11:19:54 AM Chiller Service Report


Prepared for: GRAND RIVERVIEW HOTEL
Technician: AUDA ENGINEERING SDN BHD
Chiller Name: CHILLER NO.1
Model Number: RTHDCD3UXE0XAG2A4LB
LG1A2LBLAVXXXEXBXXCD
337DAUTXXXXXXXXXX
Serial Number: G18E01691
Job Name: GRAND RIVERVIEW HOTEL
Work Order Number:
Location: KOTA BHARU
Sales Office Name:
Sales Order Number: 75U321AA
Sales Office Address:
Sales Office Phone Number:
Customer Name:
Customer Address:
Customer Phone Number:

Notes:

Chiller Status
Chiller Modes
Top Level Mode Running Sub Level Mode 4
Sub Level Mode 1 Sub Level Mode 5
Sub Level Mode 2 Sub Level Mode 6
Sub Level Mode 3

Diagnostic Modes
Chiller Mode at Time of Last Diagnostic Chiller Sub Mode at Time of Last
Diagnostic
Chiller Sub Mode at Time of Last Chiller Sub Mode at Time of Last
Diagnostic Diagnostic
Chiller Sub Mode at Time of Last Chiller Sub Mode at Time of Last
Diagnostic Diagnostic
Chiller Sub Mode at Time of Last
Diagnostic

Chiller Service Report Page 1


Chiller
Active Chilled Water Setpoint 45.0 °F Condenser Water Pump Command On
Active Chilled Water Setpoint Source Front Panel Evaporator Entering Water 51.1 °F
Temperature
Condenser Entering Water 84.9 °F Evaporator Leaving Water Temperature 44.7 °F
Temperature
Condenser Leaving Water Temperature 92.8 °F Evaporator Water Flow Status Flow
Condenser Water Flow Status Flow Evaporator Water Pump Command On

Circuit
Condenser Approach Temperature 4.4 °F Evaporator Refrigerant Pressure 39.1 PSIG
Condenser Refrigerant Pressure 118.4 PSIG Evaporator Saturated Rfgt Temp 44.0 °F
Condenser Saturated Rfgt Temp 97.2 °F EXV Position Percent 49.7%
Evaporator Approach Temperature 0.7 °F EXV Position Steps 3159 steps
Evaporator Refrigerant Liquid Level 0.28 in High Pressure Cutout Switch Good

Compressor
Compressor Oil Pressure 111.7 PSIG Oil Loss Level Sensor Wet
Compressor Running Status On Oil Pressure Ratio 0.1
Compressor Running Time 18929:58 Hr:Min Oil Return Gas Drain Solenoid Valve Open
Compressor Starts 361 Oil Return Gas Fill Solenoid Valve Closed
Differential Refrigerant Pressure 79.34 PSID Compressor Discharge Superheat 15.6 °F
Compressor Discharge Temperature 112.9 °F

Motor
Active Current Limit Setpoint 100.0% Starter Motor Current L1 332.0 A
Active Current Limit Setpoint Source Front Panel Starter Motor Current L1 % RLA 87.7%
Average Motor Current 331.0 A Starter Motor Current L2 330.0 A
Average Motor Current % RLA 88.2% Starter Motor Current L2 % RLA 87.9%
Average Phase Voltage 398.0 V Starter Motor Current L3 331.0 A
Maximum Motor Current 88.4% Starter Motor Current L3 % RLA 88.2%
Restart Inhibit Time 00:00 Min:Sec Active Current Limit Proportional Gain 2.0
Starter Input Voltage AB 397.0 V Active Current Limit Integral Time 3 Sec
Starter Input Voltage BC 406.0 V Active RLA State Feedback for Water 1.0
Control
Starter Input Voltage CA 389.0 V

Evaporator
Active Chilled Water Setpoint 45.0 °F Evaporator Refrigerant Liquid Level 0.28 in
Active Chilled Water Setpoint Source Front Panel Evaporator Refrigerant Pressure 39.1 PSIG
Evaporator Approach Temperature 0.7 °F Evaporator Saturated Rfgt Temp 44.0 °F
Evaporator Entering Water 51.1 °F Evaporator Water Flow Status Flow
Temperature
Evaporator Leaving Water Temperature 44.7 °F

