Perkin Elmer Elan DRC II ICP-MS Spectrometer

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 6

L A B O R A T O R Y

Preparing Your Laboratory for the


ELAN DRC II ICP-Mass Spectrometer

PerkinElmer SCIEX ICP-MS ■ For SEMI S2-0200 installations, a In addition, the instrument should
instruments are complete systems minimum of 300 Lux illumination be located in an area that is:

P R E P A R A T I O N
with the exception of the following is required at the floor level around
items which must be provided the ELAN® DRC II instrument. ■ Free of smoke and
by the customer: electrical power, corrosive fumes
exhaust vents, argon gas supplies In order to minimize contamination ■ Not prone to excessive vibration
with approved regulator, DRC gas problems, a dust-free environment
is necessary. For ultra-trace
■ Out of direct sunlight
supply, and coolant system. The
items shown in the following techniques, environmental ■ Away from heat radiators
checklist need to be considered contamination becomes a limiting
factor in the determination. PerkinElmer SCIEX ICP-MS
when preparing the laboratory for
To quantitate ubiquitous elements instruments have been designed
the instrument.
such as Fe, Ca, K, Na, etc. below for indoor use. The ELAN DRC II
■ Environmental conditions 1 ppb (µg/L), a class 1000 can be installed into a mobile
environment is necessary for laboratory if vibration is isolated.
■ Electrical requirements
sample preparation and analysis.
■ Space requirements This is not an indication of WARNING:
w w w. p e r k i n e l m e r. c o m

■ Exhaust ventilation the performance limitations of the Do not use the instrument in an area
■ Coolant requirements instrument, but a recommendation where explosion hazards may exist.
for an ultra-clean environment.
■ Argon gas requirements
■ DRC (dynamic reaction cell)
gas requirements

Environmental Conditions
The environment in which the
instrument is installed should meet
the following conditions.

■ The room temperature should be


between 15 and 30 °C (59-86 °F)
with a maximum rate of change
of 2.8 °C (5 °F) per hour.
■ The relative humidity should
be between 20 and 80%,
noncondensing. For optimum
performance, the room tempera-
ture should be controlled at
20 ± 2 °C (68 ± 3.6 °F), and the
relative humidity should be
between 35 and 50%.
■ The instrument should not
be operated at an elevation
greater than 2,000 meters
Figure 1. Dimensions of the ELAN DRC II ICP-MS.
(6,500 feet) above sea level.
Use of the instrument at elevations
greater than 2,000 meters is
subject to acceptance by local
inspection authorities.
Space Requirements
The system should be located near
the required electrical and gas supplies
as well as the coolant supply. If you
are installing the system in a clean
room, the roughing pumps can be
remotely located to a distance of
three meters (10 ft) from the DRC II.
The roughing pumps are then
connected to the system with an
optional kit (Part No. WE02-3935)
which contains power cables and
vacuum hoses. There can be no more
than 2 to 3 bends or couplings in the
vacuum hose over its entire length.
The diameter of the hose must
remain at least 25 mm (1 in) ID. Figure 2. Recommended workstation layout.

The ELAN DRC II is on wheels


and can be moved for service and Table I. Dimensions of the Instrument and Computer
preventative maintenance. However,
Instrument Width Height Depth Weight
a space of at least 30 cm (12 in)
cm (in.) cm (in.) cm (in.) kg (lb.)
behind the instrument is recommended.
This space behind the instrument ELAN DRC II 99 (39) 117 (46) 73 (29) 295 (650)
provides clearance for the vent hoses. Work Surface Height 87 (34)
Allow space on the right side of the DELL Computer Dimensions will vary by model
DELL Monitor Dimensions will vary by model
instrument for an accessory cart
HP LaserJet 4200 42 (16.4) 37 (14.4) 43 (16.9) 20 (45)
or table. Access for most service
procedures is through the front of
the instrument. Table II. Dimensions of the Accessories
Accessory Width Height Depth Weight
For SEMI S2-0200 installations,
cm (in.) cm (in.) cm (in.) kg (lb.)
clearances of 61 cm (24 in) behind
the instrument, 91 cm (36 in) in front, Cooling System:
and 76 cm (30 in) on the left side of Heat Exchanger
the instrument must be maintained. (PolyScience 3370) 38 (15) 63.5 (25) 38 (15) 31.3 (69)
In addition, it is required that the Refrigerated Chiller
(PolyScience 6105PE) 38 (15) 63.5 (25) 67.3 (26.5) 81 (178)
site floor be prepared to accommodate
FIAS 400MS 41.5 (16) 18.4 (7) 41 (16) 11 (24)
four 9mm diameter (3/8 in) bolts of AS 93plus
appropriate length to secure the Autosampler 44 (17) 37 (15) 34 (14) 4 (9)
instrument against seismic activity.

