Professional Documents
Culture Documents
See 1302
See 1302
• A grid is eithe r 3- phase single circuit or 3 phase two circuit transmission line,
running throughout the length and breadth of a country or a state
• The ratings and the impedances of the components are also marked on the single
line diagram
ActualValu e
% PerUnitVal ue *100
BaseValue
Table: 1.1
Single line Diagram
• The various components of powe r system components of Powe r system like
alternators, motors, transformers etc., have their voltage, power, curre nt and
impedance ratings in KV,KVA,KA and
• It will be conve nient for analysis of powe r system if the voltage, powe r, current
and impe dance ratings of components of powe r system are expressed with
reference to a common value called base value
Figure:1.1
• Hence the analysis purpose a base value is chosen for voltage, powe r, current
and impe dance
• The power system requires the base values of four quantities and they are
Voltage, Powe r, Curre nt and Impedance.
• Selection of base values for any two of the m determines the base values of the
re maining two
KVb=Base voltage in KV
Zb=Base impedance in
KVAb
Ib inamps
KV b
KVb *1000
Zb in
Ib
Zb
KVAb KVA b MVAb
KV b 1000
• The same formula holds good for Three phase system also both for star
connected and Delta connected
• In 3 phase system, the KVb is a line value and MVAb is a 3 phase MVA
1. A three Phase generator with rating 1000KVA, 33KV has its armature
resistance and synchronous reactance as 20 /Phase and 70 /Phase. Calculate P.U.
impedance of the generator.
Solution:
KVb=33KV
KVAb=1000KVA
KVb 2 332
Zb 1089
MVAb 1000
1000
Z=(20+j70) / Phase
2. A three phase, / transforme r with rating 100KVA, 11KV/400V has its primary and
secondary leakage reactance as 12 /Phase and 0.05 /Phase respectively. Calculate the
p.u reactance of the transforme r.
Solution:
Case(i)
High Voltage winding ( Primary) is chosen as base values.
KVb=11KV
KVAb=100KVA
KVb 2 112
Zb 1210
MVAb 100
1000
400
K 0.0364
11000
X2 0.05
X 01 X 1 X 2' X 1 12 12 37.737 49.737 / Phase
K 2
0.03642
Xpu =Total leakage reactance/ Base impedance
X 01 49,737
0.0411 p.u.
Zb 1210
Case(ii)
KVb 2 0.4
2
Zb 1.6
MVAb 100
1000
Transforme r line voltage ratio,
400
K 0.0364
11000
X 02 0.0659
0.0411 p.u.
Zb 1.6
4. The way in which the transformers are connected in a 3 phase circuits (/) does
not affect the per unit impedances of the equivalent circuit, although the
transforme r connection does determine the relation between the voltage bases on
the two sides of the transformer
Figure 1.2
Figure 1.3
Equivalent Circuit of Synchronous motor
Figure 1.4
Figure 1.5
Equivalent Circuit of Transformer
Figure 1.6
E2 N 2 V2 I1
K
E1 N1 V1 I 2
R
R01 R1 R 2' R1 22
K
X2
X 01 X 1 X 2' X 1
K2
Figure 1.7
S= Slip
1
Rr' 1
S = Resistance representing load
Figure :1.8
Figure:1.9
P2 Q2 P2 Q2
I | I |
|V | |V |
Where
Q
tan 1
P
Constant Impedance representation
| V |2
Z
P jQ
P jQ
Y
| V |2
P2 Q2
I IL | I L |
3 | VL |
Where
Q
tan 1
P
P2 Q2 P2 Q2
IL | I L | I | I |
3 | VL | 3 | VL |
Where Where
Q Q
tan 1 tan 1
P P
3 |V L| 2
Z
P jQ
P jQ
Y
3 | VL | 2
3. A 50Kw, three phase, connected load is fed by a 200 KVA transforme r with
voltage rating 11KV/400V through a feeder. The length of the feeder is 0.5km and the
impedance of the feeder is 0.1+j0.2 /km. If the load p.f is 0.8, Calculate the p.u
impedance of the load and feeder.
Solution:
Choose secondary winding rating of transforme r as base values
Kvb=400/1000 = 0.4KV
KVAb=200KVA
KVb 2 (0.4) 2
Zb 0.8
MVAb 200
1000
Z fed (0.1 j 0.2) * 0.5 0.05 j 0.1 / Phase
P 50
Q * sin * 0.6 37.5KVAR
cos 0.8
Load impedance/Phase
| V |2 400 2
ZL 2.5636.87 2.048 j1.536W / Phase
P jQ (50 j37.5) *10 3
Z L 2.048 j1.536
Z L , Pu 2.56 j1.92 pu
Zb 0.8
Impedance Diagram
• The impedance diagram is the equivalent circuit of Powe r system in which the
various components of powe r system are represented by their approximate or
simplified equivalent circuits
• It is used for load flow studies
Approximations made in Impedance Diagram
• The neutral reactances are neglected
• The shunt branches in equivalent circuit of Transformers & induction motor are
neglected
Reactance Diagram
• It is a simplified equivalent circuit of powe r system in which the various
components are represented by their reactances
• It can be obtained from impe dance diagram if all the resistive components are
neglected
• It is used for fault calculations
Figure:1.10
Impedance Diagram
Figure 1.11
Power System Analysis – SEE1302 Page 16
SCHOOL OF ELECTRICAL AND ELECTRONICS
DEPARTMENT OF ELECTRICAL AND ELECTRONICS
Reactance Diagram
Figure:1.12
4. A 300 MVA, 20KV, 3 generator has a subtransient reactance of 20%. The generator
supplies 2 synchronous motors through a 64Km transmission line having transforme rs
at both ends as as shown in Fig. In this, T1 is a 3 transformer and T2 is made of 3 single
phase transformer of rating 100 MVA, 127/13.2KV, 10% reactance. Series reactance of
the trans mission line is 0.5/Km. Draw the reactance diagram with all the reactances
marked in p.u. Select the generator ratings as base values.
Figure: 1.13
Solution:
MVAb,new=300MVA
KVb,ne w=20KV
Reactance of Generator G
Since the generator rating and the base values are same, the
generator p.u. reactance does not change
XG,pu,new = 20% = 0.2p.u.
Reactance of Transformer T1
2
KVbT1,old MVA b,new
X T 1, pu,new X T 1 pu,old * *
MVA
KVb,new bT1,old
2
20 300
0.1* * 0.0857
20 350
Zb
Kvb , new2
230 2
176.33
MVAb 300
32
X TL, p.u 0.1815 p.u
176.33
Reactance of Transformer T2
Voltage ratio of line voltage of 3 transformer bank =((3*127)/13.2) = (220/13.2)KV
2
KVbT 2,old MVA b,new
X T 2, pu,new X T 2 pu,old * *
MVA
KVb,new bT 2 ,old
2
13.2 300
0.1 * * 0.0915 p.u
13.8 3 *100
Reactance of Motor M 1
2
KVbM1,old MVA b,new
X M 1, pu,new X M 1 pu,old * *
MVA
KVb,new bM 1,old
2
13.2 300
0.2 * * 0.0915 p.u
13.8 200
Reactance of Motor M 2
2
KV MVAb,new
X M 2, pu,new X M 2 pu,old * bM 2,old *
KVb , new MVAbM 2 ,old
2
13.2 300
0.2 * * 0.549 p.u
13.8 100
Figure :1.14
5.Draw the reactance diagram for the powe r system shown in fig. Neglect resistance and
use a base of 100 MVA, 220KV in 50 line. The ratings of the generator, motor and
transforme r are given below.
Figure:1.15
Generator: 40MVA,25KV,X’’=20%
Synchronous motor:50MVA,11KV,X’’=30%
- Transformer : 40MVA,33/220KV,X=15%
Solution:
MVAb,new=100MVA
KVb,ne w=220KV
Reactance of Trans mission line (TL)
Zb
Kvb , new
2
2202
484
MVAb 100
50
X TL, p.u 0.1033 p.u
484
Reactance of Transformer T1
Base KV on LT side of T1 = Base KV on HT side of T1 * ( LT voltage
rating of T1 / HT voltage rating of T1 )
= 220 *(33/220) = 33KV
Kvb,new=33KV
2
KV MVAb,new
X T 2, pu,new X T 2 pu,old * bT 2,old *
KV b , new MVAbT 2,old
2
11 100
0.15 * * 0.5 p.u
11 30
2
KV MVAb,new
X M , pu,new X M pu,old * bM ,old *
KV b , new MVAbM , old
2
11 100
0.3 * * 0.6 p.u
11 50
Figure: 1.16
6. A 15MVA, 8.5KV, 3- Phase generator has a substransient reactance of 20%. It is
connected through a - transformer to a high voltage trans mission line having a total
series reactance of 70 .The load end of the line has - step down transforme r. Both
transforme r banks are composed of single Phase transforme rs connected for 3-Phase
operation. Each of three transforme rs composing three phase bank is rated 6667KVA,
10/100KV, with a reactance of 10%. The load represented as impedance, is drawing
10MVA at 12.5KV and 0.8pf lagging. Draw the single line diagram of the powe r
network. Choose a base of 10MVA,12.5KV in the load circuit and determine the
reactance diagram. Determine also the voltage at the terminals of the generator.
