INDOOR/OUTDOOR
SPECIFICATIONS MANUAL
MANUFACTURED BY :
BROTHERS LIMITED
BROTHERS LIMITED
TABLE OF CONTENTS
Burner capacity
Dimensions
Options .....................................................................................15
3
BROTHERS LIMITED
BENEFITS OF A DIRECT GAS-FIRED Finally, the benefits of a make-up air heater are:
MAKE-UP AIR HEATER • Less dust and impurities;
• Elimination of cold air infiltration;
A make-up air heater is designed to compensate for the • Easy opening and closing of the exterior doors;
air exhausted by one or more exhaust fans. It may also be • Increased efficiency of exhaust fans;
used to compensate the air used by an industrial process • Elimination of downdraft in chimneys and ventilation
or combustion air for burners. openings;
• Increased efficiency of the heating systems;
The phenomenon of negative pressure in a building, which • Preservation of the building structure integrity.
is caused by a lack of air compensation, may lead to con-
ditions such as combustion products back flow from existing
heating equipments, air infiltration through doors and win-
dows, dispersal of contaminants as well as structural dam- APPLICATIONS
ages. These conditions may be circumvented by the instal-
lation of a make-up air unit to replace exhausted or deplet- • Commercial kitchens
ed air. • Industrial laboratories
• Paint booths
In addition to the benefits indicated above, a make-up air • Compensation for negative pressure in industrial
heater can filter and heat or cool the air for additional and commercial buildings
comfort. Because it has a very high efficiency, the direct • Underground parking lots
gas-fired make-up air heater is more cost effective than • Mechanical workshops
an indirect gas-fired unit. • In most facilities requiring correction of negative
pressure and where the unit may be interlocked
The normal temperature of the air supplied by a direct to an exhaust system.
gas-fired air heater stands between 65 and 750F, but may Refer to current B-149 standard under Direct
be as low as 550F. The maximum discharge temperature Gas-fired Make-up Air Heaters
allowed by the CGA standards is 1600F. For air supply
temperature above 1000F, a special construction is required; Exception: ANYWHERE people may sleep.
consult the manufacturer.
4
BROTHERS LIMITED
2. Type of installation
• Indoor or outdoor installation
• Installation on ties, roof curb, structure, slab or other
• Side of the controls (when facing the air discharge)
3. Heating requirements
• Inlet air temperature
• Leaving air temperature
• Heating capacity
4. Unit configuration
• Single, multiple or variable air flow rates
• Air flow orientation (horizontal, vertical, up or down)
• Air discharge configuration (horizontal or vertical)
• Type of fresh air intake
• Type and location of filters
6. Remote controls
• Standard, deluxe or special remote control panel
• Room thermostat
• Others
7. Options
• Non-insulated roof curb
• Space for a cooling or recovery coil
• Discharge low limit thermostat
• Adjustable air inlet thermostat
• Lighting and/or power outlets
• Others
5
BROTHERS LIMITED
6
BROTHERS LIMITED
7
BROTHERS LIMITED
8
BROTHERS LIMITED
9
BROTHERS LIMITED
SDM 25 to SDM 75
AA
Y E A
LL
L N
X KK K M C
D
L N
FILTERS IN 2
LL FILTERS V (51)
INTAKE HOOD
(STANDARD) SECTION
(OPTIONAL)
GAS INLET
U
VERTICAL UP
DISCHARGE
2 (51) 2 (51)
Z JJ J F B
HORIZONTAL
DISCHARGE
G
i
4 (102) F H
Q
Note 1 : Add up dimensions A or AA and Y to determine the overall length of the unit with a fresh air intake hood for outdoor model.
2 : Refer to the manufacturer for G with spring vibration isolators option.
3 : Weight is for standard outdoor unit with 1-in (25-mm) insulation and standard air intake hood. Refer to the manufacturer for non-standard units.
10
BROTHERS LIMITED
C
K M
X KK D
L V 2 (51)
LL GAS INLET
FILTERS IN FILTERS U
INTAKE HOOD SECTION VERTICAL UP
(STANDARD) (OPTIONAL) DISCHARGE
2 (51)
2 (51)
F HORIZONTAL
Z JJ J B
DISCHARGE
G
I
Q 4 (102) F H
MODEL NO. SDM 100 SDM 150 SDM 200 SDM 300
FAN SIZE 18-18 20-20 25-25 28-28
in mm in mm in mm in mm
FILTERS 9-16x20 9-406x508 8-16x20 8-406x508 5-20x20 5-508x508 18-20x20 18-508x508
IN UNIT 4-16x25 4-406x635 10-20x25 10-508x635 6-20x25 6-508x635
FILTERS IN 6-20x25 6-508x635 9-20x25 9-508x635 8-16x25 8-406x635 5-20x25 5-508x635
INTAKE HOOD 8-20x25 8-508x635 15-20x20 15-508x508
Note 1 : Add up dimensions A or AA and Y to determine the overall length of the unit with a fresh air intake hood for outdoor model.
