Professional Documents
Culture Documents
Yu 2020
Yu 2020
fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2020.2977373, IEEE
Transactions on Power Delivery
> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) < 1
Abstract—To meet the ultra-fast, selective, and reliable Traditional methods, such as over-current protection,
requirements of the DC fault protection, a protection scheme for distance protection, and current differential protection, are
modular multilevel converter based HVDC grids is proposed in this difficult to meet the special requirements of MMC-HVDC for
paper. The protection scheme is consisted of main protection,
protection selectivity and operation speed[6]. As a result, it is
directional pilot protection, and faulty pole identification. The new
fault directional criterion is achieved by employing the surge urgent to explore new fast fault identification methods. At
arriving time difference of line-mode backward traveling wave and present, the fault protection technology of two-terminal line
line-mode forward traveling wave. This criterion is valid even when commutated converter based high voltage direct current
the fault current limiting reactors(FCLRs) are installed at the transmission(LCC-HVDC) is more mature[7-9]. The line
converter side of DC bus. The main protection without protection boundary composed of DC filter and flat-wave
communication and complex computation relies on co-operation of
reactor has the performance of attenuating specific harmonic
the derivative of line-mode forward traveling wave and the
directional criterion. The directional pilot protection by comparing and high-frequency transient components, which is utilized in
the double end directional criteria can be used as a backup the design of protection scheme[7]. In addition, it has a high
protection. The accumulation of zero-mode component is adopted reference value for the design of fast fault identification scheme
to discriminate the faulty pole. Simulations have demonstrated that for MMC-HVDC.
the proposed scheme is capable of identifying various types of faults Thanks to the fault current limiting reactors(FCLRs) that can
with different fault resistances at different positions. The
be installed at the ends of each line, the discriminations
robustness analysis shows that the protection scheme presented is
not sensitive to the FCLR size, noise environment, sampling between the faulty line and the sound lines are more obvious.
frequency, and the operation of hybrid DC circuit breakers. Therefore, extensive researches on non-communication base
protection scheme have carried out in MMC-HVDC. Owing to
Index Terms—DC fault protection scheme, fault analysis, fault the smoothness characteristic of FCLR, reference [10] and [11]
directional criterion, modular multilevel converter base HVDC adopt the rate of change of voltage(ROCOV) to design the fast
(MMC-HVDC), faulty pole identification DC fault protection scheme. The value of ROCOV in line side
of the faulty line is larger than the sound lines. In order to
improve the ability of fault discrimination, reference [12] and
I. INTRODUCTION
[13] measure the ROCOV through the FCLR and use its
0885-8977 (c) 2019 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: Auckland University of Technology. Downloaded on June 05,2020 at 04:00:04 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2020.2977373, IEEE
Transactions on Power Delivery
> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) < 2
Bus3 Bus4
M M Isolation Fast-mechanical
R34 Line34 R43
M M switch disconnector Auxiliary DC breaker
205.1km
C R32 R41 C
Kangbo Fenning
Hybird DCCB
Line23 Line14 Arrester 1 Arrester 2
FCLR 49.3km Main DC breaker 1 Main DC breaker 2
186.7km
F2
Measuring point
Fig. 2. Structure of the hybrid DCCB.
Bus2 Bus1
M R23 R14 M Table 1 Main parameters of the stations in Zhangbei test system
Line12 Stations
M R21 206.6km R12
M Parameters
Beijing Zhangbei Kangbo Fenning
C C F4 SM capacitance (mF) 10 10 15 15
Zhangbei F1 Beijing Number of SM 228 228 312 312
F3 F5
Arm reactor (mH) 150 150 100 100
Fig. 1. Configuration of Zhangbei MMC-HVDC. Leakage reactance (%) 15 15 15 15
Transformer ratio (kV/kV) 525/260 230/260 230/260 525/260
single-end directional start-up criterion and the surge arriving AC short circuit level (kA) 16.2 18.1 18.6 23.9
Capacity (MW) 3 000 3 000 1 500 1 500
time difference(SATD) between the zero-mode and line-mode
traveling wave, but it can only identify pole to ground faults.
