Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Using Directional Protection To Protect Isolated Neutral

Networks
It is necessary to consider special requirements when In order to use directional protection on the OSM the user
installing reclosers onto electrical distribution networks with must program a torque angle into the controller which then
isolated neutrals. Phase to ground faults in particular can determines when power flow is forward or reverse.
have capacitively coupled fault currents on adjacent
feeders when a phase to ground fault occurs. As a result When a fault occurs, the phase angle between positive
any network protection scheme needs to be able to detect sequence voltage and current is calculated. If this angle is
the direction of the fault. within +/- 90 degrees of the torque angle then the power
flow is in a forward direction and the positive sequence
In the example below, a fault is shown on the bottom feeder protection settings will be applied. If the phase angle is
downstream of recloser R4. This has resulted in outside of this area then the power flow is in a reverse
capacitively coupled fault currents in the adjacent feeders direction and the negative sequence protection settings are
to start flowing in the opposite direction into the fault used instead.
through the substation medium voltage bus connection. If
R1, R2 and R3 were not able to detect the actual direction of Using reclosers with directional protection capabilities on
the power flow, then they may trip erroneously. This would isolated neutral networks has distinct advantages. This
result in customers losing their supply unnecessarily. method can eliminate the need for substation circuit
breakers to operate to clear the fault while at the same time
The best solution would be to have just R4 trip, while the isolating just the faulted section. In addition, the reclosers
other reclosers remain closed. This is achieved by utilising provide the added ability to automatically restore the supply
reclosers with full directional protection. When the fault if the fault is transient.
occurs, R1, R2 and R3 detect that the power flow is in the
opposite direction and use this to block the fault so they do
not trip. R4 detects the power flow is flowing downstream
and trips normally, according to its earth fault settings.

All NOJA Power reclosers feature full directional protection.


To do this they measure voltage and current on all three
phases using built-in Rogowski current sensors and
capacitive voltage sensors. The controller then calculates
positive and zero sequence voltage and current to
determine the phase angle and direction of power flow. The
positive current calculation is used for overcurrent
protection while zero sequence is used for earth fault.

where: Upol polarising voltage


Iop operating current
Aop phase angle between
Upol and current Iop
At preset torque angle
Note: A full description of how
directional protection is implemented
by NOJA Power can be found in the
OSM User Manual.

You might also like