Solution:
Figure :1.17
MVAb,new=10MVA
KVb,ne w=12.5KV
MVAb,old =20MVA
2
KV MVAb,new
X T 2, pu,new X T 2 pu,old * bT 2,old *
KV b , new MVAbT 2 , old
2
17.32 10
0.1* * 0.096 p.u
12.5 20
Reactance of Trans mission line
Base KV on HT side of T2 = Base KV on LT side of T2 * ( HT voltage
rating of T2 / LT voltage rating of T2 )
= 12.5 *(173.2/17.32) = 125KV
Kvb,new=125KV
Zb
Kvb , new2
1252
1562.5
MVAb 10
70
X TL, p.u 0.0448 p.u
1562.5
Reactance of Transformer T1
Voltage ratio of line voltage of transformer
T1=(10KV/100*3KV) = (10KV/173.2KV)
MVAb,old =20MVA
2
KV MVAb,new
X T 1, pu,new X T 1 pu,old * bT1,old *
KV b , new MVAbT1,old
2
173.2 10
0.1* * 0.096 p.u
125 20
Reactance of Generator
Base KV on LT side of T1 = Base KV on HT side of T1 * ( LT voltage
rating of T1 / HT voltage rating of T1 )
= 125 *(10/173.2) = 7.217KV
Kvb,new=7.217KV
2
KV MVAb,new
X G , pu,new X G pu,old * bG,old *
KV b , new MVAbG , old
2
8.5 10
0.2 * * 0.185 p.u
7.217 15
Load
This can be represented as constant current load
p.f of load = 0.8lag
p.f angle = -cos -1 0.8=-36.87
p.u value of load (Powe r) = Actual load MVA/ Base value of MVA
= 10- 36.87 /10 = 1 - 36.87 p.u
p.u value of load voltage = Actual load voltage/Base voltage
= 12.5KV/12.5KV = 1.0 p.u
Figure:1.18
Terminal voltage of the Generator
Vt=V+I(j0.096+j0.096+j0.0448)
= 1.0+1 - 36.87 * 0.236890
=1.0+0.2368+j0.1894
=1.1421+j0.1894
=1.15779.4 p.u
• The diagonal elements of bus admittance matrix are called self admittances of
the buses
• Off – diagonal elements are called mutual admittances of the buses
Formula for determining Ybus after eliminating the last row and Column
Y jnY nk
Y jk ,new Y jk ,old
Y nn
j=1,2,3…(n-1) ; K=1,2,3……(n-1) ; n= last row and column to be eliminated
Figure: 1.19
Solution: Direct Inspection Method
The Ybus matrix of the network is,
Y jnY nk
Y jk ,new Y jk ,old
Y nn
Power System Analysis – SEE1302 Page 27
SCHOOL OF ELECTRICAL AND ELECTRONICS
DEPARTMENT OF ELECTRICAL AND ELECTRONICS
n =4 ; j=1,2,3 ; K=1,2,3
The bus admittance matrix is symmetrical, Ykj, new = YjK,new
Y24Y 42 (0)(0)
Y22,new Y22,old j1.1 j1.1
Y 44 j 0.9
Y Y (0)( j 0.5)
Y23,new Y23,old 24 43 j 0.6 j 0.6
Y 44 j 0.9
Y31,new Y13,new j 0.622
8. Determine the bus admittance matrix of the system whose reactance diagram is
shown in fig. the currents and admittances are given in p.u. Determine the reduced bus
admittance matrix afte r eliminating node-3
Figure:1.20
Solution:
( j 2 j 2 j1) 0 j2 j1
0 ( j 2 j 4) 0 j2
Ybus
j2 0 ( j 2 j 2 j 5) j5
j1 j2 j5 ( j1 j 5 j 2 j1)
j 5 0 j2 j1
0 j6 0 j 2
Ybus
j2 0 j9 j5
j1 j2 j 5 j 9
For eliminating node 3, the bus admittance matrix is re arranged by interchanging row
3 and then row 4 and then inte rchanging column 3 & column 4.
After interchanging row 3 & row 4 of Ybus matrix,
j 5 0 j2 j1
0 j6 0 j 2
Ybus
j1 j2 j 5 j 9
j2 0 j9 j5
j 5 0 j1 j2
0 j6 j 2 0
Ybus
j1 j 2 j9 j5
j2 0 j 5 j 9
Y jnY nk
Y jk ,new Y jk ,old
Y nn
Y14Y 41 ( j 2)( j 2)
Y11,new Y11,old j5 j 4.556
Y 44 j9
Y14Y 42 ( j 2 * 0)
Y12,new Y12,old 0 0
Y 44 j9
Y Y ( j 2)( j5)
Y13,new Y13,old 14 43 j1 j 2.111
Y 44 j9
Y21,new Y12,new 0
Y24Y 42 (0)(0)
Y22,new Y22,old j6 j6
Y 44 j9
Y32,new Y23,new j 2
j 4.556 0 j 2.111
Ybus 0 j6 j 2
j 2.111 j 2 j 6.222
Table:1.2
Solution:
Ybus (1,1) = 1/(0.01+j0.05) + 1/(0.07+j0.02) + 1/(0.06+j0.14) – j0.01 –
j0.02 – j0.03
= 1/(0.0511.37)+1/(0.073 0.28) +1/(0.152 1.17-
Figure: 1.21
Solution:
0.02 + j0.04 0 0
Z 0 0.0125 + j0.025 0
0 0 0.01 + j0.03
1 1 0 1 0 1
A 0 1 1
A 1 1
T
0
1 0 1 0 1 1
Ybus AT yA
1
(0.02 + j0.04) 0 0
1 0 1 1 1 0
Ybus
1 1 0 0
1
0 0 1 1
(0.0125 + j0.025)
0 1 1 1
1 0 1
0 0
(0.01 + j0.03)
11. For the given system form the admittance matrix by analytical method
Figure:1.22
1 1 0 0
0 1 1 0
^
ElementalN odeIncidce nceMatrix ( A) 0 1 0 1
0 0 1 1
1 0 1 0
1 0 0
1 1 0
Incidcence Matrix ( A) 1 0 1
0 1 1
0 1 0
j 0.2 0 j 0.6 0 0
0 j 0.3 0 j 0.8 0
Z j 0.6 0 j 0.3 0 0
0 j 0.8 0 j 0.5 0
0 0 0 0 j 0.4
Ybus AT yA
1 1
j 0.2 0 0 0
j 0.6
1 1
0 0 0 1 0 0
1 1 1 0 0 j 0.3 j 0.8 1 1 0
1
0 1 0 1 1
1
Ybus 0 0 0 1 0 1
0 0 1 1 0
j 0.6 j 0.3
1 1 0 1 1
0 j 0.8
0
j 0.5
0
0 1 0
0 1
0 0 0
j 0.4
Classification of buses
i. Load bus or PQ bus ( P and Q are specified)
ii. Generator bus or voltage controlled bus or PV bus (P and V Spe cified)
iii. Slack bus or swing bus or reference bus (|V| and are specified)
PQ bus
• A bus is called PQ bus or load bus when real and reactive components of powe r
are specified for the bus.
• In a load bus the voltage is allowed to vary within permissible limits
PV bus or Voltage Controlled bus or Gene rator bus
• A bus is called voltage controlled bus if the magnitude of voltage |V| and real
powe r (P) are specified for it.
• In a voltage controlled bus the magnitude of the voltage is not allowe d to change
Slack bus
• A bus is called s wing bus ( or Slack bus) when the magnitude and phase of bus
voltage are specified for it
• The swing bus is the reference bus for load flow solution and it is required for
accounting for line losses.
