Professional Documents
Culture Documents
PST 645ux Transforemer Protection Relay & Control Devices
PST 645ux Transforemer Protection Relay & Control Devices
Technical Manual
V 1.03
The software or hardware described in this document is furnished under a license and may be
used or disclosed only in accordance with the terms of such license.
Trademarks
SAC is a registered trademark of GUODIAN NANJING AUTOMATION CO.,LTD. All other brand
Warranty
Please inquire about the terms of warranty from your nearest SAC representative.
Please inquire about the terms of warranty from your nearest SAC representative.
Nanjing SAC Power Grid Automation Co., Ltd. - Industry and Overseas BD
No. 4528, Kangxin Highway, Kangqiao Town, Pudong New District, Shanghai, P.R. China
201319
Tel: +86 21 6105 6651
Fax: +86 21 6105 6749
This document has been carefully checked by SAC but deviations cannot be completely ruled
out. In case any errors are detected, the reader is kindly requested to notify the manufacturer.
Other than under explicit contractual commitments, in no event shall SAC be responsible or
liable for any loss or damage resulting from the use of this manual or the application of the
equipment.
Conformity
This product complies with the directive of the Council of the European Communities on the
approximation of the laws of the Member States relating to electromagnetic compatibility (EMC
Directive 2014/30/EU) and concerning electrical equipment for use within specified voltage limits
(Low-voltage directive 2014/35/EU). This conformity is the result of tests conducted by SAC in
accordance with the product standards EN60255-26 for the EMC directive, and with the product
standards EN60255-27 for the low voltage directive. The relay is designed in accordance with
the international standards of the IEC 60255 series.
Table of contents
Section 1 Introduction ............................................................................................................................. 1
1.1 Manual introduction....................................................................................................................... 1
1.2 Intended audience ........................................................................................................................ 1
1.3 Document revision history ............................................................................................................ 2
1.4 Related documents ....................................................................................................................... 2
1.5 Symbols and conventions ............................................................................................................. 2
Section 2 Overview of functions and applications ............................................................................... 4
2.1 Main protection functions .............................................................................................................. 4
2.2 Control and monitoring ................................................................................................................. 4
2.3 Communication ............................................................................................................................. 5
2.4 Basic IED functions ....................................................................................................................... 5
Section 3 Analog inputs .......................................................................................................................... 6
3.1 Introduction ................................................................................................................................... 6
3.2 Phase angle reference channel .................................................................................................... 6
3.3 Setting parameters........................................................................................................................ 6
Section 4 Local Human-Machine-Interface LHMI.................................................................................. 7
4.1 LED indicators ............................................................................................................................... 7
4.2 Function keys ................................................................................................................................ 7
4.3 Human-Machine-Interface (HMI) .................................................................................................. 9
Section 5 Protection functions ............................................................................................................. 23
5.1 Three-stage phase overcurrent protection ................................................................................. 23
5.2 HV/LV side three-stage earth fault protection ............................................................................. 30
5.3 Overload protection..................................................................................................................... 37
5.4 Zero sequence overvoltage protection ....................................................................................... 39
5.5 Under-voltage protection............................................................................................................. 41
5.6 SOTF ........................................................................................................................................... 44
5.7 Non-electricity protection ............................................................................................................ 46
Section 6 Secondary system supervision ........................................................................................... 50
6.1 Voltage circuit supervision .......................................................................................................... 50
Section 7 Control and monitoring ........................................................................................................ 52
7.1 Analog sampling for protection ................................................................................................... 52
7.2 Analog sampling for measurement ............................................................................................. 55
7.3 Binary signal sampling ................................................................................................................ 59
7.4 Binary telecontrol output ............................................................................................................. 59
7.5 Signal indications ........................................................................................................................ 60
7.6 Event record ................................................................................................................................ 63
7.7 Fault briefings ............................................................................................................................. 64
7.8 Device recording ......................................................................................................................... 65
7.9 Local resetting ............................................................................................................................. 65
7.10 Remote resetting....................................................................................................................... 65
Section 8 Station communication ........................................................................................................ 67
8.1 IEC 61850-8-1 communication protocol ..................................................................................... 67
8.2 MMS service ............................................................................................................................... 68
Section 9 Functions of the basic IED ................................................................................................... 69
9.1 Anti-shaking and confirmation of binary input ............................................................................. 69
9.2 Self-supervision with internal event list....................................................................................... 69
9.3 Time synchronization .................................................................................................................. 70
9.4 IED device naming (TERMINALNAME) ..................................................................................... 72
9.5 Product version information ........................................................................................................ 72
9.6 Primary system values (PRIMVAL)............................................................................................. 73
9.7 Authority management (ATMNG)................................................................................................ 73
Section 10 IED physical connection .................................................................................................... 75
10.1 Connecting wires ...................................................................................................................... 75
10.2 Input .......................................................................................................................................... 78
10.3 TRIP module output .................................................................................................................. 81
10.4 Time synchronization connection ............................................................................................. 84
10.5 Network connection .................................................................................................................. 85
10.6 Test port .................................................................................................................................... 85
Section 11 Technical data ...................................................................................................................... 86
11.1 Dimensions and weight ............................................................................................................. 86
11.2 Power supply ............................................................................................................................. 86
11.3 Analog inputs ............................................................................................................................. 86
11.4 Binary input ............................................................................................................................... 87
11.5 Output contact ........................................................................................................................... 87
11.6 Connecting communication....................................................................................................... 87
11.7 Packaging level ......................................................................................................................... 88
11.8 Environmental conditions and tests .......................................................................................... 88
Section 12 IED and function test .......................................................................................................... 89
12.1 EMC tests.................................................................................................................................. 89
12.2 Insulation tests .......................................................................................................................... 90
12.3 Mechanical tests ....................................................................................................................... 91
12.4 Product security ........................................................................................................................ 91
12.5 EMC compliance ....................................................................................................................... 91
Section 13 Glossary ............................................................................................................................... 92
Section 1 Introduction
The user manual contains two different manuals: technical manual and engineering manual.
The technical manual lays emphasis on the introduction of technique and application, including the
description of various recording functions and their applications provided by IED. At the same time, the
manual also introduces the principles and application settings of auxiliary functions in the IED, such as
communication, monitoring, measurement, control and other functions. The description of each function
usually consists of function block, principle and logic diagram, input and output, setting parameter,
monitoring parameter, setting guide, technical index and etc. The manual also introduces hardware
structure and connection of IED.
The technical manual works as a technical reference during engineering design, installation,
commissioning phase, and normal operation.
The engineering manual highlights the introduction of operation steps and precautions when the
IED is in use, including installation, commissioning, operation, maintenance and other parts.
The installation section contains instructions on how to install and connect the IED, including
mechanical and electrical installation and inspection.
The commissioning section contains instructions on how to commission the IED during
commissioning phase and periodic tests, which gives an itemized introduction to the commissioning
contents and method of all functions (including auxiliary ones) of the IED. Namely, instructions of
energizing and checking the outer loop, setting and configuration, verifying settings, etc. It may be
technical reference during commissioning phase and regular test.
The operation section contains introduction of operation steps when commissioning the IED,
including operation guidance to monitoring, control and setting as well as methods of viewing
disturbance recording data. It can also be used as a guidance of maintenance operation after the IED is
put in service.
This technical manual addresses the system engineer, installation and commissioning personnel
who may use technical data during engineering design, installation, commissioning phase and normal
operation.
The system engineer must have knowledge of protection system, device and function of
substation and power plant, as well as function logic of configuration. The installation and
commissioning personnel must have basic knowledge of handling electronic equipment.
1
Decommissioning
Commissioning
deinstalling &
Maintenance
Engineering
Planning &
Operation
purchase
Installing
disposal
Product guide
Engineering
manual
Technical
manual
Version number of
Date of revision Product version Revision summary
the manual
2
The electrical warning icon indicates the presence of a hazard which
could result in electrical shock.
The warning icon indicates the presence of a hazard which could result in
personal injury.
The information icon alerts the reader of important facts and conditions.
Although warning hazards are related to personal injury, it is necessary to understand that under
certain operational conditions, operation of damaged equipment may result in degraded process
performance leading to personal injury or death. Therefore, comply fully with all warning and caution
notices.