System Layout
There should be sufficient space The drain vessel should be placed
The ICP-MS system consists of the near the spectrometer for the various to the right of the instrument. The
main instrument, the computer accessories (autosampler, FIAS, laser, drain vessel should NOT be stored in
controller assembly, and a printer. electrothermal vaporizer, etc.). It is an enclosed storage area. The drain
The dimensions of the instrument recommended that the accessories be system should be checked regularly
are given in Figure 1. Table I lists the placed on a movable cart or table to and replaced when necessary. Should
dimensions of the instrument and allow for easy servicing access. it become necessary to replace the
the computer. Table II lists the drain vessel, it should be made from
dimensions of the accessories. The system computer may be a material not likely to be attacked
placed on a bench or a separate by samples being analyzed. Glass or
The ELAN can be positioned in either computer table. other brittle materials must not be used.
a linear or an L-shaped configuration.
In the L-shaped configuration, the Drain Vessels Liquid waste should always be
computer and printer are positioned segregated and clearly labeled. Never
on one leg of the L. The instrument A 15-liter drain vessel is supplied mix organic and inorganic liquids in
and an accessory table make up the with the ELAN DRC II ICP-MS. The the same drain vessel. Organic and
other leg. A recommended workstation vessel is made of HDPE (high density inorganic drain vessels should never
layout is shown in Figure 2. polyethylene) and is used to collect be stored in the same area.
the effluent from the ICP sample
introduction system.
Safe Handling of Gas Facilities Requirements and options. If the power line is
Cylinders unstable, fluctuates or is subject to
Table III provides information on surges, additional control of the
Notice: The permanent installation the gas and liquid services required incoming power may be required. A
of gas supplies is the responsibility for the ELAN DRC II. Tables IV and V means of electrically grounding the
of the user and should conform show the electrical supply requirements instrument must be available.
to local safety and building codes. and approximate power consumption
of the ELAN DRC II and its 60-Hertz-Operation Connections
■ Fasten all gas cylinders securely major accessories. The instrument is shipped with
to an immovable bulkhead or a two 400 cm line cord cables. The
permanent wall. installation kit includes two Hubbell
Electrical Requirements No. 2621 plugs and two Hubbell No.
■ When gas cylinders are stored in
Power to the ELAN DRC II is to be 2620 receptacles for use with two 60
confined areas, such as a room,
delivered from two 30 A single-phase Hz single phase outlets. The instru-
ventilation should be adequate to
200-240 V dedicated electrical branch ment is wired for power at the time
prevent toxic or explosive accumu-
circuits according to the power of installation.
lations. Move or store gas cylinders
only in a vertical position with the specifications in Table IV. Table V
50-Hertz-Operation Connections
valve cap in place. provides the electrical supply
The instrument is shipped with two
requirements and approximate power
■ Locate gas cylinders away from 400 cm line cord cables. It is up to
consumption of the major accessories
heat or ignition sources, including the service person installing the
heat lamps. Cylinders have a pressure-
relief device that will release the Table III. Services Required for the ELAN DRC II
contents of the cylinder if the
Gases ■ Argon, 414 ± 7 kPa (60 ± 1 psi) at 20 L/minute flow
temperature exceeds 52 °C (125 °F).
■ Ammonia (99.999%), 48 ± 14 kPa (7 ± 2 psi) operating, 103.4 kPa
■ When storing cylinders external (15 psi) maximum
to a building, the cylinders should Cooling Coolant circulation of at least 3.8 L/min (1.0 gpm) at an operating
be stored so that they are protected pressure of 344 ± 14 kPa (50 ± 2 psi).
against temperature extremes Table IV. ELAN DRC II Power Specifications
(including the direct rays of the
sun) and should be stored above Power Consumption
ground on a suitable floor. Maximum Volt Amperes (total, both circuits) 6000 VA
■ Mark gas cylinders clearly to Maximum Continuous Current (per circuit) 20 A
identify the contents and status Voltage Amplitude Specification
(full, empty, etc.).
Operating Voltage 200 - 240 V
■ Do not attempt to refill gas Maximum Allowable Percent Sag 5%
cylinders yourself. Maximum Allowable Percent Swell 5%
Phase (single or three) Single phase or three phase
■ Use only approved regulators and
Frequency Specification
hose connectors. Left-hand thread
fittings are used for fuel gas tank Operating Frequency 50 or 60 Hz
connections whereas right-hand Allowable Frequency Variance ± 1 Hz
fittings are used for oxidant and Waveform Specification
support gas connections.
Maximum Supply Voltage Total Distortion 5%
■ Arrange gas hoses where they will Maximum Supply Voltage Distortion by Single Harmonic 3%
not be damaged or stepped on and
Table V. Electrical Requirements of ELAN Accessories
where things will not be dropped
on them. Equipment Voltage (AC) Power
■ Perform periodic gas leak tests Computer Depends on Model Depends on Model
by applying a soap solution to all Printer: HP LaserJet 4200 100-127 V/220-240 V, 50/60 Hz 580 W
joints and seals. Cooling System:
■ It is strongly recommended that Heat Exchanger 208-240 V, 50/60 Hz, 2.75 A 660 W
DRC gases be installed in a gas (PolyScience 3370) 120V, 60HZ, 5.5A
cabinet with adequate ventilation.