• Usually one of the generator bus is selected as the swing bus
Need of Swing bus
• The slack bus is needed to account for transmission line losses
• In a powe r system the total power generated will be equal to sum of powe r
consumed by loads and losses
p 1 n
I p Y pqVq Y ppV p Y V
pq q
q 1 q p 1
Sp=Complex powe r of bus p
Pp=Real powe r of bus p
Qp=Reactive power of bus p
S p Pp jQ p
S p V p I *p
V p I *p Pp jQ p
The load flow problem can be handled more conveniently by use of I p rather than Ip*
(Vp I *p )* ( Pp jQ p )*
V p* I p Pp jQ p
Pp jQ p
Ip
V p*
Pp jQ p
Yp1V1 Yp 2V2 YppV p Y pnVn
V p*
• Iterative methods are used to solve load flow problems
• The reason to use iterative methods is the load (or powe r ) flow equations are
nonlinear algebraic equations and explicit solution is not possible
Iterative Methods
i. Gauss seidel (G-S) method
ii. Newton Raphson (N-R) method
Pp jQ p
Yp1V1 Yp 2V2 YppV p Y pnVn
V p*
p 1 n Pp jQ p
YpqVq YppVp
q 1
Y
q p 1
pq qV
V p*
Pp jQ p p 1 n
YppV p *
Y V
pq q pq q
Y V
V p q 1 q p 1
1 Pp jQ p p 1 n
Vp *
Y V
pq q pq q
Y V
Ypp V p q 1 q p 1
1 Pp jQ p p 1 n
V pk 1 k *
Y V
pq q
k 1
pq q
Y V k
Pp jQ p p 1 n
YpqVq YppV p Y V
pq q
V p* q 1 q p 1
Pp jQ p p 1 n
YpqVq YpqVq
V p* q 1 q p
p 1 n
Pp jQ p V p* Y pqVq Y pqVq
q 1 q p
p 1 n
Ppk 1 jQ pk 1 (V pk ) * Y pqVqk 1 Y pqVqk
q 1 q p
k * p 1 n
Q k 1
p (1) * Im(V p ) Y pqVqk 1 Y pqVqk ----- (2)
q 1 q p
Figure: 2.1
Ypq – series admittances
Y’pq/2- Shunt admittances
'
Y pq
I pq I pq1 I pq2 (V p Vq )Y pq V p
2
'
Y
I pq I pq1 I pq2 (V p Vq )Y pq V p
pq
'
Y pq
S pq Ppq jQ pq V I pq *
p V (V p Vq )Y pq V p
*
p
2
'
Y pq
I qp I qp1 I qp2 (Vq V p )Y pq Vq
2
Complex powe r Injected by bus q in line pq
Y pq'
S qp Pqp jQqp V I *
q qp V (Vq V p )Y pq V p
q
*
2
S pq,loss S pq S qp
Figure:2.2
Algorithm for load flow solution by Gauss seidel method
Step 1: Form Y – bus matrix
Step 2: Assume Vi =Vi(spec)0 at all generator buses
Step 3: Assume Vi =1 0=1+j0 at all load buses
i 1 n
Qik 1 (1) * Im(Vi k )* YijV jk 1 YijV jk
j 1 j i
1 Pi jQi i 1 n
Vi k 1 k *
Yii (Vi )
Y V
ij j
k 1
YijV jk
j 1 j i 1
Step 9: If i is less than numbe r of buses, increment i by 1 and go to step 6
Step 10: Compare two s ucessive iteration values for Vi
If Vi K+1 – Vik < tolerance, go to step 12
Step 11: Update the new voltage as
Vk+1 = Vk +(VK+1 – Vk )
Vk =Vk+1
K=K+1; go to step 5
Step 12: Compute relevant quantities:
Slack bus powe r,
N
S i Pi Qi V * I Vi* YijV j
j 1
Vi Vi* V j* Yijseries
*
| Vi | 2 Yii*
PLoss Pij P ji
QLoss Qij Q ji
Figure:2.3
Table:2.1
Table: 2.2
Z12 =0.05+j0.15p.u Z24 =0.10+j0.30p.u
Z13 =0.10+j0.30p.u Z34 =0.05+j0.15p.u
Z14 =0.20+j0.40p.u
Y12 =1/Z12 = 1/(0.05+j0.15) = 2-j6 Y13 =1/Z13 =1/(0.10+j0.30)=1-j3
Y14 =1/Z14 =1/(0.20+j0.40)=1-j2 Y24 =1/Z24 =1/(0.10+j0.30)=1-j3
Y34 =1/Z34 =1/(0.05+j0.15)=2-j6
Y11 =Y12 +Y13 +Y14 =2-j6+1-j3+1-j2=4-j11
Y22 =Y12 +Y24 =2-j6+1-j3=3-j9
Y33 =Y13 +y34 =1-j3+2-j6=3-j9
Y44 =Y14 +Y24 +Y34 =1-j2+1-j3+2-j6=4-j11
Y12 =Y21 =-Y12 =-(2-j6)=-2+j6
Y13 =Y31 =-Y13 =-(1-j3)=-1+j3
Y14 =Y41 =-Y14 =-(1-j2)=-1+j2
Y23 =Y32 =0
Y24 =Y42 =-Y24 =-(1-j3)=-1+j3
Y34 =Y43 =-Y34 =-(2-j6)=-2+j6
1 P2 jQ2 0
V21 0 *
Y21V1
1
Y23V3
0
Y24V 4
Y22 (V2 )
1 0.5 j 0.2
V21 (2 j 6)(1.05 j 0) 0 * (1 j 0) (1 j3)(1 j 0)
3 j9 1 j 0
1
0.5 j 0.2 2.1 j 6.3 1 j3
3 j9
3.6 j9.1 9.7862 68.42
1.03163.15 1.0300 j 0.0567 p.u
3 j9 9.4868 71.57
1 P3 jQ3 0
V31 0 *
Y31V1
1
Y32V 1
2 Y34V 4
Y33 (V3 )
1 1 j 0.5
V31 (1 j3)(1.05 j 0) 0 * (1.0300 j 0.0567) (2 j 6)(1 j 0)
3 j9 1 j 0
1
1 j 0.5 1.05 j3.15 2 j 6
3 j9
1 P4 jQ4
V41 0 *
Y41V11 Y42V21 Y43V31
Y44 (V4 )
1 0.3 j 0.1
V41 (1 j 2)(1.05 j 0) (1 j3) * (1.0300 j 0.0567) (2 j 6)(1.0333 j 0.01166)
4 j11 1 j 0
1
0.3 j 0.1 1.05 j 2.1 (1.2001 j3.0333) (1.367 j 6.433)
4 j11
The bus voltages at the end of first Gauss seidel iteration are
2. In Proble m 1, let the bus 2 be a PV bus (Generator bus) with |V2 | =1.07p.u. the
reactive powe r constraint of the generator bus is 0.3 Q2 1.0. With othe r data
re maining same (Except Q2 ), calculate the bus voltages at the end of first G-S ite ration
Solution:
p 1 n
Q pk 1 (1) * Im(V pk ) * Y pqVqk 1 Y pqVqk
q 1 q p
1 0 *
Q2,cal (1) Im (V2 ) Y21V1 Y22V2 Y23V3 Y 24V40
1 0 0
Q21,cal (1) Im(1.07 j 0)(2 j 6)(1.05 j 0) (3 j9)(1.07 j 0) (0 * (1 j 0)) (1 j3)(1 j 0)
Q’2cal =0.3531. The given Q limits are 0.3 Q2 1.0. the calculated Q2 is within
the limits. So bus 2 is treated as PV bus.
Now Q2 =0.3531, p2 =0.5, |V2 |=1.07
1 Pp jQ p p 1 n
V pk,temp
1
k *
Y V
pq q
k 1
YpqVqk
Ypp (V p ) q 1 q p 1
1 P2 jQ2
V21,temp 0 *
Y21V11 Y23V30 Y24V40
Y22 (V2 )
1 0.5 j 0.3531
V21,temp (2 j 6)(1.05 j 0) (0 * (1 j 0)) (1 j3)(1 j 0)
3 j9 1.07 j 0
1
0.4673 j 0.33 2.1 j 6.3 1 j3
3 j9
Power System Analysis – SEE1302 Page 16
SCHOOL OF ELECTRICAL AND ELECTRONICS
DEPARTMENT OF ELECTRICAL AND ELECTRONICS
3.5673 j9.63 10.2695 69.67
1.08251.9
3 j9 9.4868 71.57
21 V21,temp 1.9
Pp jQ p p 1
1 n
V pk 1 k *
Y V
pq q
k 1
YpqVqk
(V p )
Ypp q 1 q p 1
1 P3 jQ3
V31 0 *
Y31V11 Y32V21 Y34V40
Y33 (V3 )
1 1 j 0.5
V31 (1 j3)(1.05 j 0) (0 * (1.0694 j 0.0355)) (2 j 6)(1 j 0)
3 j9 1 j 0
1 P4 jQ4
V41 0 *
Y41V11 Y42V21 Y43V31
Y44 (V4 )
1 0.3 j 0.1
V41 (1 j 2)(1.05 j 0) (1 j3) * (1.0694 j 0.0355)) (2 j 6)(1.0333 j 0.01166)
4 j11 1 j 0
1
0.3 j 0.1 1.05 j 2.1 (1.1759 j3.1727) (1.367 j 6.433)
4 j11
3.8929 j11.6057 12.2412 71.46
4 j11 11.7047 70.02
3. In Proble m 2, let the reactive powe r constraint of the generator bus is 0.4 Q2 1.0.
With other data re maining same (Except Q2 ), calculate the bus voltages at the end of
first G-S iteration
Solution:
Q’2cal =0.3531. The given Q limits are 0.4 Q2 1.0. the calculated Q2 is less than the
specified lowe r limit. So bus 2 is treated as PQ bus.
Now Q2 =0.4, p2 =0.5, |V2 |=1.0
1 Pp jQ p p 1 n
V pk 1
Ypp (V pk )*
Y V
pq q
k 1
Y pq q
V k
q 1 q p 1
1 P2 jQ2
V21 0 *
Y21V11 Y23V30 Y24V40
Y22 (V2 )
1 0.5 j 0.4
V21 (2 j 6)(1.05 j 0) (0 * (1 j 0)) (1 j3)(1 j 0)
3 j9 1 j 0
1
0.5 j 0.4 2.1 j 6.3 1 j3
3 j9
1 Pp jQ p p 1 n
V k 1
p
Ypp (V pk )*
Y pqVq
k 1
Y pqVq
k
q 1 q p 1
1 P3 jQ3
V31 0 *
Y31V11 Y32V21 Y34V40
Y33 (V3 )
1 1 j 0.5
V31 (1 j3)(1.05 j 0) (0 * (1.0900 j 0.0367)) (2 j 6)(1 j 0)
3 j9 1 j 0
1 P4 jQ4
V41 0 *
Y41V11 Y42V21 Y43V31
Y44 (V4 )
1 0.3 j 0.1
V41 (1 j 2)(1.05 j 0) (1 j3) * (1.09 j 0.0367)) (2 j 6)(1.0333 j 0.01166)
4 j11 1 j 0
1
0.3 j 0.1 1.05 j 2.1 (1.2001 j3.2333) (1.367 j 6.433)
4 j11
3.9171 j11.6663 12.3063 71.44
4 j11 11.7047 70.02
The bus voltages at the end of first Gauss – Seidel iteration are,
V1 1 =1.05+j0=1.050 p.u.
V2 1 =1.09+j0.0367=1.09061.93 p.u.
V3 1 =1.0333-j0.116=1.0399-6.44 p.u.
V4 1 =1.0511-j0.0261=1.0514-1.42 p.u.