1.5.2 Document conventions
Conventions used in IED manuals. Some particular conventions may not be used in this manual.
Abbreviations and acronyms in this manual are spelled out in the glossary. The glossary also
contains definitions of important terms.
3
Section 2 Overview of functions and applications
Binary signal
Sample and monitor binary signal
sampling
4
recordings
LOCR
Local resetting Local resetting LOCRES LOCRES
ES
2.3 Communication
standards.)
Product version
Check Product version information PRODVERINF
information
5
Section 3 Analog inputs
3.1 Introduction
The analog input channel has already been configured in IED configuration. But it the IED
still needs to be set with correct secondary parameters (1A or 5A) to get correct input
results and correct operation. Secondary side input values are displayed in analog channel
supervision.
Phase angle displayed in analog channel supervision is the phase difference relative to phase
angle reference channel. Phase angle reference channel takes the channel which collects the first
valid datum as the reference channel, and its phase angle is 0.01°.
Use CT-Secondary-VAL (5A/1A) in control word 1 of protection setting value to switch secondary
CT rated parameters.
6
Section 4 Local Human-Machine-Interface LHMI
Name and function description of LED indicators in EDP03 series LV protection and control
devices are as shown in figure 4-1:
SIG FUNC
Phase overcurrent stage Ⅰ
Phase overcurrent stage Ⅱ
Phase overcurrent stage Ⅲ
Earth fault protection of high voltage side
Earth fault protection of low voltage side
Overload protection
Zero sequence overvoltage protection
Under-voltage protection
Switch-onto-fault protection
Non-electricity protection 1
Non-electricity protection 2
Non-electricity protection 3
Non-electricity protection 4
ALARM
Open Close
7
PST 645UX Transformer Protection and Control Device
SIG FUNC
OC-Ⅰ
OC-Ⅱ
OC-Ⅲ
ROCH
ROCL
OVLD
ALARM
ZOV
UV
SOTF
NON-ELEC1
NON-ELEC2
NON-ELEC3
NON-ELEC4
RESET
OPEN CLOSE
It can be seen from figure 4-2 that the button "Reset" on the device panel is used to manually reset
signal LED state of the device (Triggered), mainly used to reset magnetic-hold signal LED of the device.
Among them, "+" button is used to increase the quantity of numeric quantity, "-" button used to decrease
8
the quantity of numeric quantity, "Q" button used to exit interfaces, “←┘” button used to confirm inputs. In
addition, there are option buttons, such as “∧”, “∨”, “<” or “>”.
Keyboard operation and LCD interfaces of EDP03 LV protection and control platform device adopt
the operation mode of dialog box combined with menu. The LCD screen is bicolor and displays in
192*64 dot matrix graphics. 12*12 raster font is used. Overall structure schematic diagram of the
corresponding display interface is as shown in figure 4-3.
Normal display frame
Main menu
★CommPort 1 ★ProtEvents
★CommPort 2 ★TeleSignal
★SNTPServer ★Warnings
★OtherSetup ★TeleCotrol
★Links
★Other settings ★Telemeter
Figure 4-3 Overall structure schematic diagram of the corresponding display interface
Note: Menu items marked with ★ are responsible for performing specific functions.
9
【Main menu】
RunState Events
Settings RunSetup
FacSetup SysTest
Others
Upon entering the main menu, select menu items with “∧”, “∨”, “<” or “>” keys, enter
previous interface by pressing 【Q】 key. Other menu windows are operated in like manner.
Run state and its submenu interfaces under the main menu interface of EDP03 platform LV
protection and control device are as shown in figure 4-5.
【DIQuantity】 【Measuring】
DI_Function Enable off Measurement Ia 0.001 KA
DI_DIFF protection off Measurement Ib 0.001 KA
DI_Charging protection off Measurement Ic 0.001 KA
DI_1G1 off Measurement Ua 0.001 KV
【kWh】 【Calculation】
01.BOARD 0 01. Ua 0.000V
02.VER-DATE 0
02. Ub 0.000V
03.RESTART 0
04.RUN-S 0 03. Uc 0.000V
04. Ux 0.000V
Upon entering the option window of in-service state menu, select menu items with “∧”, “∨”, “<”
or “>” keys and enter corresponding display window by pressing【←┘】 key. In the display window,
10
use “<” and “>” keys for screen turnover and “∧” and “∨” for row turning. These keys refresh the
Events menu interface under the main menu interface of EDP03 platform LV protection and
control device is as shown in figure 4-6.
【Events】
ProtEvents Warnings
TeleSignal Operation
PrintRecord
1. The “ProtEvents” menu displays protective event information of the latest report number, and
uses “+” and “-” keys to view the last or next report, “∧” and “∨” keys to view the last or next record
uses “+” and “-” keys to view the last or next report, “∧” and “∨” keys to view the last or next record
and uses “+” and “-” keys to view the last or next report, “∧” and “∨” keys to view the last or next
Among three above-mentioned menus, press【←┘】key to print the report currently displayed. If
there exist recordings that correspond to the present report, a dialog box pops up to select the
4. In the “PrintRecord” window, use “+” and “-” keys to select reports that need printing. Press
【←┘】key to enter the “Recording Printing Channel Selection” window, and use “∧” and “∨” keys for
11
row turning to select channels that needs printing, “+” and “-” keys to select whether specific
channels are used for printing. Finally, press【←┘】key to print the selected recording channel.
5. The “Operation” menu displays operation record information of the latest report number, and
uses “+” and “-” keys to view the last or next report, “∧” and “∨” keys to view the last or next record
Settings menu interface under the main menu interface of EDP03 platform LV protection and
control device is as shown in figure 4-7.
【Settings】
DisplaySett ChangeSett
SwitchSett PrintSett
DeleteSett
In the settings menu page, enter the DisplaySett interface to view the interface display as shown
in figure 4-8.
CurrentZone: 00 zone
【DisplaySett】-PUBLIC SET PG
01.kp1 1.000
02.kp2 1.000
03.kp3 1.000
04.kp4 1.000
12
Upon entering the DisplaySett menu, use “+” and “-” keys to select settings of a zone to display,
and press "Confirm" key to view the content of this setting zone. Use ∧” and “∨” keys for row turning,
then press and hold down “>” key to display detailed information of the selected setting item. Press
and hold down “<” key to switch and display the last setting page, and “>” key to switch and display
CurrentZone: 00 zone
【ChangeSett】-PUBLIC SET PG 0
01.kp1 1.000
02.kp2 1.000
03.kp3 1.000
04.kp4 1.000
Functions of ChangeSett menu are generally similar to those of DisplaySett menu. The only
difference is that set value can be modified and solidified. Enter the ChangeSett menu, firstly select
the setting zone that needs modification.
In the ChangeSett interface, press and hold down "∧" and "∨" keys to select DisplaySett page, "
>" key to display detailed information of the selected setting entry. If the selected setting entry belongs
to the type of control word, the value of the selected setting can be modified by operation in the
detailed window. Click the four arrow keys "<", ">", "∧" and "∨"to select the setting position which
needs modification, and use "+" and "-" keys to modify set value.
In the ChangeSett window, press "Confirm" key and pop up the "Solidified Setting Zone Selection"
window to select solidified setting zone. Then pop up the password window, set value will be
successfully solidified after verification.
In the settings menu page, enter the SwitchSett interface to view the interface display as shown in
13
figure 4-10.
【SwitchSett】
Select zone 01
CurrentZone: 00 zone
【PrintSett】
Select zone: 01
CurrentZone: 00 zone
Please select print page
all pages
Upon entering PrintSett window, select the setting zone and setting pages that need printing, and
then press "Confirm" key to finish printing.
In the settings menu page, enter the DeleteSett interface to view the interface display as shown in
figure 4-12.
【DeleteSett】
Selectzone: 01
CurrentZone: 00 zone
14
【RunSetup】
LinksSetup TimeAdjust
DeviceID RunParam
ResetKMH HMISetup
In the RunSetup menu page, enter the linking piece setting interface to view the interface display
as shown in figure 4-14.
