EDTRAU342315-D

202302

Engineering Data

Design Manual
RXYQ8-60BYM
Heat Pump 50 Hz
RXYQ8-60BYM EDTRAU342315-D

1. Basic Information........................................................................................................3

2. Specification..............................................................................................................17

3. Optional Accessories of Control...............................................................................93

4. Appendix....................................................................................................................97

1
RXYQ8-60BYM EDTRAU342315-D

2
RXYQ8-60BYM EDTRAU342315-D

1. Basic Information

1. Features and Benefits.................................................................................4


2. Nomenclature..............................................................................................5
2.1 Outdoor Units.....................................................................................5
2.2 Indoor Units........................................................................................6
2.3 Air Treatment Equipment...................................................................7
3. Lineup..........................................................................................................8
3.1 Outdoor Units ....................................................................................8
3.2 Indoor Units........................................................................................9
3.3 Air Treatment Equipment.................................................................10
4. External Appearance.................................................................................11
4.1 Outdoor Units...................................................................................11
4.2 Indoor Units......................................................................................12
4.3 Air Treatment Equipment.................................................................13
5. Combination of Outdoor Units...................................................................14
6. Capacity Range.........................................................................................15
6.1 For VRV Indoor Units Only..............................................................15

3
RXYQ8-60BYM EDTRAU342315-D

1. Features and Benefits

• New line up with single modules from 8 - 24 class, reduction of installation cost and mechanical space with larger single
module, with multi-module up to 60 class.
• Redesigned chassis for ease of install, commissioning and maintenance.
• Engineered with new Daikin’s patented inverter compressor technology which is smaller, lightweight, and optimized for part
load efficiencies with TCSPF up to 7.25.
• Innovative sealed E-box technology with IP55 rating for protection from gecko, insects, dust, water and snow ingress.
• Design flexibility to enlarge system from single to dual module without changes to installed main pipe sizes.
• Industry leading piping with vertical separation up to 110 m.
• Hot gas defrost circuit allows installation without base pan heater.
• Defrost operation before the equipment is shut down speeds up the increase of discharge air temperature of the next heating
operation.
• Defrost learning function optimises the next cycle defrost start conditions to extend the heating operation time when the
deforest operation time is limited.
• Outdoor temperature operation range limit is extended to 52°CDB in cooling operation and -25°CWB in heating operation.
• The average automatic charging operation time has been shortened by 22% (14 min), and the number of on-site operations
has been reduced by performing the automatic refrigerant charging and test run at the same time.
• Service window provides quick access to multi-functional display and configuration buttons.
• Multi-functional display provides refrigerant pressures and temperatures eliminating the need to connect gauges during regular
maintenance check.
• VRT Smart II control: coordination between indoor and outdoor units minimizes energy consumption by optimizing capacity to
meet actual operation load. Further improvement of energy savings is achieved due to optimal control of the outdoor airflow
rate.
• Engineered to optimize capital on phased & tenant fit out commercial buildings.
• Refrigerant cooled inverter technology keeps PCB cool independent of ambient temperature.

8 - 12 class 14 - 20 class 22 - 24 class

4
RXYQ8-60BYM EDTRAU342315-D

2. Nomenclature
2.1 Outdoor Units

R X Y Q 60 B YM

Power supply symbol


YM: 3 phase, 380-415/380 V, 50/60 Hz
Indicates major design category
Capacity indication
Conversion to kW
8: 22.4 kW
10: 28.0 kW
60: 168 kW
Refrigerant
Q: R410A
Type
Y: Heat pump
Blank: Cooling only
Series category
X: Inverter
Unit category
R: Outdoor unit for air cooled type

5
RXYQ8-60BYM EDTRAU342315-D

2.2 Indoor Units


VRV Indoor Units

F X C Q 25 B VM

Power supply symbol, Standard symbol


V36: 1 phase, 220-240 V, 50 Hz
V1A: 1 phase, 220-240 V, 50 Hz
V1C: 1 phase, 220-240 V, 50 Hz
V1CA: 1 phase, 220-240 V, 50 Hz
V1: 1 phase, 220-240 V, 50 Hz
VE: 1 phase, 220-240/220 V, 50/60 Hz
VM: 1 phase, 220-240/220-230 V, 50/60 Hz
VEB: 1 phase, 220-240/220-230 V, 50/60 Hz

Indicates major design category

Capacity indication
Conversion to kW
25: 2.8 kW
125: 14.0 kW
250: 28.0 kW

Refrigerant
Q: R410A

Shape
FT : Round flow cassette with sensing and streamer
FS : Round flow cassette with sensing
F : Round flow cassette
Z : Compact multi flow cassette
C : Double flow cassette
E : Single flow cassette
D : Slim duct (standard/compact)
S : Middle static pressure duct
DY : Middle static pressure duct
M : Middle-high/high static pressure duct
U : 4-way flow ceiling suspended
H : Ceiling suspended
A : Wall mounted
L : Floor standing
N : Concealed floor standing

Series category
X: Inverter

Unit category
F: Indoor unit for air cooled type

6
RXYQ8-60BYM EDTRAU342315-D

2.3 Air Treatment Equipment


Outdoor-Air Processing Unit

F X M Q 80 A F VM

Power supply symbol


V1: 1 phase, 220-240 V, 50 Hz
VM: 1 phase, 220-240/220-230 V, 50/60 Hz

Outdoor-air processing unit

Indicates major design category

Capacity indication
Conversion to kW
80: 9.0 kW
140: 16.0 kW
250: 28.0 kW

Refrigerant
Q: R410A

Type
M: Ceiling mounted duct

Series category
X: Inverter

Unit category
F: Indoor unit for air cooled type

Heat Reclaim Ventilator (VAM series)

V A M 500 H VE
Power supply symbol
VE: 1 phase, 220-240/220 V, 50/60 Hz
Indicates major design category
Airflow rate (H) (m3/h)
Mounted type
Air
Ventilation

7
RXYQ8-60BYM EDTRAU342315-D

3. Lineup
3.1 Outdoor Units
VRV H SERIES

Model name Power supply


8B 10B 12B 14B 16B 18B 20B 22B 24B
RXYQ 26B 28B 30B 32B 34B 36B 38B 40B 42B YM
44B 46B 48B 50B 52B 54B 56B 58B 60B

YM: 3 phase, 380-415/380 V, 50/60 Hz

8
RXYQ8-60BYM EDTRAU342315-D

3.2 Indoor Units


VRV Indoor Units
Category

2.2 2.8 3.6 4.5 5.6 7.1 8.0 9.0 11.2 14.0 16.0 16.2 18.0 20.0 22.4 28.0
Power
Capacity range kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW supply,
Capacity index 20 25 31.25 40 50 62.5 71 80 100 125 140 145 160 180 200 250 Standard
Round Flow
Cassette with FXFTQ — 25A 32A 40A 50A 63A — 80A 100A 125A 140A — — — — —
Sensing and
Streamer
Ceiling Mounted Cassette

Round Flow
Cassette with FXFSQ — 25A 32A 40A 50A 63A — 80A 100A 125A 140A — — — — —
Sensing
VM
Round Flow FXFQ — 25A 32A 40A 50A 63A — 80A 100A 125A 140A — — — — —
Cassette
Compact Multi FXZQ 20B 25B 32B 40B 50B — — — — — — — — — — —
Flow Cassette
Double Flow FXCQ 20B 25B 32B 40B 50B 63B — 80B — 125B — — — — — —
Cassette
Single Flow FXEQ 20A 25A 32A 40A 50A 63A — — — — — — — — — — V36
Cassette
FXDQ- 20PD 25PD 32PD — — — — — — — — — — — — —
Slim Duct PDVE
VE
(Standard) FXDQ- — — — 40ND 50ND 63ND — — — — — — — — — —
NDVE
Ceiling Concealed Duct

20T 25T 32T 40T 50T 63T — — — — — — — — — — V1C


Slim Duct FXDQ
(Compact)
20T 25T 32T 40T 50T 63T — — — — — — — — — — V1CA

Middle Static FXSQ 20PA 25PA 32PA 40PA 50PA 63PA — 80PA 100PA 125PA 140PA — — — — — VE
Pressure Duct FXDYQ — — — — — — — 80MA 100MA 125MA — 145MA — — — — V1
Middle-High Static
FXMQ 20PA 25PA 32PA 40PA 50PA 63PA — 80PA 100PA 125PA 140PA — — — — — VE
Pressure Duct
High Static FXMQ — — — — — — — — — — — — 160P 180P 200P 250P V1A
Pressure Duct
4-Way Flow
Suspended

Ceiling FXUQ — — — — — — 71A — 100A — — — — — — — VEB


Ceiling

Suspended
Ceiling — — 32MA — 50MA 63MA — 80MA 100MA — — — — — — — VE
FXHQ
Suspended — — — — — — — — — 125B 140B — — — — —
VM
Wall Mounted FXAQ 20A 25A 32A 40A 50A 63A — — — — — — — — — —
Floor
Standing

FXLQ 20MA 25MA 32MA 40MA 50MA 63MA — — — — — — — — — —


Standing
Floor

VE
Concealed Floor FXNQ 20MA 25MA 32MA 40MA 50MA 63MA — — — — — — — — — —
Standing

Note:
V36, V1A, V1C, V1CA, V1: 1 phase, 220-240 V, 50 Hz
VE: 1 phase, 220-240/220 V, 50/60 Hz
VM: 1 phase, 220-240/220-230 V, 50/60 Hz
VEB: 1 phase, 220-240/220-230 V, 50/60 Hz

9
RXYQ8-60BYM EDTRAU342315-D

3.3 Air Treatment Equipment


Outdoor-Air Processing Unit

Series Model name Power supply

80AF — 140AF 200AF 250AF VM


FXMQ
— 125MF — 200MF 250MF V1

V1: 1 phase, 220-240 V, 50 Hz


VM: 1 phase, 220-240/220-230 V, 50/60 Hz

Heat Reclaim Ventilator (VAM series)

