Professional Documents
Culture Documents
8DHJ 36 Installation and Operating Manual-10
8DHJ 36 Installation and Operating Manual-10
8DHJ 36 Installation and Operating Manual-10
Type 8DJH 36
Gas-Insulated
Medium-Voltage Switchgear
INSTALLATION AND
OPERATING
INSTRUCTIONS
Safety instructions
1 Signal terms and definitions
DANGER
as used in these instructions, this means that personal injuries can occur if the relevant
precautionary measures are not taken.
➭ Observe the safety instructions.
ATTENTION
as used in these instructions, this means that damage to property or environment can occur if
the relevant precautionary measures are not taken.
➭ Observe the safety instructions.
NOTE
as used in these instructions, this points at facilitations of work, particularities for operation or
possible maloperation.
➭ Observe the notes.
Symbols used ➭ Operation symbol: Identifies an operation. Asks the operator to perform an operation.
✔ Result symbol: Identifies the result of an operation.
2 General instructions
Independently of the safety instructions given in these operating instructions, the local laws,
ordinances, guidelines and standards for operation of electrical equipment as well as for labor,
health and environmental protection apply.
DANGER
Any kind of modification on the product or alteration of the product must be coordinated with
the manufacturer in advance. Uncoordinated modifications or alterations can cause the
expiration of warranty claims, cause danger to life, limb and other legally protected interests.
The fulfillment of the type tests (according to IEC 62271-200) may not be guaranteed
anymore. This applies especially though not exclusively to the following actions, e.g. in the
course of maintenance or repairs:
➭ Original Siemens spare parts were not used.
➭ Service engineers performing replacement were not trained and certified by Siemens.
➭ Parts were fitted or adjusted incorrectly.
➭ Settings were not made in accordance with Siemens specifications.
➭ After installation and setting, no final check was performed by a service engineer approved
by Siemens, including documentation of the test results.
➭ Maintenance was not done according to the operating instructions of the Siemens
products.
Five Safety Rules of The Five Safety Rules of Electrical Engineering must be complied with during operation of the
Electrical Engineering products and components described in these operating instructions:
• Isolate.
• Secure against reclosing.
• Verify safe isolation from supply.
• Earth and short-circuit.
• Cover or barrier adjacent live parts.
Hazardous substances If hazardous materials are required to perform the work, the relevant safety data sheets and
operating instructions must be observed.
Personal protective For switchgear with proven internal arc classification according to IEC 62271 Part 200, no
equipment (PPE) protective equipment is required for operating the switchgear.
To work on switchgear where covers have to be removed, personal protective equipment
has to be worn for protection against hot gases exhausting in case of internal arc.
To select the protective equipment, the national standards and specifications of the
corresponding authorities and professional associations must absolutely be observed.
The protective equipment consists of:
• Protective clothing
• Safety shoes
• Gloves
• Helmet and face protection
• Ear protection
3 Due application
The switchgear corresponds to the relevant laws, prescriptions and standards applicable at the
time of delivery. If correctly used, it provides a high degree of safety by means of logical
mechanical interlocks and shockproof metal enclosure of live parts.
DANGER
The perfect and safe operation of this switchgear is conditional on:
➭ Observance of operating and installation instructions.
➭ Qualified personnel.
➭ Proper transportation and correct storage of the switchgear.
➭ Correct installation and commissioning.
➭ Diligent operation and maintenance.
➭ Observance of the instructions applicable at site for installation, operation and safety.
(e.g. DIN VDE 0101/0105).
4 Qualified personnel
Qualified personnel in accordance with these instructions are persons who are familiar with
transport, installation, commissioning, maintenance and operation of the product and have
appropriate qualifications for their work, as e.g.:
• Training and instruction or authorization to switch on, switch off, earth and identify power
circuits and equipment / systems as per the relevant safety standards.
• Instruction regarding the applicable specifications for the prevention of accidents and the
care and use of appropriate safety equipment.
• Training in first aid and behavior in the event of possible accidents
Description
5 Features
Typical uses 8DJH 36 switchgear is used - even under severe ambient conditions - for power distribution in
secondary distribution systems, such as
• Industrial distribution systems
• Consumer substations and transfer substations
They are available for rated voltages up to 36 kV and for rated feeder currents up to 630 A.
6 Functional modules
Panel modules
① Low-voltage compartment (option)
② Wiring duct (option)
③ Switchgear vessel, filled with gas
④ Operating mechanism of switching
device
⑤ Bushing for cable plug with bolted
contact (M16)
⑥ Cable compartment cover
⑦ Earthing busbar with earthing
connection
⑧ Pressure relief device
⑨ Three-position switch-disconnector
⑩ Control panel
⑪ Busbar
① Low-voltage compartment
(option)
② Wiring duct (option)
③ Switchgear vessel, filled with
gas
④ Operating mechanism of
switching device
⑤ Bushing for cable plug with
bolted contact
⑥ Cable compartment cover
⑦ Earthing busbar with earthing
connection
⑧ Pressure relief device
⑨ Vacuum circuit-breaker
⑩ Control board
⑪ Busbar
① Low-voltage compartment
(option)
② Wiring duct (option)
③ Cable compartment cover
④ Copper bars
⑤ Earthing bolt
⑥ Control cap
⑦ Earthing busbar with earthing
connection
⑧ Voltage transformer
⑨ Current transformer
⑩ Vessel bushing
⑪ Busbar
7 Components
Mode of operation The operating shaft forms one unit together with the three contact blades. Due to the
arrangement of the fixed contacts (earth - busbar), it is not necessary to interlock the CLOSE
and EARTHING functions.
Closing operation During the closing operation, the operating shaft with the moving contact blades changes
from the OPEN to the CLOSED position.
The spring force of the spring-operated / spring-operated/stored-energy mechanism ensures a
high closing speed and a reliable connection of the main circuit.
Opening operation During the opening operation, the arc is caused to rotate by the arc-suppression system, thus
preventing the development of a fixed root. This very effective arc extinction provides short
arcing times. The isolating distance in gas established after opening fulfils the conditions for
isolating distances according to IEC/EN 62271-102 / VDE 0671-102, IEC/EN 62271-103 /
VDE 0671-103 and IEC/EN 62271-1 / VDE 0671-1.
Earthing operation The EARTHING operation is implemented by the turning movement of the operating lever
(rotation, if required) from the OPEN to the EARTHED position.
Spring-operated The spring-operated mechanism is used for the three-position switch-disconnector in ring-
mechanism main panels (as ring-main switch). The switching movements are performed independently of
the operating speed.
Design The three-position switch-disconnector is operated through a gas-tight welded bushing at the
front of the switchgear vessel.
Ring-main feeder:
① Ready-for-service indicator
② MCU (Motor Control Unit, option)
③ ON/OFF switch for motor operating
mechanism (option)
④ Local/remote switch for motor operating
mechanism (option)
⑤ Auxiliary switch (option)
⑥ Control gate/locking device for three-position
switch-disconnector
⑦ Motor operating mechanism (option)
⑧ Sockets for capacitive voltage detecting
system (feeder)
⑨ Actuating opening for EARTHING
⑩ Position indicator for three-position switch-
disconnector
⑪ Actuating opening for DISCONNECTING
⑫ Sockets for capacitive voltage detecting
system (busbar)
Fig. 6: Front operating mechanism in ring-main
feeder
Transformer feeder:
① Ready-for-service indicator
② ON/OFF switch for motor operating mechanism (option)
③ Local/remote switch for motor operating mechanism (option)
④ ON pushbutton (mechanical operation)
⑤ Auxiliary switch (option)
⑥ Control gate/locking device for three-position switch-
disconnector
⑦ Motor operating mechanism (option)
⑧ Sockets for capacitive voltage detecting system (feeder)
⑨ Actuating opening for EARTHING
⑩ "Fuse tripped" indicator
⑪ Position indicator for three-position switch-disconnector
⑫ OFF pushbutton (mechanical operation)
⑬ Actuating opening for charging the spring energy store
⑭ Shunt release (f-release, option)
⑮ Spring energy store indicator
Fig. 7: Front operating mechanism in transformer feeder ⑯ Sockets for capacitive voltage detecting system (busbar)
Sequence 1 2 3 4
Operation
Charging the
spring
Switch position OPEN OPEN CLOSED OPEN
Position indicator
Mechanism operation Operating levers for charging the springs of the switch-disconnector and the make-proof
earthing switch. Coding of the operating levers is optionally possible.
Shunt release (f-release) Stored-energy mechanisms can optionally be equipped with a magnetic tripping coil (f-
for OPEN (optional) release, -Y3). Remote electrical tripping of the three-position switch-disconnector, e.g. from
the control room, is possible via the magnetic tripping coil, e.g. transformer overtemperature
tripping.
To avoid thermal overloading of the shunt release in the event of a continuous signal that may
be applied, the shunt release is switched off via an auxiliary switch which is mechanically
coupled with the three-position switch-disconnector.
In transformer panels, electrical continuity at the shunt release (f-release) can only be tested
when the operating lever is removed.
Auxiliary switch The operating mechanism of the three-position switch-disconnector can be optionally equipped
(optional) with an auxiliary switch for the position indication. A motor operating mechanism is equipped
with an auxiliary switch as standard.
• For switch-disconnector function: CLOSED and OPEN: 1 NO + 1 NC + 2 changeover
• For earthing switch function: CLOSED and OPEN: 1 NO + 1 NC + 2 changeover
Wiring Auxiliary switches, motor operating mechanisms or shunt releases are wired to terminal strips.
The terminal strips are feeder-related and located above the operating mechanism assembly
of the feeder concerned. Customer-side cable routing is made from the side to the terminal
strip arranged on the operating mechanism assemblies.
Operating function The closing spring is charged by means of the hand crank supplied, or by the motor (option),
until the latching of the closing spring is indicated (spring energy store indicator shows "spring
charged"). Then, the vacuum circuit-breaker can be closed manually or electrically (option).
In operating mechanisms provided for automatic reclosing (AR), the closing spring can be
recharged by hand, or automatically in case of motor operating mechanism. This enables an
immediate automatic reclosing.
Operating mechanism for The operating mechanism assigned to a circuit-breaker feeder consists of the following
circuit-breaker feeder components:
• Operating mechanism for circuit-breaker
• Operating mechanism for three-position disconnector
• Motor operating mechanism (optional)
• Position indicators
• Pushbuttons for CLOSING and OPENING the circuit-breaker
• Mechanical operations counter
• Interlocking between circuit-breaker and disconnector
• "Spring charged" indicator
The vacuum circuit-breaker consists of a vacuum interrupter unit with integrated three-
position disconnector located in the switchgear vessel, and the associated operating
mechanisms.
The vacuum circuit-breaker is a circuit-breaker for automatic reclosing.
For further data, see page 34, "Technical data".
In individual panels, the rating plate is located top-left on the front cover, in blocks it is only
provided on the left-hand panel.
① Ready-for-service indicator
② Actuating opening for three-position disconnector,
DISCONNECTING function
③ Position indicator for three-position disconnector
④ Control gate/locking device for three-position disconnector
⑤ Actuating opening for three-position disconnector, EARTHING
function
⑥ Sockets for capacitive voltage detecting system (feeder)
⑦ Spring energy store indicator for circuit-breaker
⑧ Operations counter
⑨ Position indicator for circuit-breaker
⑩ Circuit-breaker ON pushbutton (mechanical operation)
⑪ Circuit-breaker OFF pushbutton (mechanical operation)
⑫ Opening spring
⑬ Actuating opening for charging the spring energy store
⑭ Closing spring
⑮ Sockets for capacitive voltage detecting system (busbar)
① Ready-for-service indicator
② Actuating opening for three-position disconnector,
DISCONNECTING function
③ Position indicator for three-position disconnector
④ Control gate/locking device for three-position disconnector
⑤ Actuating opening for three-position disconnector, EARTHING
function
⑥ Sockets for capacitive voltage detecting system (feeder)
⑦ Closing spring
⑧ Spring energy store indicator for circuit-breaker
⑨ Operations counter
⑩ Position indicator for circuit-breaker
⑪ Opening spring
⑫ ON pushbutton for circuit-breaker (mechanical operation)
⑬ Circuit-breaker OFF pushbutton (mechanical operation)
⑭ Actuating opening for charging the spring energy store
⑮ Sockets for capacitive voltage detecting system (busbar)
Secondary components The scope of the secondary equipment of the vacuum circuit-breaker depends on the type of
application.
C.t-operated release • For tripping pulse 0.1 Ws in conjunction with suitable protection systems, e.g. protection
(option) system 7SJ45, SEG WIC; other designs on request
• Used if external auxiliary voltage is missing, tripping via protection relay
Anti-pumping • Standard
(mechanical and • Function: If constant CLOSE and OPEN commands are present at the vacuum circuit-breaker
electrical) at the same time, the vacuum circuit-breaker will return to the open position after closing,
and remains in this position until a new CLOSE command is given. In this manner,
continuous closing and opening (= pumping) is avoided.
Circuit-breaker tripping • For electrical signaling (as pulse ≥ 10ms), e.g. to remote control systems, in the case of
signal (option) automatic tripping (e.g. protection)
• Via limit switch and cutout switch
• Via auxiliary switch
• During operation of the three-position disconnector from CLOSED to OPEN and from
EARTHED to OPEN, the vacuum circuit-breaker cannot be closed
• When the vacuum circuit-breaker is closed, the three-position disconnector is interlocked
7.3 Interlocks
Mechanical interlocking • The switching gate prevents switching straight from CLOSED to EARTHED position, or from
EARTHED to CLOSED position, as the operating lever must be re-inserted in the OPEN
position.
• The cable compartment cover (HV HRC fuse compartment cover) can only be removed if the
transformer feeder is earthed and the operating lever is removed.
The three-position switch-disconnector can only be switched from the EARTHED position to
another position if the cable compartment cover (HV HRC fuse compartment cover) is fitted.
• Interlocks between the circuit-breaker and the three-position disconnector:
- Circuit-breaker in OPEN position:
The three-position disconnector can be closed and opened. The circuit-breaker is locked out.
- Circuit-breaker in CLOSED position:
The three-position disconnector cannot be operated.
• The cable compartment covers can only be removed when the associated feeder is earthed.
• A closing lockout (option) in the ring-main feeder or the circuit-breaker feeder prevents the
three-position disconnector / three-position switch-disconnector from being switched to the
CLOSED position if the cable compartment cover is removed.
• A de-earthing lockout in the transformer panel (standard), the ring-main panel or the
circuit-breaker panel (option) prevents the three-position disconnector / three-position
switch-disconnector from being switched from EARTHED to OPEN position if the cable
compartment cover is removed.
• Closing and opening with the stored-energy mechanism and the circuit-breaker operating
mechanism is not possible if the operating lever is inserted.
• The locking device (option) of the switching gate can be padlocked in all three switch
positions. The locking device can be padlocked so that no closing or no opening or no
earthing is possible. The padlock can also be fitted in such a way that none of the three
switching operations can be performed.
Electrical interlock If the operating lever for the three-position switch is inserted, the motor operating
mechanism cannot be operated from remote or locally anymore.
Features • HV HRC fuse-links according to DIN 43 625 (main dimensions) with striker in "medium"
version according to IEC/EN 60 282-1
- as short-circuit protection before transformers,
- with selectivity to upstream and downstream connected equipment,
- 1-pole insulated
• Requirements according to IEC 62 271-105 / VDE 0671-105 met by the combination of
HV HRC fuse-links with the three-position switch-disconnector
• Striker tripping when the corresponding HV HRC fuse-link is used
• Climate-independent and maintenance-free, with fuse boxes made of cast resin
• Arrangement of fuse assembly in the switchgear vessel
• Sealed fuse boxes in the gas compartment, connected with the three-position switch-
disconnector via a connecting bar
• Fuse replacement is only possible when the feeder is earthed
• Option: "Tripped indication" of the HV HRC fuse of the transformer switch for remote
electrical indication with 1NO contact
Components of the
① Handle of locking system
HV HRC fuse assembly
② Slide of fuse tripping
③ Trip lever
④ Rocker of fuse tripping
⑤ Tripping pin of HV HRC fuse
⑥ HV HRC fuse
Mode of operation In the event that an HV HRC fuse-link has tripped, the switch is tripped via an articulation
which is integrated into the cover of the fuse box.
Fig. 14: Cable connection with Fig. 15: Cable connection with pressure
pressure relief downwards relief to the rear/upwards
NOTE
In certain ring-main panels, circuit-breaker panels and cable panels, an internal arc
additive must be mounted at the cable connection:
• In panels with pressure relief to the rear
• In panels with pressure relief downwards and deeper cable compartment cover
• For bushings according to EN 50 181/DIN EN 50 181 (interface type C with bolted contact
M16)
• For thermoplastic-insulated cables
• For paper-insulated mass-impregnated cable with adapter systems
• Access to the cable compartment only if the feeder has been disconnected and earthed
• As screened (semi-conductive) version independent of the site altitude
• Connection of cable elbow plugs or cable T-plugs with bolted contact M16 for 630 A, paper-
insulated mass-impregnated cables via customary adapters, power cables as thermoplastic-
insulated single-core cables with the corresponding plugs and adapters mentioned above
Possible connections • Cable testing e.g. with measuring bolt, make nkt cables, type PAK 630, see page 170, "Cable
testing"
• Conventional sealing end: As customer supply
Fig. 16: Cable connection with plug-in Fig. 17: Cable connection with bolted
contact (interface type B) contact (interface type C)
Features • For bushings according to EN 50 181/DIN EN 50 181 (interface type B with plug-in contact)
• For bushings according to EN 50 181/DIN EN 50 181 (interface type C with bolted contact
M16)
Cable sealing ends The transformer cables are connected with cable plugs.
Number of Make Conductor cross- Elbow connectors Coupling inserts/ Surge arresters
cables per section coupling plugs
panel and
phase [mm2] plugged in plugged in Arresters Coupling unit
Number of Make Conductor cross- Cable T-plugs Coupling inserts/ Surge arresters
cables per section coupling plugs
panel and
[mm2] plugged in plugged in Arresters Coupling unit
phase
• Transformer feeder with outside-cone connection type B
1 Nexans Euromold 50...240 1 x M400TE/G – – –
Südkabel 50...300 1 x SET 36-B
nkt cables 25...300 1 x CB 36-400
Prysmian 25...300 1 x FMCT-400
Number of Make Conductor cross- Cable T-plugs Coupling inserts/ Surge arresters
cables per section coupling plugs
panel and
phase [mm2] plugged in plugged in Arresters Coupling unit
1) If this plug combination is used, or with a surge arrester, a 105 mm deeper cable compartment cover is
necessary
2) If this plug combination is used, or with a surge arrester, a 250 mm deeper cable compartment cover is
necessary
Features • Busbar extension possible on all individual panels and panel blocks (option)
• Plug-in unit consisting of contact coupling and screened silicone coupling
• Insensitive to pollution and condensation
• Switchgear installation, extension or panel replacement is possible without gas work
Design Every switchgear block and every individual panel are optionally available with busbar
extension on the right, on the left, or on both sides. This offers a high flexibility for the
creation of switchgear configurations whose functional units are lined up in any order. Local
installation and lining up is done without gas work.
