Air Conditioners

Technical Data
Ceiling Suspended Cassette Unit

EEDEN10-100

FHQ-B
Air Conditioners
Technical Data
Ceiling Suspended Cassette Unit

EEDEN10-100

FHQ-B
• Indoor Units • R-410A • FHQ-BVV1B

TABLE OF CONTENTS !

FHQ-BVV1B

1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
For indoor units only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

3 Safety device settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

4 Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

5 Control systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

6 Dimensional drawing & centre of gravity . . . . . . . . . . . . . . . . . . . . . . . . 9


Dimensional drawing ................................................. 9

7 Piping diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

8 Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
External connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

9 Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Sound level data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Sound pressure spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

10 Air flow pattern . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

• Split Sky Air • Indoor Units 1


• Indoor Units • R-410A • FHQ-BVV1B

1 Features

t i y n k BU S 1 V r AVt o 0B i o 1- ld 4Q npH- RFS•I Slim unit with super silent and greater air flow • Daikin remote controls give you easy control at your fingertips.
• Ideal for shops, restaurants or offices requiring maximum floor space • The wired remote control provides you with a schedule timer,
for furniture, decorations and fittings enabling to program the air conditioning daily or weekly.
• Can be installed in both new and existing buildings. • The optional remote ON/OFF enables you to start/stop the air
conditioning from a mobile phone via a telephone remote control
• Compact casing (only 960 to 1,590mm width).
(field supply).
• Extremely quiet in operation
• The optional forced OFF enables you to switch off the unit
• Auto-swing function ensures efficient air and temperature automatically. E.g. when a window is opened, the unit switches off.
distribution.
• The ’home leave’ operation button prevents large temperature
• Air flow distribution for ceiling heights up to 3.8m without loss of differences by continuously operating at a minimum (heating mode)
capacity. or maximum (cooling mode) preset level while you’re out or sleeping.
• Up to 4 indoor units can be connected to 1 Multi outdoor unit. All It also allows the indoor temperature to return quickly to your
indoor units are individually controllable with remote control and do favourite comfort level.
not need to be installed in the same room or at the same time. They
operate simultaneously within the same cooling operation

heat pump 2 steps optional

35˜60 optional

2 • Split Sky Air • Indoor Units


• Indoor Units • R-410A • FHQ-BVV1B

2 Specifications

2-1 FOR INDOOR UNITS ONLY FHQ35BVV1B FHQ50BVV1B FHQ60BVV1B FHQ71BVV1B FHQ100BVV1B FHQ125BVV1B
Nominal Input Cooling kW 0.111 0.111 0.115 0.117 0.135 0.144