Refrigerated Chiller 208-230 V, 60 Hz, 8 A 2000 W


(PolyScience 6105PE) 240 V, 50 Hz, 8.5 A
FIAS 400MS 110/220 V 600 W
instrument to wire it according to the The ELAN DRC II requires two venting system must provide a flow
power available at the lab. The single separate vents. The top main vent rate of approximately 210 L/sec ± 10%
phase connectors must be supplied exhausts the following: (450 ft3/min). Both of the exhaust
by either the customer or the local ports should be connected directly to
PerkinElmer office. For 50 Hz ■ plasma flexible exhaust hoses.
operation, Hubbell No. 2351 plugs ■ vacuum pump exhaust**—including The main torch box/cell gas exhaust
and Hubbell No. 2350 receptacles are
dynamic reaction cell gas must be installed, but there is an
recommended. A means of electrically
grounding the instrument must ■ DRC gas assembly manual option for the coaxial RF generator
be available. Vent/Purge switches and roughing pump exhaust. If a
150-mm (6-in) duct is not available,
Three-Phase-Operation Connections A second vent is used for the blower a 100-mm (4-in, 150 ft3/min) duct
If a three phase connection is that cools the roughing pumps, system can be connected to the inner duct.
required (by local electrical code), power supply, and ICP generator. Only the RF generator is exhausted in
the instrument can be connected via this case. The heat from the roughing
a single line cord to two of the The main venting system is required pumps is released into the laboratory.
three sides of the three phase line. The to remove combustion fumes and
three-phase line cord and connectors vapors from the torch housing, and We recommend a 100-mm (4-in) ID
must be supplied by either the to remove reaction cell gas. Exhaust torch box exhaust hose and a 150-mm
customer or the local PerkinElmer venting is important for four reasons: (6-in) ID ICP Power Supply/Roughing
office. Four meters of No. 6 AWG Pump air exhaust hose. The ELAN is
■ It protects laboratory personnel supplied with 3 m (10 ft) of 100-mm
grounding wire are provided with the
from toxic vapors that may be (4-in) and 3 m (10 ft) of 150-mm (6 in)
instrument. A means of electrically
produced by some samples. flexible tubing. This tubing permits
grounding the instrument must
be available. ■ It minimizes the effects of room the movement of the instrument
drafts and the laboratory atmosphere without disconnecting the vents from
on ICP torch stability. the laboratory system. See Table VI
Exhaust Vents and Table VII for vent specifications.
■ It helps protect the instrument
from corrosive vapors which may **When the roughing pumps are
WARNING:
The use of ICP-MS instruments without originate from the samples. mounted outside of the instrument,
adequate ventilation to outside air may their exhaust needs to be vented
constitute a health hazard. For example, ■ It removes dissipated heat which into a separate 100-mm (4-in)
the combustion of halogenated hydro- is produced by the ICP torch, ICP exhaust line providing an exhaust
carbons produces toxic vapors. When power supply and the pump motors. flow rate of at least 10 L/sec
ammonia is used as a dynamic reaction
cell gas, it can be present at very trace (21 ft3/min). In operation, the
The main 100-mm (4-in) venting
amounts in the exhaust during purging pumps produce ~1400W
system must provide a flow rate of
of the gas lines. Extreme care should (4700 BTU/hr) of heat—proper
be taken that exhaust gases are approximately 70 L/sec ± 10%
ventilation to remove this heat
vented properly. (150 ft3/min). The 150-mm (6-in)
is required.

