Data Sheet

IQ241
Controller

IQ241 Controller

Description Features
The IQ241 controllers are of medium capacity designed for the • 1 second cycle time.
control of all types of building plant. They can provide a minimum of • Optional integral/external Display Panel.
12 digital inputs, and 8 analogue voltage outputs. A further 20 I/O • Access to entire network by way of local supervisor
points can be made available by using up to 10 S cards, each connection.
providing 2 inputs or outputs of the same type (8 input only, 12 input • Facility for mounting an additional node controller.
or output). S cards can provide analogue current, analogue voltage, • High capacity DDC with PID control loops.
thermistor, or digital inputs, or analogue voltage outputs giving the • Stand alone or integrated system operation.
IQ241 sufficient capability for more complex strategies. It can • 12 digital inputs.
operate either as a stand alone device or as part of a Building • 8 analogue voltage outputs.
Management System. A standard Display Panel can be mounted • 10 slots for S cards (20 I/O points)
on the front cover, or externally. The IQ241 also has the facility to
connect any IQ system supervisor or Engineering Tool to the
network without a separate node controller.

Physical
230 Vac Input Power Knockouts for M20 cable gland
Knockout for RDS connector
Knockout for additional node RS232
(3.35”)
85 mm

24 V Input Power

I/O LEDs
325 mm
(12.8”)

S card fittings
under flap
V
1 3 5 7 9 1 1 1 3 1 5 1 7 1 9 2 1 2 3 2 5 2 7 2 9 3 1 3 3 3 5 3 7 3 9
2 4 6 8 1 0 1 2 1 4 1 6 1 8 2 0 2 2 2 4 2 6 2 8 3 0 3 2 3 4 3 6 3 8 4 0

LEDs 1 2 3 4 5 6 7 8
TX

9 1 0
RX

1 1 1 2 1 3 1 4 1 5 1 6 1 7 1 8 1 9 2 0 2 1 2 2 2 3 2 4 2 5 2 6 2 7 2 8 2 9 3 0 3 1 3 2 3 3 3 4 3 5 3 6 3 7 3 8 3 9 4 0

Channel identification label


I1 d ig ita l in p u ts I1 2 I1 3 I2 0 I2 1 I3 2
S 1 a n a lo g u e in p u ts S 8 S 9 S 1 5
L 2 0 L 9 L 8 a n a lo g u e o u tp u ts L 1

LAN 1 C 3 C 5 C 7 C 9 C 11 C 13 C 15 C 17 C 19 C 21 C 23 C 25 C 27 C 29 C 31 C 33 C 35 C 37 C 39 C AUX
24v
2 C 4 C 6 C 8 C 10 C 12 C 14 C 16 C 18 C 20 C 22 C 24 C 26 C 28 C 30 C 32 C 34 C 36 C 38 C 40 C + - + -

Network connectors
Supervisor
I/O connectors port

Earthing (grounding)bar 355 mm (13.98”) Auxiliary supply

IQ241 Controller Data Sheet TA103013 Issue 2, 4/03/2009 1


IQ241 Data Sheet

FUNCTIONALITY
The IQ241 Controller’s functionality can be divided into three sections, the strategy,firmware, and the hardware.