2-2 TECHNICAL SPECIFICATIONS FHQ35BVV1B FHQ50BVV1B FHQ60BVV1B FHQ71BVV1B FHQ100BVV1B FHQ125BVV1B


Casing Colour White
Dimensions Packing Height mm 279 279 279 279 275 275
Width mm 1046 1046 1246 1246 1486 1676
Depth mm 818 818 818 818 818 818
Unit Height mm 195 195 195 195 195 195
Width mm 960 960 1160 1160 1400 1590
Depth mm 680 680 680 680 680 680
Weight Unit kg 24.0 25.0 27.0 27.0 32.0 35.0
Packed Unit kg 31.0 32.0 35.0 35.0 41.0 45.0
Heat Dimensions Length mm 722 722 922 922 1162 1352
Exchanger Nr of Rows 2 3 2 3 3 3
Fin Pitch mm 1.75 1.75 1.75 1.75 1.75 1.75
Nr of Passes 6 6 6 6 11 11
Face m² 0.182 0.182 0.233 0.233 0.293 0.341
Area
Nr of Stages 12 12 12 12 12 12
Empty Tubeplate 2
Hole
Tube type N-Hix
Fin Type ML fin (Multi louver)
Fan Type Sirocco fan
Quantity 3 3 4 4 3 4
Air Flow Rate Cooling High m³/min 13.0 13.0 17.0 17.0 24.0 30.0
Low m³/min 10.0 10.0 13.0 14.0 20.0 25.0
Heating High m³/min 13.0 13.0 16.0 17.0 24.0 30.0
Low m³/min 10.0 10.0 13.0 14.0 20.0 25.0
Fan Motor Quantity 1 1 1 1 1 1
Model 3D12K1AA1 3D12K1AA1 4D12K1AA1 4D12K1AA1 3D12K2AA1 4D12K2AA1
Number of steps 2 2 2 2 2 2
Output W 62 62 62 62 130 130
(high)
Cooling Sound Power High dBA 53.0 54.0 55.0 55.0 58.0 60.0
Low dBA 48.0 49.0 49.0 51.0 53.0 55.0
Sound High dBA 37.0 38.0 39.0 39.0 42.0 44.0
Pressure Low dBA 32.0 33.0 33.0 35.0 37.0 39.0
Heating Sound Power High dBA 53.0 54.0 55.0 55.0 58.0 60.0
Low dBA 48.0 49.0 49.0 51.0 53.0 55.0
Sound High dBA 37.0 38.0 39.0 39.0 42.0 44.0
Pressure Low dBA 32.0 33.0 33.0 35.0 37.0 39.0
Refrigerant Type R-410A
Piping Liquid (OD) Type Flare connection
connections Diameter mm 6.4 6.4 6.4 9.5 9.5 9.5
(OD)
Gas Type Flare connection
Diameter mm 9.5 12.7 12.7 15.9 15.9 15.9
(OD)
Drain Diameter mm VP20 (I.D. 20/O.D. 26)
(OD)
Heat Insulation Foamed polystyrene/polyethylene
Safety Devices Fuse Fuse Fuse
Fan motor thermal protector

• Split Sky Air • Indoor Units 3


• Indoor Units • R-410A • FHQ-BVV1B

2 Specifications

2-2 TECHNICAL SPECIFICATIONS FHQ35BVV1B FHQ50BVV1B FHQ60BVV1B FHQ71BVV1B FHQ100BVV1B FHQ125BVV1B


Standard Item Installation and operation manual
Accessories Quantity 1 1 1 1 1 1
Item Paper pattern for installation
Drain hose
Clamp metal
Insulation for fitting
Sealing pad
Clamps
Washer for hanger bracket

2-3 ELECTRICAL SPECIFICATIONS FHQ35BVV1B FHQ50BVV1B FHQ60BVV1B FHQ71BVV1B FHQ100BVV1B FHQ125BVV1B


Power Supply Name V1
Phase 1 1 1 1 1 1
Frequency Hz 50 50 50 50 50 50
Voltage V 220-240
Power Supply Intake Outdoor unit only

4 • Split Sky Air • Indoor Units


• Indoor Units • R-410A • FHQ-BVV1B

3 Safety device settings

FHQ25~140B

Safety devices 35 40 • 50 60 71 100 125


Fuse 250V 5A 250V 5A 250V 5A - - -
FHQ~BVV1B OFF: 130 ± 5 OFF: 130 ± 5 OFF: 130 ± 5 OFF: 130 ± 5 OFF: 130 ± 5 OFF: 130 ± 5
Fan motor thermal protector °C
ON: 83 ± 20 ON: 83 ± 20 ON: 83 ± 20 ON: 83 ± 20 ON: 83 ± 20 ON: 83 ± 20

3D006611Q

• Split Sky Air • Indoor Units 5


• Indoor Units • R-410A • FHQ-BVV1B

4 Options

FHQ35∼ 60B

Name of option FHQ∼ B


35 50 60
Replacement long-life filter KAFJ501DA56 KAFJ501DA80
Drain up kit KDU50N60VE
L-type piping kit (for upward direction) KHFP5MA35 KHFP5MA63
Remote control Wired type BRC1D528
Infrared type Heat pump BRC7EA63W
Cooling only BRC7EA66
Central remote control DCS302CA51
Unified ON/OFF control DCS301BA51
Schedule timer DST301BA51
Adapter for wiring KRP1BA54
Wiring adapter (hour meter) EKRP1B2A
Adaptor for external ON/OFF and monitoring z1 KRP4AA52
Interface adapter for Sky Air series DTA112BA51
Installation box for adapter PCB KRP1CA93
Remote ON/OFF, forced OFF EKROROA
3D038056A
Note z1: Installation box for adapter PCB (KRP1CA93) is necessary.