This paper proposes a DC fault protection scheme consisted is shown in Fig. 2[3]. During normal operation, the current will
of main protection, directional pilot protection and faulty pole only flow through the bypass which is formed by an auxiliary
identification. The remainder of the paper is organized as DC breaker in series with a fast-mechanical disconnector.
follows. Section II depicts the topology and parameters of the When a DC line fault has been identified, the auxiliary DC
simulation system. Section III analyzes the propagation breaker immediately commutates the current to the main DC
property of the transient traveling waves at inductive terminal. breaker and the fast-mechanical disconnector opens[3]. After
Section IV proposes the protection scheme and discusses the 3ms delay, the main DC breakers are turned off. The rated
protection setting for the case study. Section V validates the voltage of arresters 1 and arrester 2 are 220kV and 200kV
proposed protection scheme for multiple scenarios by respectively in the simulation model.
simulations. Section VI analyzes the robustness of the proposed
protection scheme and Section VII gives the concluding III. TRANSIENT TRAVELING WAVES ANALYSIS
remarks. A. Initial Voltages at Fault Point
To design the fast dc-line protection scheme, it is requisite to
II. SIMULATION SYSTEM
analyze the MMC-HVDC system operating under fault
A four-terminal overhead line ±500kV MMC-HVDC grid conditions. In bipolar system, both of the voltages of the faulty
for renewable energy sources integration and transmission will and healthy pole suffer from large fluctuation during pole to
be constructed around 2019 in China[5]. The technical route of ground (PTG) faults. To decouple the electrical quantities of
"half bridge sub-module MMC plus large capacity hybrid DC the poles, the method of phase-modal transformation provides
circuit breaker" is adopted in this demonstration project. such a function. Therefore, the pole voltages can be resolved
Zhangbei MMC-HVDC grid is a bipolar and ring-connection into zero-mode component and line-mode component. The
configuration. Overhead transmission line is chosen for the decoupling matrix Q is[9]:
relative low cost and the high technology matureness, and it 1 1 1
adopts the metallic return scheme[19]. Q= (1)
Fig. 1 gives a schematic diagram of the monopole structure 2 1 −1
of Zhangbei MMC-HVDC grid. The four stations are Beijing, In bipolar MMC-HVDC system, the initial values of the
Zhangbei, Kangbo and Fenning respectively. The fixed DC traveling wave at the fault point are not exceptional with the
voltage control is adopted at the Beijing station which is the traditional LCC-HVDC system. In addition, it has been
relaxed node of the whole DC grid, and the other stations are thoroughly analyzed based on the superposition principle[9].
fixed active power control. In order to suppress the rapidly rise 1) PTG faults: using positive pole to ground (P-PTG) fault as
of DC fault current, it is necessary to install FCLRs on both an example, the change of zero-mode component and
sides of the lines. In Fig. 1, the FCLR in line23 is 300mH and line-mode component at the fault point can be expressed as:
the other lines are 200mH, F1-5 indicate faults occurring in − 2U N Z c 0
different areas and R(1-4)(1-4) are the signal measuring points in u f 0 =
Z c 0 + Z c1 + 2 Rg
different protection areas respectively.
