Professional Documents
Culture Documents
SA-TD10006036 GLiner-LCT4 EN
SA-TD10006036 GLiner-LCT4 EN
Copyright
© KRONES AG 2014 - No utilisation, copying and/or distribution without author's consent.
Table of contents
1 Preface ............................................................................................................. 7
1.1 Notations................................................................................... 7
1.2 Requirements ............................................................................ 7
2 Safety ............................................................................................................... 8
3 Introduction .................................................................................................... 10
6 Principles ........................................................................................................ 18
7 LCT4............................................................................................................... 31
11 Start-up........................................................................................................... 77
12 Appendices .................................................................................................... 80
1 Preface
1.1 Notations
NOTE If there is a risk of injury, damage, or loss of data, the respective warning
will be highlighted with a red bar.
1.2 Requirements
These service instructions assume that you have a basic knowledge of
the mechanical design of the conveyors and of the workflow of the con-
tainer conveyor system.
These service instructions do not impart any basic knowledge.
NOTE If system, machine or type parameters are changed or if the LCT is re-
placed, the parameters must first be saved to the USB stick.
For more details read the sections "Saving parameters" and "Loading pa-
rameters".
© KRONES AG 2014 - No utilisation, copying and/or distribution without author's consent.
2 Safety
WARNING prevented.
Do not under any circumstances reach into the cutting unit while the
machine is being jogged!
3 Introduction
The Glideliner, type Glideliner is used for bringing together, i.e. combining,
containers from multi-track conveyors onto a single-track conveyor.
This can be done via a straight sliding conveyor, a sliding conveyor with a
10-12 degree upward incline, or a sliding conveyor with a 10-12 degree
downward incline.
The Glideliner, type Block is used to control the flow of containers between
two machines. In this case the lead machine's slave machine is blocked,
thus regulating the incoming flow of containers.
4 Standardised configuration
The drawing shows the minimal Glideliner version. The containers on the
dosing conveyor are still in clusters. On the sliding conveyor the containers
are separated as a result of the different speeds of the individual belts, and
on the accelerating conveyor the gap between the containers is closed. The
intermediate conveyor is used to build up the necessary back-up pressure
in front of the machine. The control system has 4 additional analog outputs
for 4 additional conveyors. These outputs can be installed at random in
front of or between these conveyors. The 4 additional conveyors can be
parameterised in the control system.
The drawing shows the minimal Block version. The purpose of the Block is
to bring together the containers between 2 machines on one track. The lead
machine dictates the speed. The conveyors run in sync with the lead ma-
chine. The accelerating conveyor still has the job of closing the gap. At the
© KRONES AG 2014 - No utilisation, copying and/or distribution without author's consent.
same time the discharge conveyor and the speed of the controlled machine
is increased or reduced. As with the Glideliner, the Block version comes with
4 additional analog outputs for 4 conveyors which can be positioned at ran-
dom. The 4 additional conveyors can be parameterised in the control sys-
tem.
5.1 Operation
When you enter the parameters the numeric keypad is also active. Each pa-
rameter can be entered as in the past with the +/- key and the numeric
keypad. However, this option is disabled during operation if the production
type is the same as the edited type.
Offline editing
Upon opening the menus for the type
parameters you can select the type
you want to edit.
On the example display, type 0 is
shown as currently in production.
Type 1 is the type you want to edit. If
the type which you want to edit does
not match the current production
type, the bar in the setup menu will
be shown in red.
In the top right corner, the produced
type number is shown above the ed- Figure 3: Offline editing
ited type number.
Language selection
Language selection using country
flags on the main screen page 3, see
chapter 8.1.4.
© KRONES AG 2014 - No utilisation, copying and/or distribution without author's consent.
System parameters
System parameters have been intro-
duced for changing over to Glideliner
or Block.
Also, the LCT4 can be connected to
the network via Ethernet. This re-
quires you to enter the network data,
see chapter 8.4
Training manual - SA-TD10006036_GLiner-LCT4_EN.docx KRONES Academy5 New developments since the former LCT3 control systemPage 1
KRONES Glideliner control system with LCT4
Type Glideliner and type Block
Save/load parameters
Parameters can be saved to a USB stick and then can be read in again from
there (see chapter 9).