6 • Split Sky Air • Indoor Units


• Indoor Units • R-410A • FHQ-BVV1B

4 Options

FHQ∼B
Name of option Remark
71 100 125
Replacement long-life filter KAF501DA80 KAF501DA112 KAF501DA160
Drain up kit KDU50N125VE
L-type piping kit (for upward direction) KHFP5MA160
Remote control Wired type BRC1D528
Infrared type For Heat pump BRC7EA63W
For cooling only BRC7EA66
Central remote control DCS302CA51
Unified ON/OFF control DCS301BA51
Schedule timer DST301BA51
Adapter for wiring KRP1BA54
Wiring adapter for electrical appendices *1 KRP4AA52
Interface adapter for Sky Air series DTA112BA51
Installation box for adapter PCB KRP1CA93
Remote sensor KRCS01-1A
Connector for forced on, forced off EKROROA
Electrical box with earth terminal (3 blocks) KJB311AA
Electrical box with earth terminal (2 blocks) KJB212AA
3D044485B
NOTE: *1: Installation box for adapter PCB (KRP1CA93) is necessary

• Split Sky Air • Indoor Units 7


• Indoor Units • R-410A • FHQ-BVV1B

5 Dimensional drawing & centre of gravity


5-1 Dimensional drawing
FHQ35B

(Required space)
Position slit hole for taking out in piping back

(Hanging position)
(View from the front)
(Required space)

Hanging bolt (Hanging position)

Position: hole of wall for taking out in piping back

(View from the front)


(Required space)
780 From the floor side 2500 or more

300or more

30 or more 30 or more
For height installation

(Service space) (Service space)


View from the front
Brand name plate
Obstacle (Note 2)
Floor side
1 Air discharge grille
Drain pipe connection 2 Air suction grille
VP20
3 Air filter
(For left piping) 4 Gas pipe connection J9.5 flare
5 Liquid pipe connection J6.4 flare
6 Drain pipe connection VP20
7 Earth terminal (inside the electric components box) M4
8 Suspension bracket
9 Backward piping and wiring connection opening lid
10 Upward piping and wiring connection opening lid
11 Right side pipe connection - slit hole
Note:
1. Location of unit’s name plate: bottom of fan housing inside the suction 12 Left back drain pipe connection - slit hole
grille. 13 Right side drain pipe connection - slit hole
2. In case of using infrared remote control, this position will be a signal 14 Right side drain piping connection hole - slit hole
receiver. Refer to the drawing of infrared remote control in detail. 15 Hole of wall for taking out in piping back J100
3. The remote control code is the standard (about 3m outside the machine) 16 Upward drain pipe connection J60
attached.2 17 Upward gas pipe connection J36
(0.5 mm x 2 Wicks x O.D. J5.4)
18 Upward liquid pipe connection J26

3D037996A

FHQ50B

(Required space)
(Hanging position)

Position slit hole for taking out in piping back

(View from the front)


(Required space)

Hanging bolt (Hanging position)

Position: hole of wall for taking out in piping back

(View from the front)


(Required space)
780 From the floor side 2500 or more

300or more

30 or more 30 or more
(Service space) (Service space)
View from the front
For height installation