【LinksSetup】
Differential protection On+ ↑
Complex power Stage I on HV side Off+
Complex power Stage II on HV side Off+
Limit-time instantaneous off on LV side On+ ↓
Use “∧” and “∨” keys to select different linking pieces, “+” or “-” key to switch on or switch off If
it is required to give up settings, press “Q” key to exit. Press【←┘】key to start LinksSetup, then the
system prompts to enter password, and finally confirm the inputs. Only when the protection function of
linking pieces is in service, linking pieces will be displayed in the linking piece setting window.
In the RunSetup menu page, enter the TimeAdjust interface to view the interface display as
shown in figure 4-15.
【TimeAdjust】
2006-10-18 14:10:482
Sys.clk: 2006-10-18 14:10:48
Use “<” and “>” keys to select the time position that needs modification, “+” or “-” keys to
modify the value of time. If it is required to give up settings, press “Q” key to exit. Press【←┘】key to
start TimeAdjust. The system clock is the clock of real-time clock chip in the IED.
In the RunSetup menu page, enter the DeviceID interface to view the interface display as shown
in figure 4-16.
15
【DeviceID】
Input name:
Low-voltage protection device
【Code】B5
Use “<” and “>” keys to select the name position that needs modification, “+” or “-” keys to
modify the value of names. If it is required to give up settings, press “Q” key to exit. Press【←┘】key to
start IED name setting. IED name is used as the unique identification of each IED. DeviceID can also
In the RunSetup menu page, enter the interfaces of RunParam and active energy value reset to
view the interface display as shown in figure 4-17.
【RunParam】 【ResetKWH】
01.CTRL-WD1 0000 Password: 00
02.**** 0
03.**** 0 Going to reset KWH,be careful
Operation in the RunParam window is similar to that of set value, please refer to the Section
"Operation of Set Value". Upon entering Reset Active Value window, enter the correct password to
clear active energy value.
In the RunParam menu page, enter the HMISetup interface to view the interface display as shown
in figure 4-18.
【HMISetup】
CommPort1 CommPort2
SNTPServer OtherSetup
Go into HMISetup, and CommPort1 and 2 are shown for information setting. Whether CommPort1
and 2 are serial ports or Ethernet is determined by the type of communication platelet on the hardware
16
and is adaptive in the software. Go into the serial port settings, and display the setting items related to
serial ports; go into the Ethernet settings, and display the setting items related to Ethernet.
Upon entering a specific communication port setting window, use “∧” or “∨” keys to select
different setting entries, and “+” or “-” keys to select the value of different entries. If it is required to
give up settings, press “Q” key to exit. Press【←┘】key to start setting, then the system prompts to
enter password, and finally select and set the targeted communication ports. After successful setting,
the IED will be automatically rebooted.
4.3.6 FacSetup
FacSetup menu interface under the main menu interface of EDP03 platform LV protection and
control device is as shown in figure 4-19.
【FacSetup】
DIForce InnerSett
MeasCalib Protalib
【DI force】
DI_Differential protection enable off+
DI_Charging protection enable cancel force+
DI_1G1 force on+
DI_TSFS forced off+
“+” or “-” keys for options of force on, force off or cancel force. Select one certain digital input signal,
and press【←┘】key to set the status of this digital input signal. Press “Q” key to exit.
In the FacSetup menu page, enter the InnerSett value interface to view the interface display as
shown in figure 4-21.
【InnerSett】
01. V/F protection on/off On
02. Low excitation protection on/off Off
03. Over excitation protection on/off On
17
Enter the InnerSett value window; operation of InnerSett value is similar to that of set value. But
there is no concept displayed by pages, please refer to the description of set value menu.
In the FacSetup menu page, enter the MeasCalib and ProtCalib interfaces to view the interface
display as shown in figure 4-22.
【MeasCalib】 【ProtCalib】
Oprt: GainCalib Oprt: OffsetCalib
Enter the window of measurement and control set value; operation of measurement and control
set value is similar to that of set value. But there is no concept displayed by pages, please refer to the
description of set value menu.
4.3.7 SysTest
SysTest menu interface under the main menu interface of EDP03 platform LV protection and
control device is as shown in figure 4-23.
【System test】
DOTest DITest
ACTest LEDTest
MsgTest Sample
In the SysTest page, select the "DOTest" submenu under the "SysTest" menu, and the system
prompts to enter password, as shown in figure 4-24:
【DOTest】
Password: 00
After correct password input, the system goes into the hardware test mode, stops logic diagram
scanning function and reports alarming events. After exiting the alarming event window, the system
enters the DOTest operation menu, as shown in figure 4-25:
18
【DOTest】
Name: Start ±
Oprt: act±
CrtStatus: rtn
Use "∧" and "∨" keys to select different input items, "+" and "-" keys to select name and
If exit or automatically exit the window due to the keyboard unused delay for over 10 minutes, the
system automatically resumes all contacts, exits the hardware test mode, and continues logic diagram
scanning function.
In system test page, select the "DITest" submenu, and the system will prompt to enter
password. After correctly inputting password, the system will enter hardware test mode, stop logic
diagram scanning function and report alarming events. Exit the alarming event window, and the
system will enter digital input check view menu, as shown in figure 4-26.
【DITest】
Block reclosing Off
Spring uncharged alarm Off
Remote reset Off
When in this state, MMI periodically refreshes the DI state every 2 seconds. Use "∧" and "∨" keys
to select different view items.
If exit or automatically exit the window due to the keyboard unused delay for over 10 minutes, the
system automatically resumes all contacts, exits the hardware test mode, and continues logic diagram
scanning function.
In the system test page, select the "ACTest" submenu, and the system prompts to enter password.
After correct password input, the system goes into the hardware test mode, stops logic diagram
scanning function and reports alarming events. Exit the alarming event window, and the system enters
the AC test view menu, as shown in figure 4-27.
【ACTest】
Ia_1 0.013A -150.6°
Ib_1 0.013A -150.6°
Ic_1 0.013A -150.6°
Ia_2 0.013A -150.6°
19
When in this state, MMI periodically refreshes the AC quantity every 2 seconds. Use "∧" and "∨"
keys to select different view items.
If exit or automatically exit the window due to the keyboard unused delay for over 10 minutes, the
system automatically resumes all contacts, exits the hardware test mode, and continues logic diagram
scanning function.
In the system test page, select the "LEDTest" submenu and have a test of 26 indicators on the IED
panel by the signal LEDTest menu, as shown in figure 4-28.
【LEDTest】
Light (unhold) Turnoff
Light (hold) Turnoff & reset
Among these, open position, closed position and alarming LEDs are out of control. Steady light
(unhold) corresponds to extinguishing, and steady light (hold) corresponds to extinguishing and
resetting. The test process is as follows:
1. Click the "light (unhold)" menu, and all indicators are on. Then click the "Extinguished" menu, and all
indicators are off.
2. Click the "light (hold)" menu, and all indicators are on. Click the "Extinguished" menu, and all
indicators are not off. Only when clicking the "Extinguished and reset" menu, all indicators are off.
When exiting the light test window, LED state restoration is determined by IED system and
protection.
In the SysTest page, select the "MsgTest" submenu, as shown in figure 4-19.
【MsgTest】
Protevents TeleSignal
Warnings TeleCotrol
Links TeleMeter
【ProtEvents】 【Warnings】
Protection startup± IED abnormality±
Act send± Act send±
Use "+" or "-" keys to switch to different entries and press the "ENTER" key to send the
20
corresponding entry information. Press【←┘】key to send primary information to monitoring and
telecontrol backgrounds.
In the SysTest page, select the "Sample" menu, as shown in figure 4-31.
【Sample】
01. -5 -1.40 5 12
02. 6 2.45 5 7
03. 8 7.75 7 11
04. 8 5.5 7 7
After entering the selection window of channel sampling menu, use “<” and “>” keys for screen
turnover, “∧” and “∨” for row turning in the display window. These keys refresh the display quantity
every 2 seconds. Each line, in turn, displays as follows: channel sequence number, minimum value,
average value, maximum value and fluctuation range of channel sampling.
4.3.8 Others
Others menu interface under the main menu interface of EDP03 platform LV protection and
control device is as shown in figure 4-32.