(2)
The main parameters of each converter station are shown in − 2U N Z c1
Table 1[19]. In this paper, a simulation model based on u fP1 = Z + Z + 2 R
Zhangbei MMC-HVDC grid is built in PSCAD/EMTDC. The c0 c1 g
hybrid DCCBs proposed by ABB are installed at the ends of Where UN is the rated voltage of the MMC-HVDC system,
each line as shown in Fig. 1. The structure of the hybrid DCCB Zc1 and Zc0 is the line-mode and zero-mode surge impedance of
0885-8977 (c) 2019 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: Auckland University of Technology. Downloaded on June 05,2020 at 04:00:04 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2020.2977373, IEEE
Transactions on Power Delivery
> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) < 3
0885-8977 (c) 2019 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: Auckland University of Technology. Downloaded on June 05,2020 at 04:00:04 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2020.2977373, IEEE
Transactions on Power Delivery
> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) < 4
0885-8977 (c) 2019 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: Auckland University of Technology. Downloaded on June 05,2020 at 04:00:04 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2020.2977373, IEEE
Transactions on Power Delivery
> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) < 5
Once the derivative of uf1 is larger than kset, the derivative Using(16) to detection the first
surge time tb1、tf1
criterion will have “yes” output. The proposed main protection Pilot protection N du f 1
k set
Send Flag3=1 dt
is achieved by co-operation of the criterion (20) and (21). Delay SATD k1 * td N
Y ?
3) Directional Pilot Protection ? Y
Receive Flag3' Y
A directional pilot protection(DPP) scheme is achieved by Flag1=1
Flag2=1
the remote-end. And the local-end protection will wait for Fault area is identified
Flag3′ which is sent by remote-end protection. The Flag3 is Using(23) to obtain ub 0 (t ) Pole identification
defined as:
S -S set S S set − S set S S set
1, SATD k1 * td ? ? ?
Flag3= (22) P-PTG
Y
N-PTG
Y
PTP
Y
0, otherwise
Action signal to DCCB
There will be a delay from detecting a positive directional
Fig. 5. Flowchart of the overall protection scheme
fault to receiving the Flag3′ at the local-end protection. The
delay is a variable which is determined by the length of the Table 2 Protection settings at different measuring points
transmission line and the position of the fault. The delay and the Measuring points td(ms) kset(kV/ms) Sset(kV)
time sequence of the DPP scheme will be analyzed in Section R12, R21 1.38 2000 500
V-A. The local-end pilot protection will identify the fault area if R14, R41 1.25 2000 500
R23, R32 0.33 2200 600
the double end directional criteria are all positive. R34, R43 1.37 2000 500
4) Faulty Pole Identification
As deduction in (2)-(3), the accumulation of zero-mode
faulty pole identification scheme will identify the faulty pole.
component can be used for the faulty pole identification, and it
Finally, the action instructions will be issued to DCCBs.
can be given as follows:
u0 (t ) − Z c 0 i0 (t ) C. Protection Setting for the Case Study
ub 0 (t )= (23)
2 In case study, all the setting parameters are set based on
and simulation results under limiting conditions. Although td and
N kset are depend on dc network characteristics, the setup method
S = ub 0 (k + i ) (24) can be used in other dc networks. As the start-up unit, it is
i =1
necessary to check all possible line faults, especially with high
S S set , N-PTG fault resistance. Therefore, the threshold value of is set at
S − Sset , P-PTG (25) 30kV which is able to detect remote-end PTP fault with over
S S , PTP 800ohm fault resistance. The directional criterion of SATD is
set almost close to zero in faulty line, while it is td as in (9) in sound
Where S is the accumulation of zero-mode component, k is line at the same dc bus. Therefore, the threshold coefficient k1 is
the sampling point when it is satisfied the start-up element, N is set to 0.5 for best discrimination. At different measuring points,
the length for accumulation which is adopted N=6 in this paper, the values of td are given in Table 2, and they are determined by
Sset is the threshold value to discriminate the faulty pole. the length of lines. The threshold value of kset should be smaller
5) Overall Protection Scheme than the measured value after high impedance PTG fault at the
Based on the aforementioned analysis, the overall protection end of transmission line and larger than the measured value
scheme is depicted in Fig. 5. Once any pole satisfies the start after PTP bus fault at the remote-end. It is noteworthy that kset is
criterion, the subsequent protection will be triggered. In Fig. 5, mainly effected by the size of FCLR. The threshold value of Sset
we use Flag1 and Flag2 to indicate whether the directional is set to greater than a fixed value because the accumulation of
criterion and derivative criterion have “yes” outputs or not zero-mode component is close to zero after PTP faults. And it
respectively. When both criteria are satisfied, the fault area is should be smaller than the measured value after the high
identified by the local measurement based main protection. The impedance PTG fault at the end of line. The above protection
DPP scheme works like as a backup protection. the Flag3′ is the boundaries are obvious. According to the dc network in Fig. 1,
tripping signal from the remote-end. The local-end DPP the threshold values of kset and Sset at different measuring points
scheme will locate the fault area if the double-end directional are given in Table 2. Finally, the SE used for MMF is flat in the
criteria are all positive. After the fault area is identified, the case study, and it is set as g={0 0 0}.
