Professional Documents
Culture Documents
6000F - User Manual 1600
6000F - User Manual 1600
USER MANUAL
Note: This manual provides User information for both 6000F and Dryclon compressors. To
identify a 6000F model number add the prefix 6 to the model number, i.e. the 6504 is equivalent to
504.
page 1
CompAir
OWNERSHIP DATA
TECHNICAL DATA
Name:
Address:
Telephone: Fax:
Service:
page 2
Oil Free Screw User Manual
MODEL DESIGNATION
The Model Designation code identifies specific models as in the following example:
Designation 5 0 4 – 0 8 W
A B B – C C W
➤
A = MAINS SUPPLY FREQUENCY 5 = 50 HZ; 6 = 60 HZ
B = NOMINAL FREE AIR DELIVERY 04 = 400 CFM
C = DELIVERY PRESSURE 07 = 7.6 BAR
08 = 8 BAR
09 = 9 BAR
10 = 10.5 BAR
W = COOLING WATER
This publication relates to all standard operating pressure versions of the following models (50Hz and 60Hz):
Note: This manual provides User information for both 6000F and Dryclon compressors. To identify a 6000F
model number add the prefix 6 to the model number, i.e. the 6504 is equivalent to 504.
ASSOCIATED PUBLICATIONS
page 3
CompAir
WARRANTY
! WARNING
The conditions of the CompAir Warranty are set out !
in the company’s standard Conditions of Sale
available from the Distributor supplying the ● The use of replacement parts or
machine. lubricating oils not supplied or approved
by CompAir may lead to failures in
service which would not be covered by
MAINTENANCE warranty.
USE ONLY
GENUINE PARTS
AUTHORISED SERVICE AGENTS
page 4
Oil Free Screw User Manual
1
SAFETY PROCEDURES
Page
General 6
Installation Precautions 7
Operational Precautions 7
page 5
CompAir
SAFETY PROCEDURES
2.2 Cautions
2.3 Notes
page 6
Oil Free Screw User Manual – Safety Procedures
3. GENERAL SAFETY PRECAUTIONS Ensure that the air delivery pipe from the
compressor to the user’s pipework or receiver is
If using compressed air for cleaning purposes, free to expand and that no flammable material is in
ensure safety regulations are complied with and the vicinity.
appropriate clothing and eye protection is worn.
A shut-off valve must be fitted in the delivery air line
Never direct compressed air onto your skin or at to enable the compressor unit to be isolated. This is
other people. particularly important if more than one unit is to be
coupled in parallel or connected to an existing air
Never use compressed air to clean loose dirt from supply system.
clothing.
The non-return valve is not intended as an isolating
Before releasing compressed air through a hose valve and should not be relied upon for this
make sure that the free end is held securely so that purpose. In addition, it may be necessary to install
it cannot whip and cause injury. shut-off valves elsewhere in the system to allow a
dryer or other equipment to be by-passed.
Avoid injury by using a hoist to lift heavy loads.
Check that all chains, hooks, shackles and slings A safety relief valve must be installed between any
are in good condition and are of the correct compressor unit and the shut-off valve/s.
capacity. They must be tested and approved
according to local safety regulations. A pressure-relieving device must be fitted to every
pressure vessel or equipment containing air at
Cables, chains or ropes must never be applied above atmospheric pressure, when installed
directly to lifting eyes. Always use an appropriate downstream of the unit.
shackle or hook, properly positioned. Arrange lifting
cables so that there are no sharp bends. If raised platforms are required to provide access to
the unit they must not interfere with normal
Use a spreader bar to avoid side loads on hooks, operation or obstruct access for lifting or
eyes and shackles. dismantling components. Platforms and stairs
should be of grid or plate construction with safety
When a load is on a hoist stay clear of the danger rails on all open sides.
area beneath and around it. Keep lifting
acceleration and speed within safe limits. Never In order to control the risk of Legionnaires Disease,
leave a load hanging on a hoist for longer than is CompAir strongly advise against the use of water
necessary. cooling tower systems for water cooled
compressors. A closed circuit radiator system is
preferred.