STRATEGY FIRMWARE
The strategy processes inputs according to a set of instructions Communications: When operating as part of a Building
and then outputs signals which can be used to control plant. Management System, the IQ241 will be connected to other devices
by way of the IQ system Network. This means that information
Configuration: The IQ241 uses the standard IQ configuration within the IQ241 can be accessed using one of the IQ system
mode which enables configuration by way of the network, or by supervisor programs, or passed to other IQ controllers using
direct connection. Alternatively SET (System Engineering Tool) inter-controller communications, enabling the sharing of
can be used to create an .IQF strategy data file which can then information across the whole system.
be downloaded to the controller. SET can also be used to upload,
and download .IQF files for backup purposes. When connected to the network the controller can use up to 3
different addresses. One address is for the controller itself, the
Modules: The strategy consists of a number of individual second and third are optional, and are for the Network Display
functional blocks known as configuration modules. These blocks Panel, and locally connected supervisor. This means that both
can be linked in various combinations to enable plant to be the Network Display Panel and supervisor have their own
controlled appropriate to the building’s requirements. The table network addresses when connected to the network by way of
lists the different types of configuration modules and the number the controller.
of each type available with IQ241.
The controller’s address is set by a switch on the module, and
Module Type Number Module Type Number the addresses for the network display panel, and supervisor are
Sensor 48 Critical Alarm 4 software selectable.
Sensor type 15 Alarm History 20
Loop 32 IC Comms 16 HARDWARE
Function 160 Digital Inputs 48
Logic 160 Fast Sequence 8 Unit: The IQ241 is supplied in a metal and plastic enclosure
Driver 32 Zone 5 which provides IP40 protection for the unit.
Knob 30 Schedule 32
Switch 20 Calendar 20 Network: The network terminals facilitate connection of 4 or 2
Sensor log 32 User Password 6 wire cables. The address and baud rate (19k2, 9k6, or 1k2) are
Sequence step 400 Sequence time 1s selected by switches. The standard Trend node features are
Analogue Nodes 255 Digital Nodes 506 included (TX RX, and network OK indicators, bypass relay,
and network alarm generation). There is also the facility for
Display 200 Directory 40
connection of a supervisor to the network by way of the
Page 50 Group 10
controller without the need for additional node controllers. A
Route 50 Destination 7
location is also provided for mounting an extra node controller,
New Alarm Log 200 e.g. TMN, should this be required.
Full details of the modules are given in the IQ Configuration
Manual and Addendum. The IQ241 contains the normal IQ2 Address/Baud rate switch: The address on the Lan is set by
features as described in IQ Configuration Manual Addendum: poles 1 to 7 in range 1, 4 to 9, 11 to 119 and must be unique on
Engineers Journal (J), I/O Summary (i/o), Loader Issue (R(c), the Lan. The baud rate is set by poles 8 to 10 in the range 1k2,
‘c’lower case), Serial Number (R(s), ‘s’ lower case), Supply 9k6, 19k2 and must match the other nodes on the Lan. The
Frequency Option, Enhanced Logging, Module position, and
address/baud rate switch may also be used to perform a strategy
Strategy Cleardown.
cleardown; this is done by setting all the address/baud rate poles
I/O Channel reference: The IQ241 has very flexible I/O which to zero before power up (see Installation Instructions, TG103012
can be configured in a number of ways. The configuration input sheet 3 and IQ Configuration Manual Addendum). For this reason
modules (sensors and digital inputs) and the output modules the address should normally be set non-zero.
(drivers) are related to the external channels as shown in the
table below. The external channel reference for these modules Indicators: LED indicators for receive and transmit network
is displayed in configuration mode. current flow (RX, TX) and network OK ( ), also for power ( ),
Module type Module reference External channel all I/O channels ( ), and watchdog ( ). See specification
Sensor-analogue input S1 to S20 13 to 32 section for details.
S1 to S32 (not
Sensor-digital input 1 to 32 Connectors: Two part connectors are used throughout to
normally used*)
facilitate wiring. The 230 Vac input power uses a standard IEC
Digital input I1 to I32 1 to 32 connector. An earthing (grounding) bar is provided for screen
Driver channel 1 to termination.
Driver 40 to 21
driver channel 20
The table below specifies the possible modes for each channel. Power: 230 Vac 50/60 Hz, 24 Vac 50/60 Hz or 24 Vdc.
The 24 Vac supply must be isolated and can only supply 1
Mo d u l e In p u t Mo d es controller.
analogue input, digital input*, inter nal analogue, The 24 Vdc supply may be earthed (grounded) but polarity must
S1 to S20
internal digital be correct; it can supply several controllers in parallel.
S21 to S32 digital input*, internal analogue, internal digital
S33 to S48 internal analogue, internal digital
I1 to I32 digital input
I33 to I48 internal digital
Note that as sensors and digital inputs are supported separately
on the display panel, and have separate labels, use of sensor
modules in digital input mode is not normally required.

