length
IS 456-2000 clause 26.2.1
Development length of bars L d = O σs / 4 x bd

IS 456-200 clause 26.2.1.1


Table 7-5
Design bond stress ( bd ) for plain bars in tension
Concrete grade M15 M20 M25 M30 M35
2
( bd N / mm 1.0 1.2 1.4 1.5 1.7
Note-1 : bd shall be increased by 25 % for bars in compression
Note-2 : In case of deformed bars confirming to IS : 1786-1985 ,
value of bd shall be increased by 60 %.
For mild steel Fe250 σs = 0.87 x fy
For Fe415 σs = 0.67 x fy
IS 456-2000 clause 26.2.3.3
Ld ≤ M1 / V + L0
L0 = effective depth of the members or 12 O , whichever is great
if ends of the reinforcement are confined by a compressive reac
/ V increased by 30 % ( 1.3 M1 / V )

Table 7-6
Development length for single mild steel bars
Tension bars Compression bars
fy N / mm2
M15 M20 M15 M20
250 55 O 26 O 44 O 37 O
415 56 O 47 O 45 O 38 O
500 69 O 58 O 54 O 46 O

check for deflection


Basic values of span to effective depth ratios for spans upto 10
cantilever 7
simply supported 20
continuous 26
For spans above 10 m, the values in (a) may be multiplied by

10 / span in metres
calculations , except
should be made.for cantilever in which case deflecti
check for cracking
(a)The horizontal distance between parallel main
reinforcement bars ( spacing )shall not be more than t
times the effective depth of solid slab or
300 mm whichever is smaller.

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 234/242
8/12/2019 Design of Rectangular Water Tank (1)

(b)The horizontal distance between parallel


reinforcement bars ( spacing ) provided against
shrinkage and temperature (distribution bar) shall not be more
than five times the effective depth of a solid
slab or 450 mm whichever is smaller.

IS 456-2000 Clause 40.2.1.1


Overall depth of 300 or
slab , mm more 275 250 225 200
k 1.00 1.05 1.10 1.15 1.20

sketch :
The reinforcements for both the flights are shown in fig.
700

700

10 O @ 280 c/c
( Landing )
12 O @ 125 c/c
150 mm thick waist slab
8 O @ 220 c/c

12 O 125 c/c

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 235/242
8/12/2019 Design of Rectangular Water Tank (1)

Flight-B

8 O @ 22

12 O @ 125 c/c

150 mm thick waist slab


10 O @ 280 c/c
( Landing ) Flight-A

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 236/242
8/12/2019 Design of Rectangular Water Tank (1)

whichever is small
i.e. 300 mm
.)
450 mm whichever is small
or 450 mm i.e. 450 mm
.)

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 237/242
8/12/2019 Design of Rectangular Water Tank (1)

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 238/242
8/12/2019 Design of Rectangular Water Tank (1)

M40
0.30
0.38
0.51
0.60
0.68
0.74
0.79
0.84
0.88
0.92
0.95
0.98
1.01

1)

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 239/242
8/12/2019 Design of Rectangular Water Tank (1)

M40
4.0

M40
1.9

, the

er & For checking development length , l 0


ion M1 may be assumed as 8 O for HYSD
bars ( usually end anchorage is not
provided ) and 12 O for mild steel (
U hook is provided usually whose
anchorage length is 16 O.

http://slidepdf.com/reader/full/design-of-rectangular-water-tank-1 240/242