Training manual - SA-TD10006036_GLiner-LCT4_EN.docx KRONES Academy5 New developments since the former LCT3 control systemPage 1
KRONES Glideliner control system with LCT4
Type Glideliner and type Block
Container rejection/pusher
The pusher control system was up-
graded. A virtual fine clock pulse with
a resolution of approx. 1 cm is creat-
ed in the control system. This makes
the pushing out even more exact (see
chapter 8.5.12).
Conveyor mode
The conveyor mode was expanded
(see chapter 8.5.3).
© KRONES AG 2014 - No utilisation, copying and/or distribution without author's consent.
Training manual - SA-TD10006036_GLiner-LCT4_EN.docx KRONES Academy5 New developments since the former LCT3 control systemPage 1
KRONES Glideliner control system with LCT4
Type Glideliner and type Block
Training manual - SA-TD10006036_GLiner-LCT4_EN.docx KRONES Academy5 New developments since the former LCT3 control systemPage 1
KRONES Glideliner control system with LCT4
Type Glideliner and type Block
Training manual - SA-TD10006036_GLiner-LCT4_EN.docx KRONES Academy5 New developments since the former LCT3 control systemPage 1
KRONES Glideliner control system with LCT4
Type Glideliner and type Block
Training manual - SA-TD10006036_GLiner-LCT4_EN.docx KRONES Academy5 New developments since the former LCT3 control systemPage 1
KRONES Glideliner control system with LCT4
Type Glideliner and type Block
6 Principles
clock/C Rotation
s (m)
Analog 100 Hz output
voltage Frequency
Revolution
0-10Volt in Hz
Motor
Analog
current
adjustment 0-20mA
0
0 Analog 10 Rotation max 0 t (min)
value input
voltage
72,000 7 100 7
36,000 3.5 200 7
100,000 9.7 72 7
Summary:
The basic set-point value is corrected with the adjustment values of the
individual conveyors and is forwarded as an analog output voltage to the
frequency inverters.
When the gap control system is in the steady state, the area between the
lead machine and LS1 is comprised of two parts (set-point gap = actual
gap).
See Figure 23: Coherent actual gap = 2.
1st part: lead machine and back-up point (containers stand side by side),
2nd part: back-up point and LS1 (there are gaps between the containers).
The set-point gap specifies the position between the lead machine and LS1.
In Figure 23 you can see that the actual gap in the area between the back-
up point and LS1 results from the sum of the individual gaps between the
containers.
Pushing together all the containers from LS1 in the direction of the lead
machine results in the coherent actual gap of 2 container diameters
(see Figure 23).
The gap control system uses a percentage value from the gap table to re-
duce the speeds of all the conveyors in order to achieve the selected set-
point value (set-point gap = 2).
The back-up point wanders from LS1 in the direction of the lead machine.
The number of actual gaps has increased in Figure 24 from 0 to 1.
If the current gap is too big (actual gap = 3) and the back-up point too
close to the lead machine, the speeds of all the conveyors will be increased
by a percentage value from the gap table in order to achieve the selected
set-point value (set-point gap = 2).
The back-up point wanders from the lead machine in the direction of LS1.
The number of gaps is reduced.
© KRONES AG 2014 - No utilisation, copying and/or distribution without author's consent.
Once the set-point value (set-point gap = 2) is reached, the speed increase
will be cancelled.
Summary:
The gap control system keeps the number of containers and therefore the
number of gaps between the lead machine and LS1 constant.
The gap control system responds immediately to deviations of the actual
gap from the set-point gap.
Summary:
© KRONES AG 2014 - No utilisation, copying and/or distribution without author's consent.
The average value keeps the number of containers arriving from the
dosing conveyor 1 constant. It changes the speed of the conveyors as
from dosing conveyor 1 only when the average value counter has
reached the set positive or negative limit value.
For a more fluid control, adjustments to the average value are already
being made in the parts-per-thousand range. This occurs upon reach-
ing the 1/10 increments of the set limit values.
Example: set positive limit value +500
If the average value counter reaches the value +50, the average val-
ue will be increased by 0.1%.
If the average value counter reaches the value +50, the average val-
ue will again be increased by 0.1%.
Therefore, if the value +500 is reached, there will be an increase of
1%.
If the pulse-duty factor is set too high, the container back-up will not be
reduced and the containers will jam in the sliding area.