0885-8977 (c) 2019 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: Auckland University of Technology. Downloaded on June 05,2020 at 04:00:04 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2020.2977373, IEEE
Transactions on Power Delivery
> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) < 6
0885-8977 (c) 2019 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: Auckland University of Technology. Downloaded on June 05,2020 at 04:00:04 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2020.2977373, IEEE
Transactions on Power Delivery
> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) < 7
t p = t f + tr (26) 12000
0O
Where tp is the total time cost, tf is the fixed action time 50O
10000
including signal processing, criterion operation and so on, tr is 100O
200O
of Kset in faulty region, while they are far below the threshold in R21-PN
1000
no-faulty region, whatever the types of faults happen or where
the faults happen. In addition, the results of PTG faults (P-PTG 0
or N-PTG) lower than PTP fault are almost alike. The DC bus -1000
fault(F3) and the AC side three phase fault(F4) would not lead
-2000
to incorrect identification of the proposed scheme. Noteworthy,
the measuring points R14 and R23 could be excluded according -3000
0885-8977 (c) 2019 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: Auckland University of Technology. Downloaded on June 05,2020 at 04:00:04 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2020.2977373, IEEE
Transactions on Power Delivery
> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) < 8
12000
Z c1 Z c1
Ldc
10000 R12 2u fP1 (t )
R21
Z t1
Main protection (kV/ms)
Rmax
8000
6000
Fig. 12. Peterson equivalent circuit of line-mode component.
4000 0 ub1
uf1
u(p.u.)
0
u(p.u.)
2000
ub1 u
-1 -1 f1
0 0 (a) Waves Time(ms)
measured at R12 1 0 (b) WavesTime(ms)
measured at R14 2
0 50 100 150 200 250 300
Size of FCLR (mH)
300 20 300
t b1 tf1 tb1
MMF(kV)
MMF(kV)
Fig. 11. Influence of FCLR sizes for the main protection.
t f1
0 0 0
VI. ROBUSTNESS ANALYSIS 0 Time(ms) 1 0 Time(ms) 2
(c) After MMF at R12 (d) After MMF at R14
A. Influence of the Sizes and Positions of the FCLR Fig. 13. Protection results under FCLR is shared.
The main function of DC reactor is to limit the rising speed
of fault current, and the size of it is decided by the system 0 0
parameters. Therefore, it is necessary to study the effects of the uf1
u(p.u.)
u(p.u.)
uf1
sizes and positions of the FCLR for the protection schemes. ub1 ub1
To validate the influence of FCLR sizes, FCLRs varying -0.8 -0.8
from 30mH to 300mH separately are simulated in Fig. 1 system. 0 (a) Waves Time(ms)
measured at R12 1 0 (b) WavesTime(ms)
measured at R21 1
200 200
According to (5)-(6), the line-mode forward traveling waves t f1 tf1
MMF(kV)
MMF(kV)
and backward traveling waves are hardly influenced by FCLR 100 t b1 100 t b1
sizes. The size of FCLR only affects the attenuation rate
without affecting the initial value. The decay time constant is 0
Time(ms)
0
Time(ms)
0 (c) After MMF at R12 1 0 (d) After MMF at R21 1
increased with the increasing of FCLR size as in (6), but the
SATD is not affected by FCLR size obviously. Therefore, only Fig. 14. Protection results with 35db SNR.
