CERTIFICATE OF STRUCTURAL STABILITY

Client : M/s ---------------------------


Location : ----------------------------.
Job No. : ------------------
Date : ------------------------

M/s UNITED PEB SOLUTIONS Pvt. Ltd., hereby certifying that the Structural design of PEB Structures Namely
“PRODUCTION FACILITY” being built for M/s ---------------------- PVT. LTD. at ------------------, ------------------, Project
has been designed to withstand the following parameter which were referenced in the approved design & drawings and
criteria mentioned in our offer with the following loads and design standard.

Dimensions:
S.NO Components Ware house
1 Frame Type Multi-Span-02
2 Width 60.0m O/O of Steel line/ brick wall line
3 Length 60.0m O/O of Steel line/brick wall line
4 Height 8.50m Eave from FFL
5 Roof Slope 1:10
6 Building condition Fully Enclosed
7 Wall condition 3.65m brick wall & above sheeting all around the building
8 Roof sheeting 0.47 mm Roof panel (BGL)
9 Wall Sheeting 0.5mm thick TCT Color Galvalume
Loads:
S.NO Load Ware house
1 Dead Load 0.10 kN/m2 + Self weight of building
2 Collateral Load -NA-
3 Live Load 0.57 kN/m2
4 Wind Speed 44 m/s (Hyderabad)
5 Seismic Zone Zone II
6 Mezzanine Dead Load 3.50 kN/m2 (Weight of Concrete + Supporting structure)
7 Mezzanine Live Load 5.00 kN/m2
8 Crane (EOT) 3.00Ton
9 Water Tank Capacity 2000 Liters

DESIGN STANDARDS:
 AISC-89: Specification for Structural Steel Buildings. (Allowable stress design)
 IS:875 (Part 3)-2015: Code of practice for design loads for buildings and structures (Part3: Wind loads).
 IS:1893(Part 1)-2002: Criteria for Earthquake Resistant design of structures.
 AISI 2001NAS: North American specification for the Design of Cold-Formed steel structural members.
 AWS: The Structural Welding Code Steel Manual –American Welding Society (AWS-D1.1-2015).
All components including flange brace and Roof X- bracing must be intact throughout the life of the building and no
component is intended to remove during the life span of the building and also it needs timely and regular maintenance
for stability. No additional loads to be added in future.
We further certify the Structural integrity of the building for the above-mentioned design loads for the period of 25 years.