Lining up takes place as follows:
• By the busbar couplings. Tolerances between adjacent panels are compensated by spherical
fixed contacts and the movable contact couplings with degrees of freedom in all axis
directions.
• By safe dielectric sealing with screened silicone couplings that are externally earthed and
adjustable to tolerances. The silicone couplings are pressed on with a defined pressure
when the panels are interconnected.
• On free busbar ends, screened dummy plugs are inserted, each of which is pressed on
through a metal cover. A common protective cover with a warning is fixed over all 3 covers.
• By guiding tension bolts for easier switchgear installation and fixing of adjacent panels.
• By bolted panel joints with defined stops for the distances between adjacent panels and the
associated pressure of contact pieces and silicone couplings.
Technical data The technical data of the current transformers and the voltage transformers is given in the
associated order documents.
• Verification of safe isolation from supply phase by phase through insertion of the voltage
indicator in the corresponding plug-in sockets
• Voltage indicator flashes if high voltage is present (see page 162, "HR/LRM plug-in sockets")
• Indicator suitable for continuous operation
• Safe-to-touch
• Measuring system and voltage indicator can be tested
The marking for documentation of the repeat test of the interface condition is located next to
the HR/LRM plug-in sockets:
VOIS+, VOIS R+
CAPDIS-S1+/S2+
DANGER
High voltage! Danger! Do only modify the factory setting of the C2 module in the voltage
detecting system CAPDIS-S1+/S2+ after consultation with the regional Siemens representative!
➭ If the setting of the C2 module was modified by mistake, re-establish the factory setting as
follows:
- Pull out the C2 module ③ at the rear side of CAPDIS-S1+/S2+. Caution: Open printed
circuit board may be energized.
- Plug the C2 module ③ into CAPDIS-S1+/S2+ so that the marked arrow ① on the housing
points to the marking ② on the C2 module
Features of • With indication "A0" to "A8" (see page 163, "Indications VOIS, VOIS R+, CAPDIS -S1+/-S2+")
CAPDIS-S2+ • Only by pressing the "Test" pushbutton: "ERROR" indication (A8), e.g., in case of missing
auxiliary voltage
• With ready-for-service monitoring (external auxiliary power required)
• With integrated signaling relays for signals "M1" to ”M4” (auxiliary power required):
- "M1": Voltage present at phases L1, L2, L3
- "M2": Voltage not present at L1, L2 and L3 (= active zero indication)
- "M3": Earth fault or voltage failure, e.g., in one phase
- "M4": External auxiliary power missing (with operating voltage present or not)
WEGA 1.2
Features of • With indication "A1" to "A5" (see page 165, "Indications WEGA 1.2, WEGA 2.2")
WEGA 1.2 • Maintenance-free
• Integrated repeat test of the interface (self-monitoring)
• With integrated function test (without auxiliary power) by pressing the "Display Test" button
• With integrated 3-phase LRM test socket for phase comparison
• Degree of protection IP 54, temperature range –25 °C to +55 °C
• Without integrated signaling relay
• Without auxiliary power
WEGA 2.2
Features of • With indication "A0" to "A6" (see page 165, "Indications WEGA 1.2, WEGA 2.2")
WEGA 2.2 • Maintenance-free
• Integrated repeat test of the interface (self-monitoring)
• With integrated function test (without auxiliary power) by pressing the "Display Test" button
• With integrated 3-phase LRM test socket for phase comparison
• Degree of protection IP 54, temperature range –25 °C to +55 °C
• With integrated signaling relay
• Auxiliary power required
Mode of operation
① Switching-device vessel
(filled with SF6 gas)
② Measurement box
③ Magnetic coupling
④ Red indication:
not ready for service / do not switch
⑤ Green indication: ready for service
For the ready-for-service indicator, a gas-tight measurement box is installed inside the
switching-device vessel.
A coupling magnet, which is fitted to the bottom end of the measurement box, transmits its
position to an armature outside the switching-device vessel through the non-magnetizable
switching-device vessel (magnetic coupling). This armature moves the ready-for-service
indicator at the operating front of the panel.
While changes in the gas density during the loss of gas, which are decisive for the dielectric
strength, are displayed, changes in the relative gas pressure resulting from temperature and
external pressure variations are not. The gas in the measurement box has the same
temperature as that in the switching-device vessel.
The temperature effect is compensated via the same pressure change in both gas volumes.
• The switchgear operates perfectly in a range between the rated filling level of 150 kPA and
the minimum functional level of 130 kPA.
• If the gas pressure falls below 130 kPA, the switchgear must not be operated anymore.
The ready-for-service indicator changes from the green area to the red area ("Not ready for
service").
• When the ready-for-service indicator changes from the green to the red area or vice versa,
the signaling switch is tripped.
① 1 normally closed
contact
② 1 normally open
contact
7.13 Accessories
• Double-bit key with a diameter of 3 mm for the door of the low-voltage compartment
(option)
• Hand crank for charging the spring energy store in the circuit-breaker panel
① Wiring duct
② Low-voltage compartment
Shipping and If the switchgear is delivered with low-voltage compartment, please observe the different
transport data transport dimensions and weights as well as the relocation of the center of gravity.
8 Technical data
Three-position
switch-disconnector Switching capacity for general-purpose switches according to IEC 62271-103 / VDE 0671 - 103
Rated voltage Ur kV 361
Test duty TD load Rated mainly active load-breaking 100 operations Iload [I1] A 630
current Iload 20 operations 0.05 Iload A 31.5
[I1]
Test duty TD loop Rated closed-loop breaking current Iloop [I2a] A 630
Test duty TDcc Rated cable-charging breaking current ICC [l4a] A 50
Test duty TDIc Rated line-charging breaking current IIc [l4b] A 50
Test duty TDma Rated short-circuit making current Ima 50 Hz up to kA 50
60 Hz up to kA 52
Test duty TDef1 Rated earth-fault breaking current Ief1 [l6a] A 150
Test duty TDef2 Rated cable-charging breaking current and line-charging A 87
breaking current under earth-fault conditions Ief2 [former I6b( √
3 · I4a or I4b)]
Number of mechanical operating cycles / M-classification n 1,000 / M12)
Number of electrical operating cycles with Iload / Classification n 100 / E3
Number of short-circuit making operations lma / Classification n 5/E3
C-classification For general-purpose switches (no restrikes, TD: Icc, Ilc) C2
1
Design option: Switching capacity test performed with Utest = 38 kV
2
Optional: 2,000 / M2 operating cycles
Switching capacity for make-proof earthing switch according to IEC 62271-102 / VDE 0671-102
Rated voltage Ur kV 361
Rated short-circuit making current Ima 50 Hz up to kA 50
60 Hz up to kA 52
Number of mechanical operating cycles n 1000
Number of short-circuit making operations / Classification n 5 / E2
Switch-disconnector/
fuse combination Switching capacity for switch-disconnector/fuse combination according to IEC 62271-105 / VDE 0671-105
Rated voltage Ur kV 361
Rated normal current A 2002
Rated transfer current (for striker operation) 36 kV 50 Hz Itransfer A 8003
Rated transfer current (for striker operation) 36 kV 60 Hz Itransfer A 7003
Rated transfer current (for striker operation) 38 kV 60 Hz Itransfer A 7003
Rated transfer current (for release operation / protection tripping) Itransfer A
8003
36 kV 50 Hz
Rated transfer current (for release operation / protection tripping) Itransfer A
7003
36 kV 60 Hz
Rated transfer current (for release operation / protection tripping) Itransfer A
7003
38 kV 60 Hz
Maximum transformer rating kVA 2500
Tripping time for striker operation (switch-fuse combination) ms ≥ 60
Tripping time for release operation ms ≥ 130
Setting time for delay at the protection device ms ≥ 100
Switching capacity for make-proof earthing switch, with HV HRC fuses on feeder side
Rated voltage Ur kA 361
Rated short-circuit making current Ima 50 Hz kA 6.3
60 Hz kA 6.5
Rated short-time withstand current Ik with tk = 1 s kA 2.5
Disconnector
Rated voltage Ur kV 361
Rated normal current Ir A 630
Number of mechanical operating cycles / Classification n 1000 / M0
1
Design option: Switching capacity test performed with Utest = 38 kV
1
Design option: Switching capacity test performed with Utest = 38 kV
2
Automatic reclosing
Operating times, contacts The time indications in the following table refer to the application of the switchgear in
accordance with IEC 60721-3-3 Class 3K4. If the switchgear is operated beyond this range, the
indicated times may deviate.
1) For operation of the switchgear beyond the range defined by IEC 60721-3-3 Class 3K4, a minimum
command duration of 100 ms is recommended.
Closing time The interval of time between the initiation (command) of the closing operation and the
instant when the contacts touch in all poles.
Opening time The interval of time between the initiation (command) of the opening operation and the
instant when the contacts separate in all poles.
Arcing time The interval of time from the first initiation of an arc and the instant of final arc extinction in
all poles.
Break time The interval of time between the initiation (command) of the opening operation and the
instant of final arc extinction in the last-pole-to-clear (=opening time and arcing time).
Close-open contact time The interval of time - in a make-break operating cycle - between the instant when the contacts
touch in the first pole in the closing process, and the instant when the contacts separate in all
poles in the subsequent opening process.
Motor operating For DC operation, the maximum power consumption is approx. 500 W. For AC operation, the
mechanism maximum power consumption is approx. 650 VA.
Rated current of the motor protection equipment:
[V] [A]
24 DC 8
48 DC 6
60 DC 4
DC/AC 110 3
50/60 Hz
DC 220/AC 230 2
50/60 Hz
The supply voltage may deviate from the rated supply voltage specified in the table
by –15% to +10% .
Closing solenoid The closing solenoid closes the circuit-breaker. After completion of a closing operation, the
(Y9) closing solenoid is de-energized internally. It is available for AC or DC voltage.
Power consumption: 140 W or 140 VA.
Shunt release (Y1) Shunt releases are used for tripping circuit-breakers. They are designed for connection to
external voltage (DC or AC voltage). They can also be connected to a voltage transformer by
means of a protection relay.
With the shunt release (Y1), the circuit-breaker is opened electrically. ´
Power consumption: 140 W or 140 VA.
Additional release In the case of additional releases, the electrical opening command is transmitted to the
(Y2, Y4, Y6, Y7) opening latch via a directly acting magnet armature by unlatching an energy store and thus,
the circuit-breaker is opened.
Shunt release With the shunt release (Y2), the circuit-breaker is opened electrically.
(Y2) Power consumption: 70 W or 50 VA.
Undervoltage release The undervoltage release is energized as long as the circuit-breaker is in closed position. If the
(Y7) voltage at the circuit-breaker falls below a predetermined value, the undervoltage release
trips the circuit-breaker. The tripping of the undervoltage release takes place via a NC contact
in the tripping circuit or by short-circuiting the magnet coil via a NO contact. With this type of
tripping, the short-circuit current is limited by the built-in resistors.
Power consumption: 20 W or 20 VA.
Circuit-breaker tripping When the circuit-breaker is tripped by a release (e.g. by protection tripping) there is a signal
signal through the NO contact -S6. If the circuit-breaker is tripped deliberately with the mechanical
pushbutton, this signal is suppressed by the NC contact -S7.
Type approval according The vacuum interrupters fitted in the vacuum circuit-breakers are type-approved in
to German X-ray accordance with the X-ray regulations of the Federal Republic of Germany. They conform to
regulations (RöV) the requirements of the X-ray regulations of January 8, 1987 (Federal Law Gazette I 1987,
Page 114) in the new edition of April 30, 2003 (Federal Law Gazette I 2003, No. 17) up to the
value of the rated voltage stipulated in accordance with IEC/DIN VDE.
Electromagnetic The a.m. standards as well as the "EMC Guide for Switchgear"* are applied during design,
compatibility - EMC manufacture and erection of the switchgear. Installation, connection and maintenance have
to be performed in accordance with the stipulations of the operating instructions. For
operation, the legal stipulations applicable at the place of installation have to be observed
additionally. In this way, the switchgear assemblies of this type series fulfill the basic
protection requirements of the EMC guide.
The switchgear operator / owner must keep the technical documents supplied with the
switchgear throughout the entire service life, and keep them up-to-date in case of
modifications of the switchgear.
* (Dr. Bernd Jäkel, Ansgar Müller; Medium-Voltage Systems - EMC Guide for Switchgear; A&D
ATS SR/PTD M SP)
Protection against solid The 8DJH 36 panels fulfill the following degrees of protection according to IEC 62271-200,
foreign objects, electric IEC 60529 and DIN VDE 0671-200:
shock and water • IP2X standard for parts under high voltage in switchgear panels with HV HRC fuses
• IP3X option for switchgear enclosure of operating front and side walls
• IP4X option for low-voltage compartments
• IP65 for parts under high voltage in switchgear panels without HV HRC fuses, or switchgear
without air-insulated metering panels
Transport regulations According to "Annex A of the European Agreement Concerning the International Carriage of
Dangerous Goods by Road (ADR)" launched on September 30, 1957, Siemens gas-insulated
medium-voltage switchgear does not belong to the category of dangerous goods in respect of
transportation, and is exempted from special transport regulations according to ADR,
Clause 1.1.3.1 b).
Packing weights
Maximum width of Dimensions of the Packing weights for switchgear with pressure relief
the transport unit wooden pallet downwards
Maximum width of Dimensions of the Packing weights for switchgear with 250 mm deeper cable
the transport unit wooden pallet compartment cover
Switchgear weights The total weight of the switchgear results from the sum of the weights per functional unit.
Depending on the design and the degree to which it is equipped (e.g. current transformers,
motor operating mechanism, low-voltage compartment), different values will result. The table
shows mean values.
Gas leakage rate The gas leakage rate is < 0.1% per year (referred to the absolute gas pressure).
Dielectric strength • The dielectric strength is verified by testing the switchgear with rated values of short-
duration power-frequency withstand voltage and lightning impulse withstand voltage
according to IEC 62271-1 / VDE 0671-1.
• The rated values are referred to sea level and to normal atmospheric conditions
(101.3 hPa, 20 °C, 11g/m3 humidity according to IEC 60071 and VDE 0111).
• The dielectric strength decreases with increasing altitude. For site altitudes above 1000 m
(above sea level) the standards do not provide any guidelines for the insulation rating, but
leave this to the scope of special agreements.
All parts housed inside the switchgear vessel which are subjected to high voltage are
SF6-insulated against the earthed enclosure.
Site altitude The gas insulation in the switching-device vessel at a relative gas pressure of 50 kPa permits
switchgear installation at an altitude of up to 2000 m (above sea level) without the dielectric
strength being adversely affected. This also applies to the cable connection when using
screened cable T-plugs or cable elbow plugs.
In panels with HV HRC fuses and in metering panels, a decrease (reduction) of the dielectric
strength must be considered for site altitudes as of 1000 m (above sea level).
Up to 1000 m 1000 m to 2000 m (above sea level) 2000 m to 3500 m (above sea level) 3500 m to 4000 m (above sea level)
(above sea level)
No restrictions for panel types and block Not permissible:
versions. • Metering panel type cable-busbar (busbar-cable)
• Metering panel type busbar-busbar
Temperature range: -25 °C ... +40 °C (above +40 °C, reduction of permissible current Temperature range: -25 °C ... +35 °C
carrying capacity) (above +35 °C, reduction of permissible
current carrying capacity)
No restrictions Reduction of the dielectric strength Reduction of the dielectric strength Reduction of the dielectric strength
for transformer feeders and metering for transformer feeders and metering for transformer feeders and metering
panels. panels (Un = 24 kV). panels (Un = 17.5 kV).
• 2000 m (above sea level): • 3500 m (above sea level): • 4000 m (above sea level):
Ka = 1.13 Ka = 1.36 Ka = 1.45
Up = 150 kV Up = 125 kV Up = 117 kV
Ud = 62 kV Ud = 50 kV Ud = 48 kV
Altitude correction factor For site altitudes above 1000 m, the altitude correction factor Ka must be considered.
Curve m=1 for rated short-duration power-frequency withstand voltage and rated lightning
impulse withstand voltage according to IEC 62271-1 / VDE 0671-1.
Fig. 39: Correction factor Ka as a function of the site altitude in m above sea level
Note to HV HRC fuse-links According to IEC 60282-1 (2009) Clause 6.6, the breaking capacity of HV HRC fuses is tested
within the scope of the type test at 87% of their rated voltage.
In three-phase systems with resonance-earthed or isolated neutral, under double earth fault
and other conditions, the full phase-to-phase voltage may be available at the HV HRC fuse
during breaking. Depending on the size of the operating voltage of such a system, this applied
voltage may then exceed 87% of the rated voltage.
It must therefore already be ensured during configuration of the switching devices and
selection of the HV HRC fuse that only such fuse-links are used, which either satisfy the above
operating conditions, or whose breaking capacity was tested at least with the maximum
system voltage.
In case of doubt, a suitable HV HRC fuse must be selected together with the fuse
manufacturer.
Allocation of HV HRC fuses and transformers
The three-position switch-disconnector in the transformer feeder (transformer switch) was
combined with HV HRC fuse-links and tested in accordance with IEC 62271-105.
The following transformer protection table shows HV HRC fuse-links tested by Siemens, which
are recommended for transformer protection. Furthermore, the switchgear also permits fuse
protection of transformers up to ratings of 2000 kVA. For such applications, please contact
your regional Siemens representative.
The protection table applies to:
• Maximum ambient air temperature in the switchgear room of 40°C according to IEC 62 271-1
considering the influence of the switchgear enclosure
• Requirements according to IEC 62271-105
• Protection of distribution transformers according to IEC 60787
• Nominal power of transformer (no overload operation)
The specified SIBA HV HRC fuses are type-tested back-up fuses according to IEC 60282-1. The
dimensions correspond to DIN 43625. The HV HRC fuses have a thermal protection in form of
a temperature-limiting striker tripping operating in case of defective HV HRC fuse-links or high
overload currents.
Please contact your regional Siemens representative if you want to use HV HRC fuses from
other manufacturers.
Basis for selection of HV HRC fuse-links:
• IEC 60282-1
• IEC 62271-105
• IEC 60787
• Recommendations and data sheets of fuse manufacturers
• Permissible power loss in the switchgear enclosure at an ambient air temperature of 40° C
ATTENTION
Please use only fuses tested by Siemens, which are listed in the following fuse tables.
➭ The use of other fuse types must be checked by Siemens in advance. Please contact the
regional Siemens representative.