Table VI. Flow Rates and Anemometer Readings Vent Positions


Hose Diameter Flow Rate Anemometer Reading
Both of the ELAN DRC II vents are
100 mm (4 in) 70 L/s (150 ft3/min) 9 m/s (1695 fpm) located on the back of the instrument.
150 mm (6 in) 210 L/s (450 ft3/min) 11.5 m/s (2250 fpm) See Figure 3. The Torch Box exhaust
vent is 23.75 cm (9.5 in) from the
Table VII. Hose Diameter and Venting Capabilities left side of the instrument when
viewed from the rear and 101.25 cm
Hose Hose Diameter Vented Outside Lab (40.5 in) above the floor. The ICP
Watts (BTU/hr)
Power Supply/roughing pump
Torch Box Exhaust 100 mm (4 in) 200 (680) exhaust vent is 23.75 cm (9.5 in)
ICP Power Supply/Roughing Pump *150 mm (6 in)* 2800 (9400) from the left side of the instrument
ICP Power Supply Only 100 mm (4 in) 1400 (4700) (rear view) and 64.4 cm (25.75 in)
*If only the 100-mm (4-in.) ID ICP power supply exhaust hose is used, approximately 1400 W above the floor.
(4700 BTU/hr) of heat is vented into the lab. An independent room air conditioner [3000 W
(10 000 BTU/hr)] is recommended to remove this additional heat.
■ For SEMI S2-0200 compliant
operation, the laboratory must be
equipped with an exhaust ventilation
system monitor. The monitor shall
provide an audible or visual warn-
ing to the user in the event that the
exhaust ventilation system airflow
drops below a pre-determined level.

Cleaning the Instrument


Before using any cleaning or de-
contamination methods, except those
specified by the manufacturer, users
should check with the manufacturer
that the proposed method will not
damage the equipment.

Cleaning procedures can be found in


the ELAN DRC II Hardware Guide.

Figure 3. Vent locations, rear of the ELAN DRC II ICP-MS.


