AFCONS (Vikhroli) - Wind Load Calculation
AFCONS (Vikhroli) - Wind Load Calculation
AFCONS (Vikhroli) - Wind Load Calculation
Wind load on the structure have been evaluated as per the guidelines of IS:875 (Part 3) -2015
for Clad Buildings.
For the purpose of Internal Pressure/ Suction Magnitude, Building has been considered
to have Nominal Openings up to 5% (± 0.2)
Building Schematic showing wall faces & wind zones are elaborated in sketch below
Sign Used :-
EXTERNAL PRESSURE :- (Pressure acting from, Outside to Inside)
EXTERNAL PRESSURE :- (Pressure acting from, Outside to Outside)
Basic Wind Speed (Vb) = 44.00 m/s (Mumbai) …(Refer, IS:875 (Part-3)-2015)
Building Classifications :-
Terrain Category = 2 (Assumed) …(Refer 6.3.2.1, IS:875 Part-3 -2015)
Type of Structure as per Table-01 = Temporary Structure - 25 Year's Life …(Refer 6.3.1, IS:875 Part-3 -2015)
Building Dimensions :-
Building Height (H) = 9.270 m (Height of Building)
Building Width (W) = 19.480 m (Considered Max. Width)
Building Length (L) = 26.290 m (Considered Max. Length)
Where,
k1 (Risk Coefficient) = 0.91 …(Refer Table-1, IS:875 Part-3 -2015)
k2 (Terrain Roughness & Ht. Factor) = 1.00 …(Refer Table-2, IS:875 Part-3 -2015)
k3 (Topography Factor) = 1.00 …(As per Cls: 6.3.3, IS:875 Part-3 -2015)
k4 (Importance Factor) = 1.00 …(As per Cls: 6.3.4, IS:875 Part-3 -2015)
Wind Pressure (Pz) = 0.6 x Vz²² …(Refer 7.2, IS:875 Part-3 -2015)
= 961.92 N/m²
= 0.962 Kn/m²
Where,
Wind Directionality Factor (Kd) = 1.00 …(As per Cls: 7.2.1, IS:875 Part-3 -2015)
Area Averaging Factor (Ka) = 0.80 …(As per Cls: 7.2.2, IS:875 Part-3 -2015)
Combination Factor (Kc) = 1.00 ….(Table-19 : Clause- 7.3.3.13)