2 IQ241 Controller Data Sheet TA103013 Issue 2, 4/03/2009


Data Sheet IQ241

HARDWARE (continued)
Fusing: The controller has no replaceable fuses; protection is PC: A computer running an IQ system Supervisor or Engineering
provided by means of a self resetting thermally protected transformer. Tool, or an IQView or a wireless sensor receiver XW/R/IQ can
The 24 Vac or dc versions have a 4A replaceable 1¼” fuse fitted be connected to the IQ system network by way of the controller’s
in line of the supply cable inside the unit and a solid state multifuse. supervisor port without the need for an additional node controller
Note that a switch or circuit breaker must be included in the although it does have its own network address. When connected
supply to the unit and in close proximity to it, and must be clearly in this way the supervisor will have access to all devices on the
marked as the disconnecting device for the unit. network, and will function as if it were connected by way of its
The I/O modules are also individually protected against short own node controller. A wall mounting display, room display (RD),
circuits. or smart display unit (SDU) may be connected to the local
supervisor port. Both displays monitor and adjust parameters in
Battery Backup: Details about the strategy configuration, time the local IQ241 only. The RD enables temperature setpoint display
and date, and logged data are stored in RAM. A plug-in lithium and adjustment with options for occupancy override and fan
cell provides power to maintain the data in the event of power speed adjustment (see order codes section). The SDU enables
failure, or the controller being switched off. monitor and adjustment of selected parameters. Only one such
device (PC, IQView, RD, SDU, XW/R/IQ) may be connected to the
S Cards: S Cards enable the IQ configuration of the controller supervisor port at one time.
to be set up according to user requirements. Each card provides
2 input/output channels of the same type and is supplied complete The diagrams below illustrate the various combinations in which
with terminals. The range of S Cards provides analogue current, the display panels, and supervisor/engineering tools can be
analogue voltage, thermistor, and digital inputs, or analogue connected.
voltage outputs. The IQ241 has space for 10 S Cards providing IQ 2 4 1
up to 20 additional I/O channels (8 input only, 12 input or output). D P

Auxiliary Supplies: The IQ241 has two types of auxiliary B


A
Integral DP
supply which share 1000 mA. Both are thermally protected and D
C

can supply 24 Vdc at a maximum of 500 mA. The first is a single


connector for relay modules, sensors, external DP etc. V

The second consists of 20 connectors for relay modules etc.


1 3 5 7 9 1 1 1 3 1 5 1 7 1 9 2 1 2 3 2 5 2 7 2 9 3 1 3 3 3 5 3 7 3 9
2 4 6 8 1 0 1 2 1 4 1 6 1 8 2 0 2 2 2 4 2 6 2 8 3 0 3 2 3 4 3 6 3 8 4 0

T X R X

connected to channels 21 to 40. L A N A U X

The 1000 mA will normally be available, but if the IQ241 has an


1 C 3 C 5 C 7 C 9 C 1 1 C 1 3 C 1 5 C 1 7 C 1 9 C 2 1 C 2 3 C 2 5 C 2 7 C 2 9 C 3 1 C 3 3 C 3 5 C 3 7 C 3 9 C 2 4 v
2 C 4 C 6 C 8 C 1 0 C 1 2 C 1 4 C 1 6 C 1 8 C 2 0 C 2 2 C 2 4 C 2 6 C 2 8 C 3 0 C 3 2 C 3 4 C 3 6 C 3 8 C 4 0 C + - + -

integral node controller fitted, only 900 mA would be available


to be shared between the two supplies.

Displays: The IQ241 can be fitted with several different types


of display, a 2-line Display Panel, IQView, and a PC. The IQ241
has 2 ports, the local supervisor port on the front panel (RJ11)
and the NDP port under the cover on the main board. These
correspond to the two extra CNC addresses provided by the
IQ241; the local supervisor port address, and the NDP port
address.
PC, IQView, RD, SDU or XW/R/IQ
NDP 24V supply (NDP PWR) (connected via Supervisor port)

FPK or HDP
D P

(connected via DP port A

if KIT/2xx/RDS fitted) C

IQ 2 4 1

NDP Port (NDP) local supervisor port (RJ11)


2-line Display Panel: The controller may be purchased with a
2DP option fitted in the cover or there is a retrofit kit (KIT/DP2) to 1
2
3
4
5
6
7
8
9
1 0
1 1
1 2
1 3
1 4
1 5
1 6
1 7
1 8
1 9
2 0
2 1
2 2
2 3
2 4
2 5
2 6
2 7
2 8
2 9
3 0
3 1
3 2
3 3
3 4
3 5
3 6
V
3 7
3 8
3 9
4 0

add an integral 2DP. Alternatively an external 2DP (i.e. HDP, FPK, T X R X

)may be connected by fitting the KIT/2xx/RDS option which L A N 1


2
C
C
3
4
C
C
5
6
C
C
7
8
C 9 C 1 1 C 1 3 C 1 5 C 1 7 C 1 9 C 2 1 C 2 3 C 2 5 C 2 7 C 2 9 C 3 1 C 3 3 C 3 5 C 3 7 C 3 9 C
C 1 0 C 1 2 C 1 4 C 1 6 C 1 8 C 2 0 C 2 2 C 2 4 C 2 6 C 2 8 C 3 0 C 3 2 C 3 4 C 3 6 C 3 8 C 4 0 C +
2 4 v
A U X
- + -

provides a 25 way D type female connector on the upper face


of the unit. If a display panel is mounted in the front cover, it will
not be possible to connect an external 2-line display. The 2DP
provides access to parameters within the controller. Fitting an
external 2DP will reduce available 24 Vdc auxiliary current by
30 mA (see Auxiliary Supply section).