2 : Refer to the manufacturer for G with spring vibration isolators option.
3 : Weight is for standard outdoor unit with 1-in (25-mm) insulation and standard air intake hood. Refer to the manufacturer for non-standard units.
11
BROTHERS LIMITED
K M C
X KK D
L V 2 (51)
LL
FILTERS IN FILTERS U GAS INLET
INTAKE HOOD SECTION
(STANDARD) (OPTIONAL) VERTICAL UP
DISCHARGE
2 (51)
Z J
JJ P F B HORIZONTAL
DISCHARGE
J
G
i R F H
Q 4 (102)
Note : The dimensions in parentheses are in mm.
: Left-hand side controls illustrated (right-hand side optional) VERTICAL DOWN
: Support leg for outdoor model with filter section DISCHARGE
Note 1 : Add up dimensions A or AA and Y to determine the overall length of the unit with a fresh air intake hood for outdoor model.
2 : Refer to the manufacturer for G with spring vibration isolators option.
3 : Weight is for standard outdoor unit with 1-in (25-mm) insulation and standard air intake hood. Refer to the manufacturer for non-standard units.
12
BROTHERS LIMITED
SDM 700
AA
LL E L A 2 (51)
Y
X KK K
M
W T P C
D
M
KK K
N
LL L
FILTERS IN
INTAKE HOOD 4 (102) 2 (51)
(STANDARD) V U
FILTERS GAS INLET
SECTION
(OPTIONAL) VERTICAL UP DISCHARGE 2 (51)
Z J
JJ S B
F HORIZONTAL
J DISCHARGE
i R F G
Q H
Note : The dimensions in parentheses are in mm.
: Left-hand side controls illustrated (right-hand side optional)
: Filters section delivered separately VERTICAL DOWN
DISCHARGE
: Support leg for outdoor model with filter section
Note 1 : Add up dimensions A or AA and Y to determine the overall length of the unit with a fresh air intake hood for outdoor model.
2 : Refer to the manufacturer for G with spring vibration isolators option.
3 : Weight is for standard outdoor unit with 1-in (25-mm) insulation and standard air intake hood. Refer to the manufacturer for non-standard units.
13
BROTHERS LIMITED
ROOF CURBS
SDM 25 TO SDM 550 SDM 700
Exterior wood
Roof curbs
* : External dimensions
Note : 24-inch high roof curb (optional)
sectional view
SDM SDM SDM SDM SDM SDM SDM SDM SDM SDM SDM
25 50 75 100 150 200 300 375 450 550 700
A* in 71-1/8 71-1/8 71-1/8 90 90 106 109-1/2 122-1/2 119-1/2 141-1/2 117-1/2
mm 1807 1807 1807 2286 2286 2692 2781 3112 3035 3594 2985
B* in 22-1/4 35-1/8 35-1/8 44-1/2 49-1/2 57-1/2 72-1/2 76-1/2 80-1/2 91-1/2 215
mm 565 892 892 1130 1257 1461 1842 1943 2045 2324 5461
C* in 18 18 18 18 18 18 18 18 18 18 18
mm 457 457 457 457 457 457 457 457 457 457 457
F in 13-1/8 17-3/8 17-3/8 20-5/8 26-7/8 33-1/4 37-1/8 44-3/4 46-1/4 - -
mm 333 441 441 524 683 845 943 1137 1137 - -
H in 6-5/16 7-7/16 7-7/16 11-15/16 12 14-15/16 16-7/8 19-13/16 20-7/8 - -
mm 160 189 189 303 305 379 429 503 530
M in 14-7/8 20-1/8 20-1/8 23-5/8 26-7/8 33-1/4 37-1/8 41-3/4 46-1/4 - -
mm 378 511 511 600 683 845 943 1060 1137 - -
R in 4-7/16 7-1/2 7-1/2 10-7/16 11-5/16 12-1/8 17-11/16 17-3/8 17-1/8 - -
mm 113 191 191 265 287 308 449 441 435
Weight lbs 117 135 135 145 155 185 230 300 300 - -
Kg 53 61 61 66 70 84 104 136 136 - -
14
BROTHERS LIMITED
OPTIONS
BELT GUARD
SERVICE CABINET
SERVICE PLATFORM
15
BROTHERS LIMITED
OPTIONAL EQUIPMENT
• MAXITROL REMOTE TEMPERATURE SELECTOR (SHIPPED SEPARATELY)
• STOP/START/BLOWER SELECTOR
• STOP/START/BURNER SELECTOR
• BLOWER OPERATION LIGHT
• EXHAUST FAN OPERATION LIGHT
• BURNER OPERATION LIGHT
• FLAME FAILURE ALARM LIGHT
• TERMINAL BLOCK
OPTIONAL EQUIPMENT
• EXHAUST FAN STOP/START SWITCH
• DISCHARGE AIR LOW LIMIT LIGHT
• CLOGGED FILTER LIGHT
• HIGH GAS PRESSURE ALARM LIGHT
• LOW GAS PRESSURE ALARM LIGHT
• UNIT PURGE CYCLE COMPLETED LIGHT
• LOW AND HIGH AIR VOLUME LIGHTS
• TEMPERATURE SELECTOR (MAXITROL)
• KEY LOCK
Note : Refer to manufacturer for additional features
16
BROTHERS LIMITED
1 2 3
NOTE :1
8 9 8
4 6 7
5a 5b
9 8 12 8
BP
HP
S T S T
11 10 9 13
COMPONENTS DESCRIPTION
PILOT BURNER PIPING
1 Pilot Manual shut-off valve
2 Pilot Gas pressure regulator (see note 1)
3 Pilot Automatic safety shut-off valve (see note 1)
BURNER PIPING
18
BROTHERS LIMITED
TYPICAL SPECIFICATION
SDM DIRECT GAS-FIRED MAKE-UP AIR HEATERS
GENERAL
Supply and install a Bousquet model SDM-____ direct gas-fired air heater operating on natural gas (or propane), and for indoor (out-
door) installation. The manufacturer must be accredited by the CWB in compliance with standard CSA W47.1. to meet the minimum
standard applicable to all types of welds including stainless steel.