Series Model name Power supply


Heat reclaim VAM 150H 250H 350H 500H 650H 800H 1000H 1500H 2000H VE
ventilator

VE: 1 phase, 220-240/220 V, 50/60 Hz

10
RXYQ8-60BYM EDTRAU342315-D

4. External Appearance
4.1 Outdoor Units
VRV H SERIES

8, 10, 12 class 14, 16, 18, 20 class 22, 24 class

RXYQ8BYM RXYQ14BYM RXYQ22BYM


RXYQ10BYM RXYQ16BYM RXYQ24BYM
RXYQ12BYM RXYQ18BYM
RXYQ20BYM

26, 28, 30, 32 class 34, 36, 38, 40 class 42, 44 class

RXYQ26BYM RXYQ34BYM RXYQ42BYM


RXYQ28BYM RXYQ36BYM RXYQ44BYM
RXYQ30BYM RXYQ38BYM
RXYQ32BYM RXYQ40BYM

46, 48 class 50, 52 class 54, 56, 58, 60 class

RXYQ46BYM RXYQ50BYM RXYQ54BYM


RXYQ48BYM RXYQ52BYM RXYQ56BYM
RXYQ58BYM
RXYQ60BYM

11
RXYQ8-60BYM EDTRAU342315-D

4.2 Indoor Units


VRV Indoor Units

Ceiling mounted cassette


Round flow cassette with sensing and streamer type Compact multi flow cassette type

FXFTQ-A FXZQ-B

Round flow cassette with sensing type Double flow cassette type

FXFSQ-A FXCQ-B

Round flow cassette type Single flow cassette type

FXFQ-A FXEQ-A

Ceiling concealed duct


Slim duct (Standard) type Middle static pressure duct type

FXDQ-PD FXDYQ-MA
FXDQ-ND

Slim duct (Compact) type Middle-high static pressure duct type

FXDQ-T FXMQ-PA

Middle static pressure duct type High static pressure duct type

FXSQ-PA FXMQ-P

Ceiling suspended
4-way flow ceiling suspended type Ceiling suspended type

FXUQ-A FXHQ-MA FXHQ-B

12
RXYQ8-60BYM EDTRAU342315-D

Wall mounted
Wall mounted type

FXAQ-A

Floor standing
Floor standing type Concealed floor standing type

FXLQ-MA FXNQ-MA

4.3 Air Treatment Equipment

Outdoor-air processing unit Heat Reclaim Ventilator


(VAM series)
FXMQ-AF
VAM-H

Outdoor-air processing unit

FXMQ-MF

13
RXYQ8-60BYM EDTRAU342315-D

5. Combination of Outdoor Units

VRV H SERIES

Class 8 10 12 14 16 18 20 22 24
Model name RXYQ8B RXYQ10B RXYQ12B RXYQ14B RXYQ16B RXYQ18B RXYQ20B RXYQ22B RXYQ24B

Class 26 28 30 32 34 36 38 40 42
Model name RXYQ26B RXYQ28B RXYQ30B RXYQ32B RXYQ34B RXYQ36B RXYQ38B RXYQ40B RXYQ42B
Outdoor unit 1 RXYQ12B RXYQ12B RXYQ12B RXYQ12B RXYQ14B RXYQ16B RXYQ18B RXYQ20B RXYQ20B
Outdoor unit 2 RXYQ14B RXYQ16B RXYQ18B RXYQ20B RXYQ20B RXYQ20B RXYQ20B RXYQ20B RXYQ22B

Class 44 46 48 50 52 54 56 58 60
Model name RXYQ44B RXYQ46B RXYQ48B RXYQ50B RXYQ52B RXYQ54B RXYQ56B RXYQ58B RXYQ60B
Outdoor unit 1 RXYQ20B RXYQ22B RXYQ24B RXYQ12B RXYQ12B RXYQ14B RXYQ16B RXYQ18B RXYQ20B
Outdoor unit 2 RXYQ24B RXYQ24B RXYQ24B RXYQ18B RXYQ20B RXYQ20B RXYQ20B RXYQ20B RXYQ20B
Outdoor unit 3 — — — RXYQ20B RXYQ20B RXYQ20B RXYQ20B RXYQ20B RXYQ20B

System capacity Number Module Outdoor unit multi


kW Class of units 8 10 12 14 16 18 20 22 24 connection piping kit 1
22.4 8 1 l
28.0 10 1 l
33.5 12 1 l
40.0 14 1 l
45.0 16 1 l —
50.0 18 1 l
56.0 20 1 l
61.5 22 1 l
67.0 24 1 l
73.5 26 2 l l
78.5 28 2 l l
83.5 30 2 l l
89.5 32 2 l l
96.0 34 2 l l
101 36 2 l l
BHFP22R135
106 38 2 l l
112 40 2 ll
117 42 2 l l
123 44 2 l l
128 46 2 l l
134 48 2 ll
139 50 3 l l l
145 52 3 l ll
152 54 3 l ll
BHFP22R168
157 56 3 l ll
162 58 3 l ll
168 60 3 lll

Note:
+1. For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required.

14
RXYQ8-60BYM EDTRAU342315-D

6. Capacity Range
6.1 For VRV Indoor Units Only
6.1.1 Connection Ratio

Total capacity index of the indoor units


Connection ratio =
Capacity index of the outdoor units

Max. connection ratio


Types of connected indoor units Type of connected air treatment equipment
Min. FXMQ-MF FXMQ-AF
Type connection Including
FXDQ, Other When When
ratio FXFTQ25A,
FXSQ, indoor When only FXMQ-MF When only FXMQ-AF
FXFSQ25A,
FXMQ-PA, and unit FXMQ-MF is and indoor FXMQ-AF is and indoor
FXFQ25A
FXAQ models connected units are connected units are
at least one unit
connected connected
Single outdoor RXYQ8-20B 200%
units RXYQ22/24B 180%
50% 200% 130% 100% 100%* 130% A% *
Double outdoor units 160%
Triple outdoor units 130%

Notes:
1. For indoor units used for cooling only, total capacity index must be 50% or less than the capacity index of the outdoor units.
2. If the operational capacity of indoor units is more than 130%, low airflow operation is enforced in all the indoor units.
* When outdoor-air processing units (FXMQ-MF, FXMQ-AF) and standard indoor units are connected, the total connection capacity of the
outdoor-air processing units must not exceed 30% of the capacity index of the outdoor units for FXMQ-MF or B% of the capacity index of the
outdoor units, depending on the connection ratio A%, for FXMQ-AF. And the connection ratio must not exceed 100% for FXMQ-MF and 130%
for FXMQ-AF.

Connection ratio A (%) B (%)


50 ≤ connection ratio ≤ 100% 40%
100 < connection ratio ≤ 110% 30%
110 < connection ratio ≤ 120% 20%
120 < connection ratio ≤ 130% 10%

Because connection is possible depending on conditions even when the capacity index of FXMQ-MF exceeds 30% of the capacity index of the
outdoor units, contact your local distributor.

15
RXYQ8-60BYM EDTRAU342315-D

6.1.2 Outdoor Unit Combinations


VRV H SERIES
Capacity Total capacity index of Maximum number of
kW Class Model name Combination
index connectable indoor units *1 *2 connectable indoor units *1
22.4 8 200 RXYQ8B RXYQ8B 100 to 260 (400) 13 (20)
28.0 10 250 RXYQ10B RXYQ10B 125 to 325 (500) 16 (25)
33.5 12 300 RXYQ12B RXYQ12B 150 to 390 (600) 19 (30)
40.0 14 350 RXYQ14B RXYQ14B 175 to 455 (700) 22 (35)
45.0 16 400 RXYQ16B RXYQ16B 200 to 520 (800) 26 (40)
50.0 18 450 RXYQ18B RXYQ18B 225 to 585 (900) 29 (45)
56.0 20 500 RXYQ20B RXYQ20B 250 to 650 (1,000) 32 (50)
61.5 22 550 RXYQ22B RXYQ22B 275 to 715 (990) 35 (49)
67.0 24 600 RXYQ24B RXYQ24B 300 to 780 (1,080) 39 (54)
73.5 26 650 RXYQ26B RXYQ12B + RXYQ14B 325 to 845 (1,040) 42 (52)
78.5 28 700 RXYQ28B RXYQ12B + RXYQ16B 350 to 910 (1,120) 45 (56)
83.5 30 750 RXYQ30B RXYQ12B + RXYQ18B 375 to 975 (1,200) 48 (60)
89.5 32 800 RXYQ32B RXYQ12B + RXYQ20B 400 to 1,040 (1,280) 52 (64)
96.0 34 850 RXYQ34B RXYQ14B + RXYQ20B 425 to 1,105 (1,360) 55 (64)
101 36 900 RXYQ36B RXYQ16B + RXYQ20B 450 to 1,170 (1,440) 58 (64)
106 38 950 RXYQ38B RXYQ18B + RXYQ20B 475 to 1,235 (1,520) 61 (64)
112 40 1,000 RXYQ40B RXYQ20B × 2 500 to 1,300 (1,600)
117 42 1,050 RXYQ42B RXYQ20B + RXYQ22B 525 to 1,365 (1,680)
123 44 1,100 RXYQ44B RXYQ20B + RXYQ24B 550 to 1,430 (1,760)
128 46 1,150 RXYQ46B RXYQ22B + RXYQ24B 575 to 1,495 (1,840)
134 48 1,200 RXYQ48B RXYQ24B × 2 600 to 1,560 (1,920)
139 50 1,250 RXYQ50B RXYQ12B + RXYQ18B + RXYQ20B 625 to 1,625 (1,625) 64 (64)
145 52 1,300 RXYQ52B RXYQ12B + RXYQ20B × 2 650 to 1,690 (1,690)
152 54 1,350 RXYQ54B RXYQ14B + RXYQ20B × 2 675 to 1,755 (1,755)
157 56 1,400 RXYQ56B RXYQ16B + RXYQ20B × 2 700 to 1,820 (1,820)
162 58 1,450 RXYQ58B RXYQ18B + RXYQ20B × 2 725 to 1,885 (1,885)
168 60 1,500 RXYQ60B RXYQ20B × 3 750 to 1,950 (1,950)

Notes:
*1. Values inside brackets are based on connection of indoor units rated at maximum capacity, 200% for RXYQ8-20BYM, 180% for
RXYQ22/24BYM, 160% for double outdoor units, and 130% for triple outdoor units.
*2. When outdoor-air processing units (FXMQ-MF, FXMQ-AF) and standard indoor units are connected, the total connection capacity of the
outdoor-air processing units must not exceed 30% of the capacity index of the outdoor units for FXMQ-MF or B% of the capacity index of
the outdoor units, depending on the connection ratio A%, for FXMQ-AF. And the connection ratio must not exceed 100% for FXMQ-MF and
130% for FXMQ-AF.

Connection ratio A (%) B (%)


50 ≤ connection ratio ≤ 100% 40%
100 < connection ratio ≤ 110% 30%
110 < connection ratio ≤ 120% 20%
120 < connection ratio ≤ 130% 10%

Because connection is possible depending on conditions even when the capacity index of FXMQ-MF exceeds 30% of the capacity index of the
outdoor units, contact your local distributor.