Condenser

Chiller Service Report Page 2


Condenser Approach Temperature 4.4 °F Condenser Refrigerant Pressure 118.4 PSIG
Condenser Entering Water 84.9 °F Condenser Saturated Rfgt Temp 97.2 °F
Temperature
Condenser Leaving Water Temperature 92.8 °F Condenser Water Flow Status Flow

Adaptive
Frequency Drive
AFD Output Power 185.6 kW Maximum AFD Frequency 50.0 Hz
Estimated Slide Valve Position 100.0% Minimum AFD Frequency 30.0 Hz
Frequency Command 42.9 Hz

Chiller Setpoints
Chiller Setpoints
Front Panel Chilled Water Setpoint 45.0 °F Low Evap Leaving Water Temp Cutout 36.0 °F
Front Panel Current Limit Setpoint 100.0% Low Refrigerant Temperature Cutout 28.6 °F
Differential to Start 5.0 °F Condenser High Refrigerant Pressure 90.0%
Setting
Differential to Stop 2.0 °F High Evaporator Water Temp Cutout 105.0 °F
Setpoint Source Front Panel Restart Inhibit Free Starts 3
Power-Up Start Delay 0 Sec Restart Inhibit Start To Start Time 10 Min
Evaporator Water Pump Off Delay 1 Min Restart Inhibit Diagnostic Enable
Condenser Pump Prestart Time 0 Min Local Atmospheric Pressure 14.7 PSIA
Design Delta Temperature 10.0 °F Head relief request filter time 10 Min

Feature Settings
Chilled Water Reset Type Disable Capacity Control Softload Time 900 Sec
Return Reset Ratio 50.0% Current Limit Control Softload Time 600 Sec
Return Start Reset 10.0 °F Current Limit Softload Start Point 60.0%
Return Maximum Reset 5.0 °F Phase Unbalance Limit Protection Enable
Outdoor Reset Ratio 10.0% Over/Under Voltage Protection Enable
Outdoor Start Reset 90.0 °F Condenser Low Flow Ignore Disable
Outdoor Maximum Reset 5.0 °F Condenser Low Flow Ignore DP Setting 33.98 PSID

Level 4 Gains
Chilled Water Control Gain Kp 27.0 Start Sequence Type Normal
Chilled Water Control Gain Ti 40 Sec AFD Output Power Calibration 0.0 kW
Chilled water control rate (Td) 0 Sec Current Limit Slide Valve Loading 35.0
Clamp Tic
Liquid Level Control Kp 0.6 RLA State Feedback for Water Control 4.0
Liquid Level Control Ti 30 Sec Slide Valve Maximum Tic 100.0
Liquid Level Control Rate (Td) 1.2 Oil Return Gas Pump Dwell Time 0 Sec
Setting
Liquid Level Setpoint Bias 0.00 in Compressor Starts 361
Current Limit Proportional gain 8.0 Compressor Running Time 18929:58 Hr:Min
Current Limit Integral Time 60 Sec Minimum Frequency At Startup And 50.0 Hz

Chiller Service Report Page 3


Shutdown
LERTC Integral Threshold 450.0 Unit StartUp Time 15 Sec
Oil Loss Avoidance Proportional Gain 20.0 AFD Low Discharge Superheat Limit 2.5
Proportional Gain
Oil Loss Avoidance Integral Time 5 Sec AFD Low Discharge Superheat Limit 30 Sec
Integral Time
Slide Valve Max Load Tics Setpoint 7 AFD Low Discharge Superheat Limit 12.0 °F
Setpoint
Oil Loss Avoidance Setpoint 1.0

Device List
Compressor Discharge Temperature Sensor Evaporator Refrigerant Liquid Level Sensor
Condenser Entering Water Temperature Sensor Evaporator Refrigerant Pressure Transducer
Condenser Leaving Water Temperature Sensor External Auto/Stop and Emergency Stop Inputs
Condenser Refrigerant Pressure Transducer Ice Building Status Output and Master Oil Line Solenoid Valve
Condenser and Chilled Water Flow Switch/Interlock Oil Loss Level Sensor and Hot Water Mode Inputs
Condenser and Chilled Water Pump Starters Oil Pressure Transducer
Drive Speed Command Output and Drive Motor Power Input Oil Return Gas Pump Drain and Fill Solenoid Valve and Coil
Dual Port EXV Actuator 1 SSS/AFD Fault and High Pressure Cutout Switch
Dual Port EXV Actuator 2 Slide Valve Unload and Load Control Solenoid Valve and Coil
Evaporator Entering Water Temperature Sensor Starter Module
Evaporator Leaving Water Temperature Sensor