In the following example the pulse-duty factor is set to 100%. In this con-
nection see Figure 31: Slippage control
In example No. 1:
the current pulse-duty factor is 100% (T1 / T2 * 100%),
the set pulse-duty factor is not exceeded,
LED A1 lights up, containers are standing on the accelerating con-
veyor,
the slippage control system is not active!
In example No. 2:
the current pulse-duty factor is 82%,
see example No.1
© KRONES AG 2014 - No utilisation, copying and/or distribution without author's consent.
In example No. 3:
the current pulse-duty factor is 110%,
the set pulse-duty factor is exceeded,
LED A12 lights up, containers are slipping on the accelerating con-
veyor,
the slippage control system is active!
Summary:
The slippage control system immediately reduces the speed of the dosing
conveyor after it detects containers slipping on the accelerating belt (the
container back-up is reduced).
Purpose:
The purpose of the module "Stop after number of containers fallen over" is
to stop the conveyors immediately after a back-up (in the area between the
lead machine and the sliding conveyor), i.e. not until after a pile of fallen
containers has actuated the P.E. sensor.
In addition: "Stop after number of containers fallen over" when the P.E. sen-
sor is actuated for more than 2.
Mechanical requirements:
Inliner standing in a straight line.
A P.E. sensor must be connected to E11 (E3.11) and be positioned over the
collecting bin so that it can count all the fallen bottles.
A14 (A6.2) must be connected to the higher-level PLC in order to report the
back-up.
The parameters "Number of containers" and "Number of conveyor clock
© KRONES AG 2014 - No utilisation, copying and/or distribution without author's consent.
Method of operation:
The method of operation will be described using the above figure.
The parameter "Number of containers" has the value 3, and the parameter
"Number of conveyor clock pulse" has the value 5.
The signal diagram is divided into sections A to D.
In area "A":
With the accelerating conveyor in operation, an internal conveyor clock
pulse counter is continuously increased with each conveyor clock pulse
and is always set to 0 when it reaches the value parameterised under
"Number of conveyor clock pulses" and no containers have fallen in this
area.
The output A14 remains on "Low".
In area "B":
The conveyor clock pulse cycle is increased as in area "A". Each fallen
container actuates the P.E. sensor and therefore increases a container
counter (Z1).
When this container counter reaches the value 3, the conveyor clock
pulse counter and the container counter will be set to 0 (Z2). The output
A14 remains on "Low".
In area "C":
The conveyor clock pulse counter and container counter are increased
(Z3).
Because 3 containers have fallen in the area of the 5th conveyor clock
pulse (Z4), the output A14 will be set to "High" (Z5) and a signal will be
sent to the PLC to report a back-up in the area of the sliding conveyor /
accelerating conveyor.
The accelerating conveyor and the intermediate conveyor continue to
follow the lead machine.
All the conveyors as from the sliding conveyor are stopped so that no
more containers fall over. A message appears on the main screen page
and the LED of button 9 lights up red.
In area "D":
After button 9 on the LCT4 (Z6) is actuated, The conveyor clock pulse
counter and the container counter are set to 0 (Z7).
Summary:
All the conveyors as from the sliding conveyor will stop if more than a pa-
rameterised number of containers fall from the accelerating conveyor in a
parameterised conveyor clock pulse range.
Purpose:
The purpose of the module "Rejecting fallen containers" is to reject contain-
ers which did not roll out in the area of the sliding conveyor or did not fall
over until at the end of the sliding conveyor.
Mechanical requirements:
Inliner standing in a straight line.
The P.E. sensors LS21 and LS22 must be in a vertical axis.
The rejection unit must be mounted at a reasonable mechanical distance
from the LS21 and LS22 (between 50 and 300mm). If the distance is too
short, the control valve will not be able to switch early enough. If the
distance is too large, the distance calculation will be corrupted when the
speed varies.
The conveyor clock pulse or a special encoder for the pusher must be
connected to DS2.
Parameters: The parameters "Number of clock pulses container fallen"
must contain values greater than 0 ("Number of clock pulses, blowing
out" = 0 = OFF).
Method of operation:
If a container is detected, an internal counter will be increased with each
pusher clock pulse. This counter is set to 0 when the LS21 detects a gap or
the LS22 a container neck.