Coolant Requirements
The ELAN DRC II system requires
Venting System ■ Locate the blower as close to the a regulated source of filtered coolant.
Recommendations discharge outlet as possible. All The coolant supply should be filtered
joints on the discharge side should (free of sediment), and have a pH
The exhaust flow rate at the instrument be airtight, especially if toxic vapors between 6.5 and 8.5. It should be
(the ability to vent the system) is are being carried. hardness-free with <1 ppm of heavy
dependent on customer provided
minerals. The recirculator operating
blower, the duct length, material and ■ Equip the outlet end of the system
pressure should be 344 ± 13 kPa (50 ±
the number of elbows or bends used. with a backdraft damper and
2 psi). A coolant flow of at least 3.8
If an excessively long duct system or take the necessary precautions to
L/min (1.0 gpm) is required.
a system with many bends is used, keep the exhaust outlet away from
a stronger blower may be necessary open windows or inlet vents and A recirculating system containing a
to provide sufficient exhaust volume to extend it above the roof of the corrosion inhibitor is specified to
at the instrument. Smooth stainless building for proper dispersal of protect the aluminum components
steel tubing should be used instead the exhaust. of the cooling system and the interface.
of flexible stainless steel tubing Sufficient pre-mixed coolant (Part No.
where flexibility is not required to
■ Equip the exhaust end of the
system with an exhaust stack to WE01-6558) is supplied for the Heat
reduce system friction loss or “drag.” Exchanger or Refrigerated chiller.
A length of smooth stainless steel improve the overall efficiency
of the system. If laboratory temperatures do not
ducting has 20-30% less friction loss exceed 30 °C (86 °F), the heat exchanger
than a comparable length of flexible ■ For best efficiency, make sure the can be used in place of a refrigerated
ducting. When smooth stainless steel length of the duct that enters into chiller. For laboratories where the
tubing is used, elbows must be used the blower is a straight length at temperature can exceed 30 °C (86 °F),
to turn corners. These elbows should least ten times the duct diameter. a refrigerated chiller is required. The
turn at no more than 45 degrees An elbow entrance into the blower heat exchanger must be located in a well
between straight sections to reduce inlet causes a loss in efficiency. ventilated area where the air tempera-
friction losses, and the number of ture will not exceed 30 °C (86 °F).
elbows should be minimized. ■ Provide make-up air in the same
quantity as is exhausted by the For 60 Hz installations – the M3370
Additional recommendations on the system. An airtight lab causes an heat exchangers come with either
venting system include: efficiency loss in the exhaust system. NEMA L6-15P (230V) or NEMA L5-15P
■ Ensure that the system is drawing (120V) connectors. The refrigerated
■ The duct casing and venting system
properly by placing a piece of chiller comes with a NEMA L6-15P
should be made of materials suitable
cardboard over the mouth of the vent. connector.
for temperatures as high as 70 °C
(160 °F) and be installed to meet For 50 Hz installations – the refrigerated
■ Equip the blower with an indicator
local building code requirements. chiller comes with a CEE 7 connector.
light located near the instrument
to indicate to the operator when The M3370 heat exchanger comes
the blower is on. with a NEMA L6-15P connector.
Argon Gas Requirements A cylinder regulator (Part No. 0303- For SEMI S2-0200 compliant operation,
0284) which can be used with argon the supply line for the anhydrous
Argon is used as the ICP torch gas is available from PerkinElmer. The ammonia gas, the DRC gas, should be
with the ELAN DRC II. The quality regulator can be used with CGA 580 doubly-contained and exhausted.
criteria for argon is listed below. or CGA 590 fittings and includes a
color-coded hose with 1/4-inch The anhydrous ammonia gas used by
Purity ≥ 99.996% the dynamic reaction cell must meet
Swagelok fittings to permit direct
Oxygen < 5 ppm connection to the regulator and to Electronic grade or Semiconductor
Hydrogen < 1 ppm the instrument gas controls. Liquid grade specifications (99.999% pure,
Nitrogen < 20 ppm argon may be purchased from your in liquid form). The DRC is shipped
Water < 4 ppm gas supplier. with a CGA-660 ammonia cylinder
fitting. Ammonia DRC gas cylinders
Either liquid or gaseous argon can PerkinElmer SCIEX ICP-MS instru- should use this type of fitting when
be used with an ICP-MS system. The ments include the tubing necessary ordered from your local gas supplier.
choice of liquid argon or gaseous for connecting argon to the instrument.
argon tanks is determined primarily The DRC gas is consumed at a
by the availability of each and the typical rate of 0.5 mL/min; therefore
usage rate. Liquid argon is usually DRC Gas Requirements only a very small cylinder (60 L, 2 ft3)
less expensive per unit volume to of gas is required. DRC gas cylinders
The customer is required to supply should be secured upright in a
purchase, but cannot be stored for
the dynamic reaction cell gas (or ventilated enclosure such as a cabinet
extended periods. If liquid argon is
DRC gas) for introduction into the or fume hood. For additional types of
used, the tank should be fitted with
dynamic reaction cell. The type of DRC gases, the customer must purchase
an over-pressure regulator which will
gas used varies with the customer a double stage regulator capable of
vent the tank as necessary in order to
application, but the most common supplying 3 mL/min at the pressure
prevent the tank from becoming a
DRC gas used with the DRC II is listed in Table III. A suitable double
safety hazard.
anhydrous ammonia. stage regulator with the correct cylinder
Gaseous argon tanks do not require fittings can be purchased from your
PerkinElmer SCIEX provides the local gas supplier.
venting and consequently can be
pressure regulator, gas delivery
stored for extended periods without loss.
tubing, and quick connector. The
A tank of liquid argon containing
pressure regulator is capable of
4300 ft3 will last for approximately
supplying the DRC gas at a working
100 hours of continuous ICP running
pressure of 48 kPa (7 psi). The quick
time. A tank of gaseous argon will
connector is affixed to the inlet fitting
last 5 to 6 hours of ICP running time.
for DRC gas A on the rear panel of
The normal argon usage is 14-20 L/min.
the ELAN DRC II. Plumbing for a
second DRC gas (DRC gas B) is available
as an option. Fittings which are
susceptible to attack by ammonia
(such as brass) or contain O-rings
which are not clearly labeled E, EP,
or EPDM must never be used in the
DRC gas line.

PerkinElmer Life and


Analytical Sciences
710 Bridgeport Avenue
Shelton, CT 06484-4794 USA
Phone: (800) 762-4000 or
(+1) 203-925-4600
www.perkinelmer.com

© 2003 PerkinElmer, Inc. All rights reserved. PerkinElmer is a registered trademark and FIAS, DRC and Dynamic Reaction Cell are
trademarks of PerkinElmer, Inc. SCIEX and ELAN are registered trademarks of MDS SCIEX, a division of MDS, Inc. All trademarks
depicted are the property of their respective holders and owners. PerkinElmer reserves the right to change this document at any time
and disclaims liability for editorial, pictorial, or typographical errors.
006040D 040300 Printed in USA

You might also like