Comfotec Q & A
Comfotec Q & A
Answer:
For AC: 0 – 49 V
For DC: 0 – 119 V
2. What will be the circuit breaker and cable size rating for 1.2 kW lighting sub circuit?
Answer:
10A MCB, 1.5/2.5 Sq. mm
3. As per DEWA standard in radial circuit the maximum number of 13A sockets not exceed _____
nos. and in ring circuit the maximum number of 13A sockets not exceeds _____ nos.?
Answer:
5 nos. for radial circuit and 10 nos. for ring circuit.
4. Demand Factor = _____?
Answer:
Maximum Demand / Total Connected Load
5. What is the formula for power when you are about to calculate the 3 phase load?
Answer:
P = 1.732*VI*PF
6. _____ % of minimum free space required for a cable tray?
Answer:
40%
7. 400A Feeder can feed up to?
Answer:
200kW
8. Expend the following terms?
ATS
APFC
RCCB
ACB
Answer:
APFC –