【Others】
Version Environment
Filestrans CodelistPrint
Enter the “Others” window, and select the corresponding menu items with “∧”, “∨”, “<” or “>”
and return to the previous interface by pressing 【Q】 key. Operation of other menu windows is similar
to it.
In the “Others” menu page, select and enter the “Version” submenu as shown in figure 4-33.
【Version】
PST 645UX
System CRC : D6D5
System Version : 1.03
21
software. The third line displays the system released check code, and the fourth line displays the
system released version number.
In the "Others" menu page, select and enter the "Environment" submenu, as shown in figure 4-34.
【Environment】
01. Ambient temperature: 38℃
02. +24V : 23.910V
03. +10V : 9.864V
04. -10V : -9.972V
The IED working condition window displays the environment temperature inside the IED and
actual voltage value of each reference voltage. Use “∧”, “∨”, “<” or “>” keys to select corresponding
menu items. In the display window, use “<” and “>” keys for screen turnover, “∧” and “∨” for row
【FileTrans】
Source address: /data/rec/edp21ae.frw
2007/5/8 01:01:11 (6458268B)
Destination address: /U/
2007/4/8 01:11:43 (2files)
Click the "FileTrans" menu and enter the "File transfer enter password" window. Use “<” and “>”
keys to select input position, “+” and “-” keys to input password. After correct password input, enter
the "File transfer" main window. Use “∧” and “∨” keys to select to appoint source/destination address.
Use "<" and ">" keys to select the parent directories of source/destination address, "+" and "-"
keys to select the files or folders in the same level directories of source/destination address. Press
【←┘】key to enter the password window of appointed file transfer. After correct password input,
execute the operation of file transfer. If the appointed source address is the directory, transfer all files
of the whole source address directory to the destination address. But the files of subdirectory in the
source address directory are not transferred.
22
Section 5 Protection functions
Abstract: This section mainly introduces protection functions and applications of the IED. The
description of each function includes as follows: function block, principle and logic diagram, input and
output, monitored data, setting parameter, setting guide, technical data and etc.
5.1.1 Identification
IEC61850 IEC60617 ANSI/IEEE C37.2
Description
identification identifier device number
Three-stage
composite voltage
PHPTOC 3I> 50/51P
blocking phase
overcurrent protection
Operation=ON/OFF
23
5.1.3.2.1 Phase overcurrent protection
The sampled analogue phase currents from any channel are pre-processed in a discrete Fourier
filter (DFT) block. The RMS value of each phase current is derived from the fundamental frequency
components, as well as sampled values of each phase current. These phase currents are fed to the
phase overcurrent starting function block. In a comparator the RMS values are compared to the set
operation current value of the function. If a phase current is larger than the set overcurrent value, a
signal from the comparator for this phase will, without blocking conditions, trip by time delay.
i ℱ I>Settings
& T TRIP
Operation=ON
Block = OFF
Ua Uab>Settings
&
Ub ℱ Ubc>Settings
Y &
Uc
Uca>Settings Y BLOCK
Operation=ON
24
Figure 5-2 Logic diagram for undervoltage blocking
Operation principle of overcurrent protection:
Ua
Ub ℱ U2<Settings
Uc &
BLOCK
Y
Operation=ON
25
characteristic, that is, standard inverse time limit, very inverse time limit and extreme inverse time limit.
The IDMT characteristic is set by the "EXP-INV" in the setting value, and formulas of each inverse time
limit characteristic are as below:
i. Standard inverse
0.14tp
t
I 0.02
( ) 1
Ip
ii. Very inverse
13.5tp
t
I
( ) 1
Ip
iii. Extreme inverse
80tp
t
I 2
( ) 1
Ip
Where: tp is time factor, whose scope is (0.05~1). Ip is current reference value. I is fault current.
And t is tripping time.
Some of the inverse time limit time among the setting values are the numerator multiplication in the
above expression, whose unit is second, and setting scope is (0.005~127).
The long-term inverse time limit can achieve the same as well. The expression for long-term inverse
time limit is as below:
120tp
t
I
( ) 1
Ip
The phase overcurrent protection of the device can be realized via setting the relevant bit of the
control word to select definite time limit or inverse time limit mode. When selecting the inverse time limit
mode, definite time limit III stage overcurrent protection automatically is switched off, while the function
enable of the phase overcurrent III stage will change into phase overcurrent inverse time limit function
on/off.
5.1.4 Input and output
26
Output Tripping BOOLEAN Trip
All the trip logics of this IED adopt setting fixing, and all protection components, after operation,
set output section through tripping matrix. The tripping matrix is a 16-bit binary code with the setting
range of 0000~FFFFH. When protection components operating, if one bit of the tripping matrix is set
to1, the relevant output trip; while it is set to 0, the relevant output doesn't trip.
1 X3:5-6 0 9 X6:7-8 0
2 X3:5-7 0 10 X6:9-10,X6:11-12 0
3 X3:8-9 0 11 X6:13-14,X6:15-16 0
4 X3:11-12 0 12 Standby 0
5 Standby 0 13 Standby 0
6 X6:1-2 0 14 Standby 0
7 X6:3-4 0 15 Standby 0
Phase A to phase B
Uab REAL V
voltage
Phase B to phase C
Ubc REAL V
voltage
Phase C to phase A
Uca REAL V
voltage
27
5.1.6 Settings
5.1.6.1 Value settings of phase overcurrent
Values Default
Name Unit Step Description
(range) value
phase-to-phase voltage
Negative-sequence voltage
NV-OC 1.0~120.0 V 0.001 7
setting for blocking overcurrent
overcurrent
28
Tripping matrix setting for the
time mode
2.very:1
3.extreme:2
0=OFF
OC-Ⅰ 1 0 Soft switch of the first stage overcurrent
1=ON
0=OFF
OC-Ⅱ 1 0 Soft switch of the second stage overcurrent
1=ON
29
0=OFF
OC-Ⅲ 1 0 Soft switch of the third stage overcurrent
1=ON
5.2.1 Identification
IEC61850 IEC60617 ANSI/IEEE C37.2
Description
identification identifier device number
I0 TRIP
Operation=ON/OFF
30
5.2.3.2 Operational principle
Three-stage earth fault protection function is divided into 3 different sub functions, which is the
same with each stage. Among these, x is respectively the first, second and third stage, and its
operation mode is set as off/on.
Three parts of the protection:
High voltage side three-stage earth fault protection function
Low voltage side three-stage earth fault protection function
Time mode selection
5.2.3.2.1 HV side earth fault protection
The sampled values from three-phase current channel and external zero-sequence current
channel are pre-processed in a discrete Fourier filter (DFT) block. The RMS value of self-produced
zero-sequence current and external zero-sequence current is derived from the fundamental frequency
components, as well as sampled values. Select the used zero-sequence currents by self-produced
control words of zero-sequence currents and these currents are fed to the zero-sequence overcurrent
starting function block. In a comparator the RMS values are compared to the set operation current
value of the function. If the zero-sequence current is larger than the set zero-sequence overcurrent
value, a signal from the comparator for this phase will trip by time delay, among which the high voltage
side earth fault protection stage Ⅲ can be used to trip or alarm by control word KG1.7.
ia
ib
ℱ I0>Settings
ic & T TRIP/ALARM
i0 Operation=ON
31
T--------- Earth fault protection time delay
5.2.3.2.2 LV side earth fault protection
The sampled analogue phase currents from any channel are pre-processed in a discrete Fourier
filter (DFT) block. The RMS value of each phase current is derived from the fundamental frequency
components, as well as sampled values of each phase current. These phase currents are fed to the
phase overcurrent starting function block. In a comparator the RMS values are compared to the set
operation current value of the function. If a phase current is larger than the set overcurrent value, a
signal from the comparator for this phase will, without blocking conditions, trip by time delay.
i0
ℱ I0>Settings
& T TRIP
Operation=ON
0.14tp
t
I 0.02
( ) 1
Ip
32
13.5tp
t
I
( ) 1
Ip
80tp
t
I 2
( ) 1
Ip
Where: tp is time factor, whose scope is (0.05~1). Ip is current reference value. I is fault current.
And t is tripping time.
Some of the inverse time limit time among the setting values are the numerator multiplication in the
above expression, whose unit is second, and setting scope is (0.005~127).