If the internal counter reaches the value set under "Number of clock pulses
container fallen", then the rejection unit (e.g. solenoid valve) will be turned
ON. To allow the valve enough actuating time, the rejection unit is fitted
© KRONES AG 2014 - No utilisation, copying and/or distribution without author's consent.
behind the LS21 and L22. The distance must be saved in the parameter
"Distance P.E. sensor – pusher". The distance can be converted into clock
pulses via the resolution of the pusher clock pulse, and the turning on of
the rejection unit can be delayed by exactly this distance.
The rejection unit remains ON until the value in pusher clock pulses set
under "Number of clock pulses container fallen" has elapsed.
The value of the parameter "Number of clock pulses container fallen" is
based therefore only on the width of the container type.
NOTE If the value of the parameter "Number of clock pulses container fallen" is set
too low, then standing containers will be rejected. If it is high, fallen bottles
will not be detected.
If the parameter "Number of clock pulses, blowing out" is set too high, the
following containers will also be rejected.
The example in the figure "Rejecting fallen containers" is based on the fol-
lowing parameters:
Number of clock pulses bottle fallen =3
Distance P.E. sensor – pusher = 30mm
Number of increments, encoder = 10
Drive wheel circumference = 400mm
Real resolution = 40mm per clock pulse
Virtual resolution = 10mm per pusher clock pulse
Number of clock pulses, blowing-out =3
Summary:
The parameter "Number of clock pulses container fallen" sets the virtual
conveyor clock pulses for detecting a container.
A High signal at LS22 and each Low signal at LS21 will reset the detection.
The length of the blowing out in milliseconds is specified with the parame-
ter "Number of clock pulses, blowing out".
A delay in the rejection by offsetting the rejection unit relative to LS21 and
LS22 is specified by the parameter "Distance P.E. sensor – pusher". The off-
set is converted into a number of likely pusher clock pulses on the basis of
the resolution of the conveyor clock pulse or the pusher clock pulse (calcu-
© KRONES AG 2014 - No utilisation, copying and/or distribution without author's consent.
7 LCT4
NOTE The numerical keypad is enabled only when the machine has stopped or the
set type is not the type currently in production.
ENTER
For selecting a menu point.
For activating the parameter entry (the value will flash).
For confirming the parameter entry and adopting the value.
ESC
For selecting to close a menu point.
For cancelling an entry without changing the parameter.
For closing a function.
The query 'Code 3:' must be answered with the button combination
-
+
+
-
© KRONES AG 2014 - No utilisation, copying and/or distribution without author's consent.
ENTER
.
Example:
The code query must be answered
with the following button combina-
tion.
-
+
+
-
ENTER.
8 Parameter description
Type selection
Use the right-hand arrow button
to switch to the "Production type"
line and confirm with "ENTER".
From the flashing line use the
arrow buttons to set the required
container type and confirm with
"ENTER".
© KRONES AG 2014 - No utilisation, copying and/or distribution without author's consent.
first digits.
Figure 48: Set-up mode – Type selection Figure 49: Set-up mode – Type parameters
The type parameters can be edited offline. This means that e.g. type 1 can
be in production while type 2 is being edited.
When offline editing is active, the bar colour will change to "red".
The indicated output is selected with "ENTER" and the value flashing on the
right can be edited. If the machine is at a standstill, you can also enter the
value with the numerical keypad.
The penultimate line shows the current average value and indicates whether
the control system is ON or OFF.
© KRONES AG 2014 - No utilisation, copying and/or distribution without author's consent.
the conveyor.
Average value:
The average value is incre-
mented or decremented line-
arly to the set-point value of
the dosing conveyor.
E5 back-up switch
If the E5 back-up switch is ac- Figure 57: Measured value screen page 6 (dos-
ing conveyor)
tivated, the speed of the dos-
ing conveyor will be reduced
very quickly.
Slippage controller:
If the container slips under the
P.E. sensor, the dosing con-
veyor 1 must slow down very
quickly.
Gap
Set-point gap:
The set-point gap on the ac-
celerating conveyor after the
P.E. sensors LS1…3 (min.
0…max. 20) is shown here.
© KRONES AG 2014 - No utilisation, copying and/or distribution without author's consent.