16
RXYQ8-60BYM EDTRAU342315-D

2. Specification

1. Specifications............................................................................................18
1.1 Heat Pump 50/60 Hz VRV H SERIES (RXYQ-BYM).......................18
2. Dimensions................................................................................................27
2.1 Independent Unit..............................................................................27
2.2 Combination Unit.............................................................................30
3. Service Space...........................................................................................36
4. Centre of Gravity.......................................................................................37
5. Foundation of Units...................................................................................40
6. Piping Diagrams........................................................................................41
7. Wiring Diagrams........................................................................................44
8. Field Wiring...............................................................................................45
9. Electric Characteristics..............................................................................48
10.Safety Devices Setting..............................................................................51
11.Operation Limits........................................................................................53
12.Sound Levels.............................................................................................54
13.Optional Accessories.................................................................................63
14.Selection Procedure..................................................................................64
14.1 Selection Procedure.........................................................................64
15.Caution Label............................................................................................71
15.1 RXYQ8BYM / RXYQ10BYM / RXYQ12BYM / RXYQ14BYM /
RXYQ16BYM / RXYQ18BYM / RXYQ20BYM / RXYQ22BYM /
RXYQ24BYM...................................................................................71
16.Caution for Refrigerant Leaks...................................................................86
16.1 Introduction......................................................................................86
16.2 Maximum Concentration Level........................................................86
16.3 Procedure for Checking Maximum Concentration...........................87
17.Safety Devices Setting..............................................................................88
17.1 FXFTQ-A, FXF(S)Q-A......................................................................88
17.2 FXZQ-B............................................................................................88
17.3 FXCQ-B...........................................................................................88
17.4 FXEQ-A............................................................................................89
17.5 FXDQ-PD, FXDQ-ND......................................................................89
17.6 FXDQ-T............................................................................................89
17.7 FXSQ-PA.........................................................................................90
17.8 FXMQ-PA.........................................................................................90
17.9 FXMQ-P...........................................................................................90
17.10 FXUQ-A..........................................................................................91
17.11 FXHQ-MA.......................................................................................91
17.12 FXHQ-B..........................................................................................91
17.13 FXAQ-A..........................................................................................91
17.14 FXLQ-MA, FXNQ-MA.....................................................................92
17
RXYQ8-60BYM EDTRAU342315-D

1. Specifications
1.1 Heat Pump 50/60 Hz VRV H SERIES (RXYQ-BYM)
RXYQ8BYM / RXYQ10BYM / RXYQ12BYM

4D145118A

18
RXYQ8-60BYM EDTRAU342315-D

RXYQ14BYM / RXYQ16BYM / RXYQ18BYM

4D145119A

19
RXYQ8-60BYM EDTRAU342315-D

RXYQ20BYM / RXYQ22BYM / RXYQ24BYM

4D145120A

20
RXYQ8-60BYM EDTRAU342315-D

RXYQ26BYM / RXYQ28BYM / RXYQ30BYM

4D145121

21
RXYQ8-60BYM EDTRAU342315-D

RXYQ32BYM / RXYQ34BYM / RXYQ36BYM

4D145122

22
RXYQ8-60BYM EDTRAU342315-D

RXYQ38BYM / RXYQ40BYM / RXYQ42BYM

4D145123

23
RXYQ8-60BYM EDTRAU342315-D

RXYQ44BYM / RXYQ46BYM / RXYQ48BYM

4D145124

24
RXYQ8-60BYM EDTRAU342315-D

RXYQ50BYM / RXYQ52BYM / RXYQ54BYM

4D145125

25
RXYQ8-60BYM EDTRAU342315-D

RXYQ56BYM / RXYQ58BYM / RXYQ60BYM

4D145126A

26
RXYQ8-60BYM EDTRAU342315-D

2. Dimensions
2.1 Independent Unit
RXYQ8BYM / RXYQ10BYM / RXYQ12BYM
Unit: mm

3D145069

27
RXYQ8-60BYM EDTRAU342315-D

RXYQ14BYM / RXYQ16BYM / RXYQ18BYM / RXYQ20BYM


Unit: mm

3D145070

28
RXYQ8-60BYM EDTRAU342315-D

RXYQ22BYM / RXYQ24BYM
Unit: mm

3D145075

29
RXYQ8-60BYM EDTRAU342315-D

2.2 Combination Unit


RXYQ26BYM / RXYQ28BYM / RXYQ30BYM / RXYQ32BYM
Unit: mm

3D145076

30
RXYQ8-60BYM EDTRAU342315-D

RXYQ34BYM / RXYQ36BYM / RXYQ38BYM / RXYQ40BYM


Unit: mm

3D145077

31
RXYQ8-60BYM EDTRAU342315-D

RXYQ42BYM / RXYQ44BYM
Unit: mm

3D145079

32
RXYQ8-60BYM EDTRAU342315-D

RXYQ46BYM / RXYQ48BYM
Unit: mm

3D145081

33
RXYQ8-60BYM EDTRAU342315-D

RXYQ50BYM / RXYQ52BYM
Unit: mm

3D145082

34
RXYQ8-60BYM EDTRAU342315-D

RXYQ54BYM / RXYQ56BYM / RXYQ58BYM / RXYQ60BYM


Unit: mm

3D145083

35
RXYQ8-60BYM EDTRAU342315-D

3. Service Space

RXYQ8BYM / RXYQ10BYM / RXYQ12BYM / RXYQ14BYM / RXYQ16BYM / RXYQ18BYM /


RXYQ20BYM / RXYQ22BYM / RXYQ24BYM / RXYQ26BYM / RXYQ28BYM / RXYQ30BYM /
RXYQ32BYM / RXYQ34BYM / RXYQ36BYM / RXYQ38BYM / RXYQ40BYM / RXYQ42BYM /
RXYQ44BYM / RXYQ46BYM / RXYQ48BYM / RXYQ50BYM / RXYQ52BYM / RXYQ54BYM /
RXYQ56BYM / RXYQ58BYM / RXYQ60BYM

3D135459A

36
RXYQ8-60BYM EDTRAU342315-D

4. Centre of Gravity

RXYQ8BYM / RXYQ10BYM / RXYQ12BYM

Unit: mm

4D145045

37
RXYQ8-60BYM EDTRAU342315-D

RXYQ14BYM / RXYQ16BYM / RXYQ18BYM / RXYQ20BYM

Unit: mm

4D145047

38
RXYQ8-60BYM EDTRAU342315-D

RXYQ22BYM / RXYQ24BYM

Unit: mm

4D145054

39
RXYQ8-60BYM EDTRAU342315-D

5. Foundation of Units

RXYQ8BYM / RXYQ10BYM / RXYQ12BYM / RXYQ14BYM / RXYQ16BYM / RXYQ18BYM /


RXYQ20BYM / RXYQ22BYM / RXYQ24BYM / RXYQ26BYM / RXYQ28BYM / RXYQ30BYM /
RXYQ32BYM / RXYQ34BYM / RXYQ36BYM / RXYQ38BYM / RXYQ40BYM / RXYQ42BYM /
RXYQ44BYM / RXYQ46BYM / RXYQ48BYM / RXYQ50BYM / RXYQ52BYM / RXYQ54BYM /
RXYQ56BYM / RXYQ58BYM / RXYQ60BYM

3D135201A
Unit: mm

40
RXYQ8-60BYM EDTRAU342315-D

6. Piping Diagrams

RXYQ8BYM / RXYQ10BYM / RXYQ12BYM

3D144830A

41
RXYQ8-60BYM EDTRAU342315-D

RXYQ14BYM / RXYQ16BYM / RXYQ18BYM / RXYQ20BYM

3D144828A

42
RXYQ8-60BYM EDTRAU342315-D

RXYQ22BYM / RXYQ24BYM

3D143015A

43
RXYQ8-60BYM EDTRAU342315-D

7. Wiring Diagrams

RXYQ8BYM / RXYQ10BYM / RXYQ12BYM / RXYQ14BYM / RXYQ16BYM / RXYQ18BYM /


RXYQ20BYM / RXYQ22BYM / RXYQ24BYM

2D140799B

44
RXYQ8-60BYM EDTRAU342315-D

8. Field Wiring

RXYQ8BYM / RXYQ10BYM / RXYQ12BYM / RXYQ14BYM / RXYQ16BYM / RXYQ18BYM /


RXYQ20BYM / RXYQ22BYM / RXYQ24BYM

3D145117

45
RXYQ8-60BYM EDTRAU342315-D

RXYQ26BYM / RXYQ28BYM / RXYQ30BYM / RXYQ32BYM / RXYQ34BYM / RXYQ36BYM /


RXYQ38BYM / RXYQ40BYM / RXYQ42BYM / RXYQ44BYM / RXYQ46BYM / RXYQ48BYM

3D145115

46
RXYQ8-60BYM EDTRAU342315-D

RXYQ50BYM / RXYQ52BYM / RXYQ54BYM / RXYQ56BYM / RXYQ58BYM / RXYQ60BYM

3D145114

47
RXYQ8-60BYM EDTRAU342315-D

9. Electric Characteristics

RXYQ8BYM / RXYQ10BYM / RXYQ12BYM / RXYQ14BYM / RXYQ16BYM / RXYQ18BYM /


RXYQ20BYM / RXYQ22BYM / RXYQ24BYM

3D145111

48
RXYQ8-60BYM EDTRAU342315-D

RXYQ26BYM / RXYQ28BYM / RXYQ30BYM / RXYQ32BYM / RXYQ34BYM / RXYQ36BYM /


RXYQ38BYM / RXYQ40BYM / RXYQ42BYM / RXYQ44BYM / RXYQ46BYM / RXYQ48BYM

3D145112

49
RXYQ8-60BYM EDTRAU342315-D

RXYQ50BYM / RXYQ52BYM / RXYQ54BYM / RXYQ56BYM / RXYQ58BYM / RXYQ60BYM

3D145113

50
RXYQ8-60BYM EDTRAU342315-D

10.Safety Devices Setting

Safety devices RXYQ8BYM RXYQ10BYM RXYQ12BYM RXYQ14BYM


A1P 250 V, 10 A
A2P 500 V, 40 A 600 V, 63 A 500 V, 40 A
A5P — 500 V, 40 A
A3P 650 VDC, 1 A
Printed circuit board fuse
A6P — 650 VDC, 1 A
A4P 650 V, 8 A
A7P — 650 V, 8 A
A8P —
OFF : 4.0 (+0, -0.12) MPa
S1PH ON : 3.0 ± 0.15 MPa
High pressure switch
OFF : 4.0 (+0, -0.12) MPa
S2PH — ON : 3.0 ± 0.15 MPa
M1C 19.0 A 28.0 A 19.0
M2C — 19.0
Overload Protector
M1F 3.12 A 2.44 A
M2F — 2.44 A
Electronic Expansion Valve Fully close : 0 pls
EVM1
(Main) Fully open : 3000 pls
Electronic Expansion Valve
EVM2 —
(Heat Exchanger Left)
Electronic Expansion Valve Fully close : 0 pls
EVT
(Subcool Heat Exchanger) Fully open : 480 pls
Electronic Expansion Valve EVJi Fully close : 0 pls
(Refrigerant Cooling IPM) Fully open : 480 pls
Electronic Expansion Valve Fully close : 0 pls
EVJeva
(Refrigerant Cooling Air) Fully open : 480 pls
Electronic Expansion Valve Fully close : 0 pls
EVJ
(Auto Charge) Fully open : 480 pls