Transformer protection table for allocation of tested HV HRC fuse-links make SIBA
and transformers
[kV] [kV] [kV] SN [kVA] uk [%] I1 [A] Ifuse [A] Ufuse [kV] d [mm]
50 4 1.2 - - - -
75 4 1.8 6.3 20 ... 36 53 30 008 13.6.3
100 4 2.4 6.3 20 ... 36 53 30 008 13.6.3
125 4 3.0 10 20 ... 36 53 30 008 13.10
160 4 3.8 10 20 ... 36 53 30 008 13.10
200 4 4.8 16 20 ... 36 53 30 008 13.16
250 4 6.0 16 20 ... 36 53 30 008 13.16
315 4 7.6 20 20 ... 36 53 30 008 13.20
400 4 9.6 20 20 ... 36 53 30 008 13.20
500 4 12.0 25 20 ... 36 53 30 008 13.25
630 4 15.2 31.5 20 ... 36 67 30 016 13.31.5
24 36 20 800 5 19.2 40 20 ... 36 67 30 016 13.40
800 6 19.2 - - - -
1000 5 24.1 40 20 ... 36 67 30 016 13.40
1000 6 24.1 40 20 ... 36 67 30 016 13.40
1250 5 30.1 63 BSSK 20 ... 36 85 30 024 43.63
1250 6 30.1 63 BSSK 20 ... 36 85 30 024 43.63
1600 5 38.5 80 BSSK 20 ... 36 85 30 024 43.80
1600 6 38.5 - - - -
2000 5 48.1 80 BSSK 20 ... 36 85 30 024 43.80
2000 6 48.1 80 BSSK 20 ... 36 85 30 024 43.80
2500 5 60.1 - - - -
2500 6 60.1 - - - -
50 4 1.2 - - - -
75 4 1.7 6.3 20 ... 36 53 30 008 13.6.3
100 4 2.3 6.3 20 ... 36 53 30 008 13.6.3
125 4 2.9 10 20 ... 36 53 30 008 13.10
160 4 3.7 10 20 ... 36 53 30 008 13.10
200 4 4.6 16 20 ... 36 53 30 008 13.16
250 4 5.8 16 20 ... 36 53 30 008 13.16
315 4 7.3 20 20 ... 36 53 30 008 13.20
400 4 9.2 20 20 ... 36 53 30 008 13.20
500 4 11.5 25 20 ... 36 53 30 008 13.25
630 4 14.5 31.5 20 ... 36 67 30 016 13.31.5
25 36 20 800 5 18.5 40 20 ... 36 67 30 016 13.40
800 6 18.5 - - - -
1000 5 23.1 40 20 ... 36 67 30 016 13.40
1000 6 23.1 40 20 ... 36 67 30 016 13.40
1250 5 28.9 50 20 ... 36 85 30 024 13.50
1250 6 28.9 50 20 ... 36 85 30 024 13.50
1600 5 37.0 63 BSSK 20 ... 36 85 30 024 43.63
1600 6 37.0 63 BSSK 20 ... 36 85 30 024 43.63
2000 5 46.2 80 BSSK 20 ... 36 85 30 024 43.80
2000 6 46.2 80 BSSK 20 ... 36 85 30 024 43.80
2500 5 57.7 - - - -
2500 6 57.7 - - - -
Nominal Operating voltage Transformer HV HRC fuse (reference dimension e = 537 mm)
operating
max. min. Rated power Relative Nominal Rated current Operating Diameter Order No. make
voltage
impedance current voltage (outside) SIBA
voltage
[kV] [kV] [kV] SN [kVA] uk [%] I1 [A] Ifuse [A] Ufuse [kV] d [mm]
50 4 1.1 - - - -
75 4 1.7 6.3 20 ... 36 53 30 008 13.6.3
100 4 2.2 6.3 20 ... 36 53 30 008 13.6.3
125 4 2.8 10 20 ... 36 53 30 008 13.10
160 4 3.6 10 20 ... 36 53 30 008 13.10
200 4 4.5 16 20 ... 36 53 30 008 13.16
250 4 5.6 16 20 ... 36 53 30 008 13.16
315 4 7.0 20 20 ... 36 53 30 008 13.20
400 4 9.0 20 20 ... 36 53 30 008 13.20
500 4 11.2 25 20 ... 36 53 30 008 13.25
630 4 14.1 31.5 20 ... 36 67 30 016 13.31.5
25.8 36 20 800 5 17.9 40 20 ... 36 67 30 016 13.40
800 6 17.9 - - - -
1000 5 22.4 40 20 ... 36 67 30 016 13.40
1000 6 22.4 40 20 ... 36 67 30 016 13.40
1250 5 28.0 50 20 ... 36 85 30 024 13.50
1250 6 28.0 50 20 ... 36 85 30 024 13.50
1600 5 35.8 63 BSSK 20 ... 36 85 30 024 43.63
1600 6 35.8 63 BSSK 20 ... 36 85 30 024 43.63
2000 5 44.8 80 BSSK 20 ... 36 85 30 024 43.80
2000 6 44.8 80 BSSK 20 ... 36 85 30 024 43.80
2500 5 55.9 - - - -
2500 6 55.9 - - - -
50 4 1.0 - - - -
75 4 1.6 - - - -
100 4 2.1 6.3 20 ... 36 53 30 008 13.6.3
125 4 2.6 - - - -
160 4 3.3 10 20 ... 36 53 30 008 13.10
200 4 4.2 10 20 ... 36 53 30 008 13.10
250 4 5.2 16 20 ... 36 53 30 008 13.16
315 4 6.6 16 20 ... 36 53 30 008 13.16
400 4 8.4 20 20 ... 36 53 30 008 13.20
500 4 10.5 20 20 ... 36 53 30 008 13.20
630 4 13.2 25 20 ... 36 53 30 008 13.25
27.6 36 20 800 5 16.7 31.5 20 ... 36 67 30 016 13.31.5
800 6 16.7 31.5 20 ... 36 67 30 016 13.31.5
1000 5 20.9 40 20 ... 36 67 30 016 13.40
1000 6 20.9 40 20 ... 36 67 30 016 13.40
1250 5 26.1 40 20 ... 36 67 30 016 13.40
1250 6 26.1 40 20 ... 36 67 30 016 13.40
1600 5 33.5 63 BSSK 20 ... 36 85 30 024 43.63
1600 6 33.5 63 BSSK 20 ... 36 85 30 024 43.63
2000 5 41.8 80 BSSK 20 ... 36 85 30 024 43.80
2000 6 41.8 80 BSSK 20 ... 36 85 30 024 43.80
2500 5 52.3 80 BSSK 20 ... 36 85 30 024 43.80
2500 6 52.3 80 BSSK 20 ... 36 85 30 024 43.80
Nominal Operating voltage Transformer HV HRC fuse (reference dimension e = 537 mm)
operating
max. min. Rated power Relative Nominal Rated current Operating Diameter Order No. make
voltage
impedance current voltage (outside) SIBA
voltage
[kV] [kV] [kV] SN [kVA] uk [%] I1 [A] Ifuse [A] Ufuse [kV] d [mm]
50 4 1.0 - - - -
75 4 1.4 - - - -
100 4 1.9 6.3 20 ... 36 53 30 008 13.6.3
125 4 2.4 6.3 20 ... 36 53 30 008 13.6.3
160 4 3.1 10 20 ... 36 53 30 008 13.10
200 4 3.8 10 20 ... 36 53 30 008 13.10
250 4 4.8 16 20 ... 36 53 30 008 13.16
315 4 6.1 16 20 ... 36 53 30 008 13.16
400 4 7.7 20 20 ... 36 53 30 008 13.20
500 4 9.6 20 20 ... 36 53 30 008 13.20
630 4 12.1 25 20 ... 36 53 30 008 13.25
30 36 20 800 5 15.4 31.5 20 ... 36 67 30 016 13.31.5
800 6 15.4 31.5 20 ... 36 67 30 016 13.31.5
1000 5 19.2 31.5 20 ... 36 67 30 016 13.31.5
1000 6 19.2 31.5 20 ... 36 67 30 016 13.31.5
1250 5 24.1 40 20 ... 36 67 30 016 13.40
1250 6 24.1 40 20 ... 36 67 30 016 13.40
1600 5 30.8 50 20 ... 36 85 30 024 13.50
1600 6 30.8 50 20 ... 36 85 30 024 13.50
2000 5 38.5 80 BSSK 20 ... 36 85 30 024 43.80
2000 6 38.5 - - - -
2500 5 48.1 80 BSSK 20 ... 36 85 30 024 43.80
2500 6 48.1 80 BSSK 20 ... 36 85 30 024 43.80
50 4 0.9 - - - -
75 4 1.3 - - - -
100 4 1.7 6.3 20 ... 36 53 30 008 13.6.3
125 4 2.2 6.3 20 ... 36 53 30 008 13.6.3
160 4 2.8 10 20 ... 36 53 30 008 13.10
200 4 3.5 10 20 ... 36 53 30 008 13.10
250 4 4.4 - - - -
315 4 5.5 16 20 ... 36 53 30 008 13.16
400 4 7.0 20 20 ... 36 53 30 008 13.20
500 4 8.7 20 20 ... 36 53 30 008 13.20
630 4 11.0 25 20 ... 36 53 30 008 13.25
33 36 20 800 5 14.0 25 20 ... 36 53 30 008 13.25
800 6 14.0 25 20 ... 36 53 30 008 13.25
1000 5 17.5 31.5 20 ... 36 67 30 016 13.31.5
1000 6 17.5 31.5 20 ... 36 67 30 016 13.31.5
1250 5 21.9 40 20 ... 36 67 30 016 13.40
1250 6 21.9 40 20 ... 36 67 30 016 13.40
1600 5 28.0 50 20 ... 36 85 30 024 13.50
1600 6 28.0 50 20 ... 36 85 30 024 13.50
2000 5 35.0 63 BSSK 20 ... 36 85 30 024 43.63
2000 6 35.0 63 BSSK 20 ... 36 85 30 024 43.63
2500 5 43.7 80 BSSK 20 ... 36 85 30 024 43.80
2500 6 43.7 80 BSSK 20 ... 36 85 30 024 43.80
Nominal Operating voltage Transformer HV HRC fuse (reference dimension e = 537 mm)
operating
max. min. Rated power Relative Nominal Rated current Operating Diameter Order No. make
voltage
impedance current voltage (outside) SIBA
voltage
[kV] [kV] [kV] SN [kVA] uk [%] I1 [A] Ifuse [A] Ufuse [kV] d [mm]
50 4 0.8 - - - -
75 4 1.3 - - - -
100 4 1.7 6.3 20 ... 36 53 30 008 13.6.3
125 4 2.1 6.3 20 ... 36 53 30 008 13.6.3
160 4 2.7 10 20 ... 36 53 30 008 13.10
200 4 3.3 10 20 ... 36 53 30 008 13.10
250 4 4.2 - - - -
315 4 5.3 16 20 ... 36 53 30 008 13.16
400 4 6.7 16 20 ... 36 53 30 008 13.16
500 4 8.4 20 20 ... 36 53 30 008 13.20
630 4 10.5 20 20 ... 36 53 30 008 13.20
34.5 36 20 800 5 13.4 25 20 ... 36 53 30 008 13.25
800 6 13.4 25 20 ... 36 53 30 008 13.25
1000 5 16.7 31.5 20 ... 36 67 30 016 13.31.5
1000 6 16.7 31.5 20 ... 36 67 30 016 13.31.5
1250 5 20.9 40 20 ... 36 67 30 016 13.40
1250 6 20.9 40 20 ... 36 67 30 016 13.40
1600 5 26.8 50 20 ... 36 85 30 024 13.50
1600 6 26.8 50 20 ... 36 85 30 024 13.50
2000 5 33.5 63 BSSK 20 ... 36 85 30 024 43.63
2000 6 33.5 63 BSSK 20 ... 36 85 30 024 43.63
2500 5 41.8 80 BSSK 20 ... 36 85 30 024 43.80
2500 6 41.8 80 BSSK 20 ... 36 85 30 024 43.80
50 4 0.8 - - - -
75 4 1.2 - - - -
100 4 1.6 6.3 20 ... 36 53 30 008 13.6.3
125 4 2.1 6.3 20 ... 36 53 30 008 13.6.3
160 4 2.6 - - - -
200 4 3.3 10 20 ... 36 53 30 008 13.10
250 4 4.1 10 20 ... 36 53 30 008 13.10
315 4 5.2 16 20 ... 36 53 30 008 13.16
400 4 6.6 16 20 ... 36 53 30 008 13.16
500 4 8.2 20 20 ... 36 53 30 008 13.20
630 4 10.4 20 20 ... 36 53 30 008 13.20
35 36 20 800 5 13.2 25 20 ... 36 53 30 008 13.25
800 6 13.2 25 20 ... 36 53 30 008 13.25
1000 5 16.5 31.5 20 ... 36 67 30 016 13.31.5
1000 6 16.5 31.5 20 ... 36 67 30 016 13.31.5
1250 5 20.6 40 20 ... 36 67 30 016 13.40
1250 6 20.6 40 20 ... 36 67 30 016 13.40
1600 5 26.4 40 20 ... 36 67 30 016 13.40
1600 6 26.4 40 20 ... 36 67 30 016 13.40
2000 5 33.0 63 BSSK 20 ... 36 85 30 024 43.63
2000 6 33.0 63 BSSK 20 ... 36 85 30 024 43.63
2500 5 41.2 80 BSSK 20 ... 36 85 30 024 43.80
2500 6 41.2 80 BSSK 20 ... 36 85 30 024 43.80
[kV] [kV] [kV] SN [kVA] uk [%] I1 [A] Ifuse [A] Ufuse [kV] d [mm]
50 4 0.8 - - - -
75 4 1.3 - - - -
100 4 1.7 6.3 40.5 53 30 340 13.6.3
125 4 2.1 6.3 40.5 53 30 340 13.6.3
160 4 2.7 10 40.5 53 30 340 13.10
200 4 3.3 10 40.5 53 30 340 13.10
250 4 4.2 10 40.5 53 30 340 13.10
315 4 5.3 16 40.5 53 30 340 13.16
400 4 6.7 16 40.5 53 30 340 13.16
500 4 8.4 20 40.5 53 30 340 13.20
630 4 10.5 25 40.5 53 30 341 13.25
34.5 38 20 800 5 13.4 25 40.5 53 30 341 13.25
800 6 13.4 25 40.5 53 30 341 13.25
1000 5 16.7 31.5 40.5 67 30 341 13.31.5
1000 6 16.7 31.5 40.5 67 30 341 13.31.5
1250 5 20.9 40 40.5 67 30 341 13.40
1250 6 20.9 40 40.5 67 30 341 13.40
1600 5 26.8 50 40.5 85 30 342 13.50
1600 6 26.8 50 40.5 85 30 342 13.50
2000 5 33.5 80 BS 40.5 85 30 342 43.80
2000 6 33.5 80 BS 40.5 85 30 342 43.80
2500 5 41.8 80 BS 40.5 85 30 342 43.80
2500 6 41.8 80 BS 40.5 85 30 342 43.80
50 4 0.8 - - - -
75 4 1.2 - - - -
100 4 1.6 6.3 40.5 53 30 340 13.6.3
125 4 2.1 6.3 40.5 53 30 340 13.6.3
160 4 2.6 - - - -
200 4 3.3 10 40.5 53 30 340 13.10
250 4 4.1 10 40.5 53 30 340 13.10
315 4 5.2 16 40.5 53 30 340 13.16
400 4 6.6 16 40.5 53 30 340 13.16
500 4 8.2 20 40.5 53 30 340 13.20
630 4 10.4 25 40.5 53 30 341 13.25
35 38 20 800 5 13.2 25 40.5 53 30 341 13.25
800 6 13.2 25 40.5 53 30 341 13.25
1000 5 16.5 31.5 40.5 67 30 341 13.31.5
1000 6 16.5 31.5 40.5 67 30 341 13.31.5
1250 5 20.6 40 40.5 67 30 341 13.40
1250 6 20.6 40 40.5 67 30 341 13.40
1600 5 26.4 40 40.5 67 30 341 13.40
1600 6 26.4 40 40.5 67 30 341 13.40
2000 5 33.0 50 40.5 85 30 342 13.50
2000 6 33.0 50 40.5 85 30 342 13.50
2500 5 41.2 80 BS 40.5 85 30 342 43.80
2500 6 41.2 80 BS 40.5 85 30 342 43.80
[kV] [kV] [kV] SN [kVA] uk [%] I1 [A] Ifuse [A] Ufuse [kV] d [mm]
24 36 20 50 4 1.2 - - - -
75 4 1.8 - - - -
100 4 2.4 6.3 20 ... 36 55 S1T5006.08
125 4 3.0 6.3 20 ... 36 55 S1T5006.08
160 4 3.8 10 20 ... 36 55 S1T5010.08
200 4 4.8 10 20 ... 36 55 S1T5010.08
250 4 6.0 16 20 ... 36 55 S1T5016.08
315 4 7.6 16 20 ... 36 55 S1T5016.08
400 4 9.6 20 20 ... 36 55 S1T5020.08
500 4 12.0 25 20 ... 36 55 S1T5025.08
630 4 15.2 31.5 20 ... 36 55 S1T5030.08
800 5 19.2 40 20 ... 36 61 S2T5040.08
800 6 19.2 - - - -
1000 5 24.1 40 20 ... 36 61 S2T5040.08
1000 6 24.1 40 20 ... 36 61 S2T5040.08
1250 5 30.1 50 20 ... 36 61 S2T5050.08
1250 6 30.1 50 20 ... 36 61 S2T5050.08
1600 5 38.5 63 20 ... 36 78 S3T5063.08
1600 6 38.5 63 20 ... 36 78 S3T5063.08
2000 5 48.1 - - - -
2000 6 48.1 - - - -
2500 5 60.1 - - - -
2500 6 60.1 - - - -
25 36 20 50 4 1.2 - - - -
75 4 1.7 - - - -
100 4 2.3 6.3 20 ... 36 55 S1T5006.08
125 4 2.9 6.3 20 ... 36 55 S1T5006.08
160 4 3.7 10 20 ... 36 55 S1T5010.08
200 4 4.6 10 20 ... 36 55 S1T5010.08
250 4 5.8 16 20 ... 36 55 S1T5016.08
315 4 7.3 16 20 ... 36 55 S1T5016.08
400 4 9.2 20 20 ... 36 55 S1T5020.08
500 4 11.5 20 20 ... 36 55 S1T5020.08
630 4 14.5 31.5 20 ... 36 55 S1T5030.08
800 5 18.5 40 20 ... 36 61 S2T5040.08
800 6 18.5 - - - -
1000 5 23.1 40 20 ... 36 61 S2T5040.08
1000 6 23.1 40 20 ... 36 61 S2T5040.08
1250 5 28.9 50 20 ... 36 61 S2T5050.08
1250 6 28.9 50 20 ... 36 61 S2T5050.08
1600 5 37.0 50 20 ... 36 61 S2T5050.08
1600 6 37.0 50 20 ... 36 61 S2T5050.08
2000 5 46.2 - - - -
2000 6 46.2 - - - -
2500 5 57.7 80 20 ... 36 78 S3T5080.08
2500 6 57.7 - - - -
Nominal Operating voltage Transformer HV HRC fuse (reference dimension e = 537 mm)
operating
max. Min. Rated power Relative Nominal Rated current Operating Diameter Order No. make
voltage
impedance current voltage (outside) Interteknik
voltage
[kV] [kV] [kV] SN [kVA] uk [%] I1 [A] Ifuse [A] Ufuse [kV] d [mm]
25.8 36 20 50 4 1.1 - - - -
75 4 1.7 - - - -
100 4 2.2 6.3 20 ... 36 55 S1T5006.08
125 4 2.8 6.3 20 ... 36 55 S1T5006.08
160 4 3.6 10 20 ... 36 55 S1T5010.08
200 4 4.5 10 20 ... 36 55 S1T5010.08
250 4 5.6 16 20 ... 36 55 S1T5016.08
315 4 7.0 16 20 ... 36 55 S1T5016.08
400 4 9.0 20 20 ... 36 55 S1T5020.08
500 4 11.2 20 20 ... 36 55 S1T5020.08
630 4 14.1 31.5 20 ... 36 55 S1T5030.08
800 5 17.9 40 20 ... 36 61 S2T5040.08
800 6 17.9 - - - -
1000 5 22.4 40 20 ... 36 61 S2T5040.08
1000 6 22.4 40 20 ... 36 61 S2T5040.08
1250 5 28.0 50 20 ... 36 61 S2T5050.08
1250 6 28.0 - - - -
1600 5 35.8 - - - -
1600 6 35.8 - - - -
2000 5 44.8 - - - -
2000 6 44.8 - - - -
2500 5 55.9 - - - -
2500 6 55.9 - - - -
27.6 36 20 50 4 1.0 - - - -
75 4 1.6 - - - -
100 4 2.1 6.3 20 ... 36 55 S1T5006.08
125 4 2.6 6.3 20 ... 36 55 S1T5006.08
160 4 3.3 - - - -
200 4 4.2 10 20 ... 36 55 S1T5010.08
250 4 5.2 10 20 ... 36 55 S1T5010.08
315 4 6.6 16 20 ... 36 55 S1T5016.08
400 4 8.4 20 20 ... 36 55 S1T5020.08
500 4 10.5 20 20 ... 36 55 S1T5020.08
630 4 13.2 25 20 ... 36 55 S1T5025.08
800 5 16.7 31.5 20 ... 36 55 S1T5030.08
800 6 16.7 31.5 20 ... 36 55 S1T5030.08
1000 5 20.9 31.5 20 ... 36 55 S1T5030.08
1000 6 20.9 31.5 20 ... 36 55 S1T5030.08
1250 5 26.1 - - - -
1250 6 26.1 - - - -
1600 5 33.5 - - - -
1600 6 33.5 - - - -
2000 5 41.8 63 20 ... 36 78 S3T5063.08
2000 6 41.8 63 20 ... 36 78 S3T5063.08
2500 5 52.3 - - - -
2500 6 52.3 - - - -
Nominal Operating voltage Transformer HV HRC fuse (reference dimension e = 537 mm)
operating
max. Min. Rated power Relative Nominal Rated current Operating Diameter Order No. make
voltage
impedance current voltage (outside) Interteknik
voltage
[kV] [kV] [kV] SN [kVA] uk [%] I1 [A] Ifuse [A] Ufuse [kV] d [mm]
30 36 20 50 4 1.0 - - - -
75 4 1.4 - - - -
100 4 1.9 6.3 20 ... 36 55 S1T5006.08
125 4 2.4 6.3 20 ... 36 55 S1T5006.08
160 4 3.1 6.3 20 ... 36 55 S1T5006.08
200 4 3.8 10 20 ... 36 55 S1T5010.08
250 4 4.8 10 20 ... 36 55 S1T5010.08
315 4 6.1 16 20 ... 36 55 S1T5016.08
400 4 7.7 16 20 ... 36 55 S1T5016.08
500 4 9.6 20 20 ... 36 55 S1T5020.08
630 4 12.1 31.5 20 ... 36 55 S1T5030.08
800 5 15.4 31.5 20 ... 36 55 S1T5030.08
800 6 15.4 - - - -
1000 5 19.2 31.5 20 ... 36 55 S1T5030.08
1000 6 19.2 31.5 20 ... 36 55 S1T5030.08
1250 5 24.1 40 20 ... 36 61 S2T5040.08
1250 6 24.1 40 20 ... 36 61 S2T5040.08
1600 5 30.8 50 20 ... 36 61 S2T5050.08
1600 6 30.8 50 20 ... 36 61 S2T5050.08
2000 5 38.5 - - - -
2000 6 38.5 - - - -
2500 5 48.1 - - - -
2500 6 48.1 - - - -
33 36 20 50 4 0.9 - - - -
75 4 1.3 - - - -