Slippage
Selection slippage table
The higher the value, the
greater the sliding conveyor
and the dosing conveyor will
be decelerated.
Back-up stop:
If the lead machine is running
and there is no container flow
at LS1…3, A7 will be switched
to Low after the number of
container clock pulses set here
and the A7 LED will light up
red. A fault will also be en- Figure 61: Slippage
tered in the event history (nu-
merical key 9 flashes red).
The lower bar graph shows the control value of the back-up pressure con-
troller. It is limited to +/-2%. If the bar is always on one side, the conveyor
adjustment value must be changed.
If it is always negative, the adjustment value of the conveyor should be re-
duced.
If it is always positive, you should increase the conveyor adjustment value.
Reduce machine speed:
If the difference between the current
gap and set-point gap is greater than
the value set here, A13 will become
High and the lead machine should
therefore be decelerated. When the
parameter is 0, this function is deac-
tivated.
Starting speed
Can be set from 0 - 100 percent (0 V - 7 V).
The starting speed is needed so that no gaps form on the intermediate con-
veyor when the lead machine starts up. Can be set in % of the maximum
selectable machine speed.
Average value
The average value is needed for the
exact adjustment of the container
© KRONES AG 2014 - No utilisation, copying and/or distribution without author's consent.
If the conveyors remain stationary for a lengthy period, they will become dry.
Starting up with dry conveyors can result in overdosing of the dosing con-
veyor to the sliding conveyor. It makes sense in this case to reduce the ad-
justment value for the dosing conveyor by approx. 5-10%. When the con-
veyors are running, the adjustment value will then by increased via the av-
erage value control system. Here you can set the length of time after which
you want the average value to be deleted when the conveyors are stationary.
More current diagnostics variables are shown in the bottom part of the
screen page.
The current system status is indicated. The conveyor clock pulse counter for
changing over from slow filling to fast filling is shown. The "Counter stop
after number of containers" is incremented when the containers slip.
© KRONES AG 2014 - No utilisation, copying and/or distribution without author's consent.
8.5.10 Synchronisation
The synchronisation function is re-
quired in order to synchronise the
gap counter after a defined number
of containers. The speed of the accel-
erating conveyor is increased until
the containers slip under LS1..3. Then
the gap counter is zeroed and the
synchronisation ended.
The synchronisation function can be
turned ON or OFF.
The value of the synchronisation
counter defines the number of con- Figure 78: Synchronisation
tainers after which synchronisation is
© KRONES AG 2014 - No utilisation, copying and/or distribution without author's consent.
Diagnostics, pusher
The current parameters and the sig-
nals of the inputs and outputs for the
container rejection system are pre-
sented here.
Figure 83: Instruction: Turn OFF the conveyor Figure 84: Instruction: Provide a mark
Figure 85: Instruction: Operate the conveyor Figure 86: Instruction: Enter the distance
8.5.14 Ramps
The maximum acceleration time and
the braking time are entered here.
This is the ramp-up time from 0 to
10V and the ramp-down time of the
set-point value from 10V to 0V
It should be noted that the control
system will work reasonably only if
the inverter ramps are not very much
bigger. The ramps are valid for all 8
conveyors.
Figure 90: Designation, type number Figure 91: Text input, type number
Setting the type for which the adjustment values are to be determined.
© KRONES AG 2014 - No utilisation, copying and/or distribution without author's consent.
Pulse-duty factor
Pulse-duty factor:
Can be set from 75 -125.
The pulse-duty factor is the basis
for slippage detection.
See also "Control principles" "Slip-
page control system" "Pulse-duty
factor"
Container stop
V container stop release:
Can be set from 1000 - 50000
containers per hour. After fill-
ing up to the set-point gap or
after a slippage analysis, the
control system will not issue
the finished signal A3 = 1 un-
til the speed of the lead ma-
chine has dropped below the
parameterised value. This pa-
rameter is used to prevent
containers entering the infeed
worm too quickly and destroy- Figure 103: Container stop
ing it.
Coasting time:
Can be set from 0.0 – 15.0 seconds. 0.0: without moveable container
stop; in the range 0.1 - 15.0: with moveable container stop.
Container stop speed adjustment:
Can be set from 0 - 100 percent (0 - 7 V).
This indicates the speed at which the conveyors continue running for
the coasting time in seconds after the container stop is locked.