51
RXYQ8-60BYM EDTRAU342315-D

Safety devices RXYQ16BYM RXYQ18BYM RXYQ20BYM RXYQ22BYM RXYQ24BYM


A1P 250 V, 10 A
A2P 500 V, 40 A 600 V, 63 A
A5P 500 V, 40 A 600 V, 63 A
A3P 650 VDC, 1 A
Printed circuit board fuse
A6P 650 VDC, 1 A
A4P 650 V, 8 A
A7P 650 V, 8 A
A8P — 250 V, 3.15 A
OFF : 4.0 (+0, -0.12) MPa
S1PH ON : 3.0 ± 0.15 MPa
High pressure switch
OFF : 4.0 (+0, -0.12) MPa
S2PH ON : 3.0 ± 0.15 MPa
M1C 19.0 A 28.0 A
M2C 19.0 A 28.0 A
Overload Protector
M1F 2.44 A 3.12 A
M2F 2.44 A 3.12 A
Electronic Expansion Valve Fully close : 0 pls
EVM1
(Main) Fully open : 3000 pls
Electronic Expansion Valve Fully close : 0 pls
EVM2 —
(Heat Exchanger Left) Fully open : 3000 pls
Electronic Expansion Valve Fully close : 0 pls
(Subcool Heat Exchanger) EVT Fully open : 480 pls
Electronic Expansion Valve Fully close : 0 pls
EVJi
(Refrigerant Cooling IPM) Fully open : 480 pls
Electronic Expansion Valve Fully close : 0 pls
EVJeva
(Refrigerant Cooling Air) Fully open : 480 pls
Electronic Expansion Valve Fully close : 0 pls
EVJ
(Auto Charge) Fully open : 480 pls

52
RXYQ8-60BYM EDTRAU342315-D

11.Operation Limits

RXYQ8BYM / RXYQ10BYM / RXYQ12BYM / RXYQ14BYM / RXYQ16BYM / RXYQ18BYM /


RXYQ20BYM / RXYQ22BYM / RXYQ24BYM / RXYQ26BYM / RXYQ28BYM / RXYQ30BYM /
RXYQ32BYM / RXYQ34BYM / RXYQ36BYM / RXYQ38BYM / RXYQ40BYM / RXYQ42BYM /
RXYQ44BYM / RXYQ46BYM / RXYQ48BYM / RXYQ50BYM / RXYQ52BYM / RXYQ54BYM /
RXYQ56BYM / RXYQ58BYM / RXYQ60BYM

3D144885

53
RXYQ8-60BYM EDTRAU342315-D

12.Sound Levels

RXYQ8BYM (cooling)

4D145036
RXYQ8BYM (heating)

4D145037

54
RXYQ8-60BYM EDTRAU342315-D

RXYQ10BYM (cooling)

4D144986
RXYQ10BYM (heating)

4D144987

55
RXYQ8-60BYM EDTRAU342315-D

RXYQ12BYM (cooling)

4D144990
RXYQ12BYM (heating)

4D144988

56
RXYQ8-60BYM EDTRAU342315-D

RXYQ14BYM (cooling)

4D144991
RXYQ14BYM (heating)

4D144992

57
RXYQ8-60BYM EDTRAU342315-D

RXYQ16BYM (cooling)

4D144994
RXYQ16BYM (heating)

4D144995

58
RXYQ8-60BYM EDTRAU342315-D

RXYQ18BYM (cooling)

4D144996
RXYQ18BYM (heating)

4D144997

59
RXYQ8-60BYM EDTRAU342315-D

RXYQ20BYM (cooling)

4D144999
RXYQ20BYM (heating)

4D145000A

60
RXYQ8-60BYM EDTRAU342315-D

RXYQ22BYM (cooling)

4D145031
RXYQ22BYM (heating)

4D145032

61
RXYQ8-60BYM EDTRAU342315-D

RXYQ24BYM (cooling)

4D145033
RXYQ24BYM (heating)

4D145034

62
RXYQ8-60BYM EDTRAU342315-D

13.Optional Accessories

Optional accessories RXYQ8BYM RXYQ10BYM RXYQ12BYM RXYQ14BYM RXYQ16BYM


REFNET KHRP26M22H, KHRP26M33H, KHRP26M72H, KHRP26M73H
header (Max. 4 branch) (Max. 8 branch) (Max. 8 branch) (Max. 8 branch)
Distributive 2 Pipes REFNET joint BHRP26A22TA, BHRP26A33TA, BHRP26A72TA, BHRP26A73TA
Piping
Pipe size KHRP26M73HP
reducer
DIII-NET expand adaptor +
Option printed Wire harness adaptor kit DTA109A51 + BER11A H1
circuit board
External control adaptor DTA104A62
C: 3D145321A
Optional accessories RXYQ18BYM RXYQ20BYM RXYQ22BYM RXYQ24BYM
REFNET KHRP26M22H, KHRP26M33H, KHRP26M72H, KHRP26M73H
header (Max. 4 branch) (Max. 8 branch) (Max. 8 branch) (Max. 8 branch)
Distributive 2 Pipes REFNET joint BHRP26A22TA, BHRP26A33TA, BHRP26A72TA, BHRP26A73TA
Piping
Pipe size KHRP26M73HP
reducer
DIII-NET expand adaptor +
Option printed Wire harness adaptor kit DTA109A51 + BER11A H1
circuit board
External control adaptor DTA104A62
C: 3D145321A
Optional accessories RXYQ26BYM RXYQ28BYM RXYQ30BYM RXYQ32BYM RXYQ34BYM RXYQ36BYM
REFNET KHRP26M22H, KHRP26M33H, KHRP26M72H, KHRP26M73H
header (Max. 4 branch) (Max. 8 branch) (Max. 8 branch) (Max. 8 branch)
Distributive 2 Pipes REFNET joint BHRP26A22TA, BHRP26A33TA, BHRP26A72TA, BHRP26A73TA
Piping
Pipe size KHRP26M73HP
reducer
Outdoor unit multi connection piping kit BHFP22R135
DIII-NET expand adaptor +
Option printed Wire harness adaptor kit DTA109A51 + BER11A H1
circuit board
External control adaptor DTA104A62
C: 3D145321A
Optional accessories RXYQ38BYM RXYQ40BYM RXYQ42BYM RXYQ44BYM RXYQ46BYM RXYQ48BYM
REFNET KHRP26M22H, KHRP26M33H, KHRP26M72H, KHRP26M73H
header (Max. 4 branch) (Max. 8 branch) (Max. 8 branch) (Max. 8 branch)
Distributive 2 Pipes REFNET joint BHRP26A22TA, BHRP26A33TA, BHRP26A72TA, BHRP26A73TA
Piping
Pipe size
KHRP26M73HP
reducer
Outdoor unit multi connection piping kit BHFP22R135
DIII-NET expand adaptor +
Option printed Wire harness adaptor kit DTA109A51 + BER11A H1
circuit board
External control adaptor DTA104A62
C: 3D145321A
Optional accessories RXYQ50BYM RXYQ52BYM RXYQ54BYM RXYQ56BYM RXYQ58BYM RXYQ60BYM
REFNET KHRP26M22H, KHRP26M33H, KHRP26M72H, KHRP26M73H
header (Max. 4 branch) (Max. 8 branch) (Max. 8 branch) (Max. 8 branch)
Distributive 2 Pipes REFNET joint BHRP26A22TA, BHRP26A33TA, BHRP26A72TA, BHRP26A73TA
Piping
Pipe size KHRP26M73HP
reducer
Outdoor unit multi connection piping kit BHFP22R168
DIII-NET expand adaptor +
Option printed Wire harness adaptor kit DTA109A51 + BER11A H1
circuit board
External control adaptor DTA104A62
C: 3D145321A
Note:
+1 BER11A is necessary when connecting DTA109A51 to the main PCB.

63
RXYQ8-60BYM EDTRAU342315-D

14.Selection Procedure
14.1 Selection Procedure
14.1.1 Flowchart

Given Conditions:
· Design temperature and humidity (indoor & outdoor)
[1] Given conditions · Required heat load of each room
· System peak load ( if necessary)
· Piping length, level difference
· Specifications of indoor units (type and number)

Define safety factor for the indoor units and outdoor unit
[2] Selection of indoor units

Indoor unit capacity corrected for indoor air temperature (WB) ≥ Required heat load × Safety factor for the indoor units

[3] Selection of outdoor unit


Define required total heat load to outdoor unit

1) Use the sum of the peak load of each room 2) Use the system peak load

Provisionally select outdoor unit type and size based on limitation of connection ratio

Confirm that the number of indoor units connected to the outdoor unit is within limitation.

Correct for cooling & heating capacity of the outdoor unit by the following items
-Outdoor air temperature -Piping length, level difference
-Indoor air temperature -Piping heat loss
-Connection ratio -Safety factor for the outdoor unit
-Defrost (only for heating capacity)

No
Corrected capacity of the outdoor unit ≥ Required total heat load to the outdoor unit

Yes

VRV system selection is complete.

64
RXYQ8-60BYM EDTRAU342315-D

14.1.2 Selection Example

The following is a selection example based on total heat load for cooling.

Room H Room G
Room A Room F

Room B Room E
Room C Room D
Floor plan

[1] Given conditions


-Design conditions
Indoor air temperature: 18°CWB / 25°CDB, Outdoor air temperature: 33°CDB

-Determine peak load of each room (and system peak load if necessary)

-Required heat load of each room


Time Room A Room B Room C Room D Room E Room F Room G Room H Total
9:00 4.8 4.8 3.0 3.0 9.1 9.0 2.9 2.9 39.5
12:00 6.6 7.1 5.1 5.1 7.4 6.8 4.0 4.0 46.1
14:00 9.0 9.4 4.9 4.9 7.3 6.8 4.2 4.2 50.7
16:00 11.6 11.7 3.9 3.9 6.3 6.2 3.8 3.8 51.2
Total heat load (kW)

From the above heat load calculation, the maximum heat load for the system (system peak load) is 51.2 kW.