4. INSTALLATION PRECAUTIONS
page 7
CompAir
When mains power is switched on, lethal voltages 6. MAINTENANCE AND REPAIR PRECAUTIONS
are present in the electrical circuits and extreme
caution must be exercised whenever it is necessary Maintenance, repairs or modifications must only be
to carry out any work on the electrical system. carried out by competent personnel under a
qualified supervisor.
Do not open the starter compartment or touch
electrical components while voltage is applied If replacement parts are needed use only CompAir
unless it is necessary for measurements, tests or Genuine Parts.
adjustments. Such work should be carried out only
by a qualified electrician equipped with the proper Carry out the following operations before removing
tools and wearing appropriate body protection any panels from the enclosure or dismantling any
against electrical hazards. part of the unit.
When the unit is running under automatic control, 1. Isolate the compressor unit from the main
attach a sign stating ‘THIS UNIT MAY START electrical power supply. Lock the isolator in
WITHOUT WARNING’ next to the display panel. the ‘OFF’ position and remove the fuses.
If the unit is equipped with a Remote Start device, 2. Attach a label to the isolator switch and to the
attach warning notices stating ‘THIS UNIT CAN BE display panel carrying the warning ‘WORK IN
STARTED REMOTELY’ in prominent locations, PROGRESS – DO NOT APPLY VOLTAGE’.
one on the outside of the unit, the other inside the Do not switch on electrical power or attempt
control compartment. to start the unit if such a warning label is
attached.
As a further safeguard, take adequate precautions
to make sure there is no one checking or working 3. Close the isolating valve between the
on the unit before attempting to operate remote compressor unit and the user’s pipework.
start equipment. Attach a notice stating ‘CHECK Close the isolating valves in the cooling water
THAT ALL PERSONNEL ARE CLEAR OF THE inlet and outlet pipes. Attach a label to each
UNIT BEFORE STARTING’ or similar wording to valve carrying the warning ‘WORK IN
the remote start equipment. PROGRESS – DO NOT OPEN’.
Some parts of the compressor reach extremely 4. Bleed down all air pressure in the delivery
high temperatures. If panels are removed from the pipe between the non-return valve and the
enclosure take precautions against burns. The shut-off valve by carefully slackening the
cooling water outlet pipe is likely to reach 80°C and aftercooler condensate drain connection at
must be painted or marked according to the local the strainer inlet.
safety code. The pipe must be guarded or insulated
where injury to personnel could occur. 5. First and second stage pressure will be
exhausted through the dump silencers by the
If there is any indication that the compressor is action of the unloader solenoid valve. As an
overheating it must be shut down and the cause additional precaution, slacken the drain plug
investigated. Beware of burns from hot metal parts, at the base of the regulation air line filter to
hot oil and water when working on a unit which has release any residual pressure and leave it
recently been shut down. slack while work is in progress. When work is
completed remember to re-tighten the plug
The ‘Noise at Work Regulations 1989’ suggest that before starting the compressor.
ear protectors should be worn where noise levels
are 85 dB(A) or higher. With all covers in place, the Use only lubricating oils and greases approved by
noise levels of the compressors described in the CompAir. Make sure that the selected lubricants
manual are substantially lower than this figure comply with all relevant safety regulations,
unless installed in an already noisy environment. especially with regard to the risk of explosion or fire
and the possibility of decomposition or the
Be aware that high noise levels can interfere with generation of hazardous gases.
communication.
page 8
Oil Free Screw User Manual – Safety Procedures
Always clean up oil spills from the surrounding floor Check the direction of rotation of the fan motor, oil
and outside of the compressor unit before and after pump motor and main drive motor when starting up
maintenance work. Make sure that no oil is left on the compressor initially and after any work on the
or near the air intake components, including the electrical connections or switchgear (refer to the
suction regulator, which could be drawn into the Commissioning section of this manual).
compressor and contaminate the delivered air.