Alarms and Events


Date Time Active / Description Target Severity Persistence
Historic
01/17/2024 23:23 Historic Evaporator Water Flow Lost Chiller Immediate Nonlatching
Shutdown
12/01/2023 13:10 Historic Evaporator Water Flow Lost Chiller Immediate Nonlatching
Shutdown
11/12/2023 09:06 Historic Evaporator Water Flow Lost Chiller Immediate Nonlatching
Shutdown
11/09/2023 03:37 Historic Evaporator Water Flow Lost Chiller Immediate Nonlatching
Shutdown
10/19/2023 03:55 Historic Evaporator Water Flow Lost Chiller Immediate Nonlatching
Shutdown
10/15/2023 03:03 Historic Evaporator Water Flow Lost Chiller Immediate Nonlatching
Shutdown
09/22/2023 05:35 Historic Evaporator Water Flow Lost Chiller Immediate Nonlatching
Shutdown
09/10/2023 09:35 Historic Evaporator Water Flow Lost Chiller Immediate Nonlatching
Shutdown
08/20/2023 08:41 Historic Evaporator Water Flow Lost Chiller Immediate Nonlatching
Shutdown
08/16/2023 02:36 Historic Condenser Water Flow Overdue Chiller Normal Nonlatching
Shutdown
08/16/2023 02:10 Historic Power Loss Chiller Immediate Nonlatching
Shutdown
08/14/2023 15:53 Historic Evaporator Water Flow Lost Chiller Immediate Nonlatching
Shutdown
07/14/2023 17:19 Historic MP: Reset Has Occurred Platform Warning Nonlatching
07/12/2023 14:16 Historic MP: Reset Has Occurred Platform Warning Nonlatching

Chiller Service Report Page 4


07/12/2023 14:14 Historic MP: Reset Has Occurred Platform Warning Nonlatching
07/12/2023 20:01 Historic MP: Reset Has Occurred Platform Warning Nonlatching
06/30/2023 20:11 Historic MP: Reset Has Occurred Platform Warning Nonlatching
06/28/2023 20:55 Historic MP: Reset Has Occurred Platform Warning Nonlatching
06/23/2023 10:04 Historic Evaporator Water Flow Lost Chiller Immediate Nonlatching
Shutdown
06/16/2023 10:45 Historic Evaporator Water Flow Lost Chiller Immediate Nonlatching
Shutdown
06/15/2023 00:25 Historic Power Loss Chiller Immediate Nonlatching
Shutdown
05/14/2023 07:04 Historic Evaporator Water Flow Lost Chiller Immediate Nonlatching
Shutdown
03/31/2023 10:16 Historic Evaporator Water Flow Lost Chiller Immediate Nonlatching
Shutdown
03/20/2023 10:07 Historic Evaporator Water Flow Lost Chiller Immediate Nonlatching
Shutdown
03/18/2023 10:16 Historic Evaporator Water Flow Lost Chiller Immediate Nonlatching
Shutdown
03/16/2023 12:25 Historic Evaporator Water Flow Lost Chiller Immediate Nonlatching
Shutdown
03/14/2023 14:07 Historic Evaporator Water Flow Lost Chiller Immediate Nonlatching
Shutdown
03/13/2023 13:13 Historic Evaporator Water Flow Lost Chiller Immediate Nonlatching
Shutdown
03/12/2023 12:31 Historic Evaporator Water Flow Lost Chiller Immediate Nonlatching
Shutdown
03/11/2023 12:37 Historic Evaporator Water Flow Lost Chiller Immediate Nonlatching
Shutdown
03/10/2023 10:27 Historic Evaporator Water Flow Lost Chiller Immediate Nonlatching
Shutdown
02/24/2023 12:25 Historic Evaporator Water Flow Lost Chiller Immediate Nonlatching
Shutdown
02/22/2023 12:11 Historic Evaporator Water Flow Lost Chiller Immediate Nonlatching
Shutdown
02/16/2023 12:44 Historic Evaporator Water Flow Lost Chiller Immediate Nonlatching
Shutdown
02/15/2023 19:08 Historic Power Loss Chiller Immediate Nonlatching
Shutdown
02/13/2023 12:23 Historic Evaporator Water Flow Lost Chiller Immediate Nonlatching
Shutdown
02/10/2023 10:26 Historic Evaporator Water Flow Lost Chiller Immediate Nonlatching
Shutdown
01/30/2023 12:10 Historic Evaporator Water Flow Lost Chiller Immediate Nonlatching
Shutdown
01/27/2023 09:37 Historic Evaporator Water Flow Lost Chiller Immediate Nonlatching
Shutdown
01/18/2023 18:31 Historic Evaporator Water Flow Overdue Chiller Normal Nonlatching
Shutdown
01/18/2023 09:11 Historic Evaporator Water Flow Overdue Chiller Normal Nonlatching
Shutdown
01/18/2023 08:51 Historic Power Loss Chiller Immediate Nonlatching
Shutdown
01/15/2023 10:12 Historic Evaporator Water Flow Lost Chiller Immediate Nonlatching
Shutdown
01/14/2023 09:23 Historic Evaporator Water Flow Lost Chiller Immediate Nonlatching
Shutdown
01/06/2023 10:13 Historic Evaporator Water Flow Lost Chiller Immediate Nonlatching