Equivalent pipe length 76 m


Level difference
64 m

Select VRV indoor units FXMQ-PA series for each room.

-Safety factor
In this example, safety factor is not used. (i. e., safety factor = 1.0)

65
RXYQ8-60BYM EDTRAU342315-D

[2] Selection of indoor units


Calculate total heat capacity of indoor units corrected for indoor air temperature.
In case design temperature of the indoor air falls between temperatures listed in the table, calculate the capacity by
interpolation.
The corrected total heat capacity of indoor units shall satisfy the maximum heat load of each room.

Capacity table of indoor unit


Cooling capacity for Te: Auto
Indoor air temp.
Capacity 14°CWB 16°CWB 18°CWB 19°CWB 20°CWB 22°CWB 24°CWB
Model indication 20°CDB 23°CDB 26°CDB 27°CDB 28°CDB 30°CDB 32°CDB
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
FXMQ20PAVE 20 1.9 1.9 2.1 2.1 2.2 2.0 2.2 1.9 2.2 1.9 2.3 1.8 2.3 1.8
FXMQ25PAVE 25 2.5 2.2 2.6 2.3 2.8 2.5 2.8 2.3 2.8 2.2 2.9 2.1 3.0 2.2
FXMQ32PAVE 32 3.2 2.6 3.4 2.7 3.5 2.9 3.6 2.8 3.6 2.7 3.7 2.7 3.8 2.6
FXMQ40PAVE 40 4.0 3.7 4.2 4.0 4.4 4.2 4.5 3.8 4.6 3.7 4.7 3.5 4.8 3.6
FXMQ50PAVE 50 4.9 4.3 5.3 4.7 5.5 5.0 5.6 4.6 5.7 4.5 5.8 4.3 5.9 3.6
FXMQ63PAVE 63 6.3 5.1 6.7 5.5 7.0 5.8 7.1 5.5 7.2 5.4 7.3 5.3 7.5 5.2
FXMQ80PAVE 80 7.9 6.5 8.5 7.0 8.8 7.4 9.0 7.0 9.1 6.9 9.3 6.6 9.5 6.6
FXMQ100PAVE 100 9.9 8.2 10.5 8.8 11.0 9.1 11.2 8.5 11.3 8.4 11.6 8.1 11.8 7.8
FXMQ125PAVE 125 12.3 10.2 13.2 10.9 13.8 11.3 14.0 10.5 14.2 10.4 14.5 10.1 14.8 9.6
FXMQ140PAVE 140 14.1 11.8 15.0 12.5 15.7 12.8 16.0 12.0 16.2 11.9 16.5 11.5 16.9 11.2

TC : Total capacity: kW
SHC : Sensible heat capacity: kW

Selection results of indoor units


Room A Room B Room C Room D Room E Room F Room G Room H
Max. heat 11.6 11.7 5.1 5.1 9.1 9.0 4.2 4.2
load (kW)
Selected IDU FXMQ125PAVE FXMQ125PAVE FXMQ50PAVE FXMQ50PAVE FXMQ100PAVE FXMQ100PAVE FXMQ40PAVE FXMQ40PAVE
Corrected TC 13.8 13.8 5.5 5.5 11.0 11.0 4.4 4.4
(kW)

∗In case of selection based on Total Heat Load and Sensible Heat Load, select indoor units which satisfy not only the Total
Heat Load but also the Sensible Heat Load of each room. The sensible heat capacity of indoor units is to be corrected for
indoor air temperature. If the design temperature of indoor air falls between temperatures listed in table, calculate sensible
heat capacity by using the bypass factor calculated by interpolation for each indoor air temperature.

66
RXYQ8-60BYM EDTRAU342315-D

[3] Selection of outdoor unit


[3]–1 Define the required total heat load from the indoor units to the outdoor unit
Define the required total heat load (A) based on (1) the sum of the peak load of each room or (2) the system peak load.
In this example, select an outdoor unit by (2).
Therefore, (A) = 51.2 kW

[3]–2 Provisionally select outdoor unit


(1) Calculate CI (Capacity Index) of the selected indoor units.
CI of VRV indoor units
CI of FXMQ125PAVE = 125
CI of FXMQ100PAVE = 100
CI of FXMQ50PAVE = 50
CI of FXMQ40PAVE = 40
VRV Indoor Units

2.2 2.8 3.6 4.5 5.6 7.1 8.0 9.0 11.2 14.0 16.0 16.2 18.0 20.0 22.4 28.0 Power
Capacity range kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW supply,
Capacity index 20 25 31.25 40 50 62.5 71 80 100 125 140 145 160 180 200 250 Standard
Middle-High Static FXMQ 20PA 25PA 32PA 40PA 50PA 63PA — 80PA 100PA 125PA 140PA — — — — — VE
Pressure Duct

Calculate the total CI of the indoor units.


Total CI = 125 × 2 + 50 × 2 + 100 × 2 + 40 × 2 = 630

(2) Provisionally select an outdoor unit based on the total CI of the indoor units
The connection ratio of RXYQ-B shall be between 50% and 130%.
As the total CI of the indoor units is 630, outdoor units from 20 class to 50 class are connectable. Start from 20 class which is
the smallest outdoor unit.
Capacity Total capacity index of Maximum number of
kW Class Model name Combination
index connectable indoor units *1 *2 connectable indoor units *1
22.4 8 200 RXYQ8B RXYQ8B 100 to 260 (400) 13 (20)
28.0 10 250 RXYQ10B RXYQ10B 125 to 325 (500) 16 (25)
33.5 12 300 RXYQ12B RXYQ12B 150 to 390 (600) 19 (30)
40.0 14 350 RXYQ14B RXYQ14B 175 to 455 (700) 22 (35)
45.0 16 400 RXYQ16B RXYQ16B 200 to 520 (800) 26 (40)
50.0 18 450 RXYQ18B RXYQ18B 225 to 585 (900) 29 (45)
56.0 20 500 RXYQ20B RXYQ20B 250 to 650 (1,000) 32 (50)
61.5 22 550 RXYQ22B RXYQ22B 275 to 715 (990) 35 (49)
67.0 24 600 RXYQ24B RXYQ24B 300 to 780 (1,080) 39 (54)
73.5 26 650 RXYQ26B RXYQ12B + RXYQ14B 325 to 845 (1,040) 42 (52)
78.5 28 700 RXYQ28B RXYQ12B + RXYQ16B 350 to 910 (1,120) 45 (56)
83.5 30 750 RXYQ30B RXYQ12B + RXYQ18B 375 to 975 (1,200) 48 (60)
89.5 32 800 RXYQ32B RXYQ12B + RXYQ20B 400 to 1,040 (1,280) 52 (64)
96.0 34 850 RXYQ34B RXYQ14B + RXYQ20B 425 to 1,105 (1,360) 55 (64)
101 36 900 RXYQ36B RXYQ16B + RXYQ20B 450 to 1,170 (1,440) 58 (64)
106 38 950 RXYQ38B RXYQ18B + RXYQ20B 475 to 1,235 (1,520) 61 (64)
112 40 1,000 RXYQ40B RXYQ20B × 2 500 to 1,300 (1,600)
117 42 1,050 RXYQ42B RXYQ20B + RXYQ22B 525 to 1,365 (1,680)
123 44 1,100 RXYQ44B RXYQ20B + RXYQ24B 550 to 1,430 (1,760)
128 46 1,150 RXYQ46B RXYQ22B + RXYQ24B 575 to 1,495 (1,840)
134 48 1,200 RXYQ48B RXYQ24B × 2 600 to 1,560 (1,920)
139 50 1,250 RXYQ50B RXYQ12B + RXYQ18B + RXYQ20B 625 to 1,625 (1,625) 64 (64)
145 52 1,300 RXYQ52B RXYQ12B + RXYQ20B × 2 650 to 1,690 (1,690)
152 54 1,350 RXYQ54B RXYQ14B + RXYQ20B × 2 675 to 1,755 (1,755)
157 56 1,400 RXYQ56B RXYQ16B + RXYQ20B × 2 700 to 1,820 (1,820)
162 58 1,450 RXYQ58B RXYQ18B + RXYQ20B × 2 725 to 1,885 (1,885)
168 60 1,500 RXYQ60B RXYQ20B × 3 750 to 1,950 (1,950)

(3) Confirm that the number of the connected indoor units is within the limitation.
The number of the connected indoor units = 8
The Max. number of connectable indoor units of 20 class outdoor unit = 32

67
RXYQ8-60BYM EDTRAU342315-D

[3]–3 Calculate the corrected capacity of the outdoor unit.


-Calculate the connection ratio of the system.
Total CI = 630, CI of RXYQ20BYM = 500
Connection ratio = 630 / 500 = 126%

-Using the capacity table of the outdoor unit, calculate the capacity (B) corrected for outdoor air temperature, indoor air
temperature, and connection ratio.

∗ In case the outdoor air temperature, the indoor air temperature, or the connection ratio falls between temperatures listed in
the table, calculate the capacity by interpolation.