100 4 1.7 - - - -
125 4 2.2 6.3 20 ... 36 55 S1T5006.08
160 4 2.8 6.3 20 ... 36 55 S1T5006.08
200 4 3.5 10 20 ... 36 55 S1T5010.08
250 4 4.4 10 20 ... 36 55 S1T5010.08
315 4 5.5 10 20 ... 36 55 S1T5010.08
400 4 7.0 16 20 ... 36 55 S1T5016.08
500 4 8.7 20 20 ... 36 55 S1T5020.08
630 4 11.0 20 20 ... 36 55 S1T5020.08
800 5 14.0 25 20 ... 36 55 S1T5025.08
800 6 14.0 25 20 ... 36 55 S1T5025.08
1000 5 17.5 31.5 20 ... 36 55 S1T5030.08
1000 6 17.5 31.5 20 ... 36 55 S1T5030.08
1250 5 21.9 40 20 ... 36 61 S2T5040.08
1250 6 21.9 40 20 ... 36 61 S2T5040.08
1600 5 28.0 50 20 ... 36 61 S2T5050.08
1600 6 28.0 - - - -
2000 5 35.0 - - - -
2000 6 35.0 - - - -
2500 5 43.7 - - - -
2500 6 43.7 - - - -
Nominal Operating voltage Transformer HV HRC fuse (reference dimension e = 537 mm)
operating
max. Min. Rated power Relative Nominal Rated current Operating Diameter Order No. make
voltage
impedance current voltage (outside) Interteknik
voltage
[kV] [kV] [kV] SN [kVA] uk [%] I1 [A] Ifuse [A] Ufuse [kV] d [mm]
34.5 36 20 50 4 0.8 - - - -
75 4 1.3 - - - -
100 4 1.7 - - - -
125 4 2.1 6.3 20 ... 36 55 S1T5006.08
160 4 2.7 6.3 20 ... 36 55 S1T5006.08
200 4 3.3 - - - -
250 4 4.2 10 20 ... 36 55 S1T5010.08
315 4 5.3 10 20 ... 36 55 S1T5010.08
400 4 6.7 16 20 ... 36 55 S1T5016.08
500 4 8.4 20 20 ... 36 55 S1T5020.08
630 4 10.5 20 20 ... 36 55 S1T5020.08
800 5 13.4 25 20 ... 36 55 S1T5025.08
800 6 13.4 25 20 ... 36 55 S1T5025.08
1000 5 16.7 31.5 20 ... 36 55 S1T5030.08
1000 6 16.7 31.5 20 ... 36 55 S1T5030.08
1250 5 20.9 31.5 20 ... 36 55 S1T5030.08
1250 6 20.9 31.5 20 ... 36 55 S1T5030.08
1600 5 26.8 50 20 ... 36 61 S2T5050.08
1600 6 26.8 - - - -
2000 5 33.5 63 20 ... 36 78 S3T5063.08
2000 6 33.5 - - - -
2500 5 41.8 63 20 ... 36 78 S3T5063.08
2500 6 41.8 63 20 ... 36 78 S3T5063.08
35 36 20 50 4 0.8 - - - -
75 4 1.2 - - - -
100 4 1.6 - - - -
125 4 2.1 6.3 20 ... 36 55 S1T5006.08
160 4 2.6 6.3 20 ... 36 55 S1T5006.08
200 4 3.3 - - - -
250 4 4.1 10 20 ... 36 55 S1T5010.08
315 4 5.2 10 20 ... 36 55 S1T5010.08
400 4 6.6 16 20 ... 36 55 S1T5016.08
500 4 8.2 20 20 ... 36 55 S1T5020.08
630 4 10.4 20 20 ... 36 55 S1T5020.08
800 5 13.2 25 20 ... 36 55 S1T5025.08
800 6 13.2 25 20 ... 36 55 S1T5025.08
1000 5 16.5 25 20 ... 36 55 S1T5025.08
1000 6 16.5 25 20 ... 36 55 S1T5025.08
1250 5 20.6 31.5 20 ... 36 55 S1T5030.08
1250 6 20.6 31.5 20 ... 36 55 S1T5030.08
1600 5 26.4 50 20 ... 36 61 S2T5050.08
1600 6 26.4 - - - -
2000 5 33.0 63 20 ... 36 78 S3T5063.08
2000 6 33.0 - - - -
2500 5 41.2 63 20 ... 36 78 S3T5063.08
2500 6 41.2 63 20 ... 36 78 S3T5063.08
Rating plate on the front (example) Rating plate inside the operating mechanism
box (example)
9 Switchgear maintenance
Maintenance 8DJH 36 switchgear is maintenance-free. Inspection/testing of the secondary equipment such
as the capacitive voltage detecting system is done within the scope of national standards or
customer-specific regulations.
Checking the dew point The dew point needs no checking throughout the entire service life.
Checking the gas quality The gas quality needs no checking throughout the entire service life.
Replacement of Due to the fact that all parts of this switchgear have been optimized to last the normal service
components life, it is not possible to recommend particular spare parts.
Information required for spare part orders of single components and devices:
• Type and serial number of the switchgear (see rating plates)
• Description/identification of the device or part on the basis of sketch/photo or a circuit
diagram
10 End of life
SF6 gas
NOTE
The equipment contains the fluorized greenhouse gas SF6 registrated by the Kyoto Protocol
with a global warming potential (GWP) of 22 200. SF6 has to be reclaimed and must not be
released into the atmosphere.
➭ For use and handling of SF6, IEC 62271-4:High-voltage switchgear and controlgear - Part 4:
Use and handling of sulphur hexafluoride (SF6) has to be observed.
Before recycling the materials, evacuate the SF6 gas professionally and prepare it for further
use.
The switchgear can be recycled in ecological manner in compliance with existing legislation.
Auxiliary devices such as short-circuit indicators have to be recycled as electronic scrap.
Any existing batteries have to be recycled professionally.
As delivered by Siemens, the switchgear does not contain hazardous materials as per the
Hazardous Material Regulations applicable in the Federal Republic of Germany. For operation
in other countries, the locally applicable laws and regulations must be observed.
For further information, please contact the regional Siemens representative.
Installation
11 Preparing installation
11.1 Packing
The transport units can be packed as follows:
• On pallets, covered with PE protective foil
• In a seaworthy crate (switchgear is sealed with desiccant bags in PE foil)
• Other packings in special cases (e.g. latticed crate, cardboard cover for airfreight)
ATTENTION
Packing and consumable materials of the switchgear must be disposed of in an
environmentally compatible way or recycled.
➭ Observe local regulations for disposal and environmental protection.
Transport unit Transport units consist of individual panels or panel blocks with maximum three functions,
and accessories.
Checking for ➭ Check whether the delivery is complete and correct using the delivery notes and packing
completeness lists.
➭ Compare the serial number of the switchgear on the delivery note with that on the packing
and the rating plate.
➭ Check whether the accessories included in the switchgear subframe are complete.
Transport damages ➭ Temporarily open the packing in a weatherproof place to detect hidden damages. Do not
remove the PE foil until reaching the final mounting position in order to keep the switchgear
as clean as possible.
➭ Check the switchgear for transport damages.
➭ Check the gas density (see page 138, "Final tests after installation", Checking the "Ready-for-
service indicator“).
➭ Refit the packing as far as possible and useful.
➭ Determine and document detected defects and transport damages immediately, e.g. on
freight documents.
➭ As far as possible, document larger defects and transport damages photographically.
➭ Repair or have the transport damages repaired.
DANGER
Risk of injury and damage to the storage place and the stored goods if the storage space is
overloaded.
➭ Observe the load-bearing capacity of the floor.
➭ Do not stack the transport units.
➭ Do not overload lighter components by stacking.
ATTENTION
Fire risk. The transport unit is packed in flammable materials.
➭ No smoking.
➭ Keep fire extinguishers in a weatherproof place.
➭ Mark the location of the fire extinguisher.
ATTENTION
If the supplied desiccant bags are not stored in the undamaged original packings, the desiccant
bags lose their effectiveness.
➭ Do not damage or remove packing of desiccant bags.
➭ Do not unpack desiccant bags before use.
Storage in closed rooms Store the switchgear in a closed room. The storage room must have the following
characteristics:
• Floor with adequate load-bearing capacity (weights as per delivery note)
• Even floor for stable storage
• Well-ventilated and free of dust
• Dry and protected against humidity and vermin (e.g. insects, mice, rats)
• Check humidity in the packings every 4 weeks (condensation)
• To protect them against corrosion and loss, do not unpack small parts.
Outdoor storage of If the switchgear or parts thereof are delivered in seaworthy crates, these can be stored up to
switchgear packed in 6 months in other rooms or outdoors. The storage place must have the following characteristics:
seaworthy crates • Floor with adequate load-bearing capacity (weights as per delivery note)
• Protected against humidity (rain water, flooding, melting water from snow and ice),
pollution, vermin (rats, mice, termites, etc.) and unauthorized access
• Place all crates on planks and square timber for protection against floor humidity.
• After 6 months of storage, have the desiccant agent regenerated professionally. To do this,
ask for expert personnel via your regional Siemens representative.
ATTENTION
Non-observance of the following instructions can endanger people or damage the transport
units while unloading.
➭ Make sure that nobody is standing in the swinging area of lifted switchgear.
➭ Attach ropes far enough on the hoisting tackle so that they cannot exert any forces on the
panel walls under load.
➭ Observe the dimensions and weights of the transport unit (delivery note).
➭ Observe even weight distribution and the high center of gravity of the switchgear.
➭ Ensure that the lifting tools and transport gear used meet the requirements as regards
construction and load-bearing capacity.
➭ Do not climb onto the roof of the panels.
➭ If the low-voltage compartment is removed, do not step on the mounting plates of the
low-voltage compartment.
➭ Observe the instructions on the packing.
➭ Unload the transport units in packed condition and leave packed for as long as possible.
➭ Do not damage the PE protective foil.
➭ Attach ropes far enough on the hoisting tackle so that they cannot exert any forces on the
switchpanel walls under load.
➭ Sling the ropes around the ends of the wooden pallets.
➭ Move the switchgear on their wooden pallets as far as possible.
➭ Unload the transport units and set them down as close to the switchgear building as
possible in order to avoid unnecessary ways.
➭ Move the transport units into the building, if possible on their wooden pallets. Only remove
packing where absolutely necessary in order to keep the switchgear as clean as possible.
➭ Remove foil only in the building, right before assembling the transport units, and
temporarily to check for transport damages.
➭ Set the transport units down in the correct sequence directly in front of the place of
installation (leave a clearance for installation).
Unloading and transport ➭ Transport the switchgear by means of a crane or a fork-lift truck.
in original packing
Removing the The transport units are screwed on the wooden pallets with transport angles or directly in the
wooden pallets switchgear subframe.
Fig. 41: Transport unit fixed on wooden pallet with transport angle (view from the left)
NOTE
In panels with lateral cable connection, the lower cable brackets are bolted to the transport
angle.
➭ In panels with lateral cable connection, do not remove the transport angle on the left side.
If the switchgear cannot be lifted directly from the wooden pallet onto its mounting position,
please proceed as follows:
➭ Lower the transport units by means of the lateral transport angles onto roller pads
(reinforced rollers) or tubes.
➭ Lift the switchgear at the side edges with roller crowbars and slowly lower it onto the
mounting position.
➭ Remove transport angles.
Fig. 42: Points for fixing bolts (view from the left)
Switchgear transport with The transport eyes are pre-assembled at the factory. Depending on the panel type, the panels
transport eyes must be transported in different ways.
➭ Lift the panels exclusively with crane chains.
Panel type • Ring-main panel Metering panel Circuit-breaker panel with voltage transformers
• Cable panel at the busbar (as individual panel or in the
• Circuit-breaker panel panel group)
• Transformer panel
Transport Use the front holes ① of the Use the rear holes ② of the ➭ Hang in the crane chains, and lift.
procedure transport eyes. transport eyes. Always use all 4 openings of the transport
➭ Hang in the crane chains, ➭ Hang in the crane chains, eyes ③ for craning.
and lift. and lift.
Example
ATTENTION
Danger due to swinging switchgear. The center of gravity is not always located under the fixing
point.
➭ Lift the switchgear slowly..
➭ Keep the safety distances.
➭ Do not transport more than a maximum width of 2.00 m and a maximum height of 2.30 m
in a block.
➭ Observe the adhesive label with transport information provided on the switchgear.
- The angle between the crane chains at the lifting facility must be less than 90°.
- The distance between the transport eyes and the lifting facility must be at least half the
switchgear width.
① Wooden pallet
② Bolted joint between
transport unit and pallet
(outside the enclosure, front
and rear)
④ Clearance for fork-lift trucks
⑤ Cable compartment cover
⑥ Ready-for-service indicator
⑦ Center of gravity
➭ Lift or lower just slowly, as the switchgear will swing into the center of gravity when it is
lifted.
➭ While lifting the switchgear, observe loose parts such as cable-type transformers or
connecting cables.
If the pointer is in the green area, the gas density is in order. If the pointer is in the red area:
➭ Check the auxiliary switch of the ready-for-service indicator.
Checking the auxiliary During transport, the auxiliary switch of the ready-for-service indicator can latch tight in the
switch red area due to extreme vibrations.
➭ Remove the front plate of the switchgear. Push the roller lever of the auxiliary switch
carefully towards the switch.
① Roller lever
② Auxiliary switch
③ Sector disc
Fig. 44: Roller lever and sector disc of the ready- Fig. 45: Pointer position after operation of the
for-service indicator roller lever at the auxiliary switch
✔ The sector disc must return automatically so that the pointer of the ready-for-service
indicator is in the green area again. If not, please stop the installation and contact the
regional Siemens representative.
These measures basically enable proper operation of the switchgear itself. The planner or
operator of the switchgear must decide whether additional measures are required depending
on the electromagnetic environment where the switchgear is installed. Such measures must
be implemented by the installation company in charge.
In an environment with heavy electromagnetic interference it may be necessary to use
shielded cables and wires for the external connections in order to avoid interferences in the
low-voltage compartment and thus, undesired influences on the electronic protection and
control or other automation devices.
Cable shields must be electrically bonded to be able to carry high frequencies, and contacted
concentrically at the cable ends.
The shields of cables and wires are connected and earthed in the low-voltage compartment.