Brand name plate


(Note 2) 1 Air discharge grille
Obstacle 2 Air suction grille
Floor side
3 Air filter
Drain pipe connection 4 Gas pipe connection J12.7 flare
VP20 5 Liquid pipe connection J6.4 flare
(For left piping) 6 Drain pipe connection VP20
7 Earth terminal (inside the electric components box) M4
8 Suspension bracket
9 Backward piping and wiring connection opening lid
10 Upward piping and wiring connection opening lid
11 Right side pipe connection - slit hole
12 Left back drain pipe connection - slit hole
Note: 13 Right side drain pipe connection - slit hole
1. Location of unit’s name plate: bottom of fan housing inside the suction 14 Right side drain piping connection hole - slit hole
grille. 15 Hole of wall for taking out in piping back J100
2. In case of using infrared remote control, this position will be a signal 16 Upward drain pipe connection J60
receiver. Refer to the drawing of infrared remote control in detail. 17 Upward gas pipe connection J36
3. The remote control code is the standard (about 3m outside the machine) 18 Upward liquid pipe connection J26
attached.2
(0.5 mm x 2 Wicks x O.D. J5.4)

3D027536D

• Split Sky Air • Indoor Units 8


• Indoor Units • R-410A • FHQ-BVV1B

5 Dimensional drawing & centre of gravity


5-1 Dimensional drawing
FHQ60B

(Hanging position)

(Required space)
Position slit hole for taking out in piping back

(View from the front)


(Required space)

Hanging bolt (Hanging position)

Position: hole of wall for taking out in piping back

(View from the front)


780 From the floor side 2500 or more
For height installation

(Required space)
300or more

30 or more 30 or more
(Service space) View from the front (Service space)

Brand name plate


Obstacle
Floor side (Note 2) 1 Air discharge grille
2 Air suction grille
3 Air filter
Drain pipe connection 4 Gas pipe connection J12.7 flare
VP20 5 Liquid pipe connection J6.4 flare
(For left piping) 6 Drain pipe connection VP20
7 Earth terminal (inside the electric components box) M4
8 Suspension bracket
9 Backward piping and wiring connection opening lid
10 Upward piping and wiring connection opening lid
11 Right side pipe connection - slit hole
12 Left back drain pipe connection - slit hole
Note: 13 Right side drain pipe connection - slit hole
1. Location of unit’s name plate: bottom of fan housing inside the suction 14 Right side drain piping connection hole - slit hole
grille. 15 Hole of wall for taking out in piping back J100
2. In case of using infrared remote control, this position will be a signal
receiver. Refer to the drawing of infrared remote control in detail. 16 Upward drain pipe connection J60
3. The remote control code is the standard (about 3m outside the machine) 17 Upward gas pipe connection J36
attached.2 18 Upward liquid pipe connection J26
(0.5 mm x 2 Wicks x O.D. J5.4)

3D037994A

FHQ71B

(Required space)
(Hanging position)

Position slit hole for taking out in piping back

(View from the front)


(Required space)

Hanging bolt (Hanging position)

Position: hole of wall for taking out in piping back

(View from the front)


From the floor side 2500 or more
For height installation

(Required space)
300or more

30 or more 30 or more
(Service space) View from the front (Service space)

Brand name plate


Obstacle
Floor side (Note 2)
1 Air discharge grille
2 Air suction grille
Drain pipe connection 3 Air filter
VP20 4 Gas pipe connection J15.9 flare
(For left piping) 5 Liquid pipe connection J9.5 flare
6 Drain pipe connection VP20
7 Earth terminal (inside the electric components box) M4
8 Suspension bracket
9 Backward piping and wiring connection opening lid
10 Upward piping and wiring connection opening lid
11 Right side pipe connection - slit hole
Note: 12 Left back drain pipe connection - slit hole
1. Location of unit’s name plate: bottom of fan housing inside the suction 13 Right side drain pipe connection - slit hole
grille. 14 Right side drain piping connection hole - slit hole
2. In case of using infrared remote control, this position will be a signal
15 Hole of wall for taking out in piping back J100
receiver. Refer to the drawing of infrared remote control in detail.
3. The remote control code is the standard (about 3m outside the machine) 16 Upward drain pipe connection J60
attached.2 17 Upward gas pipe connection J36
(0.5 mm x 2 Wicks x O.D. J5.4) 18 Upward liquid pipe connection J26

3D027538E

• Split Sky Air • Indoor Units 9


• Indoor Units • R-410A • FHQ-BVV1B

5 Dimensional drawing & centre of gravity


5-1 Dimensional drawing
FHQ100B

(Hanging position)