Example:
Coasting time = 0.5, container stop speed adjustment = 20.0%
The conveyors coast for 0.5 seconds at 1.4 V output voltage after the
moveable container stop is locked.
NOTE The coasting time and speed are defined by the throttle of the pneumatic
cylinder.
If the containers bump loudly into each other after stopping, then the
coasting time or the coasting speed (container stop speed adjustment) must
be reduced.
If a gap forms between the machine infeed conveyor and the intermediate
conveyor, then the coasting time or the coasting speed (container stop
speed adjustment) must be increased.
© KRONES AG 2014 - No utilisation, copying and/or distribution without author's consent.
Measured values
The control system response can be observed in a selection of measured
values.
The menu has a direct link to the measured value screen pages of the type
parameters.
Read the description there.
Conveyor mode
You can set the operating mode of
the intermediate conveyor, the con-
veyor in reserve 1, the conveyor in
reserve 2, the dosing conveyor 2 and
the feed conveyor.
Intermediate conveyor
Not used
Synchronous with lead machine
Synchronous with accelerating conveyor
Vmin. conveyors
Vmin. conveyors:
The conveyors must not run
slower than the conveyor
speeds set here.
NOTE The set Vmin will be output to the conveyor in reserve 1, 2 only in conveyor
mode = 1 (lead machine)!
Training manual - SA-TD10006036_GLiner-LCT4_EN.docx KRONES Academy 8 Parameter descriptionPage 57/88
KRONES Glideliner control system with LCT4
Type Glideliner and type Block
Customer data
Specific information regarding the
customer and the machine serial
numbers can be saved here. In par-
ticular parameter documentation can
thus be clearly assigned.
Requirements:
The inspector output signal is connected to E5.
This signal issues one High pulse per rejected container.
The inspector clock pulse which outputs one High pulse per container is
connected to E11.
Can be set from 0-99.
"0" not active.
The clock pulse counter parameter defines the distance between the in-
spector rejection system and the first transfer point (after the inspector) in
inspector clock pulses. The gap increase is delayed by this value.
See under "Type parameters" "Block" "Gap increase".
Pulse-duty factor
The ""Pulse-duty factor" menu is identical to that for the Glideliner, type
Glideliner.
Container stop
V container stop release:
Can be set from 1000 - 50000
containers per hour.
After filling up to the set-point gap
or after a slippage analysis, the con-
trol system will not issue the finished
signal A3 = 1 until the speed of the
lead machine has dropped below the
parameterised value. This parameter
is used to prevent containers from
entering the infeed worm too quickly
and destroying it.
Figure 108: Container stop
Coasting time and container stop speed adjustment are the same as for the
Glideliner, type Glideliner.
Inspector coasting:
Can be set from 0.0 – 15.0 seconds. The maximum possible value
equals the coasting time.
0.0: without moveable container stop; in the range 0.1 - 15.0: with
moveable container stop. Defines how long the inspector coasts with
the "Container stop speed adjustment" when the container stop is
locked in order to minimise the gap between the inspector and the
discharge conveyor 2.
Measured values
The control system response can be observed in a selection of measured
values.
The menu has a direct link to the measured value screen pages of the type
parameters. Read the description there.
Conveyor mode
You can set the operating mode of the intermediate conveyor, the conveyor
in reserve 1, the conveyor in reserve 2, the dosing conveyor 2 and the feed
conveyor.
Intermediate conveyor
Not used
© KRONES AG 2014 - No utilisation, copying and/or distribution without author's consent.
Vmin. conveyors
Identical to Glideliner, type Glideliner
Customer data
Identical to Glideliner, type Glideliner
© KRONES AG 2014 - No utilisation, copying and/or distribution without author's consent.
8.8 Diagnostics
The diagnostics menu provides various options for checking the functiona-
bility of the LCT4 and the current response.
Event history:
Various events are logged and
indicated during operation.
They can be saved on a USB
stick.
Analog values diagram:
Records and presents the ma-
nipulated variables of the con-
veyors over a certain period.
Digital values diagram:
Records and presents the digi-
tal inputs/outputs over a cer-
tain period. Figure 113: Diagnostics
Version:
Indicates the versions of the
various modules.
LCT4 test:
Various equipment tests.