PC, IQView, RD, SDU or XW/R/IQ


(connected via Supervisor port)

IQ241 Controller Data Sheet TA103013 Issue 2, 4/03/2009 3


IQ241 Data Sheet

HARDWARE (continued)

Inputs/Outputs: The IQ241 has 12 digital inputs and 8 analogue voltage outputs. The maximum number of additional channels
provided via S Cards (2 per S card) is 20.

Inputs Outputs Max No. of


Additional S Analogue Additional S additional S cards
Digital Thermistor which can be fitted
card channels Voltage card channels
12 0 20 (10 S cards) 8 12 (6 S cards) 10

S cards ( 2 channels per card) :2 analogue current inputs (SCCI)


2 analogue voltage inputs (SCVI)
2 analogue thermistor inputs (SCTI)
2 digital inputs (SCDI)
2 analogue voltage outputs (SCVO)

4 IQ241 Controller Data Sheet TA103013 Issue 2, 4/03/2009


Data Sheet IQ241

HARDWARE (continued)

channel identification label


1 2 3 4 5 6 7 8 9 1 0 1 1 1 2 1 3 1 4 1 5 1 6 1 7 1 8 1 9 2 0 2 1 2 2 2 3 2 4 2 5 2 6 2 7 2 8 2 9 3 0 3 1 3 2 3 3 3 4 3 5 3 6 3 7 3 8 3 9 4 0
I1 d ig ita l in p u ts I1 2 I1 3 I2 0 I2 1 I3 2
S 1 a n a lo g u e in p u ts S 8 S 9 S 1 5
L 2 0 L 9 L 8 a n a lo g u e o u tp u ts L 1

Built in digital inputs Input only S cards Input or Output S cards Built in voltage outputs

External reference C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C
Channel 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40
Digital I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I
Input 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 Note outputs have
Sensor
S S S S S S S S S S S S S S S S S S S S reverse numbering
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Driver
L L L L L L L L L L L L L L L L L L L L
Output
20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
channel

Note 1 C 3 C 5 C 7 C 9 C 1 1 C 1 3 C 1 5 C 1 7 C 1 9 C 2 1 C 2 3 C 2 5 C 2 7 C 2 9 C 3 1 C 3 3 C 3 5 C 3 7 C 3 9 C

sensors
start at
2 C 4 C 6 C 8 C 1 0 C 1 2 C 1 4 C 1 6 C 1 8 C 2 0 C 2 2 C 2 4 C 2 6 C 2 8 C 3 0 C 3 2 C 3 4 C 3 6 C 3 8 C 4 0 C
channel 13

Digital Inputs (channels 1 to 12 fitted - channels 13 to 32 optional using S cards - SCDI)


(I1 to I32 correspond to channels 1 to 32)

39K
INn

5K6

yellow

0V
C 24V

Analogue Current Inputs (channels 13 to 32 optional using S cards - SCCI)


(S1 to S20 correspond to channels 13 to 32)

100K
INn

250R

0V
LOOP EXT
+ 24V
LOOP
C
EXT
0V

Analogue Voltage Inputs (channels 13 to 32 optional using S cards - SCVI)


(S1 to S20 correspond to channels 13 to 32)

100K
INn

100K

0V

C 0V

Analogue Thermister Inputs (channels 13 to 32 optional using S cards - SCTI)


(S1 to S20 correspond to channels 13 to 32)

+ 5V

10K
100K
INn

C 0V

IQ241 Controller Data Sheet TA103013 Issue 2, 4/03/2009 5


IQ241 Data Sheet

HARDWARE (continued)

Analogue Voltage Outputs (channels 33 to 40 fitted - channels 21 to 32 optional using S cards - SCVO)
(Driver output channels 1 to 20 correspond to channels 40 to 21 i.e. reverse order)

24V

22R
100R
OUTn

yellow C
0V

2K7

0V

Integral Node: If required an additional node controller (e.g. TMNH, TNME, CNC2, PNC2, INC2, LINC/FTT) may be fitted inside the
IQ241 using the node fixing kit, KIT/NODE/IQ241.