Figure:2.4
Carry out one iteration of load flow solution by Gauss seidel method. Neglect
limits on reactive powe r generation
p 1 n
Q pk 1 (1) * Im(V pk ) * Y pqVqk 1 Y pqVqk
q 1 q p
1 0 *
Q2,cal (1) Im (V2 ) Y21V1 Y22V2 Y23V3
1 0 0
Q21,cal (1) Im(1 j 0) j 2.5(1.05 j 0) ( j 7.5)(1 j 0) j5(1 j 0))
1 Pp jQ p p 1 n
V pk,temp
1
k *
Y V
pq q
k 1
YpqVqk
Ypp (V p ) q 1 q p 1
1 P2 jQ2
V21,temp 0 *
Y21V11 Y23V30
Y22 (V2 )
1 3 j 0.125
V21,temp ( j 2.5)(1.05 j 0) ( j5)(1 j 0)
j 7.5 1 j 0
1
3 j 0.125 j 2.625 j5
j 7.5
1
[3 j 7.5] 1 j 0.4 1.07721.8
j 7.5
21 V21,temp 21.8
1 Pp jQ p p 1 n
V pk 1 k *
Y V
pq q
k 1
pq q
Y V k
Ypp (V p ) q 1 q p 1
1 4 j2
V31 ( j3.333)(1.05 j 0) ( j5)(0.92849 j 0.37137)
j8.333 1 j 0
The bus voltages at the end of first Gauss seidel iteration are,
V1 1 =1.05+j0=1.050p.u.
V2 1 =0.92849+j0.37137=1.021.8p.u.
V3 1 =0.73704-j0.25724=0.78064-19.24p.u.
5. The System data for a load flow solution are given in Tables below. Determine the
voltages at the end of first iteration by Gauss seidel method. Take = 1.6
Table:2.3
Table 2.4
Solution:
Figure 2.5
Y11 =y12 +y13 =2-j8+1-j4=3-j12
Y22 =y12 +y23 +y24 =2-j8+0.666-j2.664+1-j4=3.666-j14.664
Y33 =y13 +y23 +y34 =1-j4+0.666-j2.664+2-j8=3.666-j14.664
Y44 =y24 +y34 =1-j4+2-j8=3-j12
Y12 =Y21 =-(2-j8)=-2+j8
Y13 =Y31 =-y13 =-(1-j4)=-1+j4
Y14 =Y41 =0
Y23 =Y32 =-y23 =-(0.666-j2.664)=-0.666+j2.664
Y24 =Y42 =-y24 =-(1-j4)=-1+j4
Y34 =Y43 =-y34 =-(2-j8)=-2+j8
1 Pp jQ p p 1 n
V pk 1 k *
Y V
pq q
k 1
YpqVqk
Ypp (V p ) q 1 q p 1
1 P2 jQ2
V21 0 *
Y21V11 Y23V30 Y24V40
Y22 (V2 )
1 0.5 j 0.2
V21 (2 j8)(1.06 j 0) (0.666 j 2.664)(1 j 0) (1 j 4)(1 j 0)
3.666 j14.664 1 j 0
0.5 j 0.2 2.12 j8.48 0.666 j 2.664 1 j 4
3.666 j14.664
3.286 j14.944 15.3010 77.6
1.0123 1.64 1.0119 j 0.0290 p.u
3.666 j14.664 15.1153 75.96
V pk,acc
1
V pk (V pk 1 V pk )
1 1.6(1.0119 j 0.0290 1)
1 1.6(0.0119 j 0.0290) 1.0190 j 0.0464
1 1.6(0.9942 j 0.0293 1)
1 P4 jQ4
V41 0 *
Y41V11 Y42V21 Y43V31
Y44 (V4 )
0.3 j 0.1
1 (0 *1.06) (1 j 4)(1.0190 j 0.0464)
V 1
1 j0
3 j12
4
1 1.6(0.9864 j 0.0683 1)
The bus voltages at the end of first Gauss seidel iteration are,
V1 1 =1.06+j0=1.060p.u.
V2 1 =1.019-j0.0464=1.0201-2.61p.u.
V3 1 =0.9907-j0.0469=0.9918-2.7p.u.
V4 1 =0.9782-j0.1093=0.9843-6.38 p.u.
What will be the reactive power and bus voltage when the generator bus is
treated as load bus?
• When the generator bus is treated as load bus, the reactive power of the bus is
equated to the limit it has violated, and the previous iteration value of bus
voltage is used for calculating current iteration value
Acceleration factor:
• In Gauss Seidel method, the number of iterations can be reduced, if the
correction voltage at each bus is multiplied by some constant
• It is used only for load bus
Jacobian Matrix
• The matrix forme d from the first derivatives of load flow equations is called
Jacobian matrix and it is denoted by J
How the elements of Jacobian matrix are computed?
• The elements of Jacobian matrix will change in every iteration
n
In polar form, Where, Yij=|Yij|ij, Vj=|Vj| j
I i | Yij || V j | ij j
j 1
N
Pi jQi Vi* I i Vi * YijV j
j 1
N
Pi jQi |V i| i | Yij || V j | ( ij j )
j 1
N
|V i|| Yij || V j | ( ij j i )
j 1
N
Pi |V i|| Yij || V j | cos( ij j i )
j 1
N
Qi |V i|| Yij || V j | sin( ij j i )
j 1
In Matrix form,
P 0 P2
0
P2
0
P2
0
2
2 N | V2 | | VN |
P20 2
0
0
N
0 0 0 0
PN PN PN PN
P 0
N 2
N
| V2 | | VN |
| V2 |
0
Q 0 Q 0 Q2
0
Q2
0
Q2
0
2 2
2 N | V2 | | VN |
0 | V 0
Q N 0 0 0 0 N |
Q N Q N Q N Q N
2
N
| V2 | | VN |
P J 1 J 2
Q J J 4 | V |
3
Pi
| Vi || V j || Yij | sin(ij j i ) ji
j
Pi N
2 | Vi || Yii | cos ii | V j || Yij | cos( ij j i )
| Vi | j 1
1
Pi
| Vi || Yij | cos( ij j i ) ji
|Vj |
Qi N
| Vi || V j || Yij | cos( ij j i )
i j 1
i
Qi
| Vi || V j || Yij | cos(ij j i ) ji
j
Qi
| Vi || Yij | sin(ij j i ) ji
|Vj |
1
J1 J 2 P
| V
| J 3 J 4 Q
Figure: 2.6
Algorithm for Newton Raphson Method
Step 1: Formulate Y – bus matrix
Step 2: Assume flat start for starting voltage solution
i0 =0, for i=1, …….., N for all buses except slack bus
|Vi 0 |=1.0, for i=M=1,M+2, ……..,N (for all PQ buses)
|Vi |=|Vi |(spec)
Step 3: For load buses, calculate pi cal and Qi cal
Step 4: for PV buses, check for Q-limit violation
If Qi(min) < Qi cal < Qi(max), the bus acts as P-V bus
Power System Analysis – SEE1302 Page 34
SCHOOL OF ELECTRICAL AND ELECTRONICS
DEPARTMENT OF ELECTRICAL AND ELECTRONICS
If Qi cal > Qi(max), Qi(spec)=Qi(max)
If Qi cal < Qi(min), Qi(spec)=Qi(min), the P-V bus will act as P-Q bus
Step 5: Compute mismatch vector using
Pi =Pi(spec) – Pi cal
Pi Pi
| V |
J
Qi Qi
| V |
Step 8: Obtain state correction vector
1 P
| V J
| Q
V new V old V
new old
Step 10: This procedure is continued until
|Pi | and |Qi | , otherwise go to step 3
6. The one line diagram of a simple 3 bus powe r system with gene rators at buses 1 and 3
is shown. The magnitude of voltage at bus 1 is adjusted to 1.05 pu. Voltage magnitude at
bus 3 is fixed at 1.04 pu with a real powe r generation of 200 MW. A load consisting of
400 MW and 250 Mvar is taken from the bus 2. Line impedances are marked in per
unit on a 100 MVA base, and the line charging susceptances are neglected. Obtain the
powe r flow solution by Newton Raphson method.