Do not use any flammable liquid to clean valves,
Make sure that all instructions concerning the filter elements, air pipes or any component carrying
operation and maintenance are strictly followed and a flow of air during normal operation. If chlorinated
that the complete unit, with all accessories and hydrocarbon non-flammable fluids are used for
safety devices, is kept in good running order. cleaning, safety precautions must be taken against
any toxic vapours which may be released.
The accuracy of pressure and temperature gauges
and switching thermometers must be regularly Do not use carbon tetrachloride.
checked. They must be renewed when acceptable
tolerances are exceeded. Precautions must be taken when using acids,
alkalis and chemical detergents for cleaning
Protection devices must be tested as described in machine parts and components. These materials
the Repair manual. cause irritation and are corrosive to the skin, eyes,
nose and throat. Avoid splashes and wear suitable
Keep the compressor unit clean at all times. Protect protective clothing and goggles. Do not breathe
components and exposed openings by covering mists. Ensure that soap and water are readily
with clean cloth or tape during maintenance or available.
repair work.
When disposing of condensate, old oil, used filter
Protect the motor, air intake, electrical and elements and other parts and waste material of any
regulation components against the entry of kind make sure that there is no pollution of any
moisture, e.g., when steam cleaning. drain or natural water-course and that no burning of
waste takes place which could cause pollution of
Precautions must be taken when carrying out the air. Protect the environment by using only
welding or any repair operation which generates approved methods of disposal.
heat, flames or sparks. The adjacent components
must always be screened with non-flammable
material and if the operation is to be carried out 7. PRECAUTIONS IN THE EVENT OF FIRE
near any part of the oil system, or close to a
component which may contain oil, the system must Use extreme caution when handling components
first be thoroughly purged, preferably by steam that have been subjected to fire or very high
cleaning. temperatures. Some components may contain
fluoroelastomer materials which decompose under
Never use a light source with an open flame to these conditions to form highly corrosive residues.
inspect any part of the unit. Skin contact can cause painful and penetrating
burns resulting in permanent skin and tissue
In no circumstances must any welding work or damage.
other modification be carried out on any pressure
vessel.
page 9
CompAir
page 10
Oil Free Screw User Manual
2
GENERAL DESCRIPTION
Page
Introduction 12
Air-Ends 12
Electronic Controller 12
Air System 14
Cooling System 15
Lubrication System 16
Regulation System 17
Starter 20
page 11
CompAir
GENERAL DESCRIPTION
1. INTRODUCTION 2. AIR-ENDS
3. ELECTRONIC CONTROLLER
page 12
Oil Free Screw User Manual – General Description
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
bar
psi
36 35 34 33 32 31 30 29 28 27 26 25 24 23 22 21 20 19
PI/97/067
CONTROL PANEL
page 13
CompAir
4. AIR SYSTEM Air from the second stage air-end passes through a
silencer, non-return valve, aftercooler and moisture
4.1 Description separator to the delivery outlet. The non-return
valve prevents air re-entering the compressor
The system consists of an intake air filter, silencer, during off-load running.
suction regulator, first and second stage air-ends,
intercooler, aftercooler, associated moisture During the unloading sequence air trapped
separators and safety valves, silencers, non-return between the second stage air-end and the non-
valve, regulation air line filter, shuttle valve and return valve is discharged to atmosphere through a
solenoid valve. silencer to reduce noise levels.
