NORMAL GEN
SENSING SENSING
2A 2A 2A 1600A 800A 2A 2A 2A
12V DC/24V DC
PSU
I II
RED
PILOTLIGHT
WHITE
PILOTLIGHT
BLUE
PILOTLIGHT
RED
PILOTLIGHT
WHITE
PILOTLIGHT
BLUE
PILOTLIGHT CURRENT
DSE ____ MANUAL
OTM
INPUT
START
NORMAL GEN
6A 6A 6A 6A 6A
ELU
30mA R W B T1 R4 T2 T3 R5 T4 T5 R6 T6 R7
R1 R2 R3 UVR1 UVR2 UVR3 UVR4 UVR5 UVR6 DB-FG DB-AW K2 L/M K1 P/H
20A BATTERY
CHARGER
N N
KIOSK 1 DB-AW DB-FG PUMP HOUSE KIOSK 2 EXT LIGHTS SMALL
ABSTRACTION FILTER MCC LIGHTS POWER DB-FG DB-AW K2 L/M K1 P/H
GALLERY
I II
EMERGENCY
NEUTRAL
NORMAL
CHANGE-OVER IS IN POSITION I. ESKOM POWER FAILS-GENERATOR STARTS UP -DSE GEN CONTROLLER RECIEVES GEN SENSING INPUT.
NEUTRAL
OPERATOR MUST GO TO THE GEN CONTROL PANEL AND PRESS A PUSH BUTTON , WHICH WILL SEND A DIGITAL INPUT TO THE DSE GEN CONTROLLER -
IF ALL IS WITHIN THE SET PARAMETERS THE CONTROLLER'S GEN CONTACT MUST CLOSE AND THE CHANGE-OVER WILL CHANGE OVER TO POSITION II.
R8 R9
WHEN ESKOM POWER IS AVAILABLE , GEN CONTROLLER RECIEVES THE NORMAL SENSING INPUT AND CLOSE NORMAL CONTACT
6A 6A WHICH WILL ALLOW THE CHANGE-OVER TO CHANGE TO POSITION I.
R9 R8
KEY SWITCH PHILOSOPHY
1 3
KEY SWITCH HAS 3 POSITIONS.POS-1 THE FOLLOWING BREAKERS WILL BE SWITCHED ON: DB-FG , DB-AW , KIOSK 2, KIOSK 1 AND THE LOCAL MAIN.
R8 R9
KEY SWITCH POSITION 2 : KIOSK 1 AND PUMP HOUSE.KEY SWITCH POSITION 0 : NONE OF THE BREAKERS WILL BE ON.
KEY SWITCH FUNCTIONS WILL STAY THE SAME NO MATTER IF THE CHANGE-OVER IS IN POSITION I OR II.
L N PE C 2 1 0
OTM
LOAD
IN MDB