(Required space)
Position slit hole for taking out in piping back
(View from the front)
(Required space)

Hanging bolt (Hanging position)

Position: hole of wall for taking out in piping back

(View from the front)


780 From the floor side 2500 or more
For height installation

(Required space)
300or more

30 or more 30 or more
(Service space) (Service space)
View from the front
Obstacle Brand name plate
Floor side
(Note 2) 1 Air discharge grille
Drain pipe connection 2 Air suction grille
VP20 3 Air filter
4 Gas pipe connection J15.9 flare
(For left piping) 5 Liquid pipe connection J9.5 flare
6 Drain pipe connection VP20
7 Earth terminal (inside the electric components box) M4
8 Suspension bracket
9 Backward piping and wiring connection opening lid
10 Upward piping and wiring connection opening lid
11 Right side pipe connection - slit hole
12 Left back drain pipe connection - slit hole
Note: 13 Right side drain pipe connection - slit hole
1. Location of unit’s name plate: bottom of fan housing inside the suction 14 Right side drain piping connection hole - slit hole
grille. 15 Hole of wall for taking out in piping back J100
2. In case of using infrared remote control, this position will be a signal
receiver. Refer to the drawing of infrared remote control in detail. 16 Upward drain pipe connection J60
3. The remote control code is the standard (about 3m outside the machine) 17 Upward gas pipe connection J36
attached.2 18 Upward liquid pipe connection J26
(0.5 mm x 2 Wicks x O.D. J5.4)
3D044893A

FHQ125BU
(Hanging position)

(Required space)
Position slit hole for taking out in piping back

(View from the front)


(Required space)

Hanging bolt (Hanging position)

Position: hole of wall for taking out in piping back


(View from the front)
780 From the floor side 2500 or more

(Required space)
For height installation

300or more

30 or more 30 or more
(Service space) (Service space)
View from the front
Brand name plate
Obstacle
Floor side (Note 2)
1 Air discharge grille
2 Air suction grille
Drain pipe connection VP20 3 Air filter
(For left piping) 4 Gas pipe connection J15.9 flare
5 Liquid pipe connection J9.5 flare
6 Drain pipe connection VP20
7 Earth terminal (inside the electric components box) M4
8 Suspension bracket
9 Backward piping and wiring connection opening lid
10 Upward piping and wiring connection opening lid
11 Right side pipe connection - slit hole
12 Left back drain pipe connection - slit hole
Note: 13 Right side drain pipe connection - slit hole
1. Location of unit’s name plate: bottom of fan housing inside the suction 14 Right side drain piping connection hole - slit hole
grille. 15 Hole of wall for taking out in piping back J100
2. In case of using infrared remote control, this position will be a signal
receiver. Refer to the drawing of infrared remote control in detail. 16 Upward drain pipe connection J60
3. The remote control code is the standard (about 3m outside the machine) 17 Upward gas pipe connection J36
attached.2 18 Upward liquid pipe connection J26
(0.5 mm x 2 Wicks x O.D. J5.4)
3D0448994B

10 • Split Sky Air • Indoor Units


• Indoor Units • R-410A • FHQ-BVV1B

6 Piping diagram

FHQ35∼ 125B

Indoor heat exchanger

Model A B
FHQ35B 6.4 9.5
FHQ50-60B 6.4 12.7
FHQ71,100,125B 9.5 15.9

Field pipingJA C1220T-O


To outdoor unit
Field pipingJB C1220-O

Indoor unit

O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe PSpinned pipe
4D037995H

11 • Split Sky Air • Indoor Units


• Indoor Units • R-410A • FHQ-BVV1B

7 Wiring diagram
7-1 Wiring diagram
FHQ35∼60B
Connecter discrimination colour for components.
In case of simultaneous operation system. Connecter colour for components.
Connecter colour for printed circuit board.