RXYQ20BYM Cooling capacity (VRT)


Outdoor Indoor air temp. (°CWB)
Capacity air 14 16 18 19 20 22 24
ratio (%) temp. TC PI TC PI TC PI TC PI TC PI TC PI TC PI
°CDB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
10 63.8 10.4 68.2 10.6 71.6 10.7 72.7 10.7 73.5 10.7 74.9 10.8 76.3 10.8
12 63.1 10.8 67.3 10.9 70.4 11.1 71.4 11.2 72.2 11.2 73.7 11.3 75.1 11.4
14 62.3 11.1 66.4 11.3 69.3 11.4 70.3 11.5 71.0 11.6 72.5 11.8 73.9 11.9
16 61.5 11.5 65.5 11.7 68.2 11.9 69.1 12.0 69.9 12.1 71.4 12.3 72.7 12.5
18 60.8 11.9 64.6 12.1 67.1 12.3 68.0 12.4 68.7 12.5 70.2 12.7 71.6 13.0
20 60.0 12.4 63.7 12.5 66.1 12.7 66.9 12.9 67.6 13.0 69.1 13.2 70.5 13.5
21 59.6 12.6 63.3 12.8 65.5 13.0 66.3 13.1 67.1 13.2 68.6 13.4 70.0 13.7
23 58.8 13.1 62.4 13.3 64.5 13.5 65.3 13.6 66.1 13.7 67.5 14.0 69.0 14.2
130%
25 58.0 13.6 61.5 13.8 63.5 14.0 64.3 14.1 65.0 14.2 66.5 14.5 68.0 14.8
27 57.3 14.1 60.6 14.3 62.5 14.6 63.3 14.7 64.0 14.8 65.4 15.1 66.9 15.3
29 56.5 14.7 59.6 14.9 61.5 15.1 62.3 15.3 63.0 15.4 64.4 15.7 65.9 15.9
31 55.7 15.3 58.7 15.5 60.6 15.7 61.3 15.9 62.1 16.0 63.4 16.3 64.9 16.6
33 54.9 15.9 57.8 16.1 59.6 16.4 60.4 16.5 61.1 16.6 62.5 16.9 63.9 17.1
35 54.1 16.6 56.9 16.8 58.7 17.0 59.5 17.1 60.2 17.2 61.5 17.5 62.9 17.8
37 53.2 17.1 56.0 17.3 57.8 17.5 58.5 17.6 59.3 17.8 60.6 18.2 61.8 18.5
39 52.4 17.6 55.0 17.8 56.8 18.4 57.5 18.5 57.6 18.7 59.2 18.9 60.8 19.2
10 61.7 10.4 66.3 10.5 69.9 10.7 71.3 10.8 72.5 10.8 73.8 11.0 75.1 11.1
12 60.9 10.7 65.4 10.9 68.8 11.0 70.2 11.1 71.2 11.2 72.6 11.4 73.9 11.6
14 60.2 11.1 64.5 11.2 67.8 11.4 69.0 11.5 70.0 11.6 71.4 11.8 72.7 12.0
16 59.5 11.5 63.6 11.6 66.8 11.8 67.9 11.9 68.8 12.0 70.2 12.2 71.5 12.4
18 58.8 11.9 62.7 12.0 65.8 12.2 66.9 12.3 67.7 12.4 69.1 12.7 70.4 12.9
20 58.1 12.3 61.9 12.5 64.8 12.7 65.8 12.8 66.6 12.9 68.0 13.1 69.3 13.4
21 57.8 12.6 61.4 12.7 64.3 12.9 65.3 13.0 66.1 13.1 67.4 13.4 68.8 13.6
23 57.1 13.0 60.6 13.2 63.3 13.4 64.2 13.5 65.0 13.7 66.4 13.9 67.7 14.2
120%
25 56.4 13.5 59.8 13.7 62.4 14.0 63.2 14.1 63.9 14.2 65.3 14.4 66.7 14.7
27 55.7 14.1 59.0 14.3 61.4 14.5 62.2 14.6 62.9 14.7 64.3 15.0 65.7 15.3
29 54.9 14.6 58.1 14.9 60.5 15.1 61.2 15.2 61.9 15.3 63.3 15.6 64.7 15.9
31 54.2 15.2 57.3 15.4 59.5 15.7 60.3 15.8 61.0 15.9 62.3 16.2 63.6 16.5
33 53.4 15.9 56.5 16.1 58.6 16.3 59.3 16.4 60.0 16.6 61.3 16.8 62.6 17.1
35 52.7 16.5 55.7 16.7 57.6 17.0 58.4 17.1 59.1 17.2 60.3 17.5 61.6 17.8
37 51.9 17.1 54.9 17.4 56.7 17.6 57.4 17.8 58.1 17.9 59.4 18.2 60.6 18.5
39 51.1 17.6 54.1 17.9 55.8 18.4 56.5 18.5 56.8 18.6 58.1 18.9 59.5 19.2

Connection ratio 120% 126% 130%

Cooling capacity 58.6 (B) 59.6

(B) = 58.6 + (59.6 – 58.6) × (126 – 120) / (130 – 120) = 59.2

68
RXYQ8-60BYM EDTRAU342315-D

-Confirm capacity correction factor by piping length and level difference (K1)

(K1) = 0.882
Step 3

Step 1
Step 2

Step 1) Calculate correction factor of equivalent length 76 m at vertical pipe length 70 m


Equivalent length 70 m 76 m 80 m (X) = 0.89 + (0.87 - 0.89) × (76 - 70) / (80 - 70)
Correction factor at vertical = 0.878
0.89 (X) 0.87
pipe length 70 m

Step 2) Calculate correction factor of equivalent length 76 m at vertical pipe length 60 m


Equivalent length 70 m 76 m 80 m (Y) = 0.89 + (0.88 - 0.89) × (76 - 70) / (80 - 70)
Correction factor at vertical = 0.884
0.89 (Y) 0.88
pipe length 60 m

Step 3) Calculate correction factor of equivalent length 76 m at vertical pipe length 64 m


Correction factor at (K1) = 0.884 + (0.878 - 0.884) × (64 - 60) / (70 - 60)
Vertical pipe length equivalent length = 0.882
76 m
70 m 0.878
64 m (K1)
60 m 0.884

69
RXYQ8-60BYM EDTRAU342315-D

-Calculate capacity correction factor by piping heat loss (K2)


(K2) = 1 + (heat loss factor per meter of piping × (equivalent piping length – 7.5 m)) / 100

In cooling mode, heat loss factor per meter at 33°C is calculated as below.
Heat loss factor per meter = 0.022 + (0.030 – 0.022) × (33 – 30) / (35 – 30) = 0.0268

Using "Equivalent piping length = 76 m" and "Heat loss factor per meter = 0.0268"
(K2) = 1 + (0.0268 × (76 – 7.5)) / 100 = 1.018
Cooling Ambient temperature
Heat loss factor per 5°C 10°C 15°C 20°C 25°C 30°C 35°C 40°C
meter of piping (%) 0.000 0.000 0.004 0.009 0.014 0.022 0.030 0.038

Heating Ambient temperature


Heat loss factor per -15°C -10°C -5°C 0°C 5°C 10°C 15°C 20°C
meter of piping (%) 0.100 0.093 0.086 0.078 0.071 0.064 0.057 0.049

-Calculate the corrected capacity of RXYQ20BYM(C) by using (K1) and (K2).


Corrected capacity of RXYQ20BYM(C) = (B) × (K1) / (K2) (Add defrost correction factor for heating capacity)
59.2 × 0.882 / 1.018 = 51.3 (kW)

If the corrected capacity (C) is the same or greater than the required total heat load (A), selection is complete.
If (C) < (A), return to Procedure [3]-2 and provisionally select a larger outdoor unit.

In this example, 51.3 kW (C) ≥ 51.2 kW (A), so selection is complete.

70
RXYQ8-60BYM EDTRAU342315-D

15.Caution Label
15.1 RXYQ8BYM / RXYQ10BYM / RXYQ12BYM / RXYQ14BYM / RXYQ16BYM /
RXYQ18BYM / RXYQ20BYM / RXYQ22BYM / RXYQ24BYM

2P714092-1B

71
RXYQ8-60BYM EDTRAU342315-D

2P714092-1B

72
RXYQ8-60BYM EDTRAU342315-D

2P714092-1B

73
RXYQ8-60BYM EDTRAU342315-D

2P714092-1B

74
RXYQ8-60BYM EDTRAU342315-D

2P714092-1B

75
RXYQ8-60BYM EDTRAU342315-D

2P714092-1B

76
RXYQ8-60BYM EDTRAU342315-D

2P714092-1B

77
RXYQ8-60BYM EDTRAU342315-D

15.1.1 RXYQ8BYM / RXYQ10BYM / RXYQ12BYM

3P714062-1

78
RXYQ8-60BYM EDTRAU342315-D

3P714062-1

79
RXYQ8-60BYM EDTRAU342315-D

15.1.2 RXYQ14BYM / RXYQ16BYM / RXYQ18BYM / RXYQ20BYM

3P714085-1

80
RXYQ8-60BYM EDTRAU342315-D

3P714085-1

81
RXYQ8-60BYM EDTRAU342315-D

15.1.3 RXYQ22BYM / RXYQ24BYM

3P714074-1

82
RXYQ8-60BYM EDTRAU342315-D

3P714074-1

83
RXYQ8-60BYM EDTRAU342315-D

15.1.4 RXYQ8BYM / RXYQ10BYM / RXYQ12BYM / RXYQ14BYM / RXYQ16BYM / RXYQ18BYM /


RXYQ20BYM / RXYQ22BYM / RXYQ24BYM

3P714028-1

84
RXYQ8-60BYM EDTRAU342315-D

3P714028-1

85
RXYQ8-60BYM EDTRAU342315-D

16.Caution for Refrigerant Leaks


16.1 Introduction

The installer and system specialist shall secure safety against leakage according to local regulations or standards. The following standards may
be applicable if local regulations are not available.
This system uses R410A as refrigerant. R410A itself is an entirely safe non-toxic, non-combustible refrigerant. Nevertheless care must be taken
to ensure that air conditioning facilities are installed in a room which is sufficiently large. This assures that the maximum concentration level of
refrigerant gas is not exceeded, in the unlikely event of major leak in the system and this in accordance to the local applicable regulations and
standards.

16.2 Maximum Concentration Level

The maximum charge of refrigerant and the calculation of the maximum concentration of refrigerant is directly related to the humanly occupied
space in to which it could leak.
The unit of measurement of the concentration is kg/m3 (the weight in kg of the refrigerant gas in 1m3 volume of the occupied space).
Compliance to the local applicable regulations and standards for the maximum allowable concentration level is required.

1 Direction of the refrigerant flow


2 Room where refrigerant leak has occurred (outflow of all the refrigerant from the system)
Pay special attention to places, such as basements etc., where refrigerant can stay, since refrigerant is heavier than air.

86
RXYQ8-60BYM EDTRAU342315-D

16.3 Procedure for Checking Maximum Concentration

Check the maximum concentration level in accordance with steps 1 to 4 below and take whatever action is necessary to comply.
1 Calculate the amount of refrigerant (kg) charged to each system separately.

+ =
Amount of refrigerant in a single unit system Additional charging amount (amount of
(amount of refrigerant with which the system is refrigerant added locally in accordance with the Total amount of refrigerant (kg) in the system
charged before leaving the factory) length or diameter of the refrigerant piping)

NOTICE
Where a single refrigerant facility is divided into 2 entirely independent refrigerant systems, use the amount of refrigerant with
which each separate system is charged.

2 Calculate the volume of the room (m3) where the indoor unit is installed.
In a case such as the following, calculate the volume of (A), (B) as a single room or as the smallest room.
A Where there are no smaller room divisions:

B Where there is a room division, but there is an opening between the rooms sufficiently large to permit a free flow of air back and forth.

1
2
1 Opening between the rooms
2 Partition
(Where there is an opening without a door or where there are openings above and below
the door which are each equivalent in size to 0.15% or more of the floor area.)

