1. What is the voltage range for ELV as per BS standard?

Answer:
For AC: 0 – 49 V
For DC: 0 – 119 V
2. What will be the circuit breaker and cable size rating for 1.2 kW lighting sub circuit?
Answer:
10A MCB, 1.5/2.5 Sq. mm
3. As per DEWA standard in radial circuit the maximum number of 13A sockets not exceed _____
nos. and in ring circuit the maximum number of 13A sockets not exceeds _____ nos.?
Answer:
5 nos. for radial circuit and 10 nos. for ring circuit.
4. Demand Factor = _____?
Answer:
Maximum Demand / Total Connected Load
5. What is the formula for power when you are about to calculate the 3 phase load?
Answer:
P = 1.732*VI*PF
6. _____ % of minimum free space required for a cable tray?
Answer:
40%
7. 400A Feeder can feed up to?
Answer:
200kW
8. Expend the following terms?
 ATS
 APFC
 RCCB
 ACB

Answer:

ATS – Automatic Circuit Breaker

APFC –

RCCB – Residual Current Circuit Breaker

ACB – Air Circuit Breaker

9. Mention the frequency range in UAE and KSA?


Answer:
UAE = 50 Hertz
KSA = 60 Hertz
10. What is PABX in telecommunications?
Answer:
Private Automatic Branch Exchange
11. 13A switch should have _____mA for earth leakage protection?
Answer:
30mA
12. Which fire alarm device is used to shut down the HVAC system at fire case?
Answer:
Control Module
13. A fire alarm call point should be spaced at a maximum distance of _____ apart?
Answer:
30m
14. _____ module is used to isolate a fault at the fire alarm loop and put each ____ device of the
loop.
Answer:
Isolator module in the base at each 20 device.
15. What is the maximum length of DALI cable? The recommended maximum distance between any
two devices on a DALI bus when using 1.5 Sq. mm.
Answer:
300mm