1 2 3 4 5 6 7 8 9 10 11 12 13 7
AIR
INTAKE
19
AIR
BLOW DISCHARGE
DOWN
18
20 CONDENSATE
DRAINS
PI/97/068
20
17 16 15 14
1. Air Intake Filter 8. Interstage Pressure Transmitter 15. Unloader Solenoid Valve
2. Silencer 9. Silencer 16. Regulation Line Filter
3. Suction Regulator 10. Non-return Valve 17. Shuttle Valve
4. First Stage Air-end 11. Delivery Pressure Transmitter 18. Silencer
5. Intercooler 12. Aftercooler 19. Differential Pressure Switch
6. Moisture Separator 13. Moisture Separator 20. Condensate Drain Solenoid
7. Safety Valve 14. Second Stage Air-End Valves
AIR SYSTEM
page 14
Oil Free Screw User Manual – General Description
DRAIN
9 10
8 11 VENT 2
DRAIN 12
7
4 3
PI/97/069
6 5
COOLING SYSTEM
page 15
CompAir
6. LUBRICATION SYSTEM
12
7 6
13
11
10
5
8 14
14
9
4
10
2
1
15 3 PI/97/070
LUBRICATION SYSTEM
page 16
Oil Free Screw User Manual – General Description
7. REGULATION SYSTEM
1 1
2 2
9 3 9 3
8 4
4
6 5 6 5
PI/97/071
UNLOADED LOADED
REGULATION SYSTEM
7.1 Description connected to the inlet of the first stage air end. The
higher pressure at the back of the diaphragm acts
The compressor runs continuously, loading and with the spring pressure to close the inlet valve
unloading at preset delivery pressures (P1 and P2 and open the blowdown valve, thus unloading the
set points). If air pressure remains above the P2 set compressor.
point for the run-on time the compressor will shut
down into Stand-by mode. The compressor will As the compressor unloads the interstage pressure
automatically restart as demand increases and the falls below atmospheric pressure causing the
pressure drops to the P2 set point. shuttle valve to switch. In this condition the inlet
valve is maintained closed by the vacuum at the
first stage inlet being passed via the unloader
7.2 Off Load Air Flow solenoid valve to the front of the diaphragm.
When the pressure is above the upper set point Atmospheric pressure is applied to the back of the
(P1), the controller de-energises the unloader diaphragm via the shuttle valve and unloader
solenoid valve. Interstage pressure is applied solenoid valve.
through the unloader solenoid valve to the back
(exhaust side) of the suction regulator diaphragm.
Simultaneously the front of the diaphragm is
page 17
CompAir
7.3 On Load Air Flow The compressor always starts off-load and remains
in this condition until the main motor start sequence
When the output pressure is below the lower is complete and the pre-set Load Delay time has
pressure set point (P2), the controller energises elapsed.
the unloader solenoid valve.
Suction created by the first stage air end creates a 7.4.3 Running
depression on the back (exhaust side) of the
suction regulator diaphragm chamber. The When the compressor is running a pressure
pressure differential across the diaphragm causes transmitter monitors the pressure in the user’s
the valve spindle to move and the suction regulator pipework. Pressure is maintained between the
begins to open. upper (P1) and lower (P2) pressure set points.
As the inlet valve opens, pressure in the interstage When the pressure is below the (P2) lower
increases and passes through the unloader pressure set point, the controller energises the
solenoid valve to the front (inlet side) of the unloader solenoid valve which controls the suction
diaphragm chamber. This causes the inlet valve to regulator. This causes the inlet valve to open fully
fully open and the compressor runs on load. and the compressor runs on-load.
If the compressor is started with the pressure The compressor continues to run on-load until the
above the lower pressure set point (P2), the upper (P1) pressure set point is reached. The
compressor will immediately enter Standby mode controller then de-energises the unloader solenoid
and will automatically start when the pressure falls. valve which causes the inlet valve to close, and the
compressor runs off-load. A non-return valve in the
delivery line prevents system air from exhausting
7.4 Operation through the blowdown valve.
7.4.1 Power first switched ON If the compressor is started with the pressure
above the lower (P2) pressure set point, the
When power is switched on the control system compressor will immediately enter Standby mode
checks that all pre-set conditions are correct and and will automatically start when the pressure falls.
the emergency circuits are in order. The display
shows the control program identification and part
number. When the internal checks are complete 7.4.4 Stopping
the display message changes to 'Ready to start'.
CAUTION: It is inadvisable to stop the compressor
during a motor start sequence.