The fixing kit contains nylon pillars which are screwed to the 4
hinged plate
holes in the IQ241. The node card has 4 holes that fit onto the
pillars enabling the node to be screwed into position. There is a
special 24 Vdc supply connection (labelled XNC/PWR) and a node
network connector (labelled XNC). The two on-board network board
links must be removed to enable the network to connect to the
node.

Note that an additional node controller will consume current


from the 24 Vdc auxiliary supply; see auxiliary supply section network links
above and appropriate node controller data sheet.

There is a top panel 25 Way D-type knockout for RS232 to


auxiliary node and two circular M20 knockouts for other auxiliary
node network
node cables.
connection (XNC)
node supply (XNC PWR)

6 IQ241 Controller Data Sheet TA103013 Issue 2, 4/03/2009


Data Sheet IQ241

COMPATIBILITY
Supervisors: 963, 916, IQView. Interface: It can be connected to IQ system
Utility software: PowerTool, 822+/Toolbox version 6, 841 interface modules. Check interface
Strategy Browser, 842 Change Tracker, module specification to ensure
SET, Wupdn. compatibility.
Controllers: It can communicate to other IQ system Local Display: 2-line Display Panel.
controllers using inter controller
communications.

The IQ Configuration Reference Manual Addendum covers the compatibility between different types of strategy files, and between
the IQ241 sensor logs, and supervisors and software tools.

DISPOSAL
COSHH ASSESSMENT FOR DISPOSAL OF IQ CONTROLLER. WEEE Directive :
The only part affected is the lithium battery which must be
disposed of in a controlled way. At the end of their useful life the packaging,
product, and battery should be disposed of
RECYCLING. by a suitable recycling centre.
All plastic and metal parts are recyclable. The printed circuit Do not dispose of with normal household waste.
board may be sent to any PCB recovery contractor to recover Do not burn.
some of the components for any metals such as gold and silver.

IQ241 Controller Data Sheet TA103013 Issue 2, 4/03/2009 7


IQ241 Data Sheet

INSTALLATION
The IQ241 controller must be installed in a panel, using screws and washers. The procedure involves:

mount the controller in position


route the cable to the controller
connect power (do not switch on)
connect the I/O
connect the auxiliary supply
connect network
set network address and baud rate
fit S cards if required
switch on
configure the strategy
check operation

The installation procedure is covered in the IQ241 Installation Instructions (TG103012, sections 1 and 2.1). Sections 2.2, 2.3, 2.4,
3.1, 3.2, 3.3, 3.4, 3.5 cover Connecting to a PC, Replacing the Battery, Replacing the Fuse (/24VAC, /24VDC only) Zero Address/
Baud Rate Reset, Mounting in an Enclosure (ENCLS), Connecting a remote 2-line Display.

Other installation instructions:


Post fitting an integral 2-line Display Panel, KIT/DP2 Installation Instructions, TG103173.
Fitting an integral node, KIT/NODE/IQ241 Installation Instructions, TG200672.
Fitting Remote Display Panel Support, KIT/2xx/RDS Installation Instructions, TG103128.
Fitting S Cards, SCVO, SCVI, SCCI, SCTI, SCDI, S Cards Installation Instructions, TG103127

8 IQ241 Controller Data Sheet TA103013 Issue 2, 4/03/2009


Data Sheet IQ241

CONNECTIONS

24 V Supply (option) 230 Vac Supply (option) Auxiliary Supplies

24 Vdc: +24V 0V
IEC connector 2 off 2 part connectors with 2 screw
24 Vac: 24 Vac 24 Vac
terminals for 0.5 to 2.5 mm 2 cross
Earth
section area (20 to 14 AWG) cable.
AUX
24v
+ - + -
Mat-N-Loc
to terminal
EJ105383
24V

adaptor IQ 2 4 1
(supplied) + - + -
LoadLoad

Supervisor Port
1 off RJ11 (FCC68)
V
1 3 5 7 9 1 1 1 3 1 5 1 7 1 9 2 1 2 3 2 5 2 7 2 9 3 1 3 3 3 5 3 7 3 9
2 4 6 8 1 0 1 2 1 4 1 6 1 8 2 0 2 2 2 4 2 6 2 8 3 0 3 2 3 4 3 6 3 8 4 0

