‫ﺑﺴﻤﻪ ﺗﻌﺎﻟﯽ‬
‫ﺷﺮﮐﺖ ﺑﺮق ﻣﻨﻄﻘﻪ اي ﺧﺮاﺳﺎن‬
‫ دﻓﺘﺮ ﻓﻨﯽ اﻧﺘﻘﺎل‬- ‫ﻣﻌﺎوﻧﺖ ﺑﻬﺮه ﺑﺮداري‬

7SA61214BB915PA5-V4.6 Setting Table X:Next longest line 55.2


Sbase (MVA) 100 Substation : Aboutaleb X:Next shortest line 7.7
Vbase(kV) 400 Line : Ferdwosi X:Trans at end of line 48.0
Zbase(Ω) 1600 Length ( km ) 32.1 Parallel Line No
R X R0 X0 Primary secondary Zsec/Zprim
Secondary 0.56 5.93 4.77 16.10 CT(A) 2000 1
0.55
Primary 1.027 10.786 8.667 29.275 VT(kV) 400 0.11

RF Prim
Zone1 = 0.8 Zline 25.00 1116 RG/RL for zone Z1 1.31
Zone1B = 1.2 Zline 31.47 1117 XG/XL for zone Z1 0.57
Zone2 = 1.26 Zline 31.79 1118 RG/RL zones Z1B…Z5 1.31
Zone3R= 0.56 Zline 28.00 1119 XG/RL zones Z1B…Z5 0.57
Zone4= 4.56 Zline 49.59 1130A Pole Open Current Threshold 0.05
Zone5+= 5.02 Zline 54.55 1131A Pole Open Voltage Threshold 10.00
Zone5-= 1.50 Zline 54.55 1132A Seal-in Time after ALL closures 0.30
1133A min. time for line open be. SOTF 0.50
Device Configuration 1134 Recognition Of Line Clouser With I or U or ManCl
103 Setting Group Change Option Disabled 1135 Reset Trip Command Pickup Reset
110 Trip mode 1-/3pole 1136 open pole detector w/ measur.
114 Distance Pro. Pickup (Only 7SA612) Z< 1140A CT Saturation Threshold 20.00
120 Power Swing detection Enabled 1150A Seal-in Time after MANUAL closures 0.30
121 85-21 Pilot Protection For Dist. Prot PUTT(Z1B) 1151 Manual CLOSE COMMAND generation * No
122 DTT Direct Transfer Trip Disabled 1152 Manual Closure Impulse after CONTROL None
124 50HS Instantaneous SOTF Enabled 1155 3Pole coupling With Trip
125 Weak Infeed Disabled 1156A Trip with 2Phase faults 3Pole
126 Back-Up O/C TOC IEC
131 Earth Fault O/C TOC IEC .‫ ﻣﺘﻨﺎﺳﺐ ﺑﺎ ﺷﮑﻞ زﯾﺮ ﺗﻨﻈﯿﻢ ﮔﺮدد‬201 ‫* ﮐﺪ‬
132 85-67N Pilot Prot. Gnd. OverCurrent Dir. Comp. Pickup
138 Fault Locator Enabled
140 74C Trip Circuit Supervision Disabled
Power System Data 1
201 CT starpoint * Toward Line
203 Rated Primary Voltage (Kv) 400
204 Rated Secondary Voltage (ph-ph) 110
205 CT Rated Primary Current 2000
206 CT Rated Secondary Current 1
210 V4 Voltage Transformer is Not onnected
211 Matching Ratio Phase-VT to Open-Delta-VT 1.73
215 Matching Ration Vsy1/Vsy2 1.00
220 I4 Current Transformer is Neutral Current.
221 Matching Ration I4 / Iph For CT's 1.00
207 System Starpoint is Solid Earthed
230 Rated Frequency 50
235 Phase Sequence ABC
236 Distance Measurment Unit Km
237 Setting Format For Zero seq.comp RG/RL & XG/XL