The long-term inverse time limit can achieve the same as well. The expression for long-term inverse
time limit is as below:
120tp
t
I
( ) 1
Ip
The low voltage side Ⅲ stage earth fault protection of the device can be realized via setting the
relevant bit of the control word to select definite time limit or inverse time limit mode. When low voltage
side Ⅲ stage earth fault protection selects the inverse time limit mode, definite time limit III stage earth
fault protection automatically is switched off, while the function enable of the low side earth fault
protection stage III will change into low side earth fault protection inverse time limit function on/off.
5.2.4 Input and output
Input and output Name Type Description
current
current
33
5.2.5 Monitored data
Name Type Unit Description
5.2.6 Settings
5.2.6.1 Value settings of earth fault protection
Values Default
Name Unit Step Description
(range) value
t-ROCH-Ⅰ 0.0~100.0 S 0.001 100 the first stage earth fault protection
34
Operating time-delay setting for
t-ROCL-Ⅰ 0.0~100.0 S 0.001 100 the first stage earth fault protection
35
stage earth fault protection in the
time mode
2.very:1
3.extreme:2
36
voltage side
5.3.1 Identification
IEC61850 IEC60617 ANSI/IEEE C37.2
Description
identification identifier device number
I
U TRIP
ALARM
Operation=ON/OFF
37
Ifh is the thermal overload current setting value. Thermal overload alarm and tripping are
determined by the control word KG2.13.
Max[Ip ]>I-OVLD
Trip time
Overload protection
OVLD enable
& & Trip
linking piece
5.3.6 Settings
5.3.6.1 Value settings of overload
Values Default
Name Unit Step Description
(range) value
38
Bit When set to 0 When set to 1 Description
0=OFF
OVVLD 1 0 Soft switch of overload
1=ON
5.4.1 Identification
IEC61850 IEC60617 ANSI/IEEE C37.2
Description
identification identifier device number
Zero sequence
EFPTOV U0> 59N
overvoltage protection
U TRIP
ALARM
Operation=ON/OFF
39
U0 >V-ZOV
5.4.6 Settings
5.4.6.1 Value settings of zero sequence overvoltage
Values Default
Name Unit Step Description
(range) value
40
Bit When set to 0 When set to 1 Description
0:Issue alarm signal
10 ZOV alarm ZOV trip 1:Issue trip command
for zero sequence overvoltage
15 CT-Secondary-VAL 5A CT-Secondary-VAL 1A Secondary value of CT is 5A/1A
5.5.1 Identification
IEC61850 IEC60617 ANSI/IEEE C37.2
Description
identification identifier device number
Under-voltage
PTUV 3U< 27
protection
U TRIP
Operation=ON/OFF
41
5.5.3 Operational principle
When system voltage is lower than the setting voltage, discriminate whether to clear overload.
The criteria of undervoltage components are:
1) All the three phase voltage are lower than undervoltage setting value;
2) All the three phase current are lower than one setting value.
3) CB is at closed position;
4) Delay time is up.
MAX[Vpp]<Vpp-UV
CB is at closed position
UV enable
42
5.5.6 Settings
5.5.6.1 Value settings of under-voltage
Values Default
Name Unit Step Description
(range) value
Operating voltage setting for
Vpp-UV 30~120.0 V 0.001 70 undervoltage,set according to
phase-to-phase voltage
Operating time-delay setting for
t-UV 0.1~100.0 S 0.001 100
undervoltage
Current setting for blocking
I-UV-BLK 0.04In~20In A 0.001 100
undervoltage
Tripping matrix setting for
TRPMTX-UV 0000~FFFF None 1 001
undervoltage
0=OFF
UV 1 0 Soft switch of under-voltage protection
1=ON
43
5.6 SOTF
5.6.1 Identification
IEC61850 IEC60617 ANSI/IEEE C37.2
Description
identification identifier device number
Switch-onto-fault
PTSOTF SOTF SOTF
protection
I
U TRIP
TWJ
HWJ Operation=ON/OFF
i ℱ I>Settings
44
components
Settings---The corresponding operation overcurrent set value of the channel
T---------overcurrent time delay, which is definite time
Operation conditions—operation permission condition, which is switch-onto-fault
protection.
5.6.3.2 SOTF conditions
This IED can provide switch-onto-fault protection through operation on/off. The conditions of start
are as follows:
1)The circuit breaker stays at the opening position for more than 30s;
2)The circuit breaker changes from open to closing, and allowable time is switched on for 3s.
The protection is set with independent current setting value for current operation stage and
specific time setting value.
5.6.4 Input and output
Input and output Name Type Description
5.6.6 Settings
5.6.6.1 Value settings of SOTF
Default
Name Values (range) Unit Step Description
value
45
switch-onto-fault
switch-onto-fault
switch-onto-fault
5.7.1 Identification
IEC61850 IEC60617 ANSI/IEEE C37.2
Description
identification identifier device number
Non-electricity
PTNE NE NE
protection
46
5.7.2 Function module
Alarm
BI
Operation=ON/OFF
TRIP
Non-electricity
Alarm time
& protection
SLP of NON-ELEC
alarms
47
Non-electricity DI 2 BOOLEAN Non-electricity DI 2
5.7.6 Settings
5.7.6.1 Value settings of non-electricity protection
Default
Name Values (range) Unit Step Description
value
48
5.7.8 Technical data
Function name Operating value accuracy
49
Section 6 Secondary system supervision
6.1.1 Identification
IEC61850 IEC60617 ANSI/IEEE C37.2
Description
identification identifier device number
Voltage circuit
TVTR VTS VTS
supervision
U Alarm
50
Input Ub REAL Phase B voltage
51
Section 7 Control and monitoring
7.1.1 Function
Analog sampling for protection collects current and voltage of power system, and indicates their
amplitude and phase angle on HMI. It can be used during testing and commissioning of protection and
control IEDs in order to verify proper operation and connection of instrument transformers (CT and
VT).
7.1.2 Operational principle
IED acquires data from current and voltage variables with sampling frequency of 1200 points per
second. The first phase channel acquired with valid data is taken as reference channel, whose phase
angle is 0.01°.
Sampling information can be checked on HMI.
7.1.3 Current sampling
7.1.3.1 Identification
IEC61850 IEC60617 ANSI/IEEE C37.2
Description
identification identifier device number
Zero-sequence
Input I0H REAL
current
Zero-sequence
Input I0L REAL
current
Amplitude of phase A
Output Phase A current REAL
current
52
current
Amplitude of phase C
Output Phase C current REAL
current
Amplitude of
Zero-sequence
zero-sequence
Output current of high voltage REAL
current of high voltage
side
side
Angle of
Angle of
zero-sequence
Output zero-sequence current REAL
current of high voltage
of high voltage side
side
Amplitude of
Zero-sequence
zero-sequence
Output current of low voltage REAL
current of high voltage
side
side
Angle of
Angle of
zero-sequence
Output zero-sequence current REAL
current of low voltage
of low voltage side
side
Amplitude of phase A
Ia REAL A
current
Amplitude of phase B
Ib REAL A
current
Amplitude of phase C
Ic REAL A
current
Amplitude of
53
Amplitude of
Zero sequence
Input U0 REAL
voltage
Amplitude of phase A
Output Phase A voltage REAL
voltage
Amplitude of phase B
Output Phase B voltage REAL
voltage
Amplitude of phase C
Output Phase C voltage REAL
voltage
54
Amplitude of voltage,
Ua REAL V
phase A
Amplitude of voltage,
Ub REAL V
phase B
Amplitude of voltage,
Uc REAL V
phase C
Amplitude of zero
U0 REAL V
sequence current
Amplitude of negative
U2 REAL V
sequence voltage
Name Accuracy
Frequency ≤ 0.01Hz
7.2.1 Function
Analog sampling for measurement collects current and voltage of power system, and indicates
their amplitude and phase angle on local HMI. It can be used during testing and commissioning of
protection and control IEDs in order to verify proper operation and connection of instrument
transformers (CT and VT).
7.2.2 Operational principle
IED acquires data from current and voltage variables with sampling frequency of 1200 points per
second. The first phase channel acquired with valid data is taken as reference channel, whose phase
angle is 0.01°.