Figure: 2.7
Solution:
1 1
Y11 20 j50 53.85 68.3
0.02 j 0.04 0.01 j 0.03
1
Y 12 Y21 10 j 20 22.36116.56
0.02 j 0.04
1
Y 13 Y31 10 j30 31.62108.43
0.01 j 0.03
1 1
Y 22 20 j50 58.14 63.6
0.02 j 0.04 0.0125 j 0.025
1
Y 23 Y32 16 j32 35.70116.56
0.0125 j 0.025
1 1
Y 33 26 j 62 17.23 67.25
0.01 j 0.03 0.0125 j 0.025
P2 (1* 22.36 *1.05) cos(116.56 0 0) 12 * 58.14 cos(63.6) (1* 35.70 *1.04) cos(116.56 0 0) 1.14
P3 (1.04 * 31.62 *1.05) cos(108.43 0 0) (1.04 * 35.70 *1) cos(116.56 0 0) (1.04) 2 *17.23 cos(67.25) 0.5616
N
Qi |V i|| Yij || V j | sin(ij j i )
j 1
Q2 [(1* 22.36 *1.05) sin(116.56 0 0) 12 * 58.14 sin(63.6) (1* 35.70 *1.04) sin(116.56 0 0)] 2.28
Pi N
| Vi || Yij || V j | sin( ij j i )
i j 1
i
P2
| V2 || Y21 || V1 | sin( 21 1 2) | V2 || Y23 || V3 | sin( 23 3 2) 54.28
2
Pi
| Vi || Yij || V j | sin( ij j i )
j
P 2
| V2 || Y23 || V3 | sin( 23 3 2 ) 33.28
3
P 3
llly 33.28
2
Pi N
2 | Vi || Yii | cos ii | V j || Yij | cos( ij j i )
| Vi | j 1
1
P2
2 | V2 || Y22 | cos 22 | V1 || Y21 | cos( 21 1 2 ) | V3 || Y23 | cos( 23 3 2 ) 24.86
| V2 |
Pi
| Vi || Yij | cos( ij j i ) ji
|Vj |
P3
| V3 || Y32 | cos( 32 2 3 ) 16.64
| V2 |
Qi N
| Vi || Yij || V j | cos( ij j i )
i j 1
i
Q2
| V2 || Y21 || V1 | cos( 21 1 2 ) | V2 || Y23 || V3 | cos( 23 3 2 ) 27.14
2
Qi
| Vi || Yij || V j | sin( ij j i ) ji
j
Q2
| V2 || Y23 || V3 | sin( 23 3 2 ) 16.64
3
Qi N
2 | Vi || Yii | sin ii | V j || Yij | sin(ij j i )
| Vi | j 1
1
Q2
2 | V2 || Y22 | sin 22 | V1 || Y21 | sin( 21 1 2 ) | V3 || Y23 | sin( 23 3 2 ) 49.72
| V2 |
1
20 54.28 33.28 24.86 2.86
0 1.43
3 33.28 66.04 16.64
| V2 |0 27.14 16.64 49.72 0.22
20 0.0453
30 0.0077
| V20 | 0.0265
21 0 (0.0453) 0.0453
31 0 (0.0077) 0.0077
| V21 | 1 (0.0265) 0.9735
Method II
• Symmetrical faults: The fault curre nts are equal in all the phases and can be
analysed on pe r phase basis
Unsymmetrical fault
i. Line to ground fault
ii. Line to line fault
iii. Double line to ground fault
iv. One or two open conductor faults
Figure: 3.1
Figure 3.2
Subtransient Symmetrical rms current, I’’ =oc/2
Subtransient reactance:
• It is the ratio of induced e mf on no load and the subtransient symmetrical rms
current, (i.e, it is the reactance of a synchronous machine under s ubtransient
condition)
1
X d'' X l
1 1 1
X a X f X dW
Figure: 3.3
Significance of subtransient reactance in short circuit studies:
• It is used to estimate the initial value of fault current immediately on the
occurrence of the fault
• The maximum mome ntary short circuit current rating of the circuit breaker
used for protection or fault clearing should be less than this initial fault current
Transient reactance:
• It is the ratio of induced e mf on no load and the transient symmetrical rms
current. (i.e, it is the reactance of a synchronous machine under transient
condition)
1
X d' X l
1 1
Xa X f
Figure: 3.4
1
Xd Xl Xl Xa
1
Xa
Figure:3.5
Fault Calculations
• The fault condition of a powe r system can be divided into s ubtransient, transient
and steady state periods
• The currents in the various parts of the system and in the fault are different in
these periods
• The estimation of these currents for various types of faults at various locations in
the system are commonly referred to as fault calculations
Figure: 3.6
Figure: 3.7
Base Values:
MVAb=30MVA; KVb=13.2KV
Base current, Ib = KVAb /(3 * KVb) =( (30 * 1000) / (3 * 13.2)) = 1312.16 A
= (0.6667/(0.9697 * 0.8))
= 0.8594 p.u.
Take Terminal Voltage of motor Vtm as reference vector, so the load current will
lead the terminal voltage of motor with an angle cos -1 0.8
Vtm = 0.9697 0
IL=0.8594 cos -1
0.8 = 0.8594 36.9 p.u.
Figure:3.8
Eg ” = j0.2 IL +j0.1 IL+Vtm
= j0.3 IL + Vtm
= -0.1548 +j0.2062+0.9697
=0.8149 +j0.2062 = 0.8406 14.2 p.u.
Em ” +j0.2IL = Vtm
Em ” = Vtm – j0.2IL
= 0.9697 0 - (0.2 90 * 0.8594 36.9)
Fault Condition
Figure: 3.9
j0.2 Ig ” +j0.1 Ig ” = Eg ”
j0.3Ig ” = Eg ”
Ig ” = Eg ” / j0.3
j0.2 Im ” = Em ”
Im ” = Em ” / j0.2
= ((1.0817 -7.3) / (0.2 90 ))
= 0.687-j2.716-0.687-j5.365
= -j8.081 = 8.081 -90 p.u.
Actual Value of fault current can be obtained by multiplying the p.u. values
with base current
Ig ” = 2.802 75.8 * 1312.16
Figure: 3.10
Thevenin’s equivalent impedance, Zth = ((j0.1+j0.2)*j0.2) / (j0.1+j0.2)+j0.2
= j0.12
Figure: 3.11
Curre nt in the fault = If” = Vth / Zth = 0.9697 0 / 0.12 90 = 8.081-90 p.u
Figure: 3.12
= 3.2323 90
= 4.8485 -90
To find the sub - transient fault curre nt in motor and generator
Ig ” = I1 +IL = 3.2323 90 + 0.8594 36.9 = -j3.2323 +0.6872+j0.516
Figure: 3.13
To Find generator reactance
Since the rating of the generator is chosen as base value, the p.u. reactance of the
generator will be same as the specified value.
p.u. reactance of the generator, Xd = 8% = 0.08 p.u.
To find transforme r reactance
2
KVb,old MVAb,new
X pu,new X pu,old * *
MVA
KVb , new b , old
p.u. reactance of transformer, X T
2
6.6 5
0.05 * * 0.0833 p.u.
To find feeder reactance 6.6 3
Figure:3.14
To find Eg & Vpf
• Here the generator is not delivering any load curre nt and so the induced emf of
the generator will be same as operating voltage
Actual Value of induced emf, Eg = 6.9 Kv
p.u. Value of induced e mf = Actual Value / Base Value
= 6.9 / 6.6 = 1.0455 p.u.
• The open circuit p.u. value of voltage is same at every point in a series path
irrespective of their actual voltages
Vpf = 1.0455 p.u.
Figure:3.15
p.u. value of fault current, If = Vth / Zth = 1.0455 0 / 0.1966 87.6
3. For the radial network shown in fig, a 3 – phase fault occurs at point F.
Determine the fault curre nt.
Figure: 3.16
p.u. impe dance overhead line, ZTL = Actual / Base = (6+j10) / 108.9
= 0.0551 +j0.0918 p.u.
To find the reactance of T2
Xpu,new = Xpuold * (KVb,old / KVb,new)2 * (MVAb,new / MVAb,old)
p.u. reactance of transformer T2 , XT2 = 0.087 * (33/33)2 * (10/25)
= 0.0348 p.u.
p.u. impe dance of the feeder, Zfed = Actual impedance / Base impedance
= 0.5 +j0.15 / 4.356 =0.1148 +j0.0344 p.u.
To find thevenin’s equivalent at fault point
• The thevenin’s voltage at the fault point is prefault voltage
Vth = 10 p.u.
Figure: 3.17
Zth = ((j0.2 * j0.125) / (j0.2 + j0.125))
+(j0.1+0.0551+j0.0918+j0.0348+0.1148+j0.0344)
= j0.0769 +0.1699+j0.261
= 0.1699+j0.3379
=0.378263.3 p.u.
Figure:3.18
To find fault curre nt
p.u. value of fault current, If = Vth / Zth = (10) / (0.3782 -63.3 p.u.
= 874.77A
The actual value of fault curre nt, If = p.u. valu of fault curre nt * Base current
= (2.6441 -63.3) * 874.77
= 2313 -63.3 KA
Z 11 Z 12 Z 1k Z 1n I 1 V1
Z Z 22 Z 2k Z 2 n I 2 V2
21
Z k1 Z k2 Z kk Z kn I k Vk
Z n1 Z n2 Z nk Z nn I n Vn
Figure:3.19
V1 I f Z1k
V2 I f Z 2 k
V pf I f z kk
Vn I f Z nk
• In general the change in bus q voltage due to three phase fault in bus k is given
by
Vq = -IfZqk
• The voltage at a bus after a fault in bus K is given by sum of prefault bus voltage
and change in bus voltage
• Since the system is unloaded system, the prefault voltage at all buses be
Vpf = 1.0 p.u.
V1 V pf ( I f Z1k ) 10 I f Z1k
V2 V pf ( I f Z 2 k ) 10 I f Z 2 k
Vk V pf V pf 0
Vn V pf ( I f Z nk ) 10 I f Z nk
• The fault current flowing through the lines can be estimated from the
knowledge of line impedances
Figure: 3.20
Iqr = (Vq- Vr) / Zqr = (Vq – Vr) * Yqr
4. The bus impedance matrix of four bus system with values in p.u. is given by,
= (1-0.25) / 0.290
= 3.75-90
Figure: 3.21
5. Find the fault curre nt and post fault voltages for the given system shown below
and fault being occurre d at bus 2.
Figure:3.22
1 0 0
1 1 0
Incidcence Matrix ( A) 1 0 1
0 1 1
0 1 0
j 0.2 0 j 0.6 0 0
0 j 0.3 0 j 0.8 0
Z j 0.6 0 j 0.3 0 0
0 j 0.8 0 j 0.5 0
0 0 0 0 j 0.4
1 1 0 0
0 1 1 0
^
ElementalN odeIncidce nceMatrix ( A) 0 1 0 1
0 0 1 1
1 0 1 0
1 0 0
1 1 0
Incidcence Matrix ( A) 1 0 1
0 1 1
0 1 0
j 0.2 0 j 0.6 0 0
0 j 0.3 0 j 0.8 0
Z j 0.6 0 j 0.3 0 0
0 j 0.8 0 j 0.5 0
0 0 0 0 j 0.4
Figure:3.23
Solution:
Z jn Z nk
Z jk ,new Z jk ,old
j1.2 j1.2 j1.2 j1.2 Z nn
j1.2 j1.4 j1.4 j1.4
Z bus
j1.2 j1.4 j1.55 j1.55
j1.2 j1.4 j1.55 j 3.05
n =4 ; j=1,2,3 ; K=1,2,3
Z14Z 41 j1.2 * j1.2
Z11,new Z11,old j1.2 j 0.728
Z 44 j3.05
Z Z j1.2 * j1.4
Z12,new Z12,old 14 42 j1.2 j 0.649
Z 44 j3.05
Z14Z 43 j1.2 * j1.55
Z13,new Z13,old j1.2 j 0.590
Z 44 j3.05
Z 21,new Z12,new j 0.649
Z 24Z 42 j1.4 * j1.4
Z 22,new Z 22,old j1.4 j 0.757
Z 44 j3.05
Z Z j1.4 * j1.55
Z 23,new Z 23,old 24 43 j1.4 j 0.689
Z 44 j3.05
Z31,new Z13,new j 0.590
7. Determine Zbus for system whose reactance diagram is shown in fig whe re the
impedance is given in p.u. preserve all the three nodes.