238A Earth Fault O/C : setting for 1pole AR all Stages tog.
240A Minimum Trip Command Duration 0.10 sec
241A Maximum close Command Duration 0.10 sec
242 Dead Time for CB test-autoreclosure 0.10sec
Power System Data 2 ‫ﮔﺮوه ﮐﺎرﺷﻨﺎﺳﺎن ﮐﻨﺘﺮل و ﺣﻔﺎﻇﺖ‬
‫ﺗﺎرﯾﺦ‬
1103 Measurment:full scale voltage(100%) 400 ‫ﺣﺮوﻓﯿﺎﻧﯽ‬ ‫ﺗﺎﯾﯿﺪ‬ ‫ﺳﺠﺎدي‬ ‫ﻣﺤﺎﺳﺒﻪ‬
1104 Measurment:full scale current(100%) 2000 1400/10/25
1105 Line angle(Deg) 85
1211 Angle of inc.,dist. charact. (Deg) 85 Rev.No
1107 P,Q op. measured values sign not reversed
1110 x',Line reactance per length unit (Ω/km) 0.185 5
1111 Line length (km) 32.1
Abootaleb-Ferdowsi_-7SA61214BB915PA5-V4.6 2/3
21 Distance Zones(quad.) 1346 X(Z5)-,Reactance for reverse direction (Ω) 8.93
1201 21 Distance protection is On 1361 Operating mode Z6 Inactive
1202 Ph. Current thr. for dist. meas. 0.15 Tele protection for distance protection
1211 Angle of inclination,distance charact. (Deg) 85 2101 85-21 Pilot Protection For Dist. Prot On
1208 Series Comp. Line NO 2102 Type of Line Two Terminals
1232 SOTF Zone with Pick up 2103A Send Prolong. signal (Tele for Dis) 0.1 Sec
1241 R load (Ø-E) 29 2112A DIS. Transiant block by EF NO
1242 ϕ load (Ø-E 37 50HS Instantaneous SOTF
1243 R load (Ø-Ø) 29 2401 50HS InstantaneousSOTF-O/C ON
1244 ϕ load (Ø-Ø) 37 2404 50HS SOTF-O/C Pickup 2
1317A single pole trip for faults in Z2 NO Backup Over Current
1357 Z1B enabled Before 1AR NO 2601 Operation Mode With VT Loss
1203 3I0 threshold for neutral curr. pickup 0.15 2080 SOTF Time Delay 0.0
1204 3U0 threshold zero seq. Vol. pickup 3.00 Backup Over Current I>>
1207A 3I0 Pickup Stab. 0.10 2610 Iph>> 1.50
1209A criterion of earth fault recognition 3I0> OR 3U0> 2611 T Iph>> 1.5 Sec
1221A Loop selection with 2Ph-E faults Only ϕ-ϕ loops 2612 3I0>> 0.15
1210 Condition for zone timer start W Dis. Pickup 2613 T 3I0>> 1.5 Sec
1305 T1-1-phase,delay for single phase faults 0 2614 Inst. Trip vias B.I. NO
1306 T1-multi-phase,delay for multi phase faults 0 2615 inst. Trip after SOTF. NO
1315 T2-1-phase,delay for single phase faults 0.3 2620 50B2 Pickup oo A
1316 T2-multi-phase,delay for multi phase faults 0.3 2622 50NB2 Pickup oo A
1325 T3 delay 0.9 2640 51B Pickup oo A
1335 T4 delay 0.6 2650 51NB Pickup oo A
1345 T5 delay 3 50 STUP Protection *
1355 T1B-multi-phase,delay for multi phase faults 0 2630 50 STUB pickup 1.20
1356 T1B-multi-phase,delay for multi phase faults 0 2631 50 STUB Delay 0.10
21 Distance Zones(quad.) 2632 50 N STUB Pickup 0.50
1301 Operating mode Z1 Forward 2633 50 N STUB Delay 0.10
1302 R(Z1),Resistance for ph-ph-faults (Ω) 13.75 2634 Inst. Trip Via Pilo Pro. NO
1303 X(Z1),Reactance (Ω) 4.75 2635 Inst. Mode afetr SOTF NO
1304 RG(Z1),Resistance for ph-gnd-faults 13.75 measurement supervision setup
1305 T1-1-phase,delay for single phase faults 0 2901 Measurement Supervision ON
1306 T1-multi-phase,delay for multi phase faults 0 2902A Voltage Threshold for Bal. moni. 50
1307 Zone reduction angle (load comp.) (Deg) 10 2903A Bal. factor for Voltage moni. 0.75
1351 Operating Mode Z1B (overreach zone) Forward 2904A Current Threshold for Bal. moni. 0.1
1352 R(Z1B),Resistance for ph-ph-faults (Ω) 17.31 2905A Bal. factor for Current moni 0.5
1353 X(Z1B),Reactance (Ω) 7.12 2906A Sum. Current moni threshold 0.1
1354 RG(Z1B),Resistance for ph-gnd-faults 17.31 2907A Sum. Current moni factor 0.1
1355 T1B-1Phase,delay for single ph. Faults 0.0 2908A T Bal. factor for Voltage moni 5sec
1356 T1B-multi-Ph,delay for multi ph. Faults 0.0 2909A T Current balance monitor 5sec
1357 Z1B enabled before 1st AR (int. or ext.) No 2910 Fuse Failure Monitor ON
1311 Operating mode Z2 Forward 2911A Minimum Voltage Threshold U> 15
1312 R(Z2),Resistance for ph-ph-faults (Ω) 17.49 2912A Maximum Current Threshold I< 0.1
1313 X(Z2),Reactance (Ω) 7.47 2913A Max. Voltage Threshold U< (3phase) 5
1314 RG(Z2),Resistance for ph-gnd-faults (Ω) 17.49 2914A Delta Current Threshold (3phase) 0.1
1315 T2-1-phase,delay for single phase faults 0.3 2915 Voltage Failure Supervision w/CURR.SUP
1316 T2-multi-phase,delay for multi phase faults 0.3 2916A Delay Voltage Failure Supervision 3
1317A Single Pole Trip For Faults in Z2 No 2921 Fuse Failure Monitor 0
1321 Operating mode Z3 Reverse 2941 Limit setting PhiA 200
1322 R(Z3),Resistance for ph-ph-faults (Ω) 15.40 2942 Limit setting PhiB 340
1323 X(Z3),Reactance (Ω) 3.30 2943 Minimum value I1> 0.05
1324 RG(Z3),Resistance for ph-gnd-faults (Ω) 15.40 2944 Minimum value U1> 45V
1325 T3 delay 0.9 Earth fault Overcurrent
1331 Operating mode Z4 Forward 3101 Earth fault overcurrent Function ON
1332 R(Z4),Resistance for ph-ph-faults (Ω) 27.28 3102 Block E/F for Dis. Pro. every Pickup
1333 X(Z4),Reactance (Ω) 27.05 3174 Block E/F for Dis. Pro. Pickup each Zone
1334 RG(Z4),Resistance for ph-gnd-faults (Ω) 27.28 3103 Block E/F for 1Pole Dead time YES
1335 T4 delay 0.6 3104A Stab. Slop with Iphase 10%
1341 Operating mode Z5 Non dir. 3105 3I0 thr. For Pilot Pro. 0.15
1342 R(Z5),Resistance for ph-ph-faults (Ω) 30.00 3109 single pole trip for EF pro. NO
1343 X(Z5)+,Reactance for forward direction (Ω) 29.76 3170 2nd harmonic ratio for inrush restraint 15%
1344 RG(Z5),Resistance for ph-gnd-faults (Ω) 30.00 3171 Max.current overriding inrush restraint 1.22 A
1345 T5 delay;(X(Z5)>X(Trans at end of line)=3;else=1.6) 3 3172 inst. Mode after SOTF pickup (non dir.)
Note: Impedances are presented in secondary 3173 Trip time delay after SOTF 0
.‫ را ﻓﻌﺎل ﮐﻨﺪ‬STUB ‫ ﺳﮑﺴﯿﻮﻧﺮ ﺳﺮﺧﻂ ﻓﺎﻧﮑﺸﻦ‬NC ‫* ﮐﻨﺘﺎﮐﺖ‬
Abootaleb-Ferdowsi_-7SA61214BB915PA5-V4.6 3/3
68 Power Swing Detection Fault Locator
2002 Power Swing Operation mode All zones BLK 3802 START TRIP
2006 68T Power Swing Trip no 3806 Load compensation NO
2007 68 Trip delay sfter Power Swing Blocking 0.08 Fault Recording
Group EF Overcurrent: 3I0 INV.Time 402A WaveFORM Capture Save With Pickup