Sampling information can be checked on HMI.
55
7.2.3 Current sampling
7.2.3.1 Identification
IEC61850 IEC60617 ANSI/IEEE C37.2
Description
identification identifier device number
Measured phase A
Input CIa REAL
current
Measured phase B
Input CIb REAL
current
Measured phase C
Input CIc REAL
current
Amplitude of
current
Amplitude of
current
Amplitude of
current
Amplitude of phase A
Phase A voltage REAL A
current
Amplitude of phase B
Phase B voltage REAL A
current
56
Amplitude of phase C
Phase C voltage REAL A
current
Amplitude of phase B
protection)
Phase of phase B
Angle of voltage,
Output REAL voltage(shared with
phase B
protection)
57
phase C voltage(shared with
protection)
Amplitude of phase A
Phase A voltage REAL V
voltage
Amplitude of phase B
Phase B voltage REAL V
voltage
Amplitude of phase C
Phase C voltage REAL V
voltage
Amplitude of phase A to
Phase AB line voltage REAL V
phase B voltage
Amplitude of phase B to
Phase BC line voltage REAL V
phase C voltage
Amplitude of phase C to
Phase CA line voltage REAL V
phase A voltage
58
7.3 Binary signal sampling
7.3.1 Identification
IEC61850 IEC60617 ANSI/IEEE C37.2
Description
identification identifier device number
Resolution ≤2 ms
7.4.1 Identification
IEC61850 IEC60617 ANSI/IEEE C37.2
Description
identification identifier device number
59
Binary telecontrol
output
7.5.1 Function
Indications reflect fast, condensed and reliable information of importance in the primary and in the
secondary system. It can be shown via LED indicators on the IED in a straightforward way.
7.5.2 LED indicators
There are 29 LED indicators on the device panel, showing following information respectively.
60
Linking piece of Switch of the first Light: enable the first stage overcurrent
Green
OC-Ⅰ stage overcurrent Dark: disable the first stage overcurrent
Linking piece of Switch of the third Light: enable the third stage overcurrent
Green
OC-Ⅲ stage overcurrent Dark: disable the third stage overcurrent
61
side has no operation
Switch of
Linking piece of Light: enable under-voltage protection
Green under-voltage
UV Dark: disable under-voltage protection
protection
switch-onto-fault
has no operation
Switch of
Linking piece of Light: enable non-electricity protection 1
Green non-electricity
NON-ELEC1 Dark: disable non-electricity protection 1
protection 1
62
NON-ELEC2 non-electricity Dark: disable non-electricity protection 2
protection 2
Switch of
Linking piece of Light: enable non-electricity protection 3
Green non-electricity
NON-ELEC3 Dark: disable non-electricity protection 3
protection 3
Switch of
Linking piece of Light: enable non-electricity protection 4
Green non-electricity
NON-ELEC4 Dark: disable non-electricity protection 4
protection 4
7.6.1 Function
Quick, complete and reliable information about faults in the primary and/or in the secondary system
63
is vital, for example, time-tagged events logged during faults. This information is used for different
purposes in the short perspective (e.g. corrective actions) and in the long perspective (e.g. functional
analysis). When any new recording is triggered, event recording logs the starting cause, starting name
and starting time-tag, which can be stored in CPU.
Each recording can contain more than 1000 latest events.
The fault recording information can be read via HIM.
Recording Event
7.7.1 Function
When tripping binary signal channel triggers fault recorder fault locating gives results, fault
briefings are automatically formed and stored in CPU.
When recording ends, fault briefings will be displayed automatically, or can be checked manually
as well.
The fault briefing logs the starting time of recording protection, protection operation types, fault
phases, tripping phases and RMS values of fault currents (or voltages).
Each briefing can contain up to 1000 latest events.
The fault briefing information can be read on HMI.
Trip Signal
Input FaultRepor
t
Locating
64
7.8 Device recording
7.8.1 Function
When the protection starts up or is tripped, the recording is automatically made. When recording
ends, recording files are saved automatically in CPU for check and analysis.
The protective recording logs the data preceding the recording triggering instant for 100s and after
recording triggering for 200ms.
7.9.1 Function
When fault is cleared, recording LED indicator and recording DO relay on the resetting panel are
available.
Local resetting operation can be processed via both HMI and Resetting button on IED front
panel.
RESET
RESET
OPERATION
Resetting
Input - Local resetting operation
operation
7.10.1 Function
When recording ends, it is available for users to reset recording indicating lamps and DO relays
on the remote resetting panel.
Remote resetting can be performed in the monitoring and control system or at the remote master
station.
65
RESET
RESET
OPERATION
Resetting
Input - Remote resetting operation
operation
66
Section 8 Station communication
8.1.1 Identification
IEC61850 IEC60617 ANSI/IEEE C37.2
Description
identification identifier device number
IEC 61850-8-1
IEC61850-8-1 - -
communication protocol
8.1.2 Function
The protection device supports IEC 61850-8-1 communication protocol, in which MMS can be
used for network communication between station control level and bay layer.
The IED is equipped with 3 Ethernet ports on HMI for MMS service. It meets the configuration
requirement to connect to multi-independent networks, for example, it is enable to connect to
monitoring system, information subsystem and dispatching system simultaneously.
The device also supports SNTP and IRIG-B time synchronization, both provide an accuracy of +/-
1ms.
Based on Ethernet: SNTP time synchronization
With time synchronized cording: IRIG-B time synchronization
Not supporting PRP protocol
Optional communication interface and protocol
MMS ●
● = support
8.1.3 Settings
Values
Name Unit Step Default Description
(range)
67
8.2 MMS service
8.2.1 Identification
IEC61850 IEC60617 ANSI/IEEE C37.2
Description
identification identifier device number
8.2.2 Function
MMS service supports uploading disturbance files that is applicable for any Ethernet in the standard
COMTRADE format. The service can be interoperated with IED, tools and systems that fulfilled
IEC61850 standards.
Up to 16 clients can be connected to protection device simultaneously. Reports form device can be
sent to multi-clients via IEC61850 station bus. And the configuration can be done in the model. The
criteria for interruption is 20s.
Two independent Ethernet ports are used for MMS service. They have uniform functions and can be
configured to different substation networks.
68
Section 9 Functions of the basic IED
By periodically scanning the front and rear points of displacement, the equipment confirms
primary binary displacement to decrease the jitter and short duration disturbances of binary input.
When binary value changes from 0 to 1 or from 1 to 0, the IED scans binary position every
0.467ms. When the new status continuously meets the time requirement of "CF of analog IPT", the
new binary status will be recorded.
If input voltage of binary signal is larger than 70% of rated voltage, effective action of binary signal
is set as 1; if input voltage is less than 55 percent, binary signal returns to 0.
9.2.1 Function
Self-supervision function with internal event list can response to different internal self-supervision
modules. The internal events are saved in an internal event list.
9.2.2 Operational principle
Self-supervision function operates continuously and includes:
• checking digital measurement signal;
• other alarms, such as hardware and time synchronization
Self-supervision event lists SELFSUPEVLST can be monitored by HMI.
EEPROM error
RAM error
Binary input
board error Alarming
OR signal
Binary output contact
board error
Binary input
and output
board error
69
Table 9-1 the relationship between self-supervision and hardware modules
Name Fault module Description
supply
device
DI/DO board error DI/DO board module
2 Storage unit error 02H Exit from protection and notify the manufacturer
3 Invalid sector 03H Exit from protection and notify the manufacturer
4 Setting check error 04H Exit from protection and notify the manufacturer
5 Digital DI/DO error 05H Exit from protection and notify the manufacturer
6 Sampling unit error 06H Exit from protection and notify the manufacturer
7 Software check error 07H Exit from protection and notify the manufacturer
8 Monitoring CPU alarm 08H Exit from protection and notify the manufacturer
70
LV protection and measurement and
control device
Operating setting 00 zone
Local
GPS time synchronization failure
2015/09/05 09:09:30
【Other settings】
01. Mode of synchronization: PPS +
02. Language: Simplified Chinese+
03. Communication with
background: Yes +
04. Uploading event parameters:
Yes+
After entering other settings window, use “∧” key and “∨” key to select different settable items,
and use “+” key or “-” key to choose values of respective items. If it is required to cancel the setting,
press "Q" to exit. Press【←┘】key to start setting. Enter and confirm the password when the system
prompts. Select respective communication interface to set. After setting is successful, automatic
restart will take place. Under the mode of synchronization, GPS adaption, GPS time synchronization
per second, GPS time synchronization per minute, time synchronization via IRIG-B and via SNTP are
available.