7.4.2 Starting
If the EMERGENCY STOP button is pressed the
When the START button is pressed, the water stop water stop solenoid valve closes and the main
solenoid valve opens and the ventilation fan and oil motor, ventilation fan and oil pump motor will stop
pump motor starts. When the controller detects the immediately.
oil pressure is correct the main motor start
sequence begins. The display message shows CAUTION: Emergency Stop should only be used in
‘Starting’ a genuine emergency situation.
To minimise starting current the motor runs up to The compressor may be stopped manually by
speed in Star mode. After the pre-set Star/Delta pressing the stop button. When the STOP button is
time the motor drive circuit switches to Delta mode, pressed the compressor unloads and the main
drawing full load current at full motor speed. motor stops. The water stop solenoid valve,
ventilation fan and oil pump motor continue to run
for a further 30 seconds cooling down period.
page 18
Oil Free Screw User Manual – General Description
12 13 14
1 2
15 16
4
5
17 6
18
3
+ -
11
19
21
M + -
20
10
7 8 9
16
15
PI/97/093
page 19
CompAir
8. STARTER
THERMAL
OVERLOAD
RELAY
PI/97/155
page 20
X08 X07 X06 X05
6 5 4 3 2 1 6 5 4 3 2 1 7 6 5 4 3 2 1 7 6 5 4 3 2 1
F1
F2
F3
F4
F5
X2/1
X2/1
X2/2
X2/2
X2/2
X2/4
X2/6
X3/1
X3/1
X3/1
X3/2
X4/1
X4/1
X4/2
X4/2
X5/1
X5/1
X5/2
X5/2
X6/1
X6/1
X6/2
X6/2
R301
K201
K401
K402
K403
K404
K405
K406
X04
DIGITAL IN RS-485
1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9 1 2
12
F1/F2 Fused terminal, 1·6A X01 X02 X03
PI/97/154
page 21
INTERFACE ASSEMBLY
CompAir
page 22
Oil Free Screw User Manual
3
LEADING PARTICULARS
page 23
CompAir
LEADING PARTICULARS
page 24
Oil Free Screw User Manual – Leading Particulars
page 25
CompAir
page 26
Oil Free Screw User Manual – Leading Particulars
page 27
CompAir
Approx. weight of heaviest components (compressor air-ends/gearbox, all models), kg: 740
Motor weight, (with IP22 motor) kg: 509–08W/609–07W 750
509–10W/510–08W/609–10W610–10W 794
510–10W/512–08W/610–10W/612–07W 906
512–10W/515–08/612–10W 1005
515–09W/615–09W 1400
page 28
Oil Free Screw User Manual
4
INSTALLATION
Page
Guidelines 30
Installation Procedure 31
Storage Procedures 32
Attention Required During Long-term Storage 32
Attention Required During Short-term Storage 33
Preparation for Storage for up to Twelve Months 33
Procedure with Power Connected to Compressor 34
Procedure with Compressor Disconnected from Power 34
page 29
CompAir
INSTALLATION
! WARNING
● Refer to the safety procedures before ● Lethal voltages are used in this equipment.
installation of the compressor unit. Use extreme caution when carrying out
electrical checks. Isolate the power supply
before starting any maintenance work.
The compressor unit is supplied as a complete Note: Isolating valves should be installed on both
package and does not require securing to a the inlet and outlet cooling water pipes. The water
foundation. However, the supporting floor must inlet pipe should also incorporate a flow indicator. If
have a loading capacity sufficient to support the the quality of the cooling water is in doubt it should
weight of the unit (see ‘Leading Particulars’). be treated to prevent corrosion and scale
formation. Recirculating systems should be
In operation the unit will release heat into the protected against freezing, where necessary, by
surroundings. The compressor room should using a proprietary anti-freeze with inhibitors.
therefore be of adequate size and have good
ventilation. The recommended minimum size of If the compressor is to be coupled in parallel with
room is 50 m3. The inlet and outlet ventilation another compressor or connected to an existing air
openings should each have a minimum area of supply system, additional steps must be taken as
0·5 m2. set out in the ‘Safety’ section of this manual.