Notes Indoor unit Indoor unit To outdoor


(master) (slave) unit
1. D : Terminal F, : Connector

To outdoor unit
Note) 4
Wired remote control
b : Protective earth (screw)
2. B : Field wiring
3. In case using central remote control, connect it to the
unit in accordance with the attached instruction
manual. Infrared remote
4. X24A is connected when the infrared remote control control
kit is being used. Note) 6
5. Remote control model varies according to the Note) 4
combination system, confirm technical materials and Receiver / display unit
catalogs, etc. before connecting.
6. In case installing the drain pump (M1P), remove the
jumper connector of X15A and execute the additional Note) 6
wiring for float switch and drain pump.
7. Symbols show as follows Red:red, Blk:black, Ylw:yellow, Control box
Org:orange, Gry:gray, Prp:purple, Blu:blue

1-RED, 2-WHITE, 3-BLACK S1Q Limit switch (swing flap) Infrared remote control Connector for optional parts
A1P Printed circuit board T1R Transformer(220-240V/22V) Receiver / display unit X15A Connector (float switch)
C1R Capacitor (M1F) V1TR Phase control circuit A3P Printed circuit board X25A Connector (drain pump)
F1U Fuse(F5A 250V) X1M Terminal block A4P Printed circuit board X33A Connector (adapter for wiring)
HAP Light emitting diode (service monitor green) X2M Terminal block BS1 Push button (on/off) X35A Connector (group control adapter)
KAR Magnetic relay (M1S) ? Signal receiver circuit H1P Light emitting diode (service monitor red) X40A Connector
KPR Magnetic relay (M1P) . Signal transmission circuit H2P Light emitting diode (service monitor green) (ON/OFF input from outside)
M1S Motor (swing flap) Wired remote control H3P Light emitting diode (service monitor red) X60A Connector (interface adapter for sky air series)
M1F Motor (indoor fan) R1T Thermistor (air) H4P Light emitting diode (service monitor orange) X61A
Q1M Thermo switch (M1F embedded) SS1 Selector switch (main/sub) SS1 Selector switch (main/sub)
R1T Thermistor (air) SS2 Selector switch (wireless address set)
R2T Thermistor (coil)1
R3T Thermistor (coil)2
3D037842D

FHQ71,100,125B

In case of simultaneous operation system.


Notes
Indoor unit Indoor unit To outdoor unit
(master) (slave)
1. D : Terminal F, : Connector
Note) 4
To outdoor unit

b : Protective earth (screw) Wired remote control

2. : Field wiring
3. In case using central remote control, connect it to the
unit in accordance with the attached instruction
manual.
4. X24A is connected when the infrared remote control Infrared remote
control
kit is being used. Note) 6
5. Remote control model varies according to the Note) 4
combination system, confirm technical materials and
catalogs, etc. before connecting. Receiver / display unit
6. In case installing the drain pump (M1P), remove the
jumper connector of X15A and execute the additional Note) 6
wiring for float switch and drain pump.
7. Symbols show as follows Red:red, Blk:black, Ylw:yellow,
Org:orange, Gry:gray, Prp:purple, Blu:blue

Control box

1-RED, 2-WHITE, 3-BLACK S1Q Limit switch (swing flap) Infrared remote control Connector for optional parts
A1P Printed circuit board T1R Transformer(220-240V/22V) Receiver / display unit X15A Connector (float switch)
C1R Capacitor (M1F) V1TR Phase control circuit A2P Printed circuit board X25A Connector (drain pump)
HAP Light emitting diode (service monitor green) X1M Terminal block A3P Printed circuit board X33A Connector (adapter for wiring)
KAR Magnetic relay (M1S) X2M Terminal block BS1 Push button (on/off) X35A Connector (group control adapter)
KPR Magnetic relay (M1P) ? Signal receiver circuit H1P Light emitting diode (service monitor red) X40A Connector
M1S Motor (swing flap) . Signal transmission circuit H2P Light emitting diode (service monitor green) (ON/OFF input from outside)
M1F Motor (indoor fan) Wired remote control H3P Light emitting diode (service monitor red) X60A Connector (interface adapter for sky air series)
Q1M Thermo switch (M1F embedded) R1T Thermistor (air) H4P Light emitting diode (service monitor orange) X61A
R1T Thermistor (air) SS1 Selector switch (main/sub) SS1 Selector switch (main/sub)
R2T Thermistor (coil) SS2 Selector switch (wireless address set)