Profiler:
Indicates the current CPU
workload.
Available memory space:
Indicates the memory space in
use in the various memory ar-
eas.
Glideliner memory capacity utili-
sation:
Indicates the space needed by
the various parameter struc-
tures.
Measured values:
Indicates the current control
variables
© KRONES AG 2014 - No utilisation, copying and/or distribution without author's consent.
Save on USB:
The event history can be saved to a
USB stick. The system saves a .br file
which can be opened with Automa-
tion Studio.
Dig IO:
If this flag is activated, the edges
of the following inputs and out-
puts will be logged.
E4 – Line ready
E8 – Container stop released
E16 – Start lead machine
E13 – Inspector ON
Figure 115: Save parameters on USB
A3 – Controller ready
A5 – Controller enable
A4 – Controller enable inspec-
tor
System status
The recording of the operating
states is activated here.
Reject container
If this parameter is set to "On",
the rejection of each fallen bottle
will be recorded.
© KRONES AG 2014 - No utilisation, copying and/or distribution without author's consent.
Type selection
The recording of type changes can
be activated.
Start :
Starts the recording with the
selected settings.
Stop:
Stops the recording.
Interval [ms]:
Defines the frequency at which
the recording is made. (20ms
means that the current value is
saved in intervals of 20ms.)
Sample time [min:sec]:
Defines the period of time
over which values are to re- Figure 119: Analog values diagram, functions
main available after the re-
cording is stopped. Is derived
from the interval and therefore
cannot be edited: The longer
the interval, the longer the re-
cording time.
Zoom:
Indicates how much of the re-
cording time can be seen in
the window. With x1, the com-
plete recording time will be
shown; with x2, half the re-
cording time will be shown,
etc.
Ramps
This parameter can be used to se-
lect whether the presented analog
values are presented before or af-
ter the ramp calculation.
Curves display:
Here you can select the con-
veyors for which the manipu-
lated variables are to be rec-
orded and shown.
8.8.4 Version
The version used is indicated for the
following modules:
Software
Parameter file
Automation studio
Runtime
Visual Components
I/O test
The inputs and outputs can be tested
here.
The status of the digital inputs is in-
dicated using a green (1) or grey (0)
light.
Digital outputs can be switched by
© KRONES AG 2014 - No utilisation, copying and/or distribution without author's consent.
Front panel
Keyboard test:
Testing the keys
LED test:
If this menu is selected, all of the
LEDs will be actuated in sequence
and light up briefly. This occurs in
the following order:
Red LEDs on the numerical
keys, in ascending order
Green LEDs on the numerical
keys, in ascending order
Input LEDs, in ascending order
Output LEDs, in ascending or- Figure 127: Test front panel
der
Keyboard test:
When a button is pressed, a
symbol of this button will ap-
pear in the display.
If no symbol appears, the but-
ton is faulty or the X2X bus is
interrupted.
The menu can be closed by pressing
and holding the "ESC" button for 3
seconds.
Miscellaneous
Operating hours:
You are shown the number of
hours that the LCT4 was in the
power ON state and the num-
ber of hours within this time
that were operating hours.
(Operating hours is time when
the control system was in a
© KRONES AG 2014 - No utilisation, copying and/or distribution without author's consent.
8.8.6 Profiler
The profiler automatically logs all of
the tasks performed and their pro-
cessing times under the running time.
The current CPU workload can be
read off directly (after loading the
screen page it takes approx. 1-2 sec-
onds to update).
Save on USB:
A detailed excerpt of the pro-
filer is saved to the USB stick.
The profiler excerpt is saved in
pd format and can be dis-
played and analysed with Au- Figure 130: Profiler
tomation Studio.
The files are saved with a date stamp and time stamp. The latest version is
always saved without a time stamp (for reading in again) and with a time
© KRONES AG 2014 - No utilisation, copying and/or distribution without author's consent.
stamp. To read in one of the older parameter files, its time stamp must be
removed first.
Figure 135: Confirmation prompt Figure 136: Cancel the loading process
To read a parameter file with an older time stamp, its time stamp must be
removed first.
Before the parameters are loaded you will be asked whether you want to
overwrite the parameter set. You can still cancel the loading at this point.