Chiller Service Report Page 5


Shutdown
12/30/2022 10:20 Historic Evaporator Water Flow Lost Chiller Immediate Nonlatching
Shutdown
11/17/2022 11:34 Historic Evaporator Water Flow Lost Chiller Immediate Nonlatching
Shutdown
11/11/2022 06:21 Historic AFD Drive Fault Chiller Immediate Nonlatching
Shutdown
11/11/2022 06:20 Historic AFD Drive Fault Chiller Immediate Nonlatching
Shutdown
11/01/2022 11:57 Historic Power Loss Chiller Immediate Nonlatching
Shutdown
10/19/2022 23:55 Historic Power Loss Chiller Immediate Nonlatching
Shutdown
10/12/2022 23:19 Historic MP: Reset Has Occurred Platform Warning Nonlatching
10/07/2022 12:58 Historic Evaporator Water Flow Lost Chiller Immediate Nonlatching
Shutdown
10/06/2022 13:26 Historic Evaporator Water Flow Lost Chiller Immediate Nonlatching
Shutdown
09/27/2022 02:07 Historic Condenser Water Flow Overdue Chiller Normal Nonlatching
Shutdown
09/27/2022 01:43 Historic Condenser Water Flow Lost Chiller Immediate Nonlatching
Shutdown
08/19/2022 11:12 Historic Evaporator Water Flow Lost Chiller Immediate Nonlatching
Shutdown
08/15/2022 16:55 Historic MP: Reset Has Occurred Platform Warning Nonlatching
08/09/2022 04:29 Historic MP: Reset Has Occurred Platform Warning Nonlatching
08/09/2022 04:15 Historic Evaporator Water Flow Lost Chiller Immediate Nonlatching
Shutdown
07/09/2022 11:16 Historic Evaporator Water Flow Lost Chiller Immediate Nonlatching
Shutdown
06/02/2022 10:21 Historic Evaporator Water Flow Lost Chiller Immediate Nonlatching
Shutdown
05/31/2022 11:18 Historic Evaporator Water Flow Lost Chiller Immediate Nonlatching
Shutdown
05/23/2022 10:16 Historic MP: Reset Has Occurred Platform Warning Nonlatching
04/15/2022 10:03 Historic Evaporator Water Flow Lost Chiller Immediate Nonlatching
Shutdown
04/01/2022 19:38 Historic MP: Reset Has Occurred Platform Warning Nonlatching
03/31/2022 21:20 Historic MP: Reset Has Occurred Platform Warning Nonlatching
02/19/2022 10:09 Historic Evaporator Water Flow Lost Chiller Immediate Nonlatching
Shutdown
02/05/2022 09:55 Historic Evaporator Water Flow Lost Chiller Immediate Nonlatching
Shutdown
01/24/2022 10:02 Historic Evaporator Water Flow Lost Chiller Immediate Nonlatching
Shutdown
01/08/2022 09:33 Historic Evaporator Water Flow Lost Chiller Immediate Nonlatching
Shutdown
01/03/2022 09:17 Historic Evaporator Water Flow Lost Chiller Immediate Nonlatching
Shutdown
12/27/2021 09:13 Historic Evaporator Water Flow Lost Chiller Immediate Nonlatching
Shutdown
12/24/2021 09:32 Historic Evaporator Water Flow Lost Chiller Immediate Nonlatching
Shutdown
12/23/2021 11:33 Historic Evaporator Water Flow Lost Chiller Immediate Nonlatching
Shutdown
12/21/2021 10:50 Historic Evaporator Water Flow Lost Chiller Immediate Nonlatching
Shutdown