4D043825B

• Split Sky Air • Indoor Units 12


• Indoor Units • R-410A • FHQ-BVV1B

7 Wiring diagram
7-2 External connection diagram

NOTES
1 Line voltage wiring
Control circuit wiring
2 All wiring, components and materials to be produced on the site must comply with the applicable local and national codes.
3 Use copper conductors only.
4 See wiring diagrams for details.
5 Install fuse and mainswitch for safety.
6 All field wiring and components must be provided by a licensed electrician.
7 The unit shall be grounded in compilance with the applicable local and national codes.
8 Wiring shown are general points-of-connection guides only and are not intended for or to include all details for a specific
installation.
9 Never share a common power supply with other equipment.
V1, Model T1, Model
Power supply Power supply
1∼50Hz 1∼50Hz
220V-240V 230V

Main switch Main switch

Fuse Fuse

4D044483B

• Split Sky Air • Indoor Units 13


• Indoor Units • R-410A • FHQ-BVV1B

8 Sound data
8-1 Sound level data
Sound pressure level
230V Sound power level
Model 50Hz
Measuring location
H L H L
(cooling/heating) (cooling/heating) (cooling/heating) (cooling/heating)
FHQ35BUV1B 37/37 32/32 Location of microphone
53/53 48/48
FHQ50BUV1B 38/38 33/33 54/54 49/49
FHQ60BUV1B 39/- 33/- 55/- 49/-
FHQ71BUV1B 39/39 35/35 55/55 51/51
Microphone
FHQ100BUV1B 42/42 37/37 58/58 53/53
FHQ125BUV1B 44/44 39/39 60/60 55/55

• Split Sky Air • Indoor Units 14


• Indoor Units • R-410A • FHQ-BVV1B

8 Sound data
8-2 Sound pressure spectrum

FHQ35B FHQ50B
Octave band sound pressure level

Octave band sound pressure level


H (230V)
H (230V)

L (230V) L (230V)

approximate
approximate threshold hearing
threshold hearing for continuous
for continuous noise
noise

4D028280B 4D028281B
Octave band center frequency (Hz) Octave band center frequency (Hz)

NOTES
NOTES
1 Sound pressure levels are measured in an anechoic
room. 1 Sound pressure levels are measured in an anechoic
room.
2 Operation sound levels are valid at nominal
operation condition 2 Operation sound levels are valid at nominal
operation condition
3 Operation sound level differs with operation and
ambient conditions. 3 Operation sound level differs with operation and
ambient conditions.

FHQ60B FHQ71B
Octave band sound pressure level

Octave band sound pressure level

H (230V)

L (230V)
H

approximate
threshold hearing
for continuous
noise
approximate threshold
hearing for continuous
noise

4D037997A
Octave band center frequency (Hz)

NOTES 4D028355B
Octave band center frequency (Hz)

1 Sound pressure levels are measured in an anechoic


room.
2 Operation sound levels are valid at nominal NOTES
operation condition
3 Operation sound level differs with operation and 1 Operation sound is measured in an anechoic
ambient conditions. chamber.
2 Operation sound level differs with operation and
ambient conditions.
3 Sound levels are valid at nominal operation
conditions.

• Split Sky Air • Indoor Units 15


• Indoor Units • R-410A • FHQ-BVV1B

8 Sound data
8-2 Sound pressure spectrum
FHQ100B
FHQ125B
Octave band sound pressure level

Octave band sound pressure level


H H
L
L

approximate threshold
hearing for continuous
noise approximate threshold
hearing for continuous
noise

4D028283B
Octave band center frequency (Hz)
4D028284B
Octave band center frequency (Hz)

NOTES
NOTES
1 Operation sound is measured in an anechoic
chamber. 1 Operation sound is measured in an anechoic
chamber.
2 Operation sound level differs with operation and
ambient conditions. 2 Operation sound level differs with operation and
ambient conditions.
3 Sound levels are valid at nominal operation
conditions. 3 Sound levels are valid at nominal operation
conditions.

