DISTRIBUTION IN GEN CONTROL PANEL KEY SWITCH CONTROLS

NORMAL GEN
SENSING SENSING

2A 2A 2A 1600A 800A 2A 2A 2A
12V DC/24V DC
PSU
I II
RED

PILOTLIGHT
WHITE

PILOTLIGHT
BLUE

PILOTLIGHT
RED

PILOTLIGHT
WHITE

PILOTLIGHT
BLUE

PILOTLIGHT CURRENT
DSE ____ MANUAL
OTM

INPUT
START

PILOT LIGHTS ON OUTSIDE OF DB


N N
PILOT LIGHTS ON OUTSIDE OF DB
CONTROLLER DI 1
PUSH BUTTON

NORMAL GEN
6A 6A 6A 6A 6A

M 75A M 400A M 250A M 800A M 100A M 80A


3 POS K/S R1.1 R1.2 R1.3 R2.1 R2.2 R3.1 R3.2 R4.1 T1 T1 R4.2 T2 T2 R5.1 T3 T3 R5.2 T4 T4 R6.1 T5 T5 R7.1 T6 T6

POS 1&2 POS 1 POS 1 POS 2 POS 1 POS 1 P1 P2

FROM GEN CONTROLLER EMERGENCY


TO GEN CONTROLLER EMERGENCY
FROM GEN CONTROLLER NORMAL
TO GEN CONTROLLER NORMAL
M O C M O C M O C M O C M O C M O C
10A 10A 20A 63A NORMAL SENSING
ESKOM GEN

ELU
30mA R W B T1 R4 T2 T3 R5 T4 T5 R6 T6 R7

R1 R2 R3 UVR1 UVR2 UVR3 UVR4 UVR5 UVR6 DB-FG DB-AW K2 L/M K1 P/H
20A BATTERY
CHARGER

N N
KIOSK 1 DB-AW DB-FG PUMP HOUSE KIOSK 2 EXT LIGHTS SMALL
ABSTRACTION FILTER MCC LIGHTS POWER DB-FG DB-AW K2 L/M K1 P/H
GALLERY

I II

FROM GEN CONTROLLER EMERGENCY


OTM

FROM GEN CONTROLLER NORMAL


CHANGE-OVER PHILOSOPHY
2
N
5 4
ESKOM POWER ON. DSE CONTROLLER RECIEVES NORMAL SENSING INPUT- IF ALL IS WITHIN THE SET PERAMETERS
- NORMAL CONTACT CLOSE AND SWITCH CHANGE-OVER TO POSITION I.

EMERGENCY
NEUTRAL
NORMAL
CHANGE-OVER IS IN POSITION I. ESKOM POWER FAILS-GENERATOR STARTS UP -DSE GEN CONTROLLER RECIEVES GEN SENSING INPUT.

NEUTRAL
OPERATOR MUST GO TO THE GEN CONTROL PANEL AND PRESS A PUSH BUTTON , WHICH WILL SEND A DIGITAL INPUT TO THE DSE GEN CONTROLLER -
IF ALL IS WITHIN THE SET PARAMETERS THE CONTROLLER'S GEN CONTACT MUST CLOSE AND THE CHANGE-OVER WILL CHANGE OVER TO POSITION II.
R8 R9
WHEN ESKOM POWER IS AVAILABLE , GEN CONTROLLER RECIEVES THE NORMAL SENSING INPUT AND CLOSE NORMAL CONTACT
6A 6A WHICH WILL ALLOW THE CHANGE-OVER TO CHANGE TO POSITION I.

R9 R8
KEY SWITCH PHILOSOPHY
1 3

TO GEN CONTROLLER EMERGENCY


TO GEN CONTROLLER NORMAL

KEY SWITCH HAS 3 POSITIONS.POS-1 THE FOLLOWING BREAKERS WILL BE SWITCHED ON: DB-FG , DB-AW , KIOSK 2, KIOSK 1 AND THE LOCAL MAIN.
R8 R9
KEY SWITCH POSITION 2 : KIOSK 1 AND PUMP HOUSE.KEY SWITCH POSITION 0 : NONE OF THE BREAKERS WILL BE ON.
KEY SWITCH FUNCTIONS WILL STAY THE SAME NO MATTER IF THE CHANGE-OVER IS IN POSITION I OR II.
L N PE C 2 1 0
OTM

LOAD

IN MDB

90 HOPE STREET, GEORGE , 6529


TEL : 044 873 4137
FAX : 044 873 2980
PROJECT NAME
TSOMO WTW
GSB DRAWING DETAIL
DESIGNED BY APPROVED BY APPROVED DATE

R.LIZAMORE R.LIZAMORE 2021/06/01


DB NAME: TSOMO WTW SLD'S
REV NO. PAGE
0 1