Connect the shields to earth potential - with high electrical conductivity and all around as far
as possible. Protect the contact surfaces from corrosion in case of humidity (regular
condensation).
When laying cables into the switchgear assembly, separate the control, signaling and data
cables and other lines with different signal and voltage levels by laying them on separate racks
or riser cable routes.
Corresponding to the different shield designs, there is a number of methods to perform
connection. The planning department or site management determines which of the methods
will be used, taking EMC requirements into account. The preceding points should always be
taken into account.
The shield is connected to cables or wires with clamps contacting all around. If low demands
are placed on EMC, it is also possible to connect the shield directly to earth potential (combine
or twist the shield wires) or via short cable connections. Use cable lugs or wire-end ferrules at
the connecting points.
Always keep the connecting leads of the shields as short as possible (< 10 cm).
If shields are used as protective earth conductors at the same time, the connected plastic-
insulated lead must be marked green/yellow over its entire length. Non-insulated connections
are inadmissible.
12 Switchgear installation
Cleaning agents
DANGER
For protection of personnel and environment:
➭ Read the instructions for use of cleaning agents carefully.
➭ Observe the warnings of the cleaning agents.
Mounting paste
Use only the supplied mounting paste for all installation work.
ATTENTION
Please observe the following for room planning and switchgear installation:
➭ The dimensions of the floor openings must be according to the dimension drawing in the
switchgear documentation.
➭ The height of the cable basement must at least correspond to the cable bending radius.
➭ The relief rooms must be according to the dimension drawing in the switchgear
documentation.
DANGER
Depending on the type of pressure relief, the internal arc classification according to
IEC 62271-200 is only guaranteed for a switchgear assembly comprising at least 2
interconnected panels.
➭ Install panels with rear pressure relief duct / absorber system or pressure relief to the rear/
upwards only in a switchgear assembly comprising at least 2 interconnected panels.
➭ Do only interconnect panels with the same type of pressure relief.
➭ Panels equipped with a lateral cable connection and a rear pressure relief duct can be
installed individually.
Switchgear dimensions For switchgear dimensions, see page 68, "Floor openings and fixing points" or the order
documents (dimension drawings, front views).
Pressure relief In the standard design, the pressure is relieved downwards. For further information, see
page 73, "Possibilities for pressure relief".
Room dimensions The room dimensions depend on the type of pressure relief (see page 73, "Possibilities for
pressure relief"). The required room height depends on the low-voltage compartments that
may have to be mounted.
For the internal arc classification according to IEC/EN 62271-200 / VDE 0671-200, the room
height of accessible switchgear rooms must be 2000 mm as a minimum.
Weights For data, see page 41, "Switchgear versions - Dimensions and weights".
Switchgear fixing • For floor openings and fixing points of the switchgear, see page 68, "Floor openings and
fixing points".
• Foundations:
- Steel girder construction
- Steel-reinforced concrete.
Fixing options ➭ The switchgear must be fixed to the foundation so as to guarantee sufficient pressure
resistance (bolts M8 as a minimum, in metering panel: bolts M10).
Possibilities for fastening the switchgear to the foundation:
- Bolting onto foundation rails.
- Fastening the switchgear onto the concrete using dowels size 10 mm if there are no
foundation rails available.
➭ The base pieces of the panel frames contain cutouts for fastening the switchgear (see
dimension drawing).
Supplied The HV HRC fuses supplied with the switchgear are fixed on top of the switchgear with two
HV HRC fuses tensioning straps. The HV HRC fuses and the tensioning straps must be removed from the
switchgear before start of installation.
Preparations for further To simplify installation of the panel or the high-voltage cables, the cable compartment cover
installation and the cross member can be removed.
➭ Remove the cable compartment cover (see page 136, "Removing and hanging in the cable
compartment cover").
ATTENTION
If the cross member has been removed, the panel must not be moved anymore, as there is no
brace to guarantee stability during the movement.
➭ Bring the panel to the required position.
➭ When the cross member is removed, the panel must not be moved anymore.
➭ If necessary, remove the cross member (see page 137, "Removing and mounting the cross-
member").
Pressure relief downwards (standard) Pressure relief with pressure relief duct / absorber Pressure relief to the rear/upwards
Pressure relief with pressure relief duct / absorber Pressure relief to the rear/upwards
Floor openings and fixing points for panels with deeper cable compartment covers
(e.g. double cable connections)
The floor openings depend on the selected cable connection / surge arrester.
Individual panel with pressure relief downwards Individual panel with pressure relief downwards ① Floor opening
Cable compartment cover deeper by 105 mm Cable compartment cover deeper by 250 mm ② Pressure relief duct / absorber
* Distance for panel
interconnection with metering
panel
Individual panel with pressure relief duct / absorber Individual panel with pressure relief duct /
Cable compartment cover deeper by 105 mm absorber
Cable compartment cover deeper by 250 mm
Floor openings and fixing points for panel block with deeper cable compartment
cover and pressure relief downwards (examples)
NOTE
The pressure relief directions shown are only valid for switchgear without lateral cable
connection.
Fig. 49: Switchgear installation with Fig. 50: Switchgear installation with pressure relief
pressure relief downwards downwards (top view)
Room height
Panel type Room height [mm]
Ring-main panel ≥ 2000
Transformer panel
Circuit-breaker panel
Cable panel
Metering panel
Pressure relief with rear pressure relief duct / absorber system to the rear/upwards
(option)
Installation options:
• Wall-standing arrangement
• Free-standing arrangement
Fig. 51: Switchgear installation with Fig. 52: Switchgear installation with
pressure relief duct absorber system
Fig. 53: Switchgear installation with pressure relief duct / absorber system
(top view)
Room height
Panel type Room height [mm]
Ring-main panel ≥ 2000
Transformer panel
Circuit-breaker panel
Cable panel
Metering panel ≥ 2400
ATTENTION
In case of an internal arc, a pressure load of up to 26 kPa may be applied to the switchgear
room wall used for pressure relief to the rear/upwards.
➭ The switchgear room wall used for pressure relief to the rear/upwards must withstand
pressure loads of up to 26 kPa.
Fig. 54: Switchgear installation Fig. 55: Switchgear installation with pressure relief to
with pressure relief to the rear/upwards (top view)
the rear/upwards
Room height
Panel type Room height [mm]
Ring-main panel ≥ 2000
Transformer panel
Circuit-breaker panel
Cable panel
Metering panel ≥ 2400
➭ Bolt the holder of the pressure relief duct together with the panel using Torx screws.
Wall distance ➭ Position the switchgear keeping a distance of 90/1501) mm from the wall of the switchgear
room.
Metering panels For panel groups with a metering panel, special air guides must be mounted at the end panels
(see page 78, "Special air guides for panel groups with metering panels").
① Wall of switchgear
room
② Air guides
1) For panel group with
metering panel
Fig. 58: Wall distance of the Fig. 59: Position of the air guides (example: RRT block)
switchgear
Mounting the air guides ➭ Bolt the air guide together with the panel at the top using a bolt-and-washer assembly and a
nut-and-washer assembly.
① Air guide
② Nut-and-washer assembly M8
③ Bolt-and-washer assembly
M8x20
➭ Bolt the air guide together with the panel at the bottom using 2 bolt-and-washer
assemblies.
① Air guide
② Bolt-and-washer assembly
M8x20 (2x)
➭ Fasten the second air guide to the other end panel of the switchgear in the same way.
Fig. 62: Pre-assembled air guides and covers for a panel group with
metering panel (example, view from the rear)
If metering panels are interconnected with other panels, all other panels must be installed
with a larger wall distance (150 mm). Additional air guides are supplied for this purpose,
which compensate the larger wall distance. If the adjacent panels of the metering panel are
no end panels, the air guides must be installed at the two end panels of the panel group.
The air guides are split into two parts. One part of the air guide must be re-assembled to be
used as an extension towards the wall.
➭ Remove the 5 nut-and-washer assemblies ② at the air guide extension ① .
➭ Remove the air guide extension ① and fasten it again at the rear fixing points using the nut-
and-washer assemblies.
➭ Close the unused fixing points with sealing stoppers ③ .
Fig. 63: As-delivered condition of the Fig. 64: Adjusting the wall distance with the
air guide air guide
➭ Fasten the second air guide to the other end panel of the panel group in the same way.
Space requirements for Provide sufficient space for lining up individual panels or blocks. The required wall distances
lining up are shown in the illustration and the table below (see page 65, "Installing the switchgear").
A ≥ 100 mm
B ≥ 200 mm (for lined up switchgear)
C 920 mm
(980 mm for circuit-breaker panels and
metering panels)
D 30 mm
(90 mm for panel interconnection with
metering panels)
Preconditions For lining up individual panels or blocks, the following additional measures must be taken in
advance:
Fig. 66: Spring energy store indicator: "Spring not charged" (example:
transformer feeder)
Removing the transport To interconnect the panels, the transport eyes must be removed in ring-main panels, cable
eyes for panel panels, circuit-breaker panels or transformer panels.
interconnection
➭ Undo the 3 fixing bolts ① of the transport eyes and remove the transport eyes.
In the case of a circuit-breaker panel with voltage transformers at the busbar, 2 fixing
bolts must be removed from the crane frame in order to interconnect the panels. Depending
on the accessibility and the degree to which the panel is equipped, the complete crane frame
can also be removed.
➭ To interconnect the panels: Remove 2 fixing bolts ② on each side of the clamping plate.
➭ To remove the complete crane frame ① , remove all other fixing bolts ③ .
The first transport unit is on its mounting position and the others are placed at a small
distance.
➭ Align the first transport unit laterally.
➭ Lay shims under the transport unit according to the measuring sheet of the base frame.
✔ All panels must be in vertical position and at the same level.
DANGER
High voltage! Danger!
➭ Isolate the switchgear.
➭ Secure against reclosing.
➭ Verify safe isolation from supply.
➭ Earth and short-circuit.
➭ Cover or barrier adjacent live parts.
Before interconnecting the panels, the instructions for preparing these work operations must
be executed (see page 79, "Extending existing switchgear or replacing components").
This chapter shows as an example how a panel is interconnected from the right side with a
readily assembled panel on the left side.
ATTENTION
Do not use any old components for installation.
➭ Do only use new components from the extension kit for installation.
Content of extension kit Check the content of the extension kit for the panel interconnection:
Bolt-and-washer assembly Plain washer (2x) Wiping cloth (2x) Felt strip Foam material strips with
M8x20 (12x) adhesive side (2x)
Bolt-and-washer assembly Nut-and-washer Hexagonal bolt M8 x 55 Guiding tension bolt M8 (2x) Mounting paste (1x)
M8x35 (3x) assembly M8 (5x) (2x)
Additional content of the extension kit for panels with busbar coupling:
Silicone coupling with insertable sleeve Tension spring for earthing (3x) Contact coupling (3x)
(3x)
Additional content of the extension kit for panels without busbar coupling:
Removing the cable ➭ Remove the cable compartment cover in the fixed-mounted panel and in the panel to be
compartment cover lined up, see page 136, "Removing and hanging in the cable compartment cover".
Affixing the foam ➭ Cut the foam material strips ① to size and affix them to the side wall of the left-hand panel.
material strips
➭ The length ② of the rear foam material strip depends on the two panels used for the panel
interconnection. The foam material strip must reach the lower edge of the lowest
positioned gas vessel ③ .
➭ In panels without busbar coupling, affix only the rear foam material strip.
Fig. 67: Panel with busbar coupling Fig. 68: Panel without busbar coupling
ATTENTION
Without the felt strips, the resistance of the switchgear to internal faults is not guaranteed. In
case of an internal arc, the felt strips prevent the escape of hot gases.
➭ Affix the felt strips to the side wall of the left-hand panel.
The felt strips must be affixed for a panel group with one of the following pressure relief
systems:
• Pressure relief with pressure relief duct / absorber at the rear (option)
• Pressure relief to the rear/upwards (option)
Affixing the felt strips ➭ Cut the felt strips ① to size, and affix them to the side wall of the left-hand panel.
➭ The length ② of the felt strip at the rear side of the panel depends on the length of the
previously affixed foam material strip ③ . The felt strip must connect to the foam material strip.
By removing the termination plate, the adjacent panel is used for additional pressure relief.
For further information, see page 73, "Possibilities for pressure relief".
DANGER
The termination plates must remain mounted in the end panels, as resistance to internal faults
will otherwise not be guaranteed, and persons may be injured.
➭ Check if the termination plates are mounted in the end panels.
➭ Do not remove the termination plate in end panels.
Cross member, removing The cross member must be removed before the termination plate can be removed.
➭ Remove the cross member in the fixed-mounted panel and in the panel to be lined up, see
page 137, "Removing and mounting the cross-member".
Removing the Remove the termination plate in the cable compartment of the fixed-mounted panel and of
termination plate the panel to be lined up.
➭ Undo the 8 Torx screws M5x12 at the side wall ① .
➭ Remove the termination plate ② from the cable compartment.
Fig. 70: Removing the termination plate in the fixed-mounted panel and in the panel to be
lined up
① Side wall
② Termination plate
Mounting the cross ➭ Refit the cross member in the panel to be lined up, see page 137, "Removing and mounting
member the cross-member".
NOTE
In panels with busbar coupling, continue with the installation here. For installation of panels
without busbar coupling, see page 90, "Mounting the vessel adapters on panels without
busbar coupling".
ATTENTION
Remove the protective caps used for transport from the busbar bushes. Do not damage the
busbar bushes while doing so.
➭ The protective caps are only used as transport block. Do not use them as surge-proof
caps under any circumstances.
➭ Remove the protective caps ① .
➭ Do not use any sharp or other objects as aids.
➭ If they have not been pre-assembled at the factory, equip the clamping plate in the left-
hand panel with tension springs for earthing.
➭ Insert the guiding tension bolts ① into the two openings in the clamping plate, and tighten
with nut-and-washer assemblies ② (tightening torque: 21 Nm).
➭ Clean the busbar bushes carefully inside with a lint-free wiping cloth. Use the supplied
mounting paste as cleaning agent.
ATTENTION
Mounting paste deteriorates the conductivity of the contact bolt.
➭ Do not apply mounting paste to the contact bolt.
➭ Clean the contact bolt carefully with a lint-free cloth without mounting paste.
① Busbar bushes
② Contact bolt
ATTENTION
Incorrectly inserted contact couplings can damage the switchgear.
➭ Make sure that the contact couplings are seated in the bush completely and centrally.
➭ Push the contact coupling completely into the bush. Observe that the contact coupling is
centered in the bush.
➭ Push the contact couplings into the bushes as far as they will go.
① Contact coupling
ATTENTION
The insertable sleeves are not symmetrical. If the insertable sleeves fall out of the silicone
coupling, observe the inserting direction when re-positioning them.
➭ Clean the insertable sleeves and the silicone coupling carefully with a lint-free wiping
cloth.
➭ Fit the insertable sleeves ① with the rounded side ② into the silicone coupling ③ .
ATTENTION
If the electrical contact is insufficient because the silicone coupling is dirty, the busbar will be
damaged during operation.
➭ Clean the silicone coupling carefully with a lint-free wiping cloth.
➭ The mounting paste must not applied to the blackened bead of the silicone coupling.
➭ Apply the supplied mounting paste evenly, thinly and all around to one push-on surface of
the silicone coupling.
① Blackened bead
② Push-on surface with
mounting paste
NOTE
To simplify installation:
➭ Turn the silicone couplings slightly while inserting.
Inserting the silicone ➭ Insert the silicone coupling - with the side previously coated with mounting paste - into
couplings the busbar bush as far as it will go.
➭ After inserting the silicone coupling, the tension spring for earthing must be situated
behind the blackened bead (visual check).
ATTENTION
If the electrical contact is insufficient because the silicone coupling is dirty, the busbar will be
damaged during operation.
➭ Clean the silicone coupling carefully with a lint-free wiping cloth.
➭ The mounting paste must not applied to the blackened bead of the silicone coupling.
➭ Apply the supplied mounting paste to the push-on surfaces of the silicone couplings evenly,
thinly and all around.
NOTE
In panels without busbar coupling, continue with the installation here. For installation of
panels with busbar coupling, see page 90, "Lining up the panel".
Mounting the vessel ➭ If one of the panels to be interconnected is equipped with a gas vessel, push one vessel
adapters adapter onto the guiding tension bolts.
➭ If both of the panels to be interconnected are equipped with a gas vessel, push both vessel
adapters onto the guiding tension bolts.
Mounting position of the vessel adapter: The folded edge of the vessel adapter must point
towards the gas vessel.
① Vessel adapter
Fig. 81: Pushing on the vessel Fig. 82: Pushing on the vessel
adapter for one gas vessel adapter for two gas vessels
(example)
Fig. 83: Lining up the panel with busbar Fig. 84: Lining up the panel with vessel
coupling adapters (example)
➭ Thread the guiding tension bolts ② into the clamping plate in the panel to be lined up, until
the distance ④ between the two panels is approx. 30 mm.
① Fixed-mounted panel
② Guiding tension bolt
③ Lined up panel
④ Distance approx. 30 mm
Fitting the panel ➭ Interconnect the two panels with 2 panel connecting bolts at the clamping plate, but do not
connecting bolts bolt tight (screwing direction from the left-hand to the right-hand panel).
NOTE
Please observe for the panel connecting bolts in the frame:
➭ Screw the panel connecting bolts into the setnuts provided for this purpose from the left-
hand panel into the right-hand panel.
➭ Tighten the two upper panel connecting bolts at the clamping plate ① alternatively with the
panel connecting bolt ② in the cable compartment. When bolting together, make sure that
there is a uniform distance between the panels (tightening torque: 30 Nm).
➭ Then, bolt together the two panel connecting bolts ③ at the rear in the cable compartment
(tightening torque: 30 Nm).
➭ Tighten all panel connecting bolts until both panels are joined without any gaps.
Mounting further panel ➭ Tighten all further panel connecting bolts (M8x20) in the frame (tightening torque: 30 Nm).
connecting bolts
NOTE
In the transformer panel there is no setnut provided for the bolted joint ③ .
➭ In the transformer panel, fasten the bolted joint ③ additionally with a nut-and-washer
assembly M8.
NOTE
Bolted joint ③ is only available in the ring-main panel, the transformer panel and the cable
panel.
Fastening the panel ➭ Bolt the lined up panel to the foundation, see page 65, "Installing the switchgear".
Mounting the cross ➭ Mount the cross member in the fixed-mounted panel, see page 137, "Removing and
member mounting the cross-member".
Hanging the cable ➭ Hang the cable compartment cover in on both panels, see page 136, "Removing and
compartment cover in hanging in the cable compartment cover".
✔ Repeat the previous operations until all panels have been interconnected.
ATTENTION
Do not use any old components for installation.
➭ Do only use new components from the extension kit for installation.