Figure:3.24
Solution:
Zbus = [ j 1.0 ]
j 0.6 j 0.5
Z bus
j 0.5 j1..625
Figure: 3.25
Figure 4.1
1.
Solution:
Solution:
Figure: 4.2
Figure:4.3
Sequence Impedances and networks of Transmission lines
Figure: 4.4
Figure: 4.5
The value of Z1 = Z2 = Z0
Ze ro Sequence network of three phase transformer:
Figure: 4.6
Figure: 4.7
3.
Figure: 4.8
Solution:
Figure:4.9
Figure: 4.10
Figure: 4.11
Figure: 4.12
Figure: 4.13
Figure: 4.14
Figure: 4.15
Figure:4.16
Figure:4.17
Figure: 4.18
Figure: 4.19
Figure: 4.20
Figure: 4.21
Double Line to Ground fault on Power System
Figure: 4.22
Figure: 4.23
Figure: 4.24
Figure: 4.25
Figure: 4.26
Figure: 4.27
Figure: 4.28
The line currents are given by
Ia =Ia0 +Ia1 +Ia2
I a 1 1 1 I a0
I 1 a 2 Since, Ia =0
b a I a1
I c 1 a a 2 I a 2
Ib=Ia0 +a2 Ia1 +aIa2
Ic=Ia0 +aIa1 +a2 Ia2
Ib+Ic=Ia0 +a2 Ia1 +aIa2 +Ia0 +aIa1 +a2 Ia2
=2Ia0 +(a2 +a)Ia1 +(a2 +a)Ia2
W.K.T, 1+a+a2 =0, a+a2 =-1
Ib+Ic=2Ia0 -Ia1 -Ia2
= 2Ia0 -(Ia1 +Ia2 )
=2Ia0 -(-Ia0 )
= 3Ia0
The Symmetrical components of voltages after substituting Vc=Vb are given by
Va0 =(1/3)[Va +Vb+Vb] =(1/3)[Va +2Vb ]
Va 0 1 1 1 Va
Va1 =Va2 = (1/3)[Va +aVb+a Vb] 2 V 1 1 a a 2 Vb
a1 3
=(1/3)[Va +(a+a2 )Vb ] = (1/3)[Va -Vb] V a 2 1 a 2 a Vb
V pf
I a1
Z 2 ( Z 0 3Z f )
Z1
Z 2 Z 0 3Z f
Figure: 4.29
Va1 =Vpf - ZfIa1
Va2 =Va1
Ia2 =(Va2 /Z2 )
Ia0 = -(Ia1 +Ia2 )
Fault curre nt, If=Ib+Ic = 3Ia0
4. Two 11 KV, 20MVA, three Phase star connected generators ope rate in parallel as
shown in Figure. The positive, negative and zero sequence reactance's of each being
respectively, j0.18,j0.15,j0.10 p.u. The star point of one of the generator is isolated and
Figure: 4.30
Solution:
MVAb=20MVA
KVb=11KV
Zb= (KVb)2 /MVAb = (11)2 / 20 = 6.05
Figure: 4.31
Figure: 4.32
For a single line to ground fault,
Ia1 = Ia2 = Ia0
If= Ia = 3Ia1
Hence the thevenin’s equivalent of sequence networks are connected in series as shown
in fig
The fault current is calculated by taking the prefault voltage Vpf=1 p.u.
From Fig,
Ia1 = 10 / (j0.09+j0.075+0.9918+j0.1)
= 1 / (0.9918+j0.265)
= 1 / ( 1.0266 15 )
Figure: 4.33
i. To find fault curre nt
Fault curre nt, If = Ia = 3Ia1
= 3 * 0.9741 -15
Actual value of fault current = p.u. value of fault curre nt * Base current
5. A salient pole generator without dampers is rated 20MVA, 13.8KV and has a direct
axis sub - transient reactance of 0.25 pe r unit. The negative and zero sequence reactance
are 0.35 and 0.10 per unit respectively. The neutral of the generator is solidly grounded.
Determine the sub - transient current in the generator and the line to line voltages for
sub - transient conditions when a line to line fault occurs at the generator ope rating
unloaded at rated voltage. Neglect resistance.
Solution:
Base Values
MVAb=20MVA
KVb=13.8KV
Base current, Ib = KVAb / (3 * KVb)
= 836.7 A = 837 A
Figure: 4.34
I a 1 1 1 I a0
I 1 a 2 a I a1
b
I c 1 a a 2 I a 2
a=1120 = -0.5+j0.866
a2 = 1240 = -0.5-j0.866
Ia =Ia0 +Ia1 +Ia2 =0-j1.667+j1.667=0
Ib=Ia0 +a2 Ia1 +aIa2 = -j1.667(-0.5-j0.866) + j1.667 (-0.5+j0.866)
=j0.833-1.443-j0.833-1.443 = -2.886 p.u.
Ic = Ia0 +aIa1 +a2 Ia2 =-aIa2 -a2 Ia1 =-(a2 Ia1 +aIa2 ) = -Ib = 2.886 p.u
Actual values of line curre nts are obtained by multiplying the p.u. values with base
currents
Ia =0
Ib=-2.886 * 837 =2416 180 A
Ea =1p.u
Line Value of base voltage = 13.8KV
Phase Value of base voltage = (13.8 / 3 ) = 7.9KV
Vbc = 0 KV
Vca = 1.749 180 * 7.97 = 13.94 180 KV
Assume the line to line fault is between Phase b and Phase c. Hence the fault curre nt is
Ib.
Ib = Ia0 +a2 Ia1 +aIa2
For a line to line fault, Ia0 =0 and Ia2 =-Ia1
Ib = 0+a2 Ia1 -aIa1 = Ia1 (a2 – a)
If = 2.23 p.u.
|Ia1 | = (2.23 / 1.732) = 1.2875 p.u.
Figure: 4.36
Case (iii): L-G Fault
For a single line to ground fault, on a generator the sequence networks are connected in
series as shown in Fig
For a single line to ground fault, the fault curre nt is |I a | and it is equal to 3|Ia1 |
If=3.01 p.u.
3|Ia1 | =If = 3.01 (or) |Ia1 | =(3.01/3) = 1.0033 p.u.
From Fig
Ia1 = (Ea / (jX1 +jX2 +jX0 ))
|Ia1 | =(Ea /(X1 +X2 +X0 ))
Figure: 4.37
Figure: 4.38
7. For the given network shown below a solid single line to ground fault is occurre d at
bus 3. Perform the fault analysis and determine (a) Fault current (b) Bus voltages after
fault and (c) Line currents after fault. Assume pre fault voltage 1 p.u./phase. Neglect the
shunt admittance of the line. All values are given on 100 MVA base.
Figure: 4.39
Line Impedance
Bus
Ele ments Ze ro Positive Negative
Code
Sequence Sequence Sequence
Table: 4.1
Solution:
Faulted bus numbe r =3; pre fault phase voltage, E=1.0; for solid fault Zf = 0
I3 (0) = I3(1) = I3(2) = (√3) * E / (Z33 (0) + Z33 (1) + Z33 (2) + 3Zf)
= (√3) / ( j0.135 + j0.25 +j0.25)
= -j2.7276 p.u. Fault current at bus 3, If = 3 *I3 (1) =-j8.1828 p.u.
Bus voltages after fault is
Ze ro Sequence Voltages
V1 (0) = - Z13 (0) I3(0)
= - j0.075 * (-j2.7276) = -j0.2045 pu
V2 (0) = - Z23 (0) I3(0) = -j0.2045 pu
V3 (0) = - Z33 (0) I3(0) = -j0.3682 pu
Positive Sequence Voltages
V1 (1) = (√3)E – Z13 (1) I3(1)
= (√3) – j0.15*(-j2.7276)
= 1.3229 pu
V2 (1) = (√3)E – Z23 (1) I3(1) = 1.3229 pu
V3 (1) = (√3)E – Z33 (1) I3(1) = 1.0501 pu
Negative Sequence Voltages
V1 (2) = - Z13 (2) I3(2)
= - j0.15 * (-j2.7276) = -0.4091 pu
V2 (2) = - Z23 (2) I3(2) = -0.4091 pu
Stability
The Stability of a system is defined as the ability of powe r system to return to stable
(Synchronous) operation whe n it is subjected to a disturbance
mech.rad
- Angular displace ment of rotor with respect to stationary axis in elec.rad
t - Time in seconds
Tm - Mechanical torque at the shaft of rotor (supplied by prime mover) in
N-m
Te - Net electromagnetic torque in N-m
Ta - Net accelerating torque in N-m
Pm - Mechanical Powe r input in p.u.
Pe - Electrical power output in p.u.