the derivatives of line-mode forward traveling waves with
different FCLR sizes are discussed in follows. A P-PTG fault at u f ,1 (t ) = ub1 (t ) + u f 1 (t ) (28)
1/8 length of line12 is applied at 0s with 0ohm fault resistance.
The line-mode backward and forward traveling waves can be
The protection results are shown in Fig. 11. In Fig. 11, Rmax is detected simultaneously in faulty line, but with a time delay(td)
the maximum value calculated in no-faulty region except R14
in sound line. A P-PTG fault at middle of line12(F1) with 0ohm
and R23, because R14 and R23 can be eliminated by directional
fault resistance is applied at 0s under FCLRs installed at the
criterion. It is clearly indicated that the discriminations of faulty converter side of DC bus. The simulation results are shown in
and no-faulty region are obvious even when the size of FCLR is
Fig. 13, and it is indicated that the directional criterion is still
lower than 50mH. Therefore, the proposed main protection
working. although the amplitude of uf1 in faulty line after MMF
would be effective if the FCLR is greater than 100mH. is lower, because the values of uf1 is continuous at t=τ1.
Fig. 12 is the Peterson equivalent circuit of line-mode
component when FCLRs are installed at the converter side of B. Influence of Noises
DC bus. According to Fig. 12, it can be calculated that the In the actual environment, the measured signals are mixed
initial line-mode backward traveling wave (ub1) in faulty line is with different components of noises which may interfere with
the same as (5), which is not affected by the position of FCLR. the fault protection scheme. In order to test the robustness under
However, the initial line-mode forward traveling wave (uf1) in noisy environment, a P-PTG fault at middle of line12(F1) with
faulty line is given as follows: 100ohm fault resistance is applied at 0s. Then, white noise with
u fP1 Z c1 − t −T1 35db of signal-to noise ratio(SNR) was added in the measured
u f 1 (t ) = (e − 1) (t − 1 ) (27) signals. The line-mode backward traveling waves and forward
2Z t1 + Z c1
traveling waves at R12 and R21 are shown in Fig. 14(a) and Fig.
Where Zt1 is the equivalent line-mode impedance of MMC, 14(b). The corresponding results after MMF are shown in Fig.
T=2Ldc/(2Zt1+ZC1) is the decay time constant. Comparing with 14(c) and Fig. 14(d), and it is clearly indicated that the proposed
(27) and (6), it can be found that the uf1 do not occur step DPP scheme is also applicable in the case of 35db SNR noisy
change at t=τ1 when FCLRs are installed at the converter side of environment.
DC bus. Therefore, the amplitude of uf1 after MMF is far lower
than ub1. According to Fig. 12, the initial line-mode backward C. Influence of Sampling Frequency
traveling wave is zero in sound line, and the line-mode forward In general, with the increasing of sampling frequency, the
traveling wave is the sum of ub1 and uf1, and can be given as: protection accuracy is also improved. However, the higher the
0885-8977 (c) 2019 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: Auckland University of Technology. Downloaded on June 05,2020 at 04:00:04 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2020.2977373, IEEE
Transactions on Power Delivery
> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) < 9
after MMF(kV)
forward forward Fault Detecting
Directio- Position
Methods detecti- high fault
nal or not of signal
on time resistance
Proposed scheme Yes <1ms 1 >400ohm
0 0 ROCOV[10, 11] No <1ms 1 >100ohm
0 Time(ms) 1 0 Time(ms) 1
(a) 100kHz sampling frequency (b) 50kHz sampling frequency Voltage at FCLR[13] Transient 1ms 1 300ohm
180 180
backward backward ROCOV at FCLR[12] Transient <1ms 1 >200ohm
after MMF(kV)
after MMF(kV)
forward forward Ratio of ROCOV[14] Yes <1ms 2 >200ohm
[4, 15, 16, 17]
ROTV Yes >1ms 2 >200ohm
0 0
0 (c) 20kHz Time(ms) 1 0 (d) 10kHzTime(ms) 1
sampling frequency sampling frequency judge the advantages of different protection schemes by one
Fig. 15. Protection results under different sampling frequency. specific index. Therefore, this paper compares with different
methods in directional or not, fault detection time, position of
6 ubreaker 2 signal and ability to detect fault resistance. The corresponding
Current(kA)
Voltage(p.u.)