16 • Split Sky Air • Indoor Units


• Indoor Units • R-410A • FHQ-BVV1B

9 Air flow pattern

FHQ35∼50B

Cooling - air velocity distribution

Air flow direction: horizontal

FHQ35∼50B

Cooling - air temperature distribution

Air flow direction: horizontal

4D028550

17 • Split Sky Air • Indoor Units


• Indoor Units • R-410A • FHQ-BVV1B

9 Air flow pattern

FHQ60-71B

Cooling - air velocity distribution

Air flow direction: horizontal

FHQ60-71B

Cooling - air temperature distribution

Air flow direction: horizontal

4D028551B

18 • Split Sky Air • Indoor Units


• Indoor Units • R-410A • FHQ-BVV1B

9 Air flow pattern

FHQ100B

Cooling - air velocity distribution

Air flow direction: horizontal

FHQ100B

Cooling - air temperature distribution

Air flow direction: horizontal

4D028552B

• Split Sky Air • Indoor Units 19


• Indoor Units • R-410A • FHQ-BVV1B

9 Air flow pattern

FHQ125B

Cooling - air velocity distribution

Air flow direction: horizontal

FHQ125B

Cooling - air temperature distribution

Air flow direction: horizontal

4D028553B

20 • Split Sky Air • Indoor Units


• Indoor Units • R-410A • FHQ-BVV1B

9 Air flow pattern

FHQ35∼50B

Heating - air velocity distribution

Air flow direction: 45° (downward)

FHQ35∼50B

Heating - air temperature distribution

Air flow direction: 45° (downward)

4D028554

• Split Sky Air • Indoor Units 21


• Indoor Units • R-410A • FHQ-BVV1B

9 Air flow pattern

FHQ60-71B

Heating - air velocity distribution

Air flow direction: 45° (downward)

FHQ60-71B

Heating - air temperature distribution

Air flow direction: 45° (downward)

4D028555B

22 • Split Sky Air • Indoor Units


• Indoor Units • R-410A • FHQ-BVV1B

9 Air flow pattern

FHQ100B

Heating - air velocity distribution

Air flow direction: 45° (downward)

FHQ100B

Heating - air temperature distribution

Air flow direction: 45° (downward)

4D028556B

• Split Sky Air • Indoor Units 23


• Indoor Units • R-410A • FHQ-BVV1B

9 Air flow pattern

FHQ125B

Heating - air velocity distribution

Air flow direction: 45° (downward)

FHQ125B

Heating - air temperature distribution

Air flow direction: 45° (downward)

4D028557B

24 • Split Sky Air • Indoor Units


Responsible Editor: Daikin Europe N.V., Zandvoordestraat 300, B-8400 Oostende
Prepared in Belgium by Lannoo (www.lannooprint.be), a company whose concern

Daikin’s unique position as a manufacturer of air The present publication is drawn up by way of information only and does not constitute an offer binding
conditioning equipment, compressors and refrigerants upon Daikin Europe N.V.. Daikin Europe N.V. has compiled the content of this publication to the best of its
has led to its close involvement in environmental issues. knowledge. No express or implied warranty is given for the completeness, accuracy, reliability or fitness for
for the environment is set in the EMAS and ISO 14001 systems.

For several years Daikin has had the intention to become particular purpose of its content and the products and services presented therein. Specifications are subject
a leader in the provision of products that have limited to change without prior notice. Daikin Europe N.V. explicitly rejects any liability for any direct or indirect
impact on the environment. This challenge demands the damage, in the broadest sense, arising from or related to the use and/or interpretation of this publication. All
eco design and development of a wide range of products content is copyrighted by Daikin Europe N.V..
The present publication supersedes EEDEN09-100

and an energy management system, resulting in energy


conservation and a reduction of waste.
EEDEN10-100 • 04/10 • Copyright Daikin