The Kinetic ene rgy (in MJ) of the rotor of a synchronous machine is given by
1
E KE J sm
2
*10 6
2
The mechanical and electrical angular speeds are related to the numbe r of poles in
synchronous machine as shown as
2
P
s sm or sm s
2 P
2
1 2 2
E KE J s *10 6
2 P
Let, 1
E KE M s
2
2
Where, M J 2 *10 6
s
P
H EKE
S
1
J sm
2
1
H 2 M s 2 HS
S H 2 M
S s
We Know that , s =2f
2 HS HS (in MJ-s/elec.rad)
M
2f f
HS
M
180 f (in MJ-s/elec.deg)
The value of M can be expressed in per unit by selecting a base of MVA
Let, Sb=Base MVA
SH / f Or SH / 180 f
M p.u. M p.u.
Sb Sb
If the machine rating S is chosen as base Value, then S= Sb p.u. value of M with
Machine rating as base MVA
H
M p.u. M p.u.
H
f 180 f
1. A 2 pole 50Hz, 11KV turbo alternator has a ratio of 100MW, power factor 0.85
lagging. The rotor has a moment of inertia of 10,000 Kgm2 . Calculate H and M.
Solution:
Synchronous speed in rps, ns = 2f/p =(2*50)/2 =50 rps
Synchronous speed in rad/sec, s =2ns = 2* 50 = 314.16 elect.rad/sec
2. Two powe r station A and B are located close together. Station A has four identical
generator sets each rated 100MVA and having an inertia constant of 9MJ/MVA
whe reas the station B has 3 sets each rated 200MVA, 4MJ/MVA. Calculate the inertia
constant of a single equivalent machine on a base of 100MVA .
Solution:
• Assume that the machines are swinging coherently. For two machines swinging
coherently the equivalent inertia constant, He q is given by
He q = (H1,mach *S1,mach ) / Ssys +(H2,mach *S2,mach ) / Ssys
Where, Ssys – MVA rating of system
S1,mach & H1, mach – MVA rating and ine rtia constant of machine 1
S2,mach & H2, mach – MVA rating and ine rtia constant of machine 2
Station A
The station A has four machines of identical rating
Equivalent inertia constant of station A = HA = 4( (Hmach *Smach ) / Ssys )
= 4((9 * 100)/100)
=36 MJ/MVA
Station B
Power System Analysis – SEE1302 Page 6
SCHOOL OF ELECTRICAL AND ELECTRONICS
DEPARTMENT OF ELECTRICAL AND ELECTRONICS
The station B has three machines of identical rating
Equivalent inertia constant of station A = HB = 3( (Hmach *Smach ) / Ssys )
= 3((4 * 200)/100)
= 24 MJ/MVA
He q of System
Equivalent inertia constant of the system = He q=HA+HB = 36+24 = 60MJ/MVA
Swing Equation
• The rotor of a synchronous machine is subjected to two torques, Te and Tm
which are acting in opposite directions as shown in Fig
Figure: 5.1
Where Te – Net electrical or electromechanical torque in N-m
Tm – Mechanical or shaft torque supplied by the prime move r in N-m
• Unde r steady state operating condition the Te and Tm are equal and the machine
runs at constant speed, which is called synchronous speed.
• If there is a difference between the two torques then the rotor will have an
accelerating or decelerating torque, denoted as Ta
Ta =Tm -Te
d 2 m Or d 2 m
Ta Ta J
dt 2 dt 2
d 2 m
J Tm Te
dt 2
The angular dis place ments m & m are related to synchronous speed by the following
equation,
m smt m
d m d
sm m
dt dt
• From the equation, the rotor angular velocity d m /dt is constant and equal to
• Hence d m /dt represents the deviation of the rotor speed from synchronism
d 2 m d 2 m d 2 m
dt 2 dt 2 J Tm Te
dt 2
Let, Pm,act - shaft powe r input to the machine neglecting losses (in MW)
Pe ,act - Electrical powe r developed in rotor (in MW)
2NT
P T
60 Pm,act
Tm
Pm,act smTm or sm
d 2 m
J sm Pm,act Pe,act
dt 2
1
J sm
2
J sm
2 HS
H 2 sm
S
2 HS d 2 m
Pm,act Pe,act
sm dt 2
2 HS d 2 (2 / p)
Pm,act Pe,act
2 s / P dt 2
2 HS d 2
Pm,act Pe,act
s dt 2
On substituting for s =2f
2 HS d 2 HS d 2
Pm,act Pe,act Pm,act Pe,act
2f dt 2 f dt 2
HS d 2 H d 2
Pm S Pe S Pm Pe
f dt 2 f dt 2
• This equation is called swing equation.
• It is the fundamental equation which gove rns the dynamics of the
synchronous machine rotor
• This swing equation is a second order differential equation
Figure: 5.2
• Consider a single generator supplying power through a trans mission system to a
load or to a large system at othe r end.
• Such system can be represented by a 2 – bus network as shown in fig as a
rectangular box representing the linear passive components (reactance's) of the
system including the transient reactance of the generator
Figure: 5.3
Here E1 ’ – Transient internal voltage of the generator at bus 1
E2 ’ – Voltage at the receiving end. (This may be the voltage at infinite
bus, or transient internal voltage of synchronous motor at bus 2)
The node basis matrix equation of 2 bus system of fig can be written as
I=Ybus V
Where, I1 & I2 are the currents injected by the sources E1 ’ & E2 ’ respectively to the
system
P1 jQ1 | E1' |2 (G11 jB11) | E1' || E2' ||| Y12 | (1 2 12 )
| E1' | 2 (G11 jB11 ) | E1' || E2' ||| Y12 | cos(1 2 12 ) j | E1' || E2' ||| Y12 | sin(1 2 12 )
Let = 1 - 2
Pe Pc Pmax cos( / 2)
Pe Pc Pmax sin( )
• The power angle equation can be further simplified by conside ring the network
as purely reactive network ( Neglect resistance)
Power System Analysis – SEE1302 Page 12
SCHOOL OF ELECTRICAL AND ELECTRONICS
DEPARTMENT OF ELECTRICAL AND ELECTRONICS
G11 =0, 12 = /2. so =0
On Substituting,
Pe = Pmax sin . This equation is called simplified power angle equation
H d 2
Pm Pe
f dt 2
H d 2
Pm Pmax sin
f dt 2
• This equation is the swing equation in which the electrical powe r is expressed as
a function of
| E || V |
Pmax
• Let the system beXoperating with steady state power transfer with a torque angle
0
Figure: 5.4
Power System Analysis – SEE1302 Page 14
SCHOOL OF ELECTRICAL AND ELECTRONICS
DEPARTMENT OF ELECTRICAL AND ELECTRONICS
• Now the torque angle change by a s mall amount
Pe 0 +P=Pmaxsin( 0 +)
When =0
The nonlinear swing equation can be linearized about the operating point for
steady state analysis
H d 2
Pm Pe
f dt 2
d 2
M Pm Pe
dt 2
For a torque of =( 0+), Pe = (pe0 +P)
d 2 ( 0 )
M Pm ( Pe 0 P)
dt 2
Since 0 is constant and Pm = Pe0
d 2
M P
dt 2
d 2
M ( Pmax cos 0 )
dt 2
Power System Analysis – SEE1302 Page 15
SCHOOL OF ELECTRICAL AND ELECTRONICS
DEPARTMENT OF ELECTRICAL AND ELECTRONICS
d 2
M ( Pmax cos 0 ) 0
dt 2
Let, d2
x2
and Pmax cos 0 C
dt 2
Mx 2 C 0
(Mx 2 C ) 0
Since 0 (Mx 2 C ) 0
This is the characteristic equation of the system for small changes. The stability is
determined by the roots of the characte ristic equation
C
C or x
x 2
M
M
• in a practical sysyem the system is stable for s mall incre ment in powe r
provided, Pmax cos 0>0
• The term Pmax cos 0 decides the steady state stability of the system and so it is
called Synchronizing coefficient or stiffness of the synchronous machine
• From the powe r angle curve for gene rator action, the range of 0 as 0 to
• The Fig is drawn using the equation Pe =Pmax sin
• From the above discussion, the synchronizing coefficient (Pmax cos 0 ) and real
powe r injected to the system (Pe ) are positive when is in the range of 0 to /2
• the maximum powe r that can be trans mitted without loss of stability occurs
for = 0 =/2 =90
• Since the changes in is very large in the transient state, the swing equation
cannot be linearized for a gene ral solution
• So the solution has to be obtained by using any one of nume rical techniques like
point by point method , Runga kutta method and modified Eule r’s method
• The transient stability of a single machine connected to infinite bus bar can be
easily determined by a simple criterion called equal area criterion
• The computational task involved in transient stability studies can be unde rstood
considering the transient state of a practical system
Figure: 5.5
• Consider a single machine system feeding energy through a trans mission line to
an infinite bus
• Let the Circuit breakers (C.B) be auto closure type
• In this C.B will open its contact upon sensing a fault and after a s mall time it will
close its contacts, if the fault still exist then again it will open its contact to
permanently disconnect the faulty part
• This feature is useful in clearing transient faults
• Transient fault exists for a small time and it gets cleared when the circuit is
opened
Power System Analysis – SEE1302 Page 18
SCHOOL OF ELECTRICAL AND ELECTRONICS
DEPARTMENT OF ELECTRICAL AND ELECTRONICS
• Then the circuit can be closed for normal ope ration
• Most of the auto reclosure C.B will open and close the contacts twice before
permanently disconnecting the circuit
• In majority of faults, first reclosure will be successful
• Hence system stability is improved by using autoreclosure C.B
3. Calculate (t) for various time instant by solving the swing equation using a
numerical technique. The initial value of for the solution is 0
4. Assume the fault is cleared whe n the C.B open its contact for the first time. Now
Pe( )=0. Continue calculating (t) by taking previous step value as initial
condition
5. Assume C.B close its contact and powe r feeding to infinite bus is resumed. For
this situation find Pe( ) and continue to calculate (t)
6. Examine the variations of (t). If (t) goes through a maximum value and starts
to reduce then the system is a stable system. On the other hand if (t) remains
increasing for a specified length of time then the system is considered unstable
2. The system is unstable if d /dt > 0 for a sufficiently long time (typically 1 second
or more)
For a single machine infinite bus bar system, the stability criterion stated above can be
converted to a simple condition as shown below
Consider the swing equation of a generator connected to infinite bus
H d 2
Pm Pe
f dt 2
Let the re be a change in Pe due to a large disturbance, with Pm re maining constant
Pm -Pe =Pa Where Pa is the accelerating power
H
M
f
d 2
M 2 Pa
dt
d 2 Pa
dt 2 M
d d 2 d Pa
2 2
2
dt dt dt M
d d d 2 d
2 Pa
dt dt dt M dt
d d d
2
2
2 Pa
dt dt M dt
d
2
2
2d Pa d
dt M
d 2
dt
M P d a
0
For a stable system d /dt=0, at a particular time instance. so for a stable system
2
M P d 0
0
a
• The physical meaning of integration is the estimation of the area under the curve
• Hence the integral of pa equal to zero area
• The condition of stability can be stated as:
i. The system is stable if the area under Pa - curve reduces to zero at some value
of
ii. This is possible only if the positive (accelerating) area unde r Pa - curve is equal
to the negative (decelerating) area under Pa - for a finite change in
iii. Hence this stability criterion is called equal area criterion of stability
• The equal area criterion of stability can be applied to any type of disturbances
that may occur in a single machine infinite bus bar system
Figure: 5.6
Figure: 5.7
• Consider a single generator feeding energy to infinite bus as shown in fig
• The electrical powe r transmitted by the generator is given by
| E ' || V |
Pe sin Pmax sin
X
'
Where Pmax | E || V |
X
• At this condition the mechanical powe r input is Pmo and the electrical output is
Pe 0
• Unde r ideal conditions Pm0 =Pe 0
• Pm0 =Pe0 =Pmax sin 0
• In the powe r angle curve shown in fig, the steady state operating point is point a
Let the mechanical input to the generator rotor be suddenly increased to Pm1 by
some adjustment in prime mover
• Since the mechanical powe r is more than electrical powe r, the generator will
have an accelerating power Pa given by
Pa =Pm1 -Pe
Power System Analysis – SEE1302 Page 22
SCHOOL OF ELECTRICAL AND ELECTRONICS
DEPARTMENT OF ELECTRICAL AND ELECTRONICS
Where Pe = Pmax sin
• Due to accelerating powe r the rotor speed increases and so the rotor angle also
increases
• This results in increased electrical powe r generation
• the operating point will move upwards along the powe r angle curve.