71
9.3.2.2 Time synchronization via IRIG-B
Time synchronization via IRIG-B is used for present field devices. The frame is transmitted every
second, with a large amount of information. Through encoding, pulse signals with 1, 10 and 100pps
and time and control function information of BCD encoding can be acquired. The resolution is high, in
which DC code is 10ms and AC code is 1ms.
The IRIG-B is a type of encoding time synchronization modes. Select RunSetup/HMISetup/
OtherSetup/Check time and set.
9.3.2.3 GPS time synchronization
GPS time synchronization include GPS adaption, PPM and PPS. PPM is to clear second, and
PPS is to clear millisecond. In theory, the precision of PPM is higher than PPS. Pulsed time
synchronization per minute is a general mode for microcomputer protection.
GPS time synchronization is a hard mode. Select RunSetup/HMISetup/ OtherSetup/Check time
and set.
9.3.3 Time zone from UTC
The IED supports time zone selection from UTC (Coordinated Universal Time), mainly in full time
zone. The selective range of time zone covers zero zone, UTC+1~UTC+12, and UTC-1~UTC-12. The
default selection is UTC+8. After a specific time zone is selected, it will add or minus time from base
time. Time offset of zero zone is 0. UTC+1~UTC+12 offset from base time by +1~+12, whereas,
UTC-1~UTC-12 offset from base time by -1~-12.
9.4.1 Identification
IEC61850 IEC60617 ANSI/IEEE C37.2
Description
identification identifier device number
9.4.2 Function
The naming function of the IED makes users able to identify every IED unity in the systems, which is
possible in both the substations and the whole districts or countries. Modify device name in factory
module tools.
9.5.1 Identification
IEC61850 IEC60617 ANSI/IEEE C37.2
Description
identification identifier device number
72
information
9.5.2 Function
Check the product version information in HMI, including protection software version, check code, etc.
They are very useful in case of support process (such as repair or maintenance).
9.6.1 Identification
IEC61850 IEC60617 ANSI/IEEE C37.2
Description
identification identifier device number
9.6.2 Function
Voltage and current transformation ratios (220000V/100V or 600A/5A) of analog input channels are
available in HMI.
After a successful setting, the device shows primary values of current and voltage.
Display the primary value when ordering, if required.
System frequency is usually stated when ordering and it is not necessary to set after delivery.
【Other settings】
01. Mode of synchronization: PPS +
02. Language: Simplified Chinese+
03. Communication with
background: Yes +
04. Uploading event parameters:
Yes+
73
9.7.3 Password management
The password contains general password and super password, in which initial general password
is 99, and initial super one is 66. Enter general password to implement general setting and viewing.
Enter super password to implement detailed version information, shown in figure 9-4. Select
“Other”/“Program version” and set.
【Detailed version】
BOOTROM CRC : None+
BSP CRC : None
Plateform SW : Yes +
Protection procedure: Yes+
74
Section 10 IED physical connection
All connections are made on the rear of the case. No soldering is needed.
1. Connect each signal connector terminal with one 0.5~2.5 mm2 wire.
2. Connect each signal connector terminal with one 0.5~4.0 mm2 wire.
3. Connect terminals on the communication module for IRIG-B with one 0.2 ~1.5 mm2 wire.
75
POWER TRIP CPU AC
X3 X2 X1
DYGJ1 1 1 DI1 Ia 1 2 Ia'
1
OUTPUT1 DI2
2 DYGJ2 2 2
Ib 3 4 Ib'
24V+ 3 3 RMT-STU
3 OUTPUT2
24VG 4 4 MT-SIG
4 Ic 5 6 Ic'
L+ 5 COM 5 DI-NON-ELEC1
5
OUTPUT3 I0H 7 8 I0H'
6 L- 6 6 DI-NON-ELEC2
NC 7 OUTPUT4 7 DI-NON-ELEC3
7 Iac 9 10 Iac'
FE COM 8 DI-NON-ELEC4
8 8
9 OUTPUT5A 9 DI9 Ibc 11 12 Ibc'
10 OUTPUT5B 10 DI10
11 DI11 Icc 13 14 Icc'
11 OUTPUT6
12 DI12
12 I0L 15 16 I0L'
13 13 DI13
ATS-BLK U0 17
14 DI14 18 U0’
14
15 COM-
19 20
16 GPS(+)
X4 17 GPS(-) 21 22
COM 18 GPS_GND
1 Ua 23 24 Ub
PROT-OP-SIG
2
PROT-ALM-SIG Uc 25 26 Un
3
4 COM
5 TWJ
6 HWJ
7 +KM
8 HWJ- to tripping coil
9 Manual trip input
10 Trip input
11 To tripping coil
12 Close input COM1
13 To closing coil
14 TWJ- to closing coil
15 TBJV to -KM
COM2
16 -KM
Figure10.1 Protective earthing pole is located in the lower right corner of back side.
76
10.1.2 IED connection example
Digital inputs
P-5 POWER+ DI X5-05 X5-05
Power supply
P-6 POWER- DI X5-06 X5-06
P-1 DYGJ1 Loss of DI common- X5-07
P-2 DYGJ2 power Standby X5-08
P-3 24V+ 24V Standby X5-09
P-4 24V- Outputs Standby X5-10
P-7 Standby X5-11
P-8 PE Standby X5-12
X1-01 Ia Standby X5-13
Protection current
X1-02 Ia’ Standby X5-14
X1-03 Ib
X1-04 Ib’ X6-01
Ic X6:1-2
X1-05 X6-02
X1-06 Ic’ X6-03
X1-07 I0H X6:3-4
X6-04
X1-08 I0H' X6-05
X1-09 CIa X6:5-6
X6-06
Measured current
Outputs
X1-11 CIb X6:7-8
X6-08
X1-12 CIb’ X6-09
X1-13 CIc X6:9-10
X6-10
X1-14 CIc’ X6-11
X1-15 I0L X6:11-12
X6-12
X1-16 I0L' X6-13
X1-17 U0 X6:13-14
X6-14
X1-18 U0’
X6-15
X1-19 Standby X6:15-16
X6-16
X1-20 Standby
X1-21 Standby
X1-22 X3-01
Standby OUTPUT1
X1-23 Ua X3-02
AC voltage
X1-24 X3-03
Ub OUTPUT2
X1-25 X3-04
Uc
X1-26 COM X3-05
Un
OUTPUT3 X3-06
Outputs
A X3-07
OUTPUT4
X2-01 DI X2-01
COM X3-08
X2-02 DI X2-02
OUTPUT5A X3-09
X2-03 RMT-STU
OUTPUT5B X3-10
X2-04 MT-SIG
C B X3-11
Digital inputs
77
CPU module X2 No.2
DI/DO module
X5 No.4
(optional)
DI/DO module
X6 No.4
(optional)
10.2 Input
POWER AC
X5 X1
1 1 1 2
2 2
3 3 3 4
4 4
5 6
5 L+ 5
6 L- 6 7 8
7 7
9 10
8 8
9 11 12
10
13 14
11
12 15 16
13
14 17 18
19 20
X6 21 22
1 23 24
2
3 25 26
4
5
6
7
8
9
10
11
12
13
14
15
16
1 DYGJ1
Device loss-of-supply output contact
2 DYGJ2
78
3 24V+ 24V+
4 24VG 24VG
7 NC
8 FE
79
AC current can be configured according to engineering needs. The maximum current is
CPU
X2
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
NET1
NET2
terminal
Definition Description
X2
80
Can be set as common signal through configuring
7 DI-NON-ELEC3
operation parameter.
common negative
15
terminal
The voltage of binary input values is the same as the power supply voltage of the device. That
is, if the power supply of the device is 110V DC input, positive voltage of DI circuit should also be 110V.