Content of extension kit Check the content of the extension kit for the busbar termination:
Wiping cloth (2x) Clamping cover for Clamping cap (3x) Toroidal sealing ring (3x) Busbar termination cover (1x)
dummy plugs (3x)
Cap (1x) Silicone dummy plug (3x) Mounting paste (1x) Sealing stopper (12x) Warning sign (1x)
Plain washer 8 (2x) Nut-and-washer assembly Bolt-and-washer assembly Bolt-and-washer Hexagonal bolt M8 x 55 (2x)
M8 (5x) M8x20 (12x) assembly M8x35 (3x)
Preparing installation
ATTENTION
The clamping plate may be equipped with tension springs for earthing. Before mounting the
busbar termination, the tension springs for earthing must be removed.
➭ Remove the tension springs for earthing.
➭ The silicone dummy plugs are equipped with insertable sleeves at the factory.
ATTENTION
The insertable sleeves are not symmetrical. If the insertable sleeves fall out of the silicone
dummy plug, observe the inserting direction when re-positioning them.
➭ Fit the insertable sleeves ① with the rounded side ② into the silicone dummy plug ③ .
ATTENTION
Observe extreme cleanliness.
➭ The insertable sleeve and the silicone dummy plug must be free of pollution and grease.
➭ Clean the insertable sleeve and the silicone dummy plug carefully.
① Insertable sleeve
ATTENTION
Observe extreme cleanliness.
➭ The clamping caps and the toroidal sealing rings must be free of pollution and grease.
➭ Clean the seating and the inner side of the clamping caps carefully.
Fig. 90: Cleaning the toroidal Fig. 91: Cleaning the seating and
sealing rings the inner side of the
clamping caps
ATTENTION
Damage of the silicone dummy plug during operation! If the electrical contact is insufficient or
the push-on surfaces are dirty, the silicone dummy plugs will lose their conductivity.
➭ Do not apply mounting paste to the blackened area.
➭ Grease the silicone dummy plugs uniformly with supplied mounting paste.
➭ Grease the toroidal sealing rings uniformly with supplied mounting paste.
➭ Insert the toroidal sealing ring into the annular groove of the clamping cap.
① Clamping cap
② Toroidal sealing ring
③ Silicone dummy plug
Closing the busbar ➭ Insert the dummy plug together with the toroidal sealing ring and the clamping cap into the
termination in a surge- busbar bush with a slight rotary movement, and hold it.
proof way
➭ Hang the clamping cover for dummy plugs into the clamping plate at the bottom (see black
arrow).
➭ Press the clamping cover for dummy plugs onto the clamping plate. The clamping cover for
dummy plugs fixes the dummy plug.
➭ Fasten the clamping cover for dummy plugs using a bolt-and-washer assembly M8x30 and a
nut-and-washer assembly M8 (tightening torque: 30 Nm).
① Nut-and-washer assembly M8
② Bolt-and-washer assembly M8x30
Mounting further ➭ Mount the dummy plugs and clamping covers for dummy plugs on the two other phases.
phases
Mounting the busbar ➭ Hang the busbar termination cover into the clamping plate (see black arrows).
termination cover
➭ Press the busbar termination cover onto the clamping plate at the top with light pressure.
➭ Fix the busbar termination cover using 2 bolt-and-washer assemblies M8x20 and 2 nut-and-
washer assemblies M8 (tightening torque: 30 Nm).
① Bolt-and-washer assembly
M8x20
② Busbar termination cover
③ Warning sign
④ Nut-and-washer assembly
M8
Inserting the cap ➭ Insert the cap into the opening of the side wall.
① Cap
Completing installation ➭ Depending on the position of the end panel, close the openings with sealing stoppers or
bolt-and-washer assemblies:
Non-extendable Non-extendable switchgear is connected to the substation earth through an earthing bolt.
switchgear
① Earthing point
(earthing bolt M12)
Fig. 92: Earthing point (view Fig. 93: Earthing point (view
from outside) into cable
compartment)
Extendable switchgear In extendable switchgear assemblies, earthing takes place at the earthing point of the
earthing busbar.
➭ Connect the earthing point (earthing bolt M12) of one panel to the substation earth.
① Earthing point
(earthing bolt M12)
➭ In panel blocks with up to 3 panels, it is enough to the connect the switchgear to the
substation earth only once.
➭ In panel groups comprising more than 4 panels, every fifth panel must be earthed.
① Earthing busbar
② Link
➭ Remove the cable compartment cover, see page 136, "Removing and hanging in the cable
compartment cover".
① Earthing busbar,
left-hand panel
② Link
③ Bolted joint for link,
left-hand panel
④ Bolted joint for link, r
ight-hand panel
⑤ Earthing busbar,
right-hand panel
⑥ Side wall, left-hand panel
⑦ Side wall, right-hand panel
Fig. 95: Undoing the link at the earthing Fig. 96: Interconnecting the earthing busbars
busbar with the link
➭ Undo the bolted joint (saucer-head bolt and nut-and-washer assembly) for the links ( ③ , ④
) in the left-hand and right-hand panel.
➭ Brush oxidized copper surfaces of the earthing busbars ( ① , ⑤ ).
➭ Push the link ② through the opening of the side wall.
➭ Bolt the link ② between the earthing busbars ① and ⑤ together using saucer-head bolts
and nut-and-washer assemblies ③ and ④ (tightening torque: 21 Nm).
➭ Proceed in the same way with the other joints.
✔ The units of the earthing busbar of the complete switchgear assembly are interconnected.
➭ Refit the cable brackets on all panels if they had been removed before.
➭ Refit the cable compartment cover, see page 136, "Removing and hanging in the cable
compartment cover".
Options for motor The manual operating mechanisms of 8DJH 36 switchgear can be retrofitted with motor
operating mechanism operating mechanisms for the three-position switch-disconnector.
Fig. 97: Motor block assembly of spring-operated mechanism in ring-main feeder (exemplary
illustration)
The installation instructions for retrofitting motor operating mechanisms are delivered
together with the retrofit kit.
Low-voltage ➭ After interconnecting the panels, bolt the low-voltage compartments of adjacent panels
compartment pre- together using 4 bolt-and-washer assemblies and nut-and-washer assemblies M8.
assembled at the factory
Low-voltage ➭ Place the low-voltage compartment onto the roof of the associated panel.
compartment delivered
➭ Bolt the low-voltage compartment onto the roof plate of the panel using 4 bolt-and-washer
separately
assemblies M8.
➭ Proceed in the same way with the other low-voltage compartments.
➭ Bolt the low-voltage compartments of adjacent panels together using 4 bolt-and-washer
assemblies and nut-and-washer assemblies M8 each.
Fig. 100: Bolting the low-voltage compartment Fig. 101: Bolting the low-voltage
together with the panel compartments together
➭ Lay the low-voltage cables through the cutouts in the panel roof, and establish the electrical
connection according to the circuit manual.
Fig. 105: Metering panel type cable-busbar Fig. 106: Metering panel type cable-cable
Top view into the open vessel with the bushings and the busbars
Metering panel type busbar-busbar Metering panel type busbar-cable Metering panel type cable-busbar
ATTENTION
To avoid personal damages and material damages, only instrument transformers complying
with the following standards may be used untested:
➭ Dimensions for current transformers according to DIN 42600-5 (height ≤ 390 mm)
➭ Dimensions for voltage transformers according to DIN 42600-3:
- Voltage transformer, 1-pole: width ≤ 280 mm
- Voltage transformer, 2-pole: width ≤ 380 mm
Removing the cable ➭ Remove the cable compartment covers in the metering panel, see page 136, "Removing and
compartment cover hanging in the cable compartment cover".
Removing the cross ➭ Remove the cross member in the metering panel, see page 137, "Removing and mounting
member the cross-member".
➭ Determine the positions required for the transformer supports from the instructions for
assembling the transformer supports, which are enclosed with the switchgear accessories.
➭ Re-assemble the transformer supports, if necessary.
ATTENTION
Risk of injury! The instrument transformers weigh up to 70 kg.
➭ Use an appropriate lifting tool for lifting the instrument transformers.
Order of assembly: First, fasten the current transformer and voltage transformer for phase L2
in the center of the C-rails. Then, fasten the instrument transformers for phases L1 and L3 on
the left and right at a distance of 330 ±2 mm.
Each instrument transformer is fastened at 4 points (2 times at the upper C-rail, 2 times at the
lower C-rail).
➭ For each instrument transformer, insert 2 sliding nuts with setscrew into the C-rail. Insert
the sliding nuts in upright position.
➭ Fasten each instrument transformer to the C-rails using 4 hexagonal nuts M10, strain
washers and washers (3D washers) each.
① Slide nut
② Setscrew M10 x 60
③ Hexagonal nut
M10
④ Strain washer
⑤ Plain washer (3D
washer)
ATTENTION
Insufficient electrical contact increases the contact resistance.
➭ Clean oxidized contact points.
➭ Do not damage contact surfaces.
➭ Mount the busbar without distortions and gaps.
ATTENTION
Polluted vessel bushings will cause flashovers.
➭ Clean the vessel bushing (see page 65, "Cleaning agents").
ATTENTION
Low insulation at the busbar will cause damages at the switchgear due to flashovers.
➭ Mount the control cap at the vessel bushing.
➭ Check the control cap insulation for defective spots.
Connecting the current ➭ Mount the spacers and connection bars on the current transformer (tightening
transformers torque: 40 Nm).
Metering panel type busbar-busbar Metering panel type busbar-cable (cable-busbar) Metering panel type cable-cable
① Connection bar at the top ② Connection bar at the bottom ③ Spacer* (4x)
④ Hexagonal bolt M12 (4x) ⑤ Strain washer ⑥ Connecting cable with
cable lug
* Depending on the current transformer used
➭ Clean the vessel bushing with cleaning agent and a lint-free wiping cloth.
➭ Dry the vessel bushing with a lint-free wiping cloth.
➭ Fit bolted joints with nuts M10 (tightening torque: 30 Nm).
➭ Mount the control cap with the fixing bracket onto the vessel bushing of the busbar.
➭ Verify firm seat of control cap.
ATTENTION
Risk of flashover if the minimum distances between the connecting cables of the current and
voltage transformers are too small.
➭ Cut the connecting cables between the current and voltage transformers in a suitable way,
so that the requested minimum distances to live parts are guaranteed during operation.
➭ The deflection of the connecting cable between the current and the voltage transformer
may not be more than 10 mm in every direction.
ATTENTION
Risk of flashover if the minimum distances between live parts and the flexible steel tubes for
cable routing are too small.
➭ If flexible steel tubes are used in the cable compartment for cable routing: Lay the flexible
steel tube keeping enough minimum distance to live parts.
Mounting the ➭ Undo the hexagonal bolt and strain washer at the voltage transformer.
control cap
➭ Mount the control cap together with the connecting cable onto the voltage transformer.
① Voltage transformer
② Control cap
③ Nut-and-washer
assembly M8
④ Fixing clip for control
cap
⑤ Plain washer
⑥ Fixing bracket
⑦ Threaded bolt M8
⑧ Connecting cable
⑨ Cable lug
Fig. 111: Mounting the control cap
Connecting the The deflection of the connecting cable between the current transformer and the voltage
connecting cable transformer may not be more than 10 mm in every direction.
It is permissible for the flexible connecting cable to touch parts of the same phase.
➭ Cut the connecting cable to suit the distance between the current transformer and voltage
transformer terminal.
➭ Strip the insulation of the connecting cable and press the cable lug on.
➭ Connect the connecting cable to the current transformer and voltage transformer according
to the circuit diagrams.
Possibilities of connection for the connecting cable between the voltage transformer
and the current transformer:
Metering panel type busbar-busbar Metering panel type busbar-cable Metering panel type cable-cable
(cable-busbar)
2-pole voltage Cut the connecting cable between the 2-pole voltage transformer and the current transformer
transformer to length:
① Cable lug
② Connecting cable between current
and voltage transformer
③ Control cap of voltage transformer
④ Current transformer
⑤ 2-pole voltage transformer
ATTENTION
When connecting the cable ends, please observe the following:
➭ Mount the sealing end according to the manufacturer's stipulations.
➭ If the manufacturer of the cable lugs, sealing ends or plugs has not made any stipulations,
the bolted joints must be tightened with max. 50 Nm.
Minimum distances for The following minimum distances must be adhered to for connection of high-voltage cables in
cable connections metering panels.
ATTENTION
Risk of flashover if the minimum distances between high-voltage cables and live or earthed
parts are too small.
➭ Minimum distances according to IEC 61936/VDE 0101 must be observed and checked
during installation of the high-voltage cables, and verified:
- Minimum distance at 36 kV: 320 mm
➭ If the minimum distances are too small, it must be proved by means of a dielectric test that
there is no risk of flashover.
Verified minimum distances for the cable connections in the metering panel
(dimensions given in mm)
Metering panel type busbar-cable and cable-busbar Metering panel type cable-cable
Fig. 113: Mounted high-voltage Fig. 114: Cable installation at the bottom Fig. 115: Cable installation at the top of the
cables of the current transformer current transformer
Fig. 116: Mounted high-voltage cable Fig. 117: Cable installation at the bottom of
the current transformer
ATTENTION
Risk of flashover if the minimum distances between the spherical connection bolts and live
parts are too small.
➭ Minimum distances according to IEC 61936/VDE 0101 must be observed and checked
during installation of the spherical connection bolts.
- Minimum distance at 36 kV: 320 mm
Verified minimum distances of the spherical connection bolts in the metering panel type
busbar-cable, cable-busbar and busbar-busbar:
➭ Mount the spherical connection bolts on the connection bars (tightening torque: 50 Nm).
Mounting the cross ➭ Mount the cross member in the metering panel, see page 137, "Removing and mounting
member the cross-member".
Mounting the cable ➭ Mount the cable compartment covers in the metering panel, see page 136, "Removing and
compartment covers hanging in the cable compartment cover".
The earthing connection offers different fixing options for the earthing accessories:
• with one bolt M12
• with one threaded bolt M12
• with one push-through bolt
If earthing accessories with different fixing options are used, this can make installation in the
metering panel or access to the metering panel more difficult.
Type of earthing The earthing accessories are not supplied by the factory.
accessories
DANGER
Danger, high voltage! Please observe the manufacturer information and check compatibility of
earthing accesssories.
➭ The earthing accesssories must be designed for the short-circuit currents of the respective
grid configuration.
➭ The connections of the earthing accesssories must be suitable for installation at the
switchgear.
At the air-insulated metering panel, the installation of earthing accessories was tested with
the following components:
1 Manufacturer: DEHN + SÖHNE GmbH + Co. KG, Hans Dehn-Str. 1, Postfach 1640, 92306 Neumarkt,
Germany, www.dehn.de
Type busbar-cable or
cable-busbar
(composed of two floor
plates)
Type cable-cable
(composed of three floor
plates)
➭ Fasten the floor plates additionally to the rear wall using 2 bolt-and-washer assemblies.
DANGER
High voltage! Danger!
➭ Isolate the switchgear.
➭ Secure against reclosing.
➭ Verify safe isolation from supply.
➭ Earth and short-circuit.
➭ Cover or barrier adjacent live parts.
Installing the The HV HRC fuses are delivered by the factory in the metering panel. The HV HRC fuses must
HV HRC fuses be installed before putting the metering panel into operation.
➭ Install only tested HV HRC fuses (see page 55, "Selection of HV HRC fuse-links for metering
panels").
➭ Remove the cable compartment covers in the metering panel (see page 136, "Removing and
hanging in the cable compartment cover").
➭ Install the HV HRC fuses ③ in all 3 phases into the fuse contacts ② at the top and at the
bottom between the control cap ① and the connecting bar ④ .
① Control cap
② Fuse contact
③ HV HRC fuse
④ Connection bar
➭ Refit the cable compartment covers in the metering panel (see page 136, "Removing and
hanging in the cable compartment cover").
✔ The installation of the HV HRC fuses is completed.
13.8 Removing HV HRC fuses from metering panels with fuse-protected voltage
transformers
DANGER
High voltage! Danger!
➭ Isolate the switchgear.
➭ Secure against reclosing.
➭ Verify safe isolation from supply.
➭ Earth and short-circuit.
➭ Cover or barrier adjacent live parts.
➭ Remove the cable compartment covers in the metering panel (see page 136, "Removing and
hanging in the cable compartment cover").
➭ Remove the HV HRC fuses in all 3 phases from the fuse contacts.
① Control cap
② Fuse contact
③ HV HRC fuse
④ Connection bar
➭ Refit the cable compartment covers in the metering panel (see page 136, "Removing and
hanging in the cable compartment cover").
✔ The removal of the HV HRC fuses is completed.
14 Electrical connections
In the instructions given in the following sections it is assumed that a new switchgear is being
installed which has not yet been connected to the mains, and is not live.
For extending or replacing parts of an existing switchgear, the Five Safety Rules must be
observed:
DANGER
High voltage! Danger!
➭ Isolate the switchgear.
➭ Secure against reclosing.
➭ Verify safe isolation from supply.
➭ Earth and short-circuit.
➭ Cover or barrier adjacent live parts.
ATTENTION
Surfaces of high-quality joints at the bushings can easily be damaged by incorrect handling.
➭ Observe extreme cleanliness.
➭ Avoid damages caused by the threaded bolt while pushing on.
ATTENTION
In case of spare feeders without connected cables, please observe the following:
➭ Switch the three-position switch-disconnector to "EARTHED" position and lock it.
➭ Alternatively: Mount surge-proof caps.
ATTENTION
During metal working, please ensure the following:
➭ Do not drill into the vessel.
➭ Do not leave any metal cuttings on the vessel in order to avoid rust layers.
ATTENTION
For perfect installation of the cable plugs, the following must be observed:
➭ Mount the cable plugs according to the manufacturer’s instructions.
➭ If there are no specifications by the cable plug manufacturer, please contact the regional
Siemens representative.
Fig. 123: Cable connection type B Fig. 124: Cable connection type C
Cable connection for ring-main feeder, circuit-breaker feeder and cable feeder:
① Phase L1
② Phase L2
③ Phase L3
④ Earthing connection for the
cable shield and the plug
housings
⑤ Cable bracket
⑥ Cable clamp
⑦ Cross member (removable)
⑧ Internal arc additive
Fig. 125: Cable connection type C with pressure Fig. 126: Cable connection type C with
relief downwards pressure relief to the rear
A white plastic protection ring may be factory-assembled on the outside-cone bushing type C.
This ring serves as a top for the plug, and protects the connection of the capacitive voltage
detecting system at the bushing from damages when the cable plugs are mounted.
ATTENTION
Disassembling the protection ring can cause damages at the connection of the capacitive
voltage detecting sytsem.
➭ Do not remove the protection ring.
NOTE
In certain ring-main panels, circuit-breaker panels and cable panels, an internal arc
additive must be mounted at the cable connection:
• In panels with pressure relief to the rear
• In panels with pressure relief downwards and deeper cable compartment cover
ATTENTION
If a disassembled internal arc additive is not re-assembled after cable installation, the resistance
to internal faults is not ensured, and persons may be injured in case of fault.
➭ After cable installation, re-assemble the internal arc additive.