TX RX

1 2 3 4 5 6 7 8 9 1 0 1 1 1 2 1 3 1 4 1 5 1 6 1 7 1 8 1 9 2 0 2 1 2 2 2 3 2 4 2 5 2 6 2 7 2 8 2 9 3 0 3 1 3 2 3 3 3 4 3 5 3 6 3 7 3 8 3 9 4 0
I1 d ig ita l in p u ts I1 2 I1 3 I2 0 I2 1 I3 2
S 1 a n a lo g u e in p u ts S 8 S 9 S 1 5
L 2 0 L 9 L 8 a n a lo g u e o u tp u ts L 1

channel identification label


LAN 1 C 3 C 5 C 7 C 9 C 11 C 13 C 15 C 17 C 19 C 21 C 23 C 25 C 27 C 29 C 31 C 33 C 35 C 37 C 39 C AUX
24v
2 C 4 C 6 C 8 C 10 C 12 C 14 C 16 C 18 C 20 C 22 C 24 C 26 C 28 C 30 C 32 C 34 C 36 C 38 C 40 C + - + -

Network
2 off 2 part connectors with 4 screw terminals for 0.5 to 2.5 mm2 cross section area (20 to 14 AWG) cable.

Using two wire method Using four wire method


LAN
LAN

T- R+
T- OUT IN R+ T+ R-
T+ R- R- T+
R+ OUT IN T-
Earthing bar
Earthing bar

I/O channel identification label


1 2 3 4 5 6 7 8 9 1 0 1 1 1 2 1 3 1 4 1 5 1 6 1 7 1 8 1 9 2 0 2 1 2 2 2 3 2 4 2 5 2 6 2 7 2 8 2 9 3 0 3 1 3 2 3 3 3 4 3 5 3 6 3 7 3 8 3 9 4 0
I1 d ig ita l in p u ts I1 2 I1 3 I2 0 I2 1 I3 2
S 1 a n a lo g u e in p u ts S 8 S 9 S 1 5
L 2 0 L 9 L 8 a n a lo g u e o u tp u ts L 1

Built in digital inputs Input only S cards Input or Output S cards Built in voltage outputs

External reference C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C
Channel 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40
Digital I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I
Input 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
S S S S S S S S S S S S S S S S S S S S
Sensor
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Driver
L L L L L L L L L L L L L L L L L L L L
Output
20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
channel

Note 1 C 3 C 5 C 7 C 9 C 1 1 C 1 3 C 1 5 C 1 7 C 1 9 C 2 1 C 2 3 C 2 5 C 2 7 C 2 9 C 3 1 C 3 3 C 3 5 C 3 7 C 3 9 C

sensors
start at
2 C 4 C 6 C 8 C 1 0 C 1 2 C 1 4 C 1 6 C 1 8 C 2 0 C 2 2 C 2 4 C 2 6 C 2 8 C 3 0 C 3 2 C 3 4 C 3 6 C 3 8 C 4 0 C
channel 13

Channels 13 to 32 require S cards fitted in order to function

IQ241 Controller Data Sheet TA103013 Issue 2, 4/03/2009 9


IQ241 Data Sheet

FIELD MAINTENANCE
The IQ241 controller requires virtually no routine maintenance, however it is recommended that the lithium battery be replaced every
5 years, as explained in the Installation Instructions (TG103012, sheets 2 & 3).

ORDER CODES
IQ241/[Display]/[Node]/[PSU] :12 digital inputs, 8 analogue voltage outputs, and 20 configurable channels
IQ242/[Display]/[Node]/[PSU] :12 digital inputs, 8 thermistor inputs, 8 analogue voltage outputs, and 12 configurable channels

[Display] [Node] [PSU]


Blank No display. blank No node 230 230 Vac Input power
DP IQ241 with 2-line Display Panel in front cover. TMNH Node including integral MODEM 24VAC 24 Vac Input power

TMNE Node for external MODEM 24VDC 24 Vdc Input power


CNC2 Node for Trend network
PNC2 Node for remote printer
INC2 Node for Trend Internetwork
LINC/FTT Node for LonWorks network

e.g. IQ24x/TMNH/230 Specifies an unboxed IQ241 with integral 2 line display panel, integral modem, and
230 Vac Input power.

S cards IQ241 (10 input cards max, 6 output cards max, 10 cards in total max). Note that S cards are supplied with terminals.