Ib
comparison results are shown in Table 4. Where the fault
fault detection I main
1 detection time refers to the period from traveling wave arriving
0 at measuring point to identifying the fault. The transient means
0 that the directional is valid when the initial traveling wave
0 Time(ms) 10
(a) DCCB breaking at R12 arrives, and it may be affected by fault position. The data of
1
detecting high fault resistance are from the simulation results in
Voltage(p.u.)
voltage of R14 corresponding papers. In Table 4, those methods are all based
voltage of Bus1
0 on single-end main protection.
The purpose of directional discrimination is to improve the
voltage of R12 difference of protection boundary between faulty and healthy
Time(ms)-1
0
(b) voltage at Beijing station 10 zone. The proposed new directional criterion uses the SATD
Fig. 16. Currents and voltages after DCCB breaking. instead of the magnitude of traveling waves, and it is almost
unaffected by fault resistance and fault position. Therefore, the
sampling frequency is, the more cost the protection is. The proposed DPP scheme is able to detect high resistance faults
sampling frequency is chosen as 20kHz in this paper, but the (over 800omh). Moreover, the proposed directional criterion is
proposed scheme can work at other sampling frequency. not sensitive to the sizes of FCLR. The proposed local
A P-PTG fault at middle of line12(F1) with 0ohm fault measurement based ultra-high-speed main protection can detect
resistance is applied at 0s. The protection results at R12 with faults within 1ms, which is shorter than ROTV methods. The
10kHz, 20kHz, 50kHz, 100kHz severally are shown in Fig. 15. proposed scheme is easy to achieve, and it is not required
Theoretically, as long as the sampling interval is smaller than intra-station communication. In a word, the proposed scheme
the setting value(k2 × 0.33ms) of the shortest line in Fig. 1, then meets the special protection requirements of MMC-HVDC.
the directional criterion is working. However, the proposed
scheme is impractical on the ultra-short lines. VII. CONCLUSION
D. Influence of Hybrid DCCB Operation It is crucial to have an ultra-fast, selective, and reliable DC
fault protection scheme, so that there is time to open the DCCB
The transient process of DCCB during the interruption may
before its capacity is breached. A DC fault protection scheme
cause interference to the fault protection scheme. The proposed
consisted of main protection, directional pilot protection and
protection scheme was established by the simulation platform,
faulty pole identification is presented in this paper.
and it triggers the hybrid DCCB when the DC line fault is
The simulations have demonstrated that the proposed
detected. A P-PTG fault at 1/8 length of line12 with 0ohm fault
scheme is capable of identifying various types of faults with
resistance is applied at 0s. The voltage and currents at Beijing
different fault resistances at different positions. According to
station are shown in Fig. 16 during the interruption. In Fig.
the robustness analysis, the proposed scheme is not sensitive to
16(a), Ib and Imain are the currents in bypass branch and the main
the FCLR size, noise environment, sampling frequency and the
DC breaker severally, and ubreaker is the voltage of the DCCB.
operation of hybrid DCCBs within limits. Discrimination of
According to a large number of simulations, the protection
lighting fault and dc-bus fault protection scheme have not been
values of no-faulty regions are far lower than the threshold
discussed in this paper. The dc-bus fault can be achieved by
during the interruption. Therefore, it is confirmed that the
using current differential protection. Further study considering
transient process of DCCB during the interruption do not
lightning disturbance and lightning fault identification will be
engender the performance degradation of the proposed
addressed later.
protection scheme.