➭ Remove the cable compartment cover, see page 136, "Removing and hanging in the cable
compartment cover".
➭ If required, remove the cross member ⑦ to swing in the cables.
➭ If an internal arc additive is pre-assembled in the panel: Undo 2 nut-and-washer
assemblies and disassemble the internal arc additive ⑧ .
➭ Pre-adjust the cable bracket ⑤ and the lower part of the cable clamps ⑥ .
➭ If available, mount the cable-type current transformers (see page 127, "Cable connection
with cable-type current transformers").
➭ Fit the plugs on the conductor ends according to the manufacturer’s instructions.
➭ Carefully apply mounting paste to the push-on surfaces (high-quality joints) in the plug sets
and the bushing cone (scope of supply of the plug set).
➭ Push the plug sets ① to ③ onto the bushings and fix them according to the manufacturer’s
instructions. Observe the phase sequence!
➭ If an internal arc additive was pre-assembled in the panel when installation started:
Re-assemble the internal arc additive ⑧ with 2 nut-and-washer assemblies.
➭ Mount the upper part of the cable clamps ⑥ , align the cable bracket and bolt it tight.
➭ Refit the cross member ⑦ .
➭ Connect the cable shield and the earthing of the plug housing at the cross member ⑦ .
➭ Hang in the cable compartment cover, see page 136, "Removing and hanging in the cable
compartment cover".
✔ The cable connection is completed.
Double cables Double cables and surge arresters can be connected to the following panel types using the
and surge arresters corresponding plug-in cable systems:
• Ring-main panel
• Cable panel
• Circuit-breaker panel
Precondition for mounting the floor plates: The panel must already be on its final place of
destination.
Removing the cable ➭ Remove the cable compartment cover, see page 136, "Removing and hanging in the cable
compartment cover and compartment cover".
the cross member
➭ Remove the cross member, see page 137, "Removing and mounting the cross-member".
Mounting the ➭ Push the rear floor plate into the panel until it latches into the lug at the rear wall.
rear floor plate
① Rear floor plate
② Lug at the rear wall
➭ Bolt the rear floor plate - together with the panel - to the foundation at the fixing points (see
page 68, "Floor openings and fixing points").
Installing the cables ➭ Lead the high-voltage cables into the cable compartment.
➭ Push rubber sleeves over the high-voltage cables.
➭ Perform cable installation (see page 119, "Connecting high-voltage cables").
➭ Push the high-voltage cables with the rubber sleeves ① into the cutouts provided for this
purpose in the rear floor plate.
➭ Mount the cross member, see page 137, "Removing and mounting the cross-member".
Mounting the ➭ Insert the rubber sleeve for the secondary wires into the front floor plate.
front floor plate
➭ Insert the front floor plate between the rubber sleeves of the high-voltage cables and the
lug of the cross member. Then, bolt the front floor plate tight using 2 nut-and-washer
assemblies M8.
① Nut-and-washer assembly
M8
② Rear floor plate
③ Front floor plate
④ Rubber sleeves for high-
voltage cables
⑤ Rubber sleeve for
secondary wires
⑥ Lug of cross member
⑦ Cross member
⑧ Fixing point of foundation
➭ Mount the cable compartment cover, see page 136, "Removing and hanging in the cable
compartment cover".
ATTENTION
Surfaces of high-quality joints at the bushings can easily be damaged by incorrect handling.
➭ Observe extreme cleanliness.
➭ Avoid damages caused by the threaded bolt while pushing on.
ATTENTION
In case of spare feeders without connected cables, please observe the following:
➭ Switch the three-position switch to "EARTHED" position and lock it.
➭ Alternatively: Mount surge-proof caps.
ATTENTION
During metal working, please ensure the following:
➭ Do not drill into the vessel.
➭ Do not leave any metal cuttings on the vessel in order to avoid rust layers.
ATTENTION
For perfect installation of the cable plugs, the following must be observed:
➭ Mount the cable plugs according to the manufacturer's stipulations.
➭ If there are no stipulations by the cable plug manufacturer, please contact the regional
Siemens representative.
DANGER
The lateral cable connection box contains external connections according to IEC 62271-200.
The lateral cable connection box is not a compartment, and is therefore not subject to an
internal arc classification (IAC).
➭ Do not close the bottom of the lateral cable connection box.
The components for the lateral cable connection are pre-assembled at the factory.
Available cable connection options:
• Single cable connection
• Double cable connection
• Triple cable connection
① Bushing, phase L1
② Bushing, phase L2
③ Bushing, phase L3
④ Earthing connection for the
cable shield and the plug
housings
⑤ Cable connection box
Removing the cable ➭ Disassemble the cable connection box ⑤ , undo the 5 bolt-and-washer assemblies, and
connection box remove the cable connection box upwards.
Preparing cable ➭ Remove the upper part from all cable clamps.
installation
➭ Pre-adjust the cable bracket and the lower part of the cable clamps. There must be a
distance of approx. 150 mm between the outgoing feeder cables.
Mounting the cables ➭ Fit the cable plugs on the conductor ends of the outgoing feeder cables according to the
manufacturer’s instructions.
➭ Carefully apply mounting paste to the push-on surfaces (high-quality joints) in the plug sets
and the bushing cone (scope of supply of the plug set).
➭ Push the plug sets onto the bushings and fix them according to the manufacturer’s
instructions. Observe the phase sequence!
➭ Lead the outgoing feeder cables along the lower parts of the cable clamps, and mount the
upper parts of the cable clamps.
➭ Align the cable bracket and bolt it tight.
➭ Connect the cable shield and the earthing of the plug housing to the earthing connection.
Mounting the cover ➭ Hang the cable connection box in again and fasten with 5 bolt-and-washer-assemblies.
✔ The installation of the cable connection is completed.
Mounting position of The transformer mounting plates are pre-assembled on the cable bracket at the factory. The
cable-type current cable-type current transformers are supplied in the cable compartment and must be mounted
transformers on the high-voltage cables on site.
① Cable plug
② Cable bracket
③ Transformer
mounting plate
④ Cable clamp
⑤ Cable shield
⑥ Current
transformer
Transformer 4MC7033
type
Panel width 430 mm 430 mm 500/590 mm
Transformer 65/110/170 mm 285 mm 65/110/170/285 mm
height
Mounting
position
NOTE
➭ To provide enough space for the transformer cables, place the current transformers slightly
turned on the transformer mounting plate.
① Nut-and-washer
assembly M8 (2x)
② Transformer mounting
plate
③ Cable clamp
④ Nut-and-washer
assembly M8 (2x)
⑤ Self-tapping Torx screw
M6x16 (4x)
⑥ Current transformer
⑦ Saucer-head bolt
M8x20 (2x)
⑧ Transformer foot
⑨ Transformer bar
⑩ Saucer-head bolt
M8x20 (2x)
⑪ Adjustment rail for
transformer
⑫ Transformer foot
Fig. 137: Principle of installation for WIC1 Fig. 138: Principle of installation for 4MS430 current
current transformers transformers
Preparing transformer ➭ Clean the voltage transformer socket carefully inside with a lint-free wiping cloth.
installation
ATTENTION
If the electrical contact is insufficient or the silicone adapters are dirty, the switchgear might be
damaged during operation.
➭ Observe extreme cleanliness. Clean the surface of the silicone adapters carefully inside and
outside.
➭ Clean the bushing in the panel carefully with a lint-free wiping cloth.
➭ Apply mounting paste evenly to the bushing in the panel.
Setting down the voltage ➭ While setting down the voltage transformer, let excess air out of the inside cone with a
transformer onto the cable strap. To let excess air out, put a cable strap ② into the inside cone and fix it on the
bushings outside of the transformer (adhesive tape ① ).
Fig. 140: Letting excess air out of the voltage transformer with a cable strap
DANGER
Risk of injury! The voltage transformers weigh up to 70 kg.
➭ Use an appropriate lifting tool for lifting the voltage transformers.
➭ While setting down the voltage transformer, pull out the cable strap carefully.
➭ Verify intact condition of the cable strap. If the cable strap was damaged when it was pulled
out, remove the voltage transformer again and eliminate the residues of the cable strap in
the inside cone.
Bolting the voltage ➭ Bolt the voltage transformer together with the positioning socket ④ using 4 pan-head
transformer together screws with hexagon socket ① , washer ② and clamping ring ③ (tightening torque:
21 Nm).
➭ Mount the voltage transformers of the two other phases in the same way.
ATTENTION
The transmission linkage of the ready-for-service indicator ② must move freely.
➭ Lay the cables following the dotted line.
The terminal strips of the secondary equipment supplied are assigned to the associated
operating mechanisms or feeders. For information about the external connection, see the
supplied circuit diagrams.
① Wiring duct
② Ready-for-service indicator
③ Terminal strip
Wire routing
Fig. 143: Wire routing for switchgear Fig. 144: Wire routing for switchgear with
without wiring duct wiring duct
Recommended wire routing for secondary equipment: At the side, from the rear or from
above. Wire routing through the wiring duct is possible for panel blocks. For extendable
switchgear, wire routing through the wiring duct is recommended.
➭ Remove the fixing bolts of the front plate.
➭ Remove the front plate of the switchgear to the front.
➭ Following the circuit diagrams, connect the wires to the terminal strip ③ or directly to
equipment terminals (e.g. CAPDIS S2+, short-circuit indicator), and lay them cleanly. Route
the wire laterally to the outside (arrow) through cut-out stopper. If available, use the wiring
duct ① .
➭ Do not switch on auxiliary voltage yet.
Fig. 145: Simple protection IKI-30 Fig. 146: Simple protection IKI-30
without wiring duct with wiring duct
➭ Undo the 2 fixing bolts ④ of the cover ① and remove the cover.
➭ Undo the 2 fixing bolts ⑥ of the mounting plate and remove the mounting plate ⑤ .
15 Recurring activities
Precondition To remove the cable compartment cover, the associated feeder must be earthed.
NOTE
For the following panel types, the cable compartment cover is screwed on additionally:
• Metering panels
• Panels with pressure relief to the rear/upwards
• Panels with pressure relief duct / absorber
Hanging the cable ➭ Hang in the cable compartment cover ① from above.
compartment cover in
➭ For panels with pressure relief to the rear/upwards or panels with pressure relief duct /
absorber: Bolt the cable compartment cover together with the panel using 2 bolts
M6x50 ② .
➭ For metering panels: Bolt the 3 cable compartment covers together with the panel using
15 bolt-and-washer assemblies M6x16 ③ and 3 bolts M6x50 ② .
➭ De-earth the feeder.
Removing the cross ➭ Undo the 8 Torx screws ② at the cross member ① .
member
➭ The floor fixing bolt ③ must be removed if the panel was already fastened to the
foundation.
➭ Remove the cross member ① .
① Cross member
② Torx screw M6x16
③ Floor fixing bolt
Metering panel:
Removing the cross ➭ Undo the 20 bolt-and-washer assemblies ② at the cross member ① .
member
➭ The 6 floor fixing bolts ③ must be removed if the panel was been fastened to the
foundation.
➭ Remove the cross member ① .
① Cross member
② Torx screw M6x16
③ Floor fixing bolt
16 Commissioning
DANGER
During operation of electrical equipment and switchgear, parts of this equipment are under
dangerous electrical voltage. Mechanical components may move quickly, even remotely
controlled.
➭ Do not remove covers.
➭ Do not reach into openings.
Rating plate ➭ Check the data on the rating plate and the auxiliary voltage of the control and end devices
as against the requirements.
Readiness for service ➭ Check ready-for-service indicator (see page 62, "Checking the ready-for-service indicator ").
High-voltage connections ➭ Check earthing of cable terminations on all connected high-voltage cables.
➭ If provided by the customer, perform cable test (see page 170, "Cable testing")
Termination plates in end ➭ For switchgear with pressure relief duct, check if the termination plates are mounted in the
panels side walls of the end panel.
Feeder without cables ➭ Switch the switching device to EARTHED position and lock it, and cover the bushings with
surge-proof caps.
Bolted joints ➭ Check the tightening torques of the bolted joints of the low-voltage equipment at random.
➭ Check all switchgear parts that have been disassembled and assembled again at site during
installation or that have been installed subsequently, in order to verify correct assembly and
completeness.
Final work ➭ Remove any attached instruction labels or documents that are not required anymore for
operation.
➭ Remove any tools, materials etc. that are not required anymore from the area of switchgear.
➭ Remove dirt from the area of switchgear.
➭ Fit all covers.
➭ Put the caps on the capacitive test sockets.
➭ Touch up scratches and impacts in the surface painting, if necessary. To do this, a paint pen
is available optionally.
Checking the accessories ➭ Make sure that the following accessories are ready to hand:
• Operating instructions
• Operating lever for operating the panel
• Circuit diagrams
• Warning signs
DANGER
Putting defective switchgear into operation can endanger the life of people and damage the
switchgear.
➭ Never put switchgear into operation if during test operation a part of it does not work as
described in here.
➭ Perform test operations with auxiliary voltage only!
Test operation / Electrical Before commissioning, verify the perfect operation of the switchgear without high voltage by
function test test operation.
➭ Switch the three-position switch-disconnector with motor operating mechanism several
times to CLOSED and OPEN position.
➭ After completion of test operation, the three-position switch must be in OPEN position.
➭ Switch on all auxiliary voltages and control voltages and verify correct polarity.
➭ Check whether the mechanical and/or electrical interlocking conditions are fulfilled without
using excessive force.
➭ Check whether the switch positions of the three-position switches are displayed correctly.
Fig. 147: Retaining screw ① of the striker at the undervoltage release in position B
Malfunction during test If there are any faults that cannot be cleared at site:
operation
➭ Do not put the switchgear into operation.
➭ Inform the competent Siemens representative.
Preparations before The operating personnel must have been trained, the installation work checked and test
energizing operation must have been carried out successfully without malfunctions.
➭ Close all covers.
➭ Make sure that the capacitive test sockets are covered with caps.
➭ Switch the switching devices of feeders without connected cables to EARTHED position and
lock them, or cover the bushings with surge-proof caps.
➭ Reset short-circuit indicators.
✔ Now you can switch on the operating voltage and put the switchgear into operation as
described hereafter.
Energizing the first ➭ First, apply voltage from opposite substation, then switch the feeder from "OPEN" to
feeder/incoming feeder "CLOSED" position.
DANGER
Short-circuit in case of different phase sequence of the incoming feeders.
➭ Make sure that all incoming feeders have the same phase sequence.
➭ To check the phase sequence, use only phase comparison test units which are adequate
for HR or LRM test sockets.
➭ Verify correct terminal-phase connections of the next incoming feeder and switch on the
incoming feeder.
➭ Energize tested incoming feeder.
➭ Plug the measuring cables of the phase comparison test unit into the test sockets for phase
L1 of the two panels.
Operation
DANGER
The internal arc classification of the switchgear according to IEC 62271-200 has only been
proved by tests for the switchgear sides with internal arc classification and with closed high-
voltage compartments.
➭ Determine the IAC classification of the switchgear by means of the data on the rating plate
(see page 55, "Rating plates").
➭ Regulations for access to switchgear areas without internal arc classification according to
IEC 62271-200 must be defined by the entrepreneur or the switchgear operator.
DANGER
During operation of electrical equipment and switchgear, parts of this equipment are under
dangerous electrical voltage. Mechanical components may move quickly, even remotely
controlled.
➭ Do not remove covers.
➭ Do not reach into openings.
ATTENTION
If the gas filling is insufficient, this can cause personal injuries and material damages.
➭ Check readiness for service before performing any switching operation; to do this, verify
that the pointer of the ready-for-service indicator is in the green area.
ATTENTION
Earthing a live incoming cable will result in a short circuit and trip an upstream circuit-breaker.
➭ Verify safe isolation from supply of the feeder before earthing.
Local-remote switch The local-remote switch determines the location from which the three-position switch can be
(option) motor-operated. The local-remote switch latches tight in the selected setting.
Local setting:
Local operation by motor
Remote setting:
Remote operation by
motor from the control
room or monitoring
station
Momentary-contact On site, the disconnector or the earthing switch can be closed or opened via the motor-
rotary control switch for operating mechanism (option). This function is only active if the local-remote switch (option)
motor operating is in Local position.
mechanism (option)
After operation, the momentary-contact rotary control switch automatically switches back to
the central position.
17.2 Indicators
Earthing switch
Circuit-breaker
Circuit-breaker panel
1)
One operating cycle corresponds to one closing operation and one opening operation of the circuit-breaker
Ready-for-service indicator
DANGER
Mortal danger, and damage to the switchgear if the switch-disconnector is operated without
the switchgear being ready for service!
➭ Operate the switch-disconnector only if the indicator shows service readiness of the
switchgear (ready-for-service indicator: green).
➭ If the switchgear is not ready for service, isolate the switchgear in the opposite substation,
and inform the Siemens representative.
DANGER
Possible malfunctioning caused by switchgear damage. Using incorrect operating levers can
damage or deactivate the safety equipment of the switchgear.
➭ Use only the operating levers corresponding to the switchgear type.
Anti-reflex lever The standard operating lever can be converted into an anti-reflex lever. To do so, remove the
setscrew ① from the standard operating lever.
① Setscrew
Fig. 151: Standard operating lever, Fig. 152: Converting the standard
short operating lever into an
anti-reflex lever
Disconnector Circuit-breaker
Actuating opening Earthing switch none
Switch-disconnector Transformer switch
Possible switching Only EARTHING and DE- No switching operations • Only CLOSING and • Charging the spring
operations EARTHING possible possible OPENING possible
Precondition: • Only possible if the
circuit-breaker is
Spring energy store not open
charged
NOTE
If the opening spring of the transformer switch was tripped by a fuse-link:
➭ The fuse indicator is red (see arrow).
➭ The motor operating mechanism (option) is out of operation.
DANGER
Non-observance of the following instructions can endanger people or damage the switchgear.
➭ The sequence of the following instructions has to be followed by all means.
➭ All instructions have to be executed.
① Ready-for-service indicator
② Control gate/locking device (option for
spring-operated mechanism)
③ Padlock (option)
④ Operating lever
1
Initial situation:
Feeder in OPEN position
➭ Check the ready-for-service indicator
(see page 145, "Ready-for-service indicator").
➭ Remove the padlock (optional) from the locking device.
2
Open the actuating opening for the switch-disconnector.
➭ Push the control gate (optional) upwards, and hold it.
3
Switch the three-position switch-disconnector to CLOSED
position.
➭ Insert the operating lever and turn straight clockwise as
far as it will go.
4
The feeder is connected with the busbar.
➭ Remove the operating lever (the control gate returns to its
initial position).
➭ Fit the padlock (optional) at the locking device at the
desired position (see page 146, "Mechanical interlocking
with padlock").
1
Initial situation:
Feeder in CLOSED position
➭ Check the ready-for-service indicator
(see page 145, "Ready-for-service indicator").
➭ Remove the padlock (optional).
2
Open the actuating opening for the switch-disconnector.
