This document provides specifications for the FTC Series of uninterruptible power supply (UPS) systems, including the FTC 4000, 6000, 8000, and 10K models. It lists technical details such as voltage and frequency regulation capabilities, battery specifications, output waveform quality, and transient response. Environmental factors like operating temperature and noise levels are also outlined. The UPS systems provide fully intelligent double conversion online power with capacities ranging from 4000 to 10000VA. They include microprocessor control panels, communication ports, and optional software and accessories.
This document provides specifications for the FTC Series of uninterruptible power supply (UPS) systems, including the FTC 4000, 6000, 8000, and 10K models. It lists technical details such as voltage and frequency regulation capabilities, battery specifications, output waveform quality, and transient response. Environmental factors like operating temperature and noise levels are also outlined. The UPS systems provide fully intelligent double conversion online power with capacities ranging from 4000 to 10000VA. They include microprocessor control panels, communication ports, and optional software and accessories.
This document provides specifications for the FTC Series of uninterruptible power supply (UPS) systems, including the FTC 4000, 6000, 8000, and 10K models. It lists technical details such as voltage and frequency regulation capabilities, battery specifications, output waveform quality, and transient response. Environmental factors like operating temperature and noise levels are also outlined. The UPS systems provide fully intelligent double conversion online power with capacities ranging from 4000 to 10000VA. They include microprocessor control panels, communication ports, and optional software and accessories.
Mode Micro-processor control fully Intelligent Double Conversion On-Line Capacity VA Rated 4000 6000 8000 10000 Watt Rated 3200 4800 6400 8000 Input Voltage 160 - 245 V 160 - 245 V 1 - phase 160 - 245 V 3 - phase 380/220V + 15/-20% Wiring Single phase: L-N + Ground 3 phase "Wye or Delta + Ground Frequency 50/60 Hz +/- 5% tracking range Output Voltage Single phase: same as Input Nominal Single phase 208, 220, 230 or 240 V related to input Regulation +/- 2 upon changes of line or load ; with +/- 10% adjustable range Power factor 0,8-1 Lagging Frequency 50/60 Hz +/- 0,5% (Free-running) Waveform Pure Sineware; THD < 3% at Linear Load; < 5% at 0.7 P.F. load Transient +/-4% under full load change, recovered within 100 milisecond Synchronization 1 Hz/sec, slew rate; Interver Hz free running when I/P Hz over +/- 5% Crest factor better than 3 : 1 Battery Lead-acid maintenance free, 3-5 years life time Spec. 12V/7AH 16 pcs 12V/17AH 16 pcs 12V/26AH 16 pcs Runtime (full/half) 12-14/30-35 min 20-22/40-50 10--12/25-30 18-20/40-50 Recharge to 90 % within 8 hours Static Swicth Hybrid (triac+_relay) type with current-limited inrush protection Auto Mode Active when inverter High/Low voltage, Inrush overload, Over Temperature & auto resumes Manual Mode Push control keypad to manually transfer from inverter to bypass and vice versa Control Panel General Micro-computer to monitor & control system operation, log operation history & alarm messages Control 8 keys ti manipulate: 1. Control On/Off of AC Input or System; Bypass loop activation 2. Display operating Status & Data. 3. Setting of System parameters. 4. Alarm reset LCD Display Two lines 32 characters alphanumerical display provides 1. System operating Status (auto display). 2. Data such as O/P Volt., Amp., .etc LED Display Utility status; On Battery. Inverter O/P; Bypass O/P; Overload, System Fault, Weak battery, Sync Communication Port (DB9) Signals provide both of serial signal for UPS software & contact closure signal for Novell/AS400 application Application contact closure signal provides messages of UPS On/Bypass/Power Fail/Battery Low Protection Overload 120% 30 min.; 150% 25sec. Shortcircuit Cut off outputs of both inverter & bypass never to trip House breaker Thortcircuit Internal thermal switch to protect from over-temperature, then transfer to bypass loop Circuit Breaker Protect AC input & battery loops EMI Filter 10-100Khz at 40dB; 100Mhz at 70dB Mechanical Dimension (cm/in) 26x60x70/10.2x24x28 39x68x70/15.4x27x28 39x79x82/15.4x31.1x32.3 (WxDxH)* Net Wt. (kgs/lbs) 96/211 185/407 220/484 280/616 Connection Hard-wiring for both input and output Effectic Noise Inverter > 90%, System > 84% Acoustic Noise <50dBA <55dBA <60dBA Environment 0-40 degree C, 0-90% RH Non-condensing Options 1. Intelligent UPS Software Package 2. Long Runtime Models: 4 amp. Charger - 35C1, 55C1 8 amp. Charger - 35C2, 55C2, 80C2 12 amp. Charger - 55C3, 80C3, 10KC3 (battery not included)* 3. Input Isolation Transformer for Universal input Voltage Selection 4. Socket Panel for installing U.S. twist-locking sockets.
*The dimension includes the height of casters.
*The above specification is subject to change without prior notice. *All tradenames mentioned are the properties of their respective owners. *Please consult with factory for battery application *10KVA requires additional unit of battery bank.