3110 Operation Mode Inactive 403A Scope of Waveform Data Fault event
3120 Operation Mode Inactive 410 Max. length of a Waveform Capture Re. 2
3130 Operation Mode Inactive 411 Captured Waveform Prior to Trigger 0.1
3140 Operation Mode Forward 412 Captured Waveform after Event 0.1
3141 3I0p Pickup ‫ﻣﻄﺎﺑﻖ ﺗﻨﻈﯿﻤﺎت ﺟﺮﯾﺎﻧﯽ‬ 413 Capture Time via Binary Input 1
3143 3I0p Time Dial ‫ﻣﻄﺎﺑﻖ ﺗﻨﻈﯿﻤﺎت ﺟﺮﯾﺎﻧﯽ‬
3147 Additional Time Delay 0
3148 Instant. trip via pilot prot.BI YES
3149 3I0p SOTF Trip NO
3150 Inrush blocking YES
3151 IEC Curve N.I
3160 Polarization with U0+IY
3162A ALPHA, Lower angle for forward dir. 320
3163A BETA, upper angle for forward dir. 140
3164 min. zero seq. voltage for polarizing 3
Tele protection for DEF
3201 85-67N Pilot Prot. For Dir.G. O/C ON
3202 Line Configuration Two Terminals

3203A Send Prolong 0.1


3209A Tr. Block duration Ext. fault 0.04
3210A Tr. Block duration Ext. fault 0.05
3212A EF. Tr. BLK. By DIS. NO

35

30

25

20

15

10

0
-40 -30 -20 -10 0 10 20 30 40
-5

Polygonal
-10characteristic

-15