➭ Push the control gate (optional) upwards, and hold it.
3
Switch the three-position switch-disconnector to OPEN
position.
➭ Insert the operating lever and turn straight counter-
clockwise as far as it will go.
4
The feeder is disconnected from the busbar.
➭ Remove the operating lever (the control gate returns to its
initial position).
➭ Fit the padlock (optional) at the locking device at the
desired position (see page 146, "Mechanical interlocking
with padlock").
1
Initial situation:
Feeder in OPEN position
➭ Check the ready-for-service indicator
(see page 145, "Ready-for-service indicator").
➭ Remove the padlock (optional).
2
Open the actuating opening for the earthing switch.
➭ Push the control gate (optional) downwards, and hold it.
3
Switch the three-position switch-disconnector to EARTHED
position.
➭ Insert the operating lever and turn straight clockwise as far
as it will go.
4
The feeder is earthed.
➭ Remove the operating lever (the control gate returns to its
initial position).
➭ Fit the padlock (optional) at the locking device at the
desired position (see page 146, "Mechanical interlocking
with padlock").
1
Initial situation:
Feeder in EARTHED position
➭ Check the ready-for-service indicator
(see page 145, "Ready-for-service indicator").
➭ Remove the padlock (optional).
2
Open the actuating opening for the earthing switch.
➭ Push the control gate (optional) downwards, and hold it.
3
Switch the three-position switch-disconnector to OPEN position.
➭ Insert the operating lever and turn straight counter-
clockwise as far as it will go.
4
The feeder is de-earthed.
➭ Remove the operating lever (the control gate returns to its
initial position).
➭ Fit the padlock (optional) at the locking device at the
desired position (see page 146, "Mechanical interlocking
with padlock").
DANGER
Non-observance of the following instructions can endanger people or damage the switchgear.
➭ The sequence of the following instructions has to be followed by all means.
➭ All instructions have to be executed.
DANGER
If the operating lever is still inserted when the transformer switch is tripped by means of a test
fuse, persons can be injured.
➭ Remove the operating lever.
ATTENTION
Avoid no-load operations as this can damage the operating mechanism.
➭ Close the operating mechanism first, and then open it .
① Ready-for-service indicator
② OFF pushbutton
③ ON pushbutton
④ Control gate/locking device
⑤ Padlock (option)
⑥ Operating lever
ATTENTION
Risk of injury! When charging the spring, the operating lever is inserted in the actuating
opening. If no operating lever ejection system is available, the operating lever rotates and can
thereby injure the operator.
➭ Remove the operating lever after charging the spring.
1
Initial situation:
Feeder in OPEN position
➭ Check the ready-for-service indicator
(see page 145, "Ready-for-service indicator").
➭ Remove the padlock (optional).
2
Open the actuating opening for charging the operating
spring.
➭ Push the control gate (optional) upwards, and hold it.
3
Charge the operating spring of the three-position switch-
disconnector.
➭ Insert the operating lever and turn straight clockwise as
far as it will go.
4
The spring energy store indicator shows "spring charged".
➭ Remove the operating lever (the control gate returns to
its initial position).
The feeder is ready to close.
5
Connect the feeder to the busbar.
➭ Actuate the ON pushbutton.
➭ Fit the padlock (optional) at the locking device at the
desired position (see page 146, "Mechanical interlocking
with padlock").
The spring energy store indicator still shows "spring charged".
1
Initial situation:
• Feeder in CLOSED position
• The spring energy store indicator shows "spring
charged".
1
Initial situation:
Feeder in OPEN position
➭ Check the ready-for-service indicator
(see page 145, "Ready-for-service indicator").
➭ Remove the padlock (optional).
2
Open the actuating opening for the earthing switch.
➭ Push the control gate (optional) downwards, and hold it.
3
Switch the three-position switch-disconnector to EARTHED
position.
➭ Insert the operating lever and turn straight clockwise as
far as it will go.
4
The feeder is earthed.
➭ Remove the operating lever (the control gate returns to
its initial position).
➭ Fit the padlock (optional) at the locking device at the
desired position (see page 146, "Mechanical interlocking
with padlock").
1
Initial situation:
Feeder in EARTHED position
➭ Check the ready-for-service indicator
(see page 145, "Ready-for-service indicator").
➭ Remove the padlock (optional).
2
Open the actuating opening for the earthing switch.
➭ Push the control gate (optional) downwards, and hold it.
3
Switch the three-position switch-disconnector to OPEN
position.
➭ Insert the operating lever and turn straight counter-
clockwise as far as it will go.
4
The feeder is de-earthed.
➭ Remove the operating lever (the control gate returns to
its initial position).
➭ Fit the padlock (optional) at the locking device at the
desired position (see page 146, "Mechanical interlocking
with padlock").
DANGER
Non-observance of the following instructions can endanger people or damage the switchgear.
➭ The sequence of the following instructions has to be followed by all means.
➭ All instructions have to be executed.
The following chapter describes the manual switching operations at the panel.
Charging the spring If the circuit-breaker is not equipped with a motor operating mechanism, the spring energy
energy store manually store can be charged manually (see page 156, "Charging the spring energy store in the circuit-
breaker feeder manually").
Charging the spring If the circuit-breaker is equipped with a motor operating mechanism (option), the closing
energy store with motor spring is charged automatically after applying auxiliary voltage.
operating mechanism
Operating the circuit- The circuit-breaker can be operated manually with pushbuttons or electrically.
breaker
① Ready-for-service indicator
② Actuating opening for
charging the closing spring
③ Circuit-breaker ON
pushbutton
④ Circuit-breaker OFF
pushbutton
⑤ Control gate/locking device
(option for three-position
switch-disconnector)
⑥ Padlock (option)
⑦ Operating lever
⑧ Hand crank for charging the
closing spring
ATTENTION
The max. service life of the circuit-breaker panel depends on the permissible number of
switching operations of the switching device used (see page 35, "Three-position switch-
disconnector " and see page 36, "Three-position disconnector ").
➭ Check the number of operating cycles of the switching devices regularly.
➭ When the switching device reaches the maximum permissible number of operating cycles,
a preventive maintenance and visual inspection must be performed, if required.
20.2 Charging the spring energy store in the circuit-breaker feeder manually
During manual operation or if the auxiliary voltage fails (motor operating mechanism), the
spring energy store must be charged manually. The closing spring is charged automatically
after applying control voltage.
Auxiliary means required: Hand crank
1
Initial situation:
• Circuit-breaker in OPEN position
• Three-position disconnector in OPEN
position
• The spring energy store indicator shows
"spring not charged".
3
Charge the circuit-breaker closing spring.
➭ Insert the hand crank and turn clockwise
until the spring energy store indicator
shows "spring charged".
➭ Remove the hand crank.
The circuit-breaker can be closed and opened
again.
Circuit-breaker with automatic reclosing
(AR):
In order to ensure the operating sequence
O - 0.3 s - CO for automatic reclosing of a
circuit-breaker with automatic reclosing
feature (AR), the closing spring must be re-
charged again manually after closing.
➭ Refit the protective cover.
1
Initial situation:
• Circuit-breaker in OPEN position
• Three-position disconnector in CLOSED
position
• The spring energy store indicator shows
"spring charged".
➭ Check the ready-for-service indicator
(see page 145, "Ready-for-service
indicator").
2
Close the circuit-breaker.
➭ Actuate the ON pushbutton.
The spring energy store indicator shows
"spring not charged".
The position indicator for the circuit-breaker is
in CLOSED position.
1
Initial situation:
Circuit-breaker in CLOSED position
➭ Check the ready-for-service indicator
(see page 145, "Ready-for-service
indicator").
2
Open the circuit-breaker.
➭ Actuate the OFF pushbutton.
The position indicator for the circuit-breaker is
in OPEN position.
1
Initial situation:
• Three-position disconnector in OPEN
position
• Circuit-breaker in OPEN position
➭ Check the ready-for-service indicator
(see page 145, "Ready-for-service
indicator").
➭ Remove the padlock (optional).
2
Open the actuating opening for the
disconnector.
➭ Push the control gate upwards, and hold
it.
3
Switch the three-position disconnector to
CLOSED position.
➭ Insert the operating lever and turn
clockwise as far as it will go.
4
The three-position disconnector is closed.
➭ Remove the operating lever (the control
gate returns to its initial position).
➭ Fit the padlock (optional) at the locking
device at the desired position (see page
146, "Mechanical interlocking with
padlock").
1
Initial situation:
• Three-position disconnector in CLOSED
position
• Circuit-breaker in OPEN position
➭ Check the ready-for-service indicator (see
page 145, "Ready-for-service indicator").
➭ Remove the padlock (optional).
2
Open the actuating opening for the three-
position disconnector.
➭ Push the control gate upwards, and hold it.
3
Switch the three-position disconnector to
OPEN position.
➭ Insert the operating lever and turn
counter-clockwise as far as it will go.
4
The three-position disconnector is open.
➭ Remove the operating lever (the control
gate returns to its initial position).
➭ Fit the padlock (optional) at the locking
device at the desired position (see page
146, "Mechanical interlocking with
padlock").
1
Initial situation:
• Three-position disconnector in OPEN
position
• Circuit-breaker in OPEN position
➭ Check the ready-for-service indicator (see
page 145, "Ready-for-service indicator").
➭ Remove the padlock (optional).
2
Open the actuating opening for the earthing
switch.
➭ Push the control gate downwards, and
hold it.
3
Switch the three-position disconnector to
EARTHED position.
➭ Insert the operating lever and turn
clockwise as far as it will go.
4
The three-position disconnector is
EARTHED.
➭ Remove the operating lever (the control
gate returns to its initial position).
➭ Fit the padlock (optional) at the locking
device at the desired position (see page
146, "Mechanical interlocking with
padlock").
1
Initial situation:
• Three-position disconnector in EARTHED
position
• Circuit-breaker in OPEN position
3
Switch the three-position disconnector to OPEN
position.
➭ Insert the operating lever and turn counter-
clockwise as far as it will go.
4
The three-position disconnector is de-
earthed.
➭ Remove the operating lever (the control
gate returns to its initial position).
➭ Fit the padlock (optional) at the locking
device at the desired position (see page
146, "Mechanical interlocking with
padlock").
➭ Hang in the cable compartment cover, see page 136, "Removing and hanging in the cable
compartment cover".
✔ The voltage transformer disconnector is isolated from high-voltage, earthed and secured
against reclosing.
✔ The voltage transformer disconnector is connected to high voltage and secured against
unauthorized opening.
➭ Hang in the cable compartment cover, see page 136, "Removing and hanging in the cable
compartment cover".
DANGER
High voltage! Danger! Verify safe isolation from supply without any doubt!
Possible sources of failure:
- Defective voltage indicator (or device for function testing of the coupling section)
- Maloperation of the voltage indicator (or device for function testing of the coupling
section)
Test the perfect function of the voltage indicator and the coupling section in accordance
with national standards:
- On a live panel
- With a test unit according to IEC 61243-5/EN 61243-5
- On all phases
➭ Remove covers from plug-in sockets (capacitive test sockets L1, L2, L3).
➭ Plug voltage indicator in all three phases L1, L2, L3 of the plug-in sockets.
✔ If the indicator does not flash or light up in any of the three phases, the phases are not live.
DANGER
High voltage! Danger! Verify safe isolation from supply without any doubt!
Possible sources of failure:
- Defective voltage indicator (or device for function testing of the coupling section)
- Maloperation of the voltage indicator (or device for function testing of the coupling
section)
DANGER
High voltage! Danger! Do only modify the factory setting of the C2 module in the voltage
detecting system CAPDIS-S1+/S2+ after consultation with the regional Siemens representative!
➭ If the setting of the C2 module was modified by mistake, re-establish the factory setting as
follows:
- Pull out the C2 module ③ at the rear side of CAPDIS-S1+/S2+. Caution: Open printed
circuit board may be energized.
- Plug the C2 module ③ into CAPDIS-S1+/S2+ so that the marked arrow ① on the housing
points to the marking ② on the C2 module
① "Test" button
② Cover
③ LC display
④ Duct for signaling
cables CAPDIS-M
⑤ Test socket L2
⑥ Earth socket
⑦ Test socket L3
Fig. 161: CAPDIS-S2+: Cover closed
⑧ Test socket L1
⑨ Short instructions
① LC display
② Test socket L2
③ Earth socket
④ Test socket L3
⑤ Test socket L1
DANGER
High voltage! Danger! Verify safe isolation from supply without any doubt!
Possible sources of failure:
- Defective voltage indicator (or device for function testing of the coupling section)
- Maloperation of the voltage indicator (or device for function testing of the coupling
section)
Indications
WEGA 1.2, WEGA 2.2 Indication WEGA 1.2 WEGA 2.2
L1 L2 L3 L1 L2 L3
A0 For WEGA 2.2: Operating voltage not present, auxiliary power
present, LCD illuminated
ATTENTION
If one HV HRC fuse has tripped, the HV HRC fuses in the other two phases may have been
stressed.
➭ If one HV HRC fuse has tripped, always replace the HV HRC fuse in all three phases.
ATTENTION
Risk of hand injuries due to hot fuse-links or bruises and sharp edges at the locking system
during fuse replacement.
➭ Do not replace HV HRC fuse-links with bare hands.
➭ Wear safety gloves.
Removing the cable The cable compartment cover can only be removed if the earthing switch is in EARTHED
compartment cover position.
When the cable compartment cover is removed, the earthing switch is interlocked in EARTHED
position.
➭ Isolate and earth the transformer feeder.
➭ Remove the cable compartment cover, see page 136, "Removing and hanging in the cable
compartment cover".
Detaching the gasket of ➭ Detach the gasket of the HV HRC fuse-link. For this purpose, turn the handle of the locking
the HV HRC fuse-link system of the HV HRC fuse-link 90° upwards or downwards.
Withdrawal of the
HV HRC fuse-link
ATTENTION
HV HRC fuse-links may be hot!
➭ Let HV HRC fuse-link cool down, or wear gloves when withdrawing the HV HRC fuse-link.
Replacing
HV HRC fuse-links
ATTENTION
Incorrectly selected or mounted fuse-links and extension tubes damage the fuse box or the
switchgear.
➭ Only fuse-links with reference dimension 537 mm are permissible.
➭ Lay the HV HRC fuse-link with the locking system on a flat, clean and firm underground.
➭ Undo the screw of the hose clamp with suitable tools (slot screwdriver).
① Locking system
② HV HRC fuse-link
③ Screw of the hose clamp
➭ Fasten the bolt of the hose clamp ③ again (tightening torque: 3 Nm).
➭ Replace the HV HRC fuse-link in the other phases analogously.
Inserting the
HV HRC fuse slide
ATTENTION
Incorrectly selected or mounted HV HRC fuse-links and extension tubes can damage the fuse
box or the switchgear.
➭ Only HV HRC fuse-links with reference dimension 537 mm are permissible.
➭ Push the HV HRC fuse-link with locking system into the fuse box as far as it will go.
➭ The locking system can only be inserted completely if the slide of the fuse tripping ② points
towards the tripping rocker ① .
① Tripping rocker
② Slide of fuse tripping
Interlocking of HV HRC ➭ Interlock HV HRC fuse-links in the fuse box. For this purpose, turn the handles of the locking
fuse-links system of the HV HRC fuse-links 90° upwards or downwards until they latch in.
Lock the fuse-link of phase L3 ③ first, then the fuse-links of phases L1 ① and L2 ② .
Hanging the cable ➭ The cable compartment cover can only be hung in correctly if the HV HRC fuse slides are
compartment cover in latched in correctly.
➭ Hang in the cable compartment cover, see page 136, "Removing and hanging in the cable
compartment cover".
24 Cable testing
DANGER
Cable testing with connected cables represents a special stress for the isolating distance. If the
busbar of the switchgear under test or the opposite substation are live with operating voltage,
adequate measures must be taken in order to prevent overvoltages. Normally, the switch-
disconnector is not interlocked during the cable test.
➭ Fit switching prohibition signs.
➭ Secure the locking device (option) with a lock.
DANGER
If the voltage transformer disconnector is closed, the test voltage can destroy the voltage
transformer and cause personal injuries.
➭ Switch the voltage transformer disconnector to EARTHED position before testing the cables
and secure it (see page 161, "Disconnecting the feeder voltage transformer").
➭ If voltage transformers are mounted at the cable feeder in the panel, open the voltage
transformer disconnector (see page 161, "Disconnecting the feeder voltage transformer").
Preparations ➭ Remove the cable compartment cover, see page 136, "Removing and hanging in the cable
compartment cover".
➭ Undo the screw-type cone at the T-plug or at the adapter.
➭ Fit cable test equipment (e.g. measuring bolts) according to the operating instructions of
the plug manufacturers.
① Bushing
② Measuring bolt
③ Test lead
④ Earthing connection of cable shield
⑤ Earthing connection of plug
⑥ T-plug
ATTENTION
The cables, cable plugs and voltage detecting systems may be damaged by too high test
voltages.
➭ Observe the specifications of the manufacturers of the cables, cable plugs and voltage
detecting systems (maximum test values).
➭ De-earth.
➭ Perform the test according to the recommendations of the cable manufacturers or the
customers' specifications.
DANGER
Normally, the switch-disconnector panel is not interlocked during the cable sheath test.
Prevent switching to OPEN or CLOSED position as follows:
➭ Fit switching prohibition signs.
➭ Secure the locking device (option) with a lock.
➭ Closing lock-out (option)
T V
Technical data ................................................................ 34 Vacuum circuit-breaker ................................................... 15
Technical data, three-position disconnector..................... 36 Vacuum circuit-breaker, technical data ............................37
Technical data, three-position switch-disconnector.......... 35 Verification of safe isolation from supply ...................... 162
Three-position disconnector, technical data..................... 36 Verification of safe isolation from supply,
HR/LRM plug-in sockets ................................................. 162
Three-position switch-disconnector................................. 11
Vessel adapter, installation..............................................90
Three-position switch-disconnector, technical data.......... 35
VOIS ............................................................................. 163
Tightening torques ......................................................... 43
Voltage detecting systems ..............................................25
Tools .............................................................................. 65
Voltage transformer at the cable connection ................. 132
Torques .......................................................................... 43
Voltage transformer disconnector, closing..................... 161
Transformer feeder, connecting to the busbar ............... 152
Voltage transformer disconnector, opening................... 161
Transformer feeder, control board................................. 151
Voltage transformers, dimensions and
Transformer feeder, de-earthing ................................... 154
mounting positions....................................................... 106
Transformer feeder, disconnecting from the busbar ...... 153
Voltage transformers, installation in the
Transformer feeder, earthing ........................................ 153 circuit-breaker panel ..................................................... 130
Transformer feeder, operation ...................................... 151 Voltage transformers, installation on the busbar............ 130
Transformer installation, metering panel....................... 106
W
Transformer protection table........................................... 46 WEGA 1.2/2.2 ............................................................... 165
Transformer protection table, make Inter-Teknik ............. 51