E. Comparison Studies REFERENCES
The proposed scheme is compared with the existing methods [1] R. Li, L. Xu, D. Holliday, F. Page, S. J. Finney, and B. W. Williams,
which are based on the characteristics of FCLR. It is difficult to "Continuous operation of radial multiterminal HVDC systems under DC
0885-8977 (c) 2019 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: Auckland University of Technology. Downloaded on June 05,2020 at 04:00:04 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2020.2977373, IEEE
Transactions on Power Delivery
> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) < 10
fault," IEEE Transactions on Power Delivery, vol. 31, no. 1, pp. 351-361, [22] F. Namdari and M. Salehi, "A high-speed protection scheme based on
Feb. 2016. initial current traveling wave for transmission lines employing
[2] B. J. Rui, V. A. Lacerda, R. M. Monaro, J. C. M. Vieira, and D. V. Coury, mathematical morphology," IEEE Transactions on Power Delivery, vol.
"Selective non-unit protection technique for multiterminal VSC-HVDC 32, no. 1, pp. 246-253, Feb. 2017.
grids," IEEE Transactions on Power Delivery, vol. 33, no. 5, pp. [23] F. Kong, Z. Hao, S. Zhang and B. Zhang, "Development of a Novel
2106-2114, Oct. 2018. Protection Device for Bipolar HVDC Transmission Lines," IEEE
[3] J. Häfner and B. Jacobson, "Proactive hybrid HVDC breakers - a key Transactions on Power Delivery, vol. 29, no. 5, pp. 2270-2278, Oct.
innovation for reliable HVDC grids," presented at the The electric power 2014.
system of the future - Integrating supergrids and microgrids International
Symposium in Bologna, Italy, 2011.
[4] W. Xiang, S. Yang, L. Xu, J. Zhang, W. Lin, and J. Wen, "A transient
voltage based DC fault line protection scheme for MMC based DC grid
embedding DC breakers," IEEE Transactions on Power Delivery, vol. 34, Xiuyong Yu obtained his B.E. degrees in
no. 1, pp. 334-345, Feb. 2019. electrical engineering from China Agricultural
[5] M. Kong X. Pei, H. Pang, J. Yang, X. Dong, Y. Wu, and X. Zhou, "A
University (CAU), China, in 2015. He is
lifting wavelet-based protection strategy against DC line faults for
Zhangbei HVDC grid in China," in 2017 19th European Conference on currently pursuing his PhD degree at Institute
Power Electronics and Applications(European Conference on Power of Electrical Engineering of the Chinese
Electronics and Applications, New York: IEEE, 2017. Academy of Sciences (CAS).
[6] D. Tzelepis, A. Dyśko, G. Fusiek, J. Nelson, P. Niewczas, D. Vozikis, P.
His main research interests include fault
Orr, N. Gordon, and CD Booth, "Single-ended differential protection in
MTDC networks using optical sensors," IEEE Transactions on Power protection of DC distribution network and
Delivery, vol. 32, no. 3, pp. 1605-1615, Jun. 2017. MMC-HVDC grids.
[7] M. You, B. H. Zhang, R. F. Cao, and J. D. Xu, "Study of non-unit
transient-based protection for HVDC transmission lines," in Power and
Energy Engineering Conference, 2009. APPEEC 2009. Asia-Pacific,
2009, pp. 1-5. Liye Xiao is currently a Professor with the
[8] F. Kong, Z. Hao, and B. Zhang, "A novel traveling-wave-based main Institute of Electrical Engineering, Chinese
protection scheme for ±800 kV UHVDC bipolar transmission lines," Academy of Sciences, China.