The modules at position 3 are DI/DO modules. The sketch diagram is shown as follows:
81
TRIP
X3
1
2
3
4
5
6
7
8
9
10
11
12
13
14
X4
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
1
OUTPUT1 Output1
2
3
OUTPUT2 Output2
4
6 OUTPUT3 Output3
7 OUTPUT4 Output4
11
OUTPUT6 Output6
12
13
ATS-BLK Blocking automatic transfer switching
14
Note1: Output 5A is the normally open output contact for relay CKJ1. Output 5B is the normally close output
contact for relay CKJ1. They are two contacts for the same relay.
82
(2) Definition for TRIP module terminal X4
terminal
Definition Description
X4
The voltage of binary input values is the same as the power supply voltage of the device. That
is, if the power supply of the device is 110V DC input, positive voltage of DI circuit should also be
110V.
83
10.4 Time synchronization connection
CPU
X2
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
NET1
NET2
1)Definition for the time synchronization terminal of CPU module terminal X2:
84
synchronization function of SNTP.
If the method of synchronization is set to SNTP synchronization, the client IP address (IP
address B) should be set the same as the server IP address (PC IP address) to ensure the
point-to-point synchronization function of SNTP. It can be set through "Operational setting" -
"HMI setting" - "Other settings" - "Time synchronization setting".
(2) IRIG-B time synchronization operation: First, connect the IRIG+ and IRIG- pins of the external
clock source respectively to the GPS+ and GPS- pins of the MMI module. Then send IRIG-B
signal using external GPS time synchronization equipment to complete time synchronization for
the device. It can be set through "Operational setting" - "HMI setting" - "Other settings" - "Time
synchronization setting".
The EDP03 series low-voltage protection and measurement and control devices each has two
network port for network connections on the HMI panel. The two kinds of network port equipment each
has its own IP address, which is illustrated by Table 10-2 as follows:
From the previous sector 10.5, it can be seen that the Ethernet test port of the HMI device is the
COM 2 port on the HMI panel. Settings for the time synchronization port are shown in the following Table
10-3.
Table10-3: Illustration for test port COM2
Double-stranded
COM2 192.168.0.123 255.255.0.0
wire
IP Address, IP-Mask and port selection of the above-mentioned test port can be set through
"operational setting" - "HMI setting" - "Communication port 2".
85
Section 11 Technical data
Width 165 mm
Depth 197.7 mm
overload capability:
2*Rated Value
I • Continuous
40*Rated Value
•1s
10*Rated Value
• 16 s
86
Continuous effective value 1.5*Rated Value
Voltage tolerance:
Ethernet interface
Ethernet interface Protocol Cable data transfer
rate
protocol
protocol
Serial interface
Serial interface Protocol Cable data transfer
rate
IRIG-B Port
Type Protocol Cable
pin header
87
recommendation: CAT 5,BeldenRS-485 (9841-
Description Value
Environment
Description Reference value
Relative humidity
<93%,no condensation
storage
Environment test
Description Type test value Reference standard
Damp heat test steady state 240 h at +40ºC, humidity 93% IEC 60068-2-78
88
Section 12 IED and function test
other ports
non-communication port
f=0.15 - 80 MHz
● other ports 4 kV
line-to-line
Power frequency(50/60Hz)
1000 A/m IEC 61000-4-8:2009
magnetic field
100 A/m
● 3s
● continuous
89
Impulse magnetic field test 1000 A/m IEC 61000-4-9:2001
70%/500 ms
power down
terminal) CISPR22:2008
● Radiated, RF-emission
measured at 3m distance
measured at 3m distance
Dielectric test
90
communication port
energy 0.5J
energy 0.5J
Insulation resistance
● insulation resistance
91
Section 13 Glossary
ℱ Fourier transform
AC Alternating current
A/D converter Analog/Digital converter
AI Analog input
ANSI American National Standards Institute
BI Binary input
BOS Binary output status
CAN Controller Area Network. ISO standard (ISO 11898) for serial communication
CCITT Consultative Committee for International Telegraph and Telephony. A United Nations
sponsored standard body within the International Telecommunications Union.
COMTRADE Standard format according to IEC60255-24
CPU Central processing unit
CRC Cyclic redundancy check
CT Current transformer
DC Direct current
DFT Discrete Fourier transform
DHCP Dynamic Host Configuration Protocol
DI Digital input
DR Disturbance record
DRAM Dynamic random access memory
DRH Disturbance report handler
DSP Digital signal processor
EIA Electronics Industries Association
EMC Electromagnetic compatibility
EMI Electromagnetic interference
ESD Electrostatic discharge
GI General interrogation command
GOOSE Generic object-oriented substation event
GPS Global positioning system
HDLC protocol High level data link control, protocol based on the HDLC standard
LHMI Human-machine-interface
IEC International Electrical Committee
IEC 60044-6 IEC Standard, Instrument transformers – Part 6: Requirements for protective current
transformers for transient performance
92
IEC 61850 Substation automation communication standard
IEEE Institute of Electrical and Electronics Engineers, Inc.
IEEE 802.12 A network technology standard that provides 100 Mbits/s on twisted-pair or optical
fiber cable
IED Intelligent electronic device
IP 1. Internet protocol. The network layer for the TCP/IP protocol widely used on Ethernet networks. IP
is a connectionless, best-effort packet switching protocol. It provides packet routing,
fragmentation and re-assembly through the data link layer.
2. Ingression protection according to IEC standard
IP20 Ingression protection level is 20, according to IEC standard
IP40 Ingression protection level is 40, according to IEC standard
IP54 Ingression protection level is 54, according to IEC standard
IRF Internal failure signal
IRIG-B Inter range instrumentation group time code format B, standard 200
ITU International Telecommunications Union
LAN Local area network
LCD Liquid crystal display
LED Light-emitting diode
OV Over-voltage
Process bus Bus or LAN used at the process level, that is, in near proximity to the measured and/or
controlled components
PSM Power supply module
VT ratio Voltage transformer ratio
RISC Reduced instruction set computer
RMS value True root-mean-square (value)
RS485 Serial link according to EIA standard RS485
RTC Real-time clock
RTU Remote terminal unit
SA Substation Automation
SCADA Supervision, control and data acquisition
SCT System configuration tool according to standard IEC61850
SDU Service data unit
SNTP Simple network time protocol. It is used to synchronize computer clocks on local area
networks. This reduces the requirement to have accurate hardware clocks in every embedded
system in a network. Each embedded node can synchronize with a remote clock, providing the
93
remote clock requires accuracy.
TCP Transmission control protocol. The most common transport layer protocol used on Ethernet and
the Internet.
TCP/IP Transmission control protocol over Internet Protocol. TCP/IP was developed by DARPA for
Internet working and encompasses both network layer and transport layer protocols. While TCP
and IP specify two protocols at specific protocol layers, TCP/IP often refer to the entire US
Department of Defense protocol suite based upon these, including Telnet, FTP, UDP and
RDP.TPZ, TPY, TPX,TPS using the current transformer class in IEC standard.
UTC Universal Time Coordinated A coordinated time scale, maintained by the Bureau International
des Poids et Mesures (BIPM), which forms the basis of a coordinated dissemination of standard
frequencies and time signals. UTC is derived from International Atomic Time (TAI) by the
addition of a whole number of "leap seconds" to synchronize it with Universal Time 1 (UT1).
Thus allowing for the eccentricity of the Earth's orbit, the rotational axis tilt (23.5 degrees), but
still showing the Earth's irregular rotation, on which UTC is based. The Coordinated Universal
Time is expressed by a 24-hour clock and uses the Gregorian calendar. It is used for airplane
and ship navigation, while it is sometimes known by the military name, "Zulu time". "Zulu" in the
phonetic alphabet stands for "Z" which stands for longitude zero.
VT Voltage transformer
3IO The zero-sequence current. Often referred to as the zero-sequence or the earth-fault current
3UO The zero sequence voltage. Often referred to as the zero-sequence voltage or the neutral point
voltage
94
Contact Us
Nanjing SAC Power Grid Automation Co., Ltd. - Industry and Overseas BD
No. 4528, Kangxin Highway, Kangqiao Town, Pudong New Area, Shanghai, P.R.China 201319
Tel: +86 21 6105 6651
Fax: +86 21 6105 6749