SCVO 2 Analogue voltage outputs S card


SCVI 2 Analogue voltage inputs S card
SCCI 2 Current inputs S card
SCTI 2 Thermistor inputs S card
SCDI 2 Digital inputs S card

CABLE/EJ101442 Adapter cable RJ11 to 9 way ‘D’ type female for local PC connector

Retrofit kits

KIT/DP2 Kit to retrofit 2-line Display Panel, HDP, FPK to front cover of IQ22x, IQ23x, IQ241/242, IQ250 (does
not include 2-line display panel)
KIT/2xx/RDS Kit to enable connection of 2-line Display (FPK or HDP) externally (does not include 2 line-display
panel)
KIT/NODE/IQ241 Kit for fitting additional integral node (does not include node)

Enclosures

ENCLS 600 mm x 600 mm x 210 mm IP55 enclosure (does not include NDP)

Other Displays

SDU/IQ Smart Display Unit for wall mounting enabling monitoring and adjustment of parameters
RD/IQ/K Room Display for wall mounting, including temperature, setpoint display and adjustment
RD/IQ/KOS Room Display for wall mounting, including temperature, setpoint display and adjustment, and occupancy
override
RD/IQ/KOSF Room Display for wall mounting, including temperature, setpoint display and adjustment, occupancy
override, and fan speed adjustment

10 IQ241 Controller Data Sheet TA103013 Issue 2, 4/03/2009


Data Sheet IQ241

SPECIFICATIONS
CONTROLLER

Electrical Inputs/Outputs
Signal Cable :Analogue voltage, Current, Thermistor,
CPU :68332 32 bit micro controller or Digital inputs, and Analogue voltage
CPU speed :16.78 MHz outputs. IQ system TP/1/1/22/HF/200
recommended (Belden 8761)
Cycle time :1 s
Channels 1 to 12 12 digital inputs. Internally, or self
Memory :256 kbyte battery backed SRAM, and
powered volt free contact. Wetting
256 kbyte Flash.
current 4 mA @ 24 Vdc, count rate 32 Hz
Supply voltage
max. 1 Status LED per channel. ON if
/230 :230 Vac +15 -10 %, 50 to 60 Hz
input is closed.
/24VAC :24 Vac +15 -10 %, 50 to 60 Hz (24Vac
Channels 13 to 20 8 universal inputs, 4 slots to fit IQ system
supply must be isolated).
analogue voltage input, current input,
/24VDC :24 Vdc +25% -10% (24 V to 36 Vdc)
thermistor input, or digital input S cards.
Auxiliary supply :24 Vdc, 1000 mA dependent on
Channels 21 to 32 12 universal I/O, 6 slots to fit IQ system
configuration, see page 5 for further
analogue voltage input, current input,
details.
thermistor input, digital input, or analogue
Consumption :60 VA max
voltage output S cards.
Fusing
Channels 33 to 40 8 analogue voltage outputs. 8 bit resolution
/230 :No replaceable fuses required. All
(256 steps). 0 to 10 V with 20 mA current
protection self resetting.
limit, accuracy ±100 mV equivalent to ±1 %
/24VAC, /24VDC :4 A, 1¼”, replaceable fuse fitted in line
span. 1 Status LED per channel. Light
of supply cable inside unit.
intensity increases with output voltage.
Battery backup :Battery maintains time, and logged data
with mains off for at least 5 years. Mechanical
Battery :Saft LM2450, 3 V, or equivalent
Dimensions :325 mm x 355 mm x 85 mm (12.8” x
Clock accuracy :30 s per month (typical).
13.90” x 3.35”)
Network display panel :Icon driven display panel with backlit
Material
display, for use on single or multi Lan
Chassis :Steel
systems. Can be mounted in front cover,
Cover :Fire retardant ABS
or externally.
Weight :5.6 kg
Display panel :2 x 40 character display, with 4
Connectors
programmable softkeys. Can be mounted
/230 :IEC plug
in front cover, or externally via display
/24 :Mat-N-Loc to screw terminal adaptor.
panel connector.
Network :2 part connector with 4 screw terminals for
Network :20 mA serial 2 wire current loop, opto
0.5 to 2.5 mm2 cross section area (20 to 14
isolated, polarity independent receiver,
AWG) cable.
balanced transmitter.
I/O :2 part connector with 2 screw terminals for
Supervisor
0.5 to 2.5 mm2 cross section area (20 to 14
transmission :RS232, EIA/TIA/232E, V28
AWG) cable.
Distance
Supervisor port :RJ11 (FCC68), for IQ system utility
Supervisor :15 m
software connected via adaptor cable
Network :Dependent on cable type, see table
CABLE/EJ101442.
below.
Display panel 25 way D type (if KIT/RDS fitted).
Cable 1k2 baud 9k6 baud 19k2 baud No. of Wires
Environmental
Belden 9182 1000 m 1000 m 700 m 2
Belden 9207 1000 m 1000 m 500 m 2
IQ system EMC
TP/1/1/22/HF/200 1000 m 700 m 350 m 2 Emissions :EN50081-1.
(Belden 8761) Immunity :EN50082-2.
IQ system Safety :EN61010.
TP/2/2/22/HF/200 1000 m 500 m 250 m 4
(Belden 8723)
Ambient limits
storage :-10 °C to 50 °C
Baud rate operating :0 °C to 45 °C
Network :Selectable by switch 1k2, 9k6, or 19k2, humidity :0 to 90 %RH non-condensing
set to be same as other nodes on Lan.
NDP :9k6. Indicator Lamps
Supervisor :9k6.
Network addresses PWR :(green) ON when power supply is
Controller :Selectable by switch, 116 nodes connected.
addressable (1,4 to 119 excluding 10) WD :(red) ON if controller has a software
set to be unique on Lan. fault.
Supervisor port :Software selectable, 116 nodes LAN :(green) ON if network is operating.
addressable (1,4 to 119 excluding 10) Flashes if prohibited address set (0, 2,
set to be unique on Lan. 3, >119).
NDP port :Software selectable, 116 nodes TX :(yellow) ON if current is flowing from
addressable (1,4 to 119 excluding 10) the network transmitter.
set to be unique on Lan. RX :(yellow) ON if current is entering the
network receiver.