• At Point b again the mechanical powe r Pm1 equals the electrical powe r Pe 1 ,
whe re Pe 1 is the electrical powe r output corresponding to torque angle 1
• Now the rotor angle cannot stay at this point because the inertia of the rotor will
make the rotor to oscillate with respect to point b
• Hence the torque angle will continue to increase till point c, whe n the operating
point moves from b to c, the electrical powe r is more than mechanical powe r
the power Pa given by equation is negative and it is called decelerating powe r
• In this region (i.e., from point b to c) the rotor angle increases but the rotor
speed decreases due to decelerating powe r
• The point c is decided by the damping of the system
• At point c the speed of rotor will be equal to synchronous speed
• At point a the speed is synchronous speed ( s )
• From point a to b the speed increases and then from point b to c the speed
decreases
• Once again at point c the speed is equal to synchronous speed (s )
• Thus the rotor oscillates between point a and point c before settling to point b
• In Fig , the area A1 is the accelerating area and area A2 is the deceleration area
• The equal area criterion says that, the system is stable if
P d 0
0
a
• From the above discussion it is clear, that there is a upper limit for increase in
mechanical powe r input Pm
• As the mechanical powe r is increased, a limiting condition is finally reached at a
point where A1 equals the area above Pm1,max line as shown in fig
• The corresponding can be 1,max
Figure: 5.8
Pm1,max
sin 1,max Pm1,max P
Pmax 1,max sin 1
2,max sin 1 m1,max
Pmax Pmax
• From Fig it is understood, any further increase in Pm1,max will make the area A2
less than the area A1
• This means that the acceleration powe r is more than the deceleration powe r
• Hence the system will have an excess kinetic energy which causes to increase
beyond point c
• If the increases beyond c the deceleration powe r changes to acceleration powe r
and so the system will become unstable
• The system will remain stable even though the rotor may oscillate beyond =90 ,
as long as the equal area criterion is met.
• Hence the condition of =90 for stability is applicable only for steady state
stability and not for transient stability
Clearing time and clearing angle
Figure: 5.9
• Consider a single machine system shown in Fig
• Let the mechanical input be Pm and the machine is operating in steady state
with torque angle 0
Figure: 5.10
• Let a three fault phase fault occur at point F in the system
• Now Pe=0 and the operating point drops to b
• It means the powe r transferred to infinite bus is ze ro and the entire powe r
generated is flowing through the fault
• Now the ope rating point moves along bc
• Let the fault be transient in nature and so the fault be cleared by opening of the
C.B at point c whe re = c and the correspondind time be tc
• Here tc is called clearing time and c is called clearing angle
• It is assumed that the C.B closes its contact imme diately after opening
• Hence normal ope ration is restored
• Now the ope rating point shifts to point d
• Now the rotor decelerates and the operating point moves along dc
• For this transient state, if an angle 1 can be found such that A2=A1, then the
system is found to be stable
• The stable system may finally settles down to the steady operating point a in an
oscillatory manner due to damping in the system
• In the above discussion it is assumed that the fault is cleared at c, but if the fault
clearing is delayed then the angle 1 continue to increase to an upper limit max
• This corresponds to a point where equal areas for A1 and A2 can be found for a
given Pm as shown in fig
Figure: 5.11
• For this situation the fault would have been cleared at an angle cc
• This angle cc is called critical clearing angle
• If the fault is not cleared within critical time, then 1 would increase to a value
greater than max
• In this situation the area A2 will be less than the area A1 and so the system would
be unstable
• For a 3 – Phase fault in simple systems, the equations for cc and tcc can be
obtained as
max = - 0
Pm = Pe =Pmax sin 0
P d P
cc
A1 m m 0
Pm ( cc 0 )
0
When the Powe r feeding is resumed after the fault, Pe = Pmax sin
For a stable system A1=A2. Hence the equations of A1 & A2 can be equated to
solve cc
Pmax cos cc Pm cc Pm 0 Pmax cos max Pm max Pm cc
Pm
cos cc ( max 0 ) cos max
Pmax
Pm
cc cos 1 ( max 0 ) cos max
Pmax
Consider the swing equation of single machine system
H d 2
Pm Pe
f dt 2
f
Pm t 2 0
2H Where 0 is the integral constant
f
cc Pm t cc2 0
2H
2 H ( cc 0 )
t cc
fPm
H d 2
Pm Pe
f dt 2
H
M
f
Pe Pmax sin
Pa Pm Pe Pm Pmax sin
d 2
M Pa
dt 2
d 2 Pa
dt 2 M
• In point by point method, the solution of (t) is obtained by dividing the time into
small equal values of t
Assumptions:
1. The accelerating powe r pa computed at the beginning of an interval is assumed
constant from the middle of the preceding interval to the middle of the interval
being considered
2. The angular velocity is assumed constant throughout any interval. This constant
value is the value corresponding to the midpoint of concerned interval
• The solution starts from the initial condition values, that corresponds to a stable
operating point
Let 0 be the angle corresponding to initial operating point
Figure: 5.12
n-1 – The value of at the end of (n-1) th interval
d 2 Pa
d Pa Pa t
dt 2 M Pa
dt M t M M
Let n-3/2 – the value of at the end of nth inte rval
t
n 1 / 2 n 3 / 2 Pa
M ( n 1)
t
n 3 / 2 n 1 / 2 Pa
M ( n1)
t
t
n1 tn3 / 2
For a change in in nth interval,
n tn1 / 2
n – The Value of at the end of nth interval,
n n1 n
• The above process of computation is repeated to obtain Pa(n), (n+1) and (n+1)
• The solution of (t) is thus obtained in discrete form ove r the desired length of
time
• The normal desired length of time is 0.5 sec
• The continuous form of solution is obtained by drawing a smooth c urve through
discrete values
Modified Euler’s Method
• This method is used to solve the swing equation
• In this the swing equation are transforme d into the state variable form
d
dt
d d f
( ) pa
dt dt H
d f
( ) pa
dt H
3. Assume the occurrence of fault and initialize time i=0. calculate the reduced
admittance matrix for this condition. Set count j=0.
4. Determine the state derivatives and calculate the first state estimate
d
i*1 i / t (t )
dt
d
iP1 i / i t
dt
5. Second estimate of the variable can be obtained if derivatives at t1 =t0 +t so that the
generated powe r can be calculated
6. Determine the average value of the state derivative and obtain the second estimate of
the state variables and the second estimate of the internal voltage angle and machine
angular s peeds
d d P
/ i / i 1
ic1 i dt dt
(t )
2
7. Compute final internal voltage of the generation at the end of [t0 +t] and print
the results
8. Check if t < tcc. If yes advance time by t and go to step 4
The relation between and t for various generators are obtained and stability of
the system can be estimated for a particular type of fault and particular clearing time
Algorithm
1. Obtain a load flow solution for the pre transient condition
2. Calculate the generator internal voltages behind transient reactances
3. Assume the occurrences of a fault and calculate the reduce admittance matrix
for the condition and initialize the time count k=0, initialize j=0
4. Determine the following conditions
K1 k =f1 ( k, k )t
I1 k =f2 ( k, k )t