Project: ETAP Page: 1

Location: 19.0.1C Date: 03-15-2024

Contract: SN:

Engineer: Revision: Base


Study Case: LF
Filename: SLD VLPC~~ Config.: Normal

LOAD FLOW REPORT

Bus Voltage Generation Load Load Flow XFMR


ID kV % Mag. Ang. MW Mvar MW Mvar ID MW Mvar Amp %PF %Tap

* Bus1 33.000 100.000 0.0 1.280 0.746 0.000 0.000 Bus2 1.280 0.746 25.9 86.4

Bus2 0.400 96.767 -2.5 0.000 0.000 0.000 0.000 Bus3 1.269 0.667 2138.0 88.5

Bus1 -1.269 -0.667 2138.0 88.5

Bus3 0.400 94.445 -3.4 0.000 0.000 0.000 0.000 Bus2 -1.248 -0.633 2138.0 89.2

Bus4 0.115 0.061 199.7 88.4

Bus10 0.459 0.230 783.9 89.4

Bus5 0.674 0.342 1154.5 89.2

Bus4 0.400 94.282 -3.4 0.000 0.000 0.000 0.000 Bus3 -0.115 -0.061 199.7 88.4

Bus6 0.115 0.061 199.7 88.4

Bus5 0.400 91.320 -4.3 0.000 0.000 0.657 0.320 Bus3 -0.657 -0.320 1154.5 89.9

Bus6 0.230 89.173 -4.2 0.000 0.000 0.000 0.000 Bus7 0.115 0.059 363.0 89.0

Bus4 -0.115 -0.059 363.0 89.0

Bus7 0.230 88.981 -4.2 0.000 0.000 0.000 0.000 Bus6 -0.115 -0.059 363.0 89.1

Bus8 0.080 0.049 264.7 85.0

Bus9 0.035 0.009 101.8 96.8

Bus8 0.230 88.818 -4.3 0.000 0.000 0.080 0.049 Bus7 -0.080 -0.049 264.7 85.0

Bus9 0.230 88.981 -4.2 0.000 0.000 0.035 0.009 Bus7 -0.035 -0.009 101.8 96.8

Bus10 0.400 89.229 -5.5 0.000 0.000 0.441 0.201 Bus3 -0.441 -0.201 783.9 91.0
* Indicates a voltage regulated bus ( voltage controlled or swing type machine connected to it)
# Indicates a bus with a load mismatch of more than 0.1 MVA