IQ241 Controller Data Sheet TA103013 Issue 2, 4/03/2009 11


IQ241 Data Sheet

SPECIFICATIONS (continued)

Version
Firmware :v3 or greater
Board :AM102710 v5
SCVO card :AM1022780 v2
Input S Card :AM102777 v2

S CARDS
Dimensions :32 mm x 45 mm x 10 mm ( 1.26” x 1.77”
x 0.39”)

Analogue voltage input card


Analogue voltage
inputs :2 channels per card, 12 bit resolution
(4096 steps). Minimum 60 dB series mode
rejection at supply frequency. 0 to 10 V,
input resistance 200 k, accuracy 50 mV
equivalent to ±0.5% of span.

Analogue Current input card


Analogue current
inputs :2 channels per card, 12 bit resolution
(4096 steps). Minimum 60 dB series mode
rejection at supply frequency. 0 to 20
mA, input resistance 250  0.1%,
accuracy 0.5 % of span (i.e. 100 µA).

Analogue Thermistor input card


Analogue Thermistor
inputs :2 channels per card, 12 bit resolution
(4096 steps). Minimum 60 dB series mode
rejection at supply frequency. Thermistor,
bridge resistor 10 k 0.1%, accuracy
0.5 % of span. Bridge supply 5 V.
Digital input card
Digital inputs :2 channels per card. Wetting current 4 mA
@ 24 Vdc, count rate 32 Hz max. 1 Status
LED per channel. ON if contact closed.

Analogue voltage output card


Analogue voltage
outputs :2 channels per card, 8 bit resolution
(256 steps). 0 to 10 V with 20 mA current
limit, accuracy ±100 mV equivalent to
±1 % span. 1 Status LED per channel.
Light intensity increases with output
voltage.

Please send any comments about this or any other Trend technical publication to techpubs@trendcontrols.com

© 2009 Honeywell Technologies Sàrl, ECC Division. All rights reserved. Manufactured for and on behalf of the Environmental and Combustion Controls
Division of Honeywell Technologies Sàrl, Z.A. La Pièce, 16, 1180 Rolle, Switzerland by its Authorized Representative, Trend Control Systems Limited.

Trend Control Systems Limited reserves the right to revise this publication from time to time and make changes to the content hereof without
obligation to notify any person of such revisions or changes.
Trend Control Systems Limited
P.O. Box 34, Horsham, West Sussex, RH12 2YF, UK. Tel:+44 (0)1403 211888 Fax:+44 (0)1403 241608 www.trendcontrols.com
Trend Control Systems USA
6670 185th Avenue NE, Redmond, Washington 98052, USA. Tel: (425)897-3900, Fax: (425)869-8445 www.trendcontrols.com

12 IQ241 Controller Data Sheet TA103013 Issue 2, 4/03/2009

You might also like