Chiller Service Report Page 6


12/18/2021 19:51 Historic Evaporator Water Flow Lost Chiller Immediate Nonlatching
Shutdown
12/17/2021 09:37 Historic Evaporator Water Flow Lost Chiller Immediate Nonlatching
Shutdown
12/15/2021 10:38 Historic Evaporator Water Flow Lost Chiller Immediate Nonlatching
Shutdown
12/11/2021 09:17 Historic Evaporator Water Flow Lost Chiller Immediate Nonlatching
Shutdown
11/26/2021 09:32 Historic Evaporator Water Flow Lost Chiller Immediate Nonlatching
Shutdown
11/20/2021 09:26 Historic Evaporator Water Flow Lost Chiller Immediate Nonlatching
Shutdown
11/16/2021 10:36 Historic Evaporator Water Flow Lost Chiller Immediate Nonlatching
Shutdown
11/12/2021 10:59 Historic Evaporator Water Flow Lost Chiller Immediate Nonlatching
Shutdown
10/26/2021 22:09 Historic Evaporator Water Flow Lost Chiller Immediate Nonlatching
Shutdown
10/26/2021 11:49 Historic Evaporator Water Flow Lost Chiller Immediate Nonlatching
Shutdown
10/24/2021 11:29 Historic Evaporator Water Flow Lost Chiller Immediate Nonlatching
Shutdown
10/23/2021 10:47 Historic Evaporator Water Flow Lost Chiller Immediate Nonlatching
Shutdown
10/21/2021 10:36 Historic Evaporator Water Flow Lost Chiller Immediate Nonlatching
Shutdown
10/14/2021 10:29 Historic Evaporator Water Flow Lost Chiller Immediate Nonlatching
Shutdown
10/12/2021 11:38 Historic Evaporator Water Flow Lost Chiller Immediate Nonlatching
Shutdown
10/07/2021 10:23 Historic Evaporator Water Flow Lost Chiller Immediate Nonlatching
Shutdown
10/06/2021 16:38 Historic Evaporator Water Flow Lost Chiller Immediate Nonlatching
Shutdown
10/02/2021 10:05 Historic Evaporator Water Flow Lost Chiller Immediate Nonlatching
Shutdown
09/30/2021 08:47 Historic Evaporator Water Flow Lost Chiller Immediate Nonlatching
Shutdown
09/28/2021 08:54 Historic Evaporator Water Flow Lost Chiller Immediate Nonlatching
Shutdown
09/28/2021 05:43 Historic AFD Drive Fault Chiller Immediate Nonlatching
Shutdown
09/28/2021 05:43 Historic AFD Drive Fault Chiller Immediate Nonlatching
Shutdown
09/18/2021 15:24 Historic Evaporator Water Flow Lost Chiller Immediate Nonlatching
Shutdown
09/17/2021 15:12 Historic Evaporator Water Flow Lost Chiller Immediate Nonlatching
Shutdown

Tracer TU Configuration PC Environment


Version Version - 11.2.23 Operating System Microsoft Windows 10
Pro
System Architecture x64
Operating System Version 6.2

TU Display Units Date and Time

Chiller Service Report Page 7


Unit System Inch-Pound Time Format 12-Hour
Pressure Units psig Date Format MMDDYYYY
Date Separator Slash (/)
Date and Time 02/11/2024 11:20 AM

Protocol
Protocol Not Installed

Chiller Configuration
Controller
Connected To Local USB Build Part Number 6200-0624-8.01
Firmware Version 8.01 Boot Part Number 6200-0446-1.00
Application Part Number 6200-0623-7.10 Unit Sales Order Number 75U321AA
Hardware Serial Number 1181600009 Unit Model Number RTHDCD3UXE
0XAG2A4LBL
G1A2LBLAVX
XXEXBXXCD3
37DAUTXXXX
XXXXXX
Hardware Part Number X13651144-01 Unit Serial Number G18E01691

Signed:
Date:

Copyright © 2021 Trane, Inc. All rights reserved. Trane, the Trane logo and Tracer TU are either registered trademarks or
trademarks of Trane in the United States and/or other countries.
Protected by U.S. Patents.

Chiller Service Report Page 8