3 Calculating the refrigerant density using the results of the calculations in steps 1 and 2 above.
Total volume of refrigerant in the refrigerant system

Size (m3) of smallest room in which there is an indoor unit installed ≤ Maximum concentration level (kg/m3)

If the result of the above calculation exceeds the maximum concentration level, a ventilation opening to the adjacent room shall be made.

4 After opening to the adjacent room are mode, re-calculate.


If result of calculation exceeds the maximum concentration level. Room re-modified are required, please contact your dealer.

87
RXYQ8-60BYM EDTRAU342315-D

17.Safety Devices Setting


17.1 FXFTQ-A, FXF(S)Q-A

FXFTQ25AVM FXFTQ32AVM FXFTQ40AVM


Model FXF(S)Q25AVM FXF(S)Q32AVM FXF(S)Q40AVM
Printed circuit board fuse 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A
Fan motor thermal protector — — —
Drain pump thermal protector °C — — —

FXFTQ50AVM FXFTQ63AVM FXFTQ80AVM


Model FXF(S)Q50AVM FXF(S)Q63AVM FXF(S)Q80AVM
Printed circuit board fuse 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A
Fan motor thermal protector — — —
Drain pump thermal protector °C — — —

FXFTQ100AVM FXFTQ125AVM FXFTQ140AVM


Model FXF(S)Q100AVM FXF(S)Q125AVM FXF(S)Q140AVM
Printed circuit board fuse 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A
Fan motor thermal protector — — —
Drain pump thermal protector °C — — —
C: 3D112954D

17.2 FXZQ-B

Model FXZQ20BVM FXZQ25BVM FXZQ32BVM


Printed circuit board fuse 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A
Fan motor
current protection Nominal A 0.74 0.74 0.74
Fan motor
thermal protector Maximum °C 108 108 108
Drain pump fuse — — —

Model FXZQ40BVM FXZQ50BVM


Printed circuit board fuse 250 V, 3.15 A 250 V, 3.15 A
Fan motor
current protection Nominal A 0.74 0.74
Fan motor
thermal protector Maximum °C 108 108
Drain pump thermal fuse — —
C: 4D128550D

17.3 FXCQ-B

Model FXCQ20BVM FXCQ25BVM FXCQ32BVM FXCQ40BVM


Printed circuit board fuse 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A
Printed circuit board fuse — — — —
(Fan driver)
Fan motor thermal fuse °C — — — —
Fan motor thermal protector °C — — — —
Drain pump thermal fuse °C — — — —

Model FXCQ50BVM FXCQ63BVM FXCQ80BVM FXCQ125BVM


Printed circuit board fuse 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A
Printed circuit board fuse 250 V, 5 A 250 V, 5 A
— —
(Fan driver) 250 V, 6.3 A 250 V, 6.3 A
Fan motor thermal fuse °C — — — —
Fan motor thermal protector °C — — — —
Drain pump thermal fuse °C — — — —
3D118231B

88
RXYQ8-60BYM EDTRAU342315-D

17.4 FXEQ-A

Model FXEQ20AV36 FXEQ25AV36 FXEQ32AV36


Printed circuit board (A1P) fuse 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A
OFF: 106±5°C OFF OFF: 106±5°C OFF OFF: 106±5°C OFF
Fan motor thermal protector °C ON : 96±15°C ON ON : 96±15°C ON ON : 96±15°C ON

Model FXEQ40AV36 FXEQ50AV36 FXEQ63AV36


Printed circuit board fuse 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A
Fan motor temperature OFF: 106±5°C OFF OFF: 106±5°C OFF OFF: 106±5°C OFF
°C
protection ON : 96±15°C ON ON : 96±15°C ON ON : 96±15°C ON
C: 4D085034A

17.5 FXDQ-PD, FXDQ-ND

Model FXDQ20PDVE FXDQ25PDVE FXDQ32PDVE


Printed circuit board fuse 250 V, 5 A 250 V, 5 A 250 V, 5 A
Fan motor temperature OFF: 130±5 OFF: 130±5 OFF: 130±5
°C
protector ON : 83±15 ON : 83±15 ON : 83±15
Drain pump thermal fuse °C 145 145 145

Model FXDQ40NDVE FXDQ50NDVE FXDQ63NDVE


Printed circuit board fuse 250 V, 5 A 250 V, 5 A 250 V, 5 A
Fan motor temperature OFF: 130±5 OFF: 130±5 OFF: 130±5
°C
protector ON : 83±15 ON : 83±15 ON : 83±15
Drain pump thermal fuse °C 145 145 145
3D104897B

17.6 FXDQ-T

Model FXDQ20TV1C FXDQ25TV1C FXDQ32TV1C


Printed circuit board fuse A1P 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A
Fan motor temperature OFF: 100+15
- 10 OFF: 100+15
- 10 OFF: 100+15
- 10
°C
protection +15
ON : 95 - 10
+15
ON : 95 - 10
+15
ON : 95 - 10

Model FXDQ40TV1C FXDQ50TV1C FXDQ63TV1C


Printed circuit board fuse A1P 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A
Fan motor temperature OFF: 100+15
- 10 OFF: 100+15
- 10 OFF: 100+15
- 10
°C
protection +15
ON : 95 - 10
+15
ON : 95 - 10
+15
ON : 95 - 10
C: 4D115160A

Model FXDQ20TV1CA FXDQ25TV1CA FXDQ32TV1CA


Main printed circuit board A1P
fuse
250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A
Multitenant printed circuit A2P
board fuse
Fan motor temperature OFF: 100+15
- 10 OFF: 100+15
- 10 OFF: 100+15
- 10
°C
protection +15
ON : 95 - 10
+15
ON : 95 - 10
+15
ON : 95 - 10

Model FXDQ40TV1CA FXDQ50TV1CA FXDQ63TV1CA


Main printed circuit board A1P
fuse
250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A
Multitenant printed circuit A2P
board fuse
Fan motor temperature OFF: 100+15
- 10 OFF: 100+15
- 10 OFF: 100+15
- 10
°C
protection +15
ON : 95 - 10
+15
ON : 95 - 10
+15
ON : 95 - 10
C: 4D117785

89
RXYQ8-60BYM EDTRAU342315-D

17.7 FXSQ-PA

Model FXSQ20PAVE FXSQ25PAVE FXSQ32PAVE FXSQ40PAVE


Printed circuit board fuse 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A
Printed circuit board fuse 250 V, 6.3 A 250 V, 6.3 A 250 V, 6.3 A 250 V, 6.3 A
(Fan driver)
Drain pump thermal fuse °C — — — —

Model FXSQ50PAVE FXSQ63PAVE FXSQ80PAVE FXSQ100PAVE


Printed circuit board fuse 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A
Printed circuit board fuse 250 V, 6.3 A 250 V, 6.3 A 250 V, 6.3 A 250 V, 6.3 A
(Fan driver)
Drain pump thermal fuse °C — — — —

Model FXSQ125PAVE FXSQ140PAVE


Printed circuit board fuse 250 V, 3.15 A 250 V, 3.15 A
Printed circuit board fuse 250 V, 6.3 A 250 V, 6.3 A
(Fan driver)
Drain pump thermal fuse °C — —
C: 3D104897B

17.8 FXMQ-PA

Model FXMQ20PAVE FXMQ25PAVE FXMQ32PAVE FXMQ40PAVE


Printed circuit board fuse 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A
Printed circuit board fuse 250 V, 5 A 250 V, 5 A 250 V, 5 A 250 V, 5 A
(Fan driver)
Drain pump thermal fuse °C — — — —

Model FXMQ50PAVE FXMQ63PAVE FXMQ80PAVE FXMQ100PAVE


Printed circuit board fuse 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A
Printed circuit board fuse 250 V, 6.3 A 250 V, 6.3 A 250 V, 6.3 A 250 V, 6.3 A
(Fan driver)
Drain pump thermal fuse °C — — — —

Model FXMQ125PAVE FXMQ140PAVE


Printed circuit board fuse 250 V, 3.15 A 250 V, 3.15 A
Printed circuit board fuse 250 V, 6.3 A 250 V, 6.3 A
(Fan driver)
Drain pump thermal fuse °C — —
C: 3D104897B

17.9 FXMQ-P

Model FXMQ160PV1A FXMQ180PV1A FXMQ200PV1A FXMQ250PV1A


Printed circuit board fuse 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A
Printed circuit board fuse 250 V 10 A 250 V 10 A 250 V 10 A 250 V 10 A
(Fan driver)
C: 3D111223

90
RXYQ8-60BYM EDTRAU342315-D

17.10 FXUQ-A

Model FXUQ71AVEB FXUQ100AVEB


Fuse 250 V, 3.15 A 250 V, 3.15 A
Fan motor thermal fuse °C — —
Fan motor thermal protector °C — —
4D013856M

17.11 FXHQ-MA

Model FXHQ32MAVE FXHQ50MAVE FXHQ63MAVE


Printed circuit board fuse 250 V, 5 A 250 V, 5 A 250 V, 5 A
Fan motor thermal fuse °C — — —
OFF: 130±5 OFF: 130±5 OFF: 130±5
Fan motor thermal protector °C ON : 80±20 ON : 80±20 ON : 80±20

Model FXHQ80MAVE FXHQ100MAVE


Printed circuit board fuse 250 V, 5 A 250 V, 5 A
Fan motor thermal fuse °C — —
OFF: 130±5 OFF: 130±5
Fan motor thermal protector °C ON : 80±20 ON : 80±20
C: 3D034597Q
C: 4D137428

17.12 FXHQ-B

Model FXHQ125BVM FXHQ140BVM


Fuse 250 V, 3.15 A 250 V, 3.15 A
Fan motor thermal fuse °C DC 500 V, 4 A DC 500 V, 4 A
Fan motor thermal protector °C — —
4D121708A

17.13 FXAQ-A

Model FXAQ20AVM FXAQ25AVM FXAQ32AVM


Printed circuit board fuse 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A
Fan motor thermal fuse °C — — —
Fan motor thermal protector °C — — —

Model FXAQ40AVM FXAQ50AVM FXAQ63AVM


Printed circuit board fuse 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A
Fan motor thermal fuse °C — — —
Fan motor thermal protector °C — — —
4D122550A

91
RXYQ8-60BYM EDTRAU342315-D

17.14 FXLQ-MA, FXNQ-MA

FXLQ20MAVE FXLQ25MAVE FXLQ32MAVE


Model FXNQ20MAVE FXNQ25MAVE FXNQ32MAVE
Printed circuit board fuse 250 V, 5 A 250 V, 5 A 250 V, 5 A
Fan motor thermal fuse °C — — —
Fan motor thermal OFF: 135±10 OFF: 135±10 OFF: 135±10
°C
protector ON : 120 or less ON : 120 or less ON : 120 or less

FXLQ40MAVE FXLQ50MAVE FXLQ63MAVE


Model FXNQ40MAVE FXNQ50MAVE FXNQ63MAVE
Printed circuit board fuse A1P 250 V, 5 A 250 V, 5 A 250 V, 5 A
Fan motor thermal fuse °C — — —
Fan motor thermal OFF: 135±10 OFF: 135±10 OFF: 135±10
°C
protector ON : 120 or less ON : 120 or less ON : 120 or less
C: 3D034529G

92
RXYQ8-60BYM EDTRAU342315-D

3. Optional Accessories of Control

1. System Configuration................................................................................94
2. Building Management System...................................................................95

93
RXYQ8-60BYM EDTRAU342315-D

1. System Configuration

No. Item Model No. Function


n Up to 16 groups of indoor units (128 units) can be easily
DCS303A51 controlled using the large LCD panel. ON/OFF,
1 Residential central remote controller (Note 2) temperature settings and scheduling can be controlled
individually for indoor units.

