36-Division 16-Section 16380 Fire Detection and Alarm System-Version 2.0
36-Division 16-Section 16380 Fire Detection and Alarm System-Version 2.0
(ADSSC)
DIVISION 16 ELECTRICAL
03
04
05
06
07
08
09
10
TABLE OF CONTENTS
5. SIGNALLING APPLIANCES............................................................................. 7
9. INSTALLATION ................................................................................................ 8
1. GENERAL REQUIREMENTS
a) All items described within this section shall comply with the provisions of
Section 15001: General M&E Requirements.
c) The design of the fire detection and alarm systems shall comply with BS
5839-1. Individual components of the system shall comply with BS
5839, BS EN 54 and BS 5446.
e) The fire alarm and detection system shall be designed, installed and
commissioned by a specialist contractor having a minimum of five years
documented experience and suitably certified by Department of Civil
Defence, Abu Dhabi.
2. DESIGN BASIS
a) The basis of the design for all systems shall be Type M as defined by BS
5839 (i.e. the provision of manual break glass alarm units, supplemented
by automatic detection to meet the required level of property or life
protection.
d) Initiating Device Circuits: Supervised zone module with alarm and ‘fault’
indication; occurrence of single ground or open condition places circuit in
‘fault’ mode but does not disable that circuit from initiating an alarm.
f) A Municipal Trip Circuit and Switch shall be supplied, with the following
output connections:
i. Visual and audible fault alarm indicated by zone at fire alarm control
panel.
i. Sound and display local fire alarm signalling devices with march
time signal.
ii. Transmit non-coded or zone-coded signal as specified to municipal
connection, remote station equipment or central station as
specified.
iii. Indicate location of alarm zone on fire alarm control panel and on
remote annunciator panel as specified.
iv. Transmit signal by zone to building smoke removal system.
v. Transmit signals to building elevator control panel to initiate return
to main floor or alternate floor.
vi. Transmit signal to building mechanical systems to initiate shutdown
of fans and damper operation.
vii. Transmit signal to release door hold-open devices by zone.
l) Alarm Reset: System remains in alarm mode until manually reset with
key-accessible reset function; system resets only if initiating circuits are
out of alarm mode
m) Lamp Test: Manual lamp test function causes alarm indication at each
zone at fire alarm control panel and at annunciator panel.
4. INITIATING DEVICES
5. SIGNALLING APPLIANCES
b) Alarm Lights: NFPA 72G or other approved standard, strobe lamp and
flasher with red lettered "FIRE" on white lens.
6. AUXILIARY APPLIANCES
i. Power Branch Circuit Conductors: Brown for phase, Blue for neutral
and Green and Yellow for earth.
ii. Initiating Device Circuit: Brown, Blue.
iii. Detector Power Supply: Brown, Blue or as specified
iv. Signal Device Circuit: Blue positive, white negative or as specified.
v. Door Release: Brown, Blue or as specified.
vi. Municipal Trip Circuit: Orange, Orange or as specified.
vii. Municipal Fire Alarm Loop: Black, White or as specified.
9. INSTALLATION
b) Install manual station with operating handle 1.4m above finished floor
level. Install audible and visual signal devices 2.3m above finished floor
level.
c) Use 1.5mm² minimum size conductors for fire alarm detection and signal
circuit conductors. Install wiring in cable.
e) Mount outlet box for electric door holder to withstand 40kg pulling force.