Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Fire Safety in Cable Tunnels, Risers and Flats

A complete fire detection solution.


A cable tray fire, however small can cause extensive interruption and damage to
building structures, processes and subsequent consequential loss. However by
using Patol Linear Heat Detection Cable systems the outbreak of fire may be
detected before there is any damage to property or equipment.
Typically, cable tunnels, risers and flats use multi-level cable trays / ladder racking
for cable containment.

Linear Heat Detection Cable may be Metron actuators are initiated when an A typical cable tray installation will be arranged
economically applied to monitor above each appropriate firing current is applied. On firing, into zones which are often defined by:-
level to provide rapid detection of overheating the metron protracts a steel pin which shatters
cables caused by electrical malfunctions or the quartzoid bulb of the sprinkler head or  Physical barriers or Fire Breaks.
external conditions. multi-jet control valve. Often the requirement is  Access ways etc, for firefighting
to operate a number of these devices personnel.
Linear Heat Detection Cable systems are simultaneously, this especially in the case of
available with zonal monitors providing distance sprinklers, where a number may be resident  Zoning of sprinklers or other
location or monitored operating signals for within the same zone of LHDC detection. The extinguishants.
sprinklers fitted with single shot metron metron actuators are electrically connected in
actuators or zonal valves. series, each with a current activated bypass Each zone will require a length of Linear Heat
device connected in parallel to provide Detection Cable (LHDC) and a zone monitor.
continuity monitoring, thereby reporting a fault The length of LHDC in any zone may be
should a single unit fail whilst retaining the determined by the physical constraints or by
ability to operate all other serviceable metron reference to “Characteristics” of LHDC systems,
actuators in the event of a fire. this typically is up to 500 metres.
With this combination of early detection and The zone monitor may be located in or adjacent
sprinkler operation, fires can be controlled and to the zone and this as well as the sprinkler
extinguished with little or no damage to actuation signal provides repeat signals to a
cables. Patol Linear Heat Detection Cable has control area. Alternatively a multi-zone panel
been proved to respond to a small fire within can be installed in a central location connected
seconds and repeatedly tested to be less than via suitable interposing cables to the LHDC and
Metron Actuated Sprinkler one minute using a standard crib fire. extinguishing control circuits.

1 D1231-2
Fire Safety in Cable Tunnels, Risers and Flats

Depending on the type of LHDC employed, The graphs show a typical application where Commissioning and Routine Maintenance
various levels of monitoring are available. 300m of LHDC Analogue is employed in
conjunction with a zone monitor adjusted for a Commissioning and routine maintenance of the
Resettable LHDC (Analogue) 3 Volt set point. Patol Analogue Linear Heat Detection Cable
 The graph on the left shows that the system can be conducted at site by use of a
The Patol resettable type LHDC (Analogue) is a calibrated 1 metre test oven and can be tested
coaxial cable and the properties of the inner whole of the zone will with stand ambient repeatedly without detriment to its operation.
insulator has a resistive negative temperature temperatures up to 53°C without any
coefficient. As the LHDC is elevated in alarm triggers
temperature an analogue signal is monitored at  The graph on right shows that a
the controller. Pre-alarm and Alarm set point temperature elevation of a 10m section of
outputs are configured to operate indications the zone will produce an alarm trigger at
and outputs at fixed temperatures for a known a maximum of 118°C
length of LHDC.  Margin and tolerance are applied to the
Zone Monitor Controllers are equipped with curves. In practice the withstand will be
sensitivity / trip adjustments. The graphs show greater than 53°C.
The portable 1 metre test oven concept of
three typical settings. Note: For further information refer to full LHDC testing allows accessible LHDC to be subjected
The controller also monitors for open and short Data Sheet. to temperatures within the alarm range. Thus
circuit LHDC faults and provides an indication confirming correct calibration setting selection
and output for either condition. and alarm levels in accordance with the project
specification.

A M BI E NT NO N AL A RM C HA RA CT E R IS T I CS
D ETE C TIO N P OINT ALA RM C HA RA CTE RIS TICS

75 150
KEY
70 140
3V Set Point
65 130
2V Set Point
60 120
118 1V Set Point
55 110
53
50 100
45 90
40 80
35 70 65
30 60
25 50

30 100 300 1000 1 10 100 300


Detector Length - m
Detector Length - m

T-Clips Non-resettable LHDC (Digital)


The Patol non-resettable type LHDC (Digital) is
a two core twisted pair cable. The two cores
are tinned copper coated spring steel
conductors. The insulation of the two cores is a
Universal specially formulated polymer such that it
Support plasticizes at a fixed specific temperature. This
Bracket L Bracket provides a switch contact which is monitored at
the zonal monitor. The zone monitor can
provide indications and outputs for a fire or
open circuit fault conditions. Digital cable
V-Clips monitors are also available to provide fire
distance location along the LHDC with a
maximum length of 2,000 metres.
Rod and Bobbin
Contact Details:
Patol Limited
Edge Clip Archway House
Bath Road
Padworth, Reading,
Typical LHDC Fixing Methods Berkshire.
RG7 5HR
A variety of LHDC fixing methods are available for all applications and all cable Tel: +44 (0)1189 701 701
containment types. Fax: +44 (0)1189 701 700
Email: info@patol.co.uk
See Sales Information Sheet : Application Fixings Document No. D1183 Web: www.Patol.co.uk
2 D1231-2

You might also like