2 Interface adaptor for SkyAir series H DTA112BA51 n Adaptors required to connect products other than those
(Note 3) of the VRV system to the high-speed DIII-NET
communication system adopted for the VRV system.
3 Central control adaptor kit For UAT(Y)-K(A),FD-K H DTA107A55 HTo use any of the above optional controllers, an
appropriate adaptor must be installed on the product
4 Wiring adaptor for other air-conditioner H DTA103A51 unit to be controlled.
n Up to 1024 units can be centrally controlled in 64
DTA109A51 + different groups.
5 DIII-NET expand adaptor + Wire harness adaptor kit n Wiring restrictions (max. length: 1,000 m, total wiring
BER11A
length: 2,000 m, max. number of branches: 16) apply to
each adaptor.

5-1 External control adaptor DTA104A62 n Demand control of individual or multiple systems.
n Low noise option for individual or multiple systems.

Notes:
1. Installation box for H adaptor must be obtained locally.
2. For residential use only. Cannot be used with other centralized control equipment.
3. No adaptor is required for some indoor units.

94
RXYQ8-60BYM EDTRAU342315-D

2. Building Management System

No. Item Model No. Function


intelligent Touch n Air-Conditioning management system that can be controlled by a
1 Basic Hardware DCS601C51
intelligent Controller compact all-in-one unit.
1-1 Touch Hardware DIII-NET plus adaptor DCS601A52 n Additional 64 groups (10 outdoor units) is possible.
Controller Option n VRV system that is connected to intelligent Touch Controller can
1-2 Software Web software DCS004A51 be operated from the user's PC via a web page.
1-3 Electrical box with earth terminal (4 blocks) KJB411A n Wall embedded switch box.
intelligent Touch n Air-conditioning management system that can be controlled by
2 Basic Hardware DCM601B51
Manager touch screen.
2-1 DIII plus adaptor DGE601A52 n Additional 64 groups (10 outdoor units) are possible.
Hardware DIII plus adaptor and Max. 6 DIII plus adaptor slots can be
2-2 DIII plus adaptor slot DGE601A53 connected to intelligent Touch Manager.

intelligent iTM power n Power consumption of indoor units are calculated based on
2-3 Touch proportional DCM002A51 operation status of the indoor unit and outdoor unit power
Manager distribution consumption measured by kWh metre.
Option
n Building energy consumption is visualised.
2-4 Software iTM energy navigator DCM008A51 Wasted air-conditioning energy can be found out.
n BACnet® equipment can be managed by intelligent Touch
2-5 BACnet® client DCM009A51 Manager.
2-6 HTTP Interface DCM007A51 n Interface for intelligent Touch Manager by HTTP
n VRV smart controller (website or mobile app via smartphone or
2-7 Reiri for Office DCPF01 tablet) for small to medium scale building
Reiri for Office n VRV smart controller with touch panel (website or mobile app via
2-8
(Touchscreen Controller) H1 DCPF04-AU smartphone or tablet) for small to medium scale building
Reiri for Office
2-9 DCPF05 n VRV smart controller for large scale building
Basic Hardware (Controller Extension)
Reiri for Office
2-10 DCPF10 n Control all VRV units via Reiri for Office on multisite
(Multisite Extension)
2-11 Reiri for Home DCPH01 n VRV smart home automation and smart control solution
Reiri for Home
2-12 DCPH02 n VRV smart centralised controller
(Lite Version)
2-13 DCPA01 n Interface adaptor for Reiri
Adaptor for Reiri
2-14 Hardware DCPA01B n Interface adaptor for Reiri with installation box
2-15 IAQ Sensor DC for Reiri DCPE02S n IAQ Sensor for Reiri (24V AC/DC)
Smartphone/
Commercial Automatic
2-16 Tablet control DCPN001 n Set back, Scene, Interlock Automatic Changeover functions for
Control individual controller
Commercial Data n Operation Report, Error Report; Trend Graph, Energy Graph
2-17 DCPN002
Analytics functions for individual controller
PPD & Tenant Billing n Power Proportional Distribution and billing function for individual
2-18 DCPN003
Option Software Management controller
(Commercial) Realtime Energy
2-19 DCPN004 n Real Time Energy Display function for individual controller
Monitoring (REM)
Multisite Branch
2-20 DCPN005 n To expand the multisite control limit by 1 site
Expansion
iTM Tenant Billing
2-21 DCPN008 n Billing function for iTM Power Proportional Distribution data
Management
Residential Automatic n Setback, Setpoint Range, Remote Control Prohibition, Automatic
2-22 Software DCPN006
Control Changeover functions for individual controller
(Residential)
2-23 Residential System Report DCPN007 n Operation Report, Error Report functions for individual controller
2-24 Di unit DEC101A51 n 8 pairs based on a pair of ON/OFF input and abnormality input.
2-25 Dio unit DEC102A51 n 4 pairs based on a pair of ON/OFF input and abnormality input/output.
n Interface unit to allow communications between VRV and BMS.
3 H2 Interface for use in BACnet® DMS502B51 Operation and monitoring of air-conditioning systems through
BACnet® communication.
n Expansion kit, installed on DMS502B51, to provide 2 more
3-1 Optional DIII board DAM411B51 DIII-NET communication ports. Not usable independently.

Communication Optional Di board n Expansion kit, installed on DMS502B51, to provide 16 more


3-2 DAM412B51 wattmeter pulse input points. Not usable independently.
interface
n Interface unit to allow communications between VRV and BMS.
4 H3 Interface for use in LONWORKS® DMS504B51 Operation and monitoring of air-conditioning systems through
LONWORKS® communication.
H5 n Use of the Modbus® protocol enables the connection of the
5 Modbus® communication adaptor DTA116A51 VRV system with a variety of home automation systems from
other manufacturers.
Contact/ Unification adaptor for computerised
6 analog signal control H DCS302A52 n Interface
units.
between the central monitoring board and central control

95
RXYQ8-60BYM EDTRAU342315-D

Notes:
+1. Reiri for Office (Touchscreen Controller) DCPF04-AU includes built-in Commercial Automatic Control functions (Set back, Scene, Interlock Automatic Changeover).
+2 BACnet® is a registered trademark of American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE).
+3. LONWORKS® is a trademark of Echelon Corporation registered in the United States and other countries.
+4. Installation box for H adaptor must be obtained locally.
+5. Modbus® is a registered trademark of Schneider Electric S.A.

96
RXYQ8-60BYM EDTRAU342315-D

4. Appendix

1. ED book list...............................................................................................98

97
RXYQ8-60BYM EDTRAU342315-D

1. ED book list
Refer to the latest version.

Design Manual.................................................. RXYQ-B ......EDTRAU342315-D


(This booklet)
Capacity Table Book
Heat Pump...................................................... RXYQ-B ........ EDTRMT342320-C

Installation
Heat Pump...................................................... RXYQ-B ........ EDTRMT342320-N

Indoor Units
Ceiling Mounted Cassette

Round Flow Cassette with Sensing and Streamer type.... FXFTQ-A ........... EDTFMT392208

Round Flow Cassette with Sensing type............. FXFSQ-A ........... EDFMT391769D

Round Flow Cassette type............................... FXFQ-A ........... EDFMT391770D

Compact Multi Flow Cassette type.................... FXZQ-B ........... EDTFMT392234

Double Flow Cassette type.............................. FXCQ-B ........... EDTFMT392235

Single Flow Cassette type............................... FXEQ-A ............. EDFMT391734

Ceiling Concealed Duct


FXDQ-PD
Slim Duct (Standard) type................................ FXDQ-ND ............. EDFAU391829

Slim Duct (Compact) type................................ FXDQ-T ........... EDBFAU392101

Middle Static Pressure Duct type...................... FXSQ-PA ........... EDFMT391737A

Middle Static Pressure Duct type...................... FXDYQ-MA ............. EDFAU391818

Middle-High Static Pressure Duct type............... FXMQ-PA ........... EDFMT391738A

High Static Pressure Duct type......................... FXMQ-P ............... EDAU391723

Ceiling Suspended

4-Way Flow Ceiling Suspended type.................. FXUQ-A ............. EDFMT391732

Ceiling Suspended type.................................. FXHQ-MA ........... EDTFMT392147

Ceiling Suspended type.................................. FXHQ-B ........... EDTFMT392236

Wall Mounted

Wall Mounted type......................................... FXAQ-A ........... EDTFMT391910

Floor Standing
FXLQ-MA
Floor Standing type / Concealed Floor Standing type.... FXNQ-MA ............. EDFMT391742

Air Treatment Equipment


Outdoor-Air Processing Unit................................ FXMQ-AF .........EDTFMT392138A
Outdoor-Air Processing Unit................................ FXMQ-MF ............. EDFMT391745
Heat Reclaim Ventilator (VAM series)................... VAM-H .......... EDMMT712101A

98
Warning Ask a qualified installer or contractor to install this product. Do not try to install the product yourself.
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.
Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or
contractor to install those parts and accessories. Use of unauthorised parts and accessories or
improper installation of parts and accessories can result in water or refrigerant leakage, electrical
shock, fire or explosion.
Read the user’s manual carefully before using this product. The user’s manual provides important
safety instructions and warnings. Be sure to follow these instructions and warnings.
Notice About harmonics, since this product is equipped with an inverter, harmonics will be generated. If local
laws require the suppression of harmonics on the building, please take harmonic suppression
measures on the electrical equipment side. Please contact your local sales company for details.
If you have any enquiries, please contact your local importer, distributor and/or retailer.

Cautions on product corrosion


1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.
2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install
the outdoor unit close to the sea shore, contact your local distributor.

VRV is a trade mark of Daikin Industries, Ltd.