PERFORMANCE
The heater shall have the capacity to heat_________ CFM of standard air from _____oF to _____oF, for a net heat output of
__________ MBH. The fuel used will be natural gas (or propane) at an inlet pressure of _____ inches WC.
UNIT CONSTRUCTION
The support frame will be made of welded U-shaped structural steel. The walls and roof will be single wall and built with 18
gauge satin finish steel panels with 1-inch thick reinforced-coated fiberglass insulating material. Each panel should not exceed
20 inches wide, and have 2-90o plied edges in order to provide structural rigidity. They will be assembled together with screws,
and sealed with a PVC gasket and a urethane joint for positive waterproofing and air tightness. The outer surfaces of the unit
will be treated with a phosphate cleaner-conditioner and covered with an anticorrosive epoxy based primer exceeding the
Canadian (type 1-GP-40) and American (type TT-P-636 D) standards for salt mist and humidity. The finish will be ensured with
first quality high performance alkyd resin enamel applied at the plant. Each unit section will have hinged gasgetted doors with
screwed knob handles for easy access to every components.
The burner will be Midco air flow type, consisting of cast iron gas distributor and stainless diffuser baffles, factory mounted on a
galvanized steel profile plate equipped with air flow adjustable plates. All gas piping and control equipment required for the proper
operation of the unit shall be factory installed, and tested.
The gas pilot piping will be equipped with an electronic spark ignitor, manual shut-off valve, gas pressure regulator, automatic shut-
off valves, manual cock and 2 pressure test ports. The gas supply of the main burner will include a pressure regulator, an automatic
quick-closing shut-off valve, an automatic slow-opening valve, a manual ignition valve, 3 pressure test ports and a modulating gas
valve. The burner and gas piping assembly will have a modulating turndown ratio of at least 25:1.
19
BROTHERS LIMITED
FAN SECTION
The fan section will be designed according to the Air Movement and Control Association (AMCA) standards. The fan and motor will be
installed on a steel structure welded in compliance with the CWB standards and rest on anti-vibration rubber pads. An access door will
provide access for maintenance of the fan, motor, bearings, belts and pulleys. The fan will be a centrifugal foreward-curved (FC) type,
double width double inlet wheel (DWDI), model_________. The motor will be_______HP, 1800 RPM, open drip-proof (ODP), thermally
protected and with premium efficiency; it will be installed on a base to enable the adjustment of the belt tension and pulleys alignment.
FILTERS
The filters shall be pleated large surface disposable type, 2-inch thick and 30% efficient.
Option 1: Filters will be mounted in galvanized steel sliding frame located in air intake hood, equipped with an access hinged panel
for easy replacement.
Option 2: Filters will be mounted inside the unit in galvanized steel sliding frames, and accessible through a hinged access door;
rubber gaskets will be provided where required to ensure thighness between filters and access door, and to avoid air by-pass and
maximize filtration.
INLET DAMPER
The air inlet damper will be parallel blades standard construction in galvanized steel and equipped with an on-off electric actuator.
AIR INTAKE
The air intake hood will be “angle” type, mounted on unit end, and equipped with a bird screen. Inlet hood air velocity shall not exceed
500 FPM.
CERTIFICATION
All SDM direct gas fired make-up air heaters must be CSA approved and certified according to standards CAN/CSA3.7 - ANSI Z83.4.
Each unit shall be fired tested and pre-adjusted at factory prior to shipment. Site start-up shall be performed by a qualified technician,
with appropriate cards for gas equipment, and authorized by the manufacturer.
OPTIONS
20
Rev. (05/04) - Printed in Canada
BROTHERS LIMITED
2121, Nobel
Sainte- Julie (Quebec)