Automatic version update:
During the loading, the version
string of the parameter set
saved in the file will be evalu-
ated. If it is no longer up to
date, an automatic update
routine will be started and the
© KRONES AG 2014 - No utilisation, copying and/or distribution without author's consent.
Training manual - SA-TD10006036_GLiner-LCT4_EN.docx KRONES Academy 9 Loading and saving parametersPage 73/88
KRONES Glideliner control system with LCT4
Type Glideliner and type Block
Query mode:
To be able to assign the pa-
© KRONES AG 2014 - No utilisation, copying and/or distribution without author's consent.
Training manual - SA-TD10006036_GLiner-LCT4_EN.docx KRONES Academy 9 Loading and saving parametersPage 74/88
KRONES Glideliner control system with LCT4
Type Glideliner and type Block
Training manual - SA-TD10006036_GLiner-LCT4_EN.docx KRONES Academy 9 Loading and saving parametersPage 75/88
KRONES Glideliner control system with LCT4
Type Glideliner and type Block
Password query:
The password is "c".
Operation:
To operate, you need the follow-
ing keys on the PC keyboard:
"Enter" = "Return"
"ESC"= "ESC"
„?“ = "F12"
„1“ – "9" = "F1" – "F9"
"0" = "F10"
Text input:
For entering texts (customer
data, type designations,…) you
can use the complete PC key-
© KRONES AG 2014 - No utilisation, copying and/or distribution without author's consent.
board.
Training manual - SA-TD10006036_GLiner-LCT4_EN.docx KRONES Academy 10 Remote access via a VNC ViewerPage 76/88
KRONES Glideliner control system with LCT4
Type Glideliner and type Block
11 Start-up
11.2.1 Language
Go to the menu point "Set-up mode" "Machine parameters" and select
the required language.
© KRONES AG 2014 - No utilisation, copying and/or distribution without author's consent.
11.3.2 Ramps
Go to the menu point "Set-up mode""Type parameters""Ramps" and
set the parameters "Starting ramp" and "Braking ramp" to 2.0 seconds.
11.4 Optimisation
12 Appendices
X20 AO 4622
X20 DO 9322
X20 DI 9371
X20 AO 4622
X20 DO 9322
X20 DI 9371
X20 DS1319
1 2 1 2 1 2 1 2 1 2 1 2 1 2
X20 BR 9300
3 4 3 4 3 4 3 4 3 4 3 4 3 4
5 6 5 6 5 6 5 6 5 6
7 8 7 8 7 8 7 8 7 8
9 10 9 10 9 10 9 10
11 12 11 12 11 12 11 12
Training manual - SA-TD10006036_GLiner-LCT4_EN.docx KRONES Academy13 Connection assignments – IO modules X2X busPage 82/88
KRONES Glideliner control system with LCT4
Type Glideliner and type Block
Training manual - SA-TD10006036_GLiner-LCT4_EN.docx KRONES Academy13 Connection assignments – IO modules X2X busPage 83/88
KRONES Glideliner control system with LCT4
Type Glideliner and type Block
13.3.1 Glideliner
13.3.2 Block
Training manual - SA-TD10006036_GLiner-LCT4_EN.docx KRONES Academy13 Connection assignments – IO modules X2X busPage 84/88
KRONES Glideliner control system with LCT4
Type Glideliner and type Block
13.4.1 Glideliner
13.4.2 Block
Training manual - SA-TD10006036_GLiner-LCT4_EN.docx KRONES Academy13 Connection assignments – IO modules X2X busPage 85/88
KRONES Glideliner control system with LCT4
Type Glideliner and type Block
13.5.1 Glideliner
13.5.2 Block
13.6.1 Glideliner
Training manual - SA-TD10006036_GLiner-LCT4_EN.docx KRONES Academy13 Connection assignments – IO modules X2X busPage 86/88
KRONES Glideliner control system with LCT4
Type Glideliner and type Block
13.6.2 Block
13.7.1 Glideliner
13.7.2 Block
Training manual - SA-TD10006036_GLiner-LCT4_EN.docx KRONES Academy13 Connection assignments – IO modules X2X busPage 87/88
KRONES Glideliner control system with LCT4
Type Glideliner and type Block
Training manual - SA-TD10006036_GLiner-LCT4_EN.docx KRONES Academy13 Connection assignments – IO modules X2X busPage 88/88