Gis Instrument Transformers Eng

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

GIS

INSTRUMENT TRANSFORMERS
MAIN
FEATURES
Trench is a world leader in the design and manufacture of high voltage equipment on electric utility and high energy industrial systems.
GIS current and voltage transformers are used to convert high transmission line currents (up to 6000 A) and voltages (up to 800 kV) to standardized low
and easily measurable values, which are used for metering, protection and control of the high voltage system. As such, the need for accurate and reliable
current and voltage transformation is essential. Our GIS current and voltage transformers are adaptable to any OEM specific requirement and adaptation
to GIS switchgears.

General Product Design Product process


Instrument transformers acc. to IEC 61869, 72,5 kV - 800 kV - one phase design is available Optimized design to manufacturing
ANSI: IEEE C57.13, (others on request) up to 245 kV - both one phase and three phase Lean manufacturing concept applied to the
Rated primary voltage 72,5 - 800 kV designs whole supply chain
Rated primary current up to 6000A SF6 insulation Partial discharge free design and process
Housings acc. to international Pressure Vessel Maintenance free during a long life time of
CT RATINGS: Regulation more then 30 years
Rated secondary current of 1A, 2A or 5 A Terminal box protection degree IP55 Trench Management System has been certified
Rated short time thermal current up to 80 kA to ISO9001, ISO 14001 and BS OHSAS 18001
Rated short circuit withstand up to 200 kAp For GIS current tranformers: Testing facilities are accreditated according to
245 kV and higher - core in air design available ISO 17025
VT RATINGS:
Maximum simultaneous burden in cl 0,2 For GIS voltage transformers:
up to 200 VA Integrated Isolation Device (IID)
Maximum simulteneous burden 0,3Z/0,15Y optional (manual or motor)
Thermal limiting output up to 2500 VA Ferroresonance damping device - optional
Up to 145kV BLUE (clean air) - optional
Special tests are also available to meet Power VT is available for all GIS voltage transformer types
specific customer requirements
Units for service for old GIS design starting from 60s
on request.
PRODUCT
STRUCTURE

Three phase design up to 245 kv

Core in Three phase voltage Three phase voltage


gas three phase transformer with IID transformer without IID
Current Transformer

One phase up to 800 kV

Core in One phase One phase


air one phase Voltage Trasformer Voltage Trasformer
Current Trasformer with IID without IID
CA-000014-2021-03-EN
Trench Germany GmbH
SE T NP BIC S EMEA TG OFM
Nuernberger Str. 199
96050 Bamberg, Germany
Phone +49 951 1803-0

www.trenchgroup.com