IEEE Transactions on Power Delivery, vol. 31, no. 5, pp. 2159-2168,
His research interests include the
May. 2016.
[9] Y. Zhang, N. Tai, and B. Xu, "Fault analysis and traveling-wave applications of superconductivity, including
protection scheme for bipolar HVDC lines," IEEE Transactions on the fault-current limiters, and HVDC
Power Delivery, vol. 27, no. 3, pp. 1583-1591, Jul. 2012. technology.
[10] J. Sneath and A. D. Rajapakse, "Fault detection and interruption in an
earthed HVDC grid using ROCOV and hybrid DC breakers," IEEE
Transactions on Power Delivery, vol. 31, no. 3, pp. 973-981, Jun. 2016.
[11] W. Leterme, J. Beerten, and D. Van Hertem, "Nonunit protection of
HVDC grids with inductive DC cable termination," IEEE Transactions
on Power Delivery, vol. 31, no. 2, pp. 820-828, Apr. 2016.
[12] R. Li, L. Xu, and L. Yao, "DC fault detection and location in meshed
multi-terminal HVDC systems based on DC reactor voltage change rate,"
IEEE Transactions on Power Delivery, vol. 32, no. 3, pp. 1516-1526, Jun.
2017.
[13] C. Li, A. M. Gole, and C. Zhao, "A fast DC fault detection method using
DC reactor voltages in HVdc grids," IEEE Transactions on Power
Delivery, vol. 33, no. 5, pp. 2254-2264, Apr. 2018.
[14] N. M. Haleem and A. D. Rajapakse, "Application of new directional logic
to improve DC side fault discrimination for high resistance faults in
HVDC grids," Journal of Modern Power Systems and Clean Energy, vol.
5, no. 4, pp. 560-573, Jul. 2017.
[15] B. Li, J. He, Y. Li, and Y. Ou. "Single-ended protection scheme based on
boundary characteristic for the multi-terminal VSC-based DC distribution
system," Proceedings of the CSEE, vol.36, no.21, pp. 5741-5749, Nov.
2016.
[16] A. E. B. Abu-Elanien, A. S. Abdel-Khalik, A. M. Massoud, and S. Ahmed,
"A non communication based protection algorithm for multi-terminal
HVDC grids," Electric Power Systems Research, vol. 144, pp. 41-51, Mar.
2017.
[17] J. Liu, N. Tai, and C. Fan, "Transient-voltage based protection scheme for
DC line faults in multi-terminal VSC-HVDC system," IEEE Transactions
on Power Delivery, vol. 32, no. 3, pp. 1483-1494, Jun. 2017.
[18] N. Tong, X. Lin, Y. Li, Z. Hu, N. Jin F. Wei, and Z. Li, "Local
measurement-based ultra-high-speed main protection for long distance
VSC-MTDC," IEEE Transactions on Power Delivery, vol. 34, no. 1, pp.
353-364, Feb. 2019.
[19] X. Sun, S. Cao, G. Bu, H. Wang, X. Lei, amd B. Lu, "Construction
scheme of overhead line flexible HVDC grid," Power System Technology,
vol.40, no.3, pp. 678-682, Mar. 2016.
[20] N. A. Belda, C. A. Plet and R. P. P. Smeets, "Analysis of Faults in
Multiterminal HVDC Grid for Definition of Test Requirements of HVDC
Circuit Breakers," IEEE Transactions on Power Delivery, vol. 33, no. 1,
pp. 403-411, Feb. 2018.
[21] Q. H. Wu, Z. Lu, and T. Y. Ji, Protective Relaying of Power Systems
Using Mathematical Morphology. 1st, New York: Springer, 2009.
0885-8977 (c) 2019 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: Auckland University of Technology. Downloaded on June 05,2020 at 04:00:04 UTC from IEEE Xplore. Restrictions apply.