After the bearing run continuously for 60.000 hours, or when abnormal conditions ( noise, vibration ) the bearing
must be replaced by Profesional Enginers
Regular Inspections :
Connection parts, whether loosned, if loosned must be re tightened
Whether the Insulating Layer of conductor, if it is damaged, insulating must be replaced with special insulating
tape for binding treatment
Installation bolt, if loosned must be re-tightened
The motor surface should be CLEAN
Attention:
When the motor is not used for long time (more than a month) please be sure to empty the coolant in the coolant in
the motor
Troubleshooting :
No Fault Phenomena Couse analysis Exclusive measures
1 Flexible idling abnormal Bearing damage Replace bearing
sound The change of coaxiality between stator and Find out the couse of stator and rotor
rotor results in friction between stator and deformation damage
rotor
2 Excessive idle current The driver does not match and the relationship Adjust the phase relationship between the
between the main motor phase and the main motor and the spinning variable to
spinning phase is wrong minimize the no-load current
3 Excessive load current Same no.2 Same no.2
4 No-load noise exceeding Installation is unreasonable Re-assemble
standard
Bearing damage Replace damage bearing
5 Vibration Speed of motor Dynamic equilibrium state change Find out if the original state of the dynamic
exceeds the standard The accuracy of dynamic balance is not balance changes and restore the dynamic
enough. With the increase of rotational speed, balance
the vibration speed increases
6 Abnormal rise of motor Abnormal increase of load Lower the load to normal
temperature