The ventilation inlet opening should be positioned If the compressor is coupled to a header used by
as low down as possible. The outlet opening other compressors, ensure that condensate from
should be positioned as high up as possible, the header cannot flow back into the compressor.
preferably in the roof or ceiling.
If air usage fluctuates rapidly or if the volume of the
A minimum of 1·5 m headroom is recommended user’s pipework is less than 4·25 m3 for each unit, a
above the compressor and a minimum of 1 m receiver of appropriate capacity should be installed
clearance on all sides for air circulation and to give between the compressor and the user’s pipework.
access for servicing. Do not obstruct doorways,
passages or walkways. Compressor units are inhibited against the effects
of moisture before shipment. If all blanking covers
The recommended cooling water quality is detailed and protective tapes remain secure and
in Appendix 5. undamaged the effective life of this process is 12
months from the date shown on the test card with
Service connections are required as follows: the machine. Refer to Section 3, ‘Storage
Procedures’, for details of attention required during
1. Air delivery outlet to the user’s pipework. storage and for the procedure to be followed if the
storage period is longer than 12 months.
2. Electrical power supply: 3-phase plus earth.
page 30
Oil Free Screw User Manual – Installation
1 2 3 4 5
PI/97/116
8 7 6
BASEFRAME CONNECTIONS
page 31
CompAir
page 32
Oil Free Screw User Manual – Installation
2. In the case of a new compressor, inspect the If power and cooling water are disconnected, rotate
crate on arrival and ensure that there is no the drive coupling by hand at weekly intervals as
water in the packing, the base of the described in para 3.1 item 4.
compressor or the protective plastic covering. If
there is evidence of moisture, dry out any damp
areas and also ensure that the packing and 3.3 Preparation for Storage for up to Twelve
plastic covering is dry before replacing. Months (full inhibition procedure)
6. If this is not effective and the coupling is still not For the solution, mix 64 gm of Shell VPI 280
free, contact the local CompAir distributor. (dicychlorohexyl ammonium nitrite) with
2 litres of acetone.
7. If the compressor is stored in conditions of high
humidity, renew the desiccant packs (500 gm Quantity required: 2 litres of solution
silica gel or equivalent) in the interstage per compressor.
moisture separator after 6 months.
Note: This inhibitor solution is not oil-based.
8. In the case of a new compressor, replace
protective covering. When using Shell VPI 280 agitate the solution
by shaking the spray can during application.
9. At the end of each 12 month storage period the
full inhibition procedure must be carried out.
3.3.2 Equipment Required:
3.2 Attention Required During Short-Term One spray gun with standard nozzle and baffle
Storage (up to one month) plate nozzle.
The compressor should be started and run for 10 to One plastic storage container.
15 minutes at least once each week. This
procedure applies to (a) a compressor which is Waterproof adhesive tape, as required.
shut down for a short period but remains connected
to power and coolant, and (b) a compressor which Plastic caps.
remains on ‘Standby’ duty in a multiple unit
installation.
page 33
CompAir
3.4 Procedure with Power Connected to likely to fall below freezing point, the water
Compressor circuit should be flushed through with a good,
standard automotive grade, anti-freeze
If the compressor has already been disconnected solution at the manufacturer’s recommended
from power, see para 3.5. strength.
9. Stop compressor. 20. Seal off the inspection opening with waterproof
tape, ensuring that the seal is air-tight.
10. Spray Shell VPI 280 solution into delivery
connection for 10 seconds (approx. 10 ml). 21. Paint all bare metal and exposed machined
surfaces with one coat of Croda CS 1033A
11. Replace inlet filter mesh and seal with preservative.
waterproof tape.
After completion of this procedure the compressor
12. Seal air delivery connection with waterproof may be left in store for up to 12 months but should
tape. be inspected regularly as detailed in para 3.2
‘Attention required during long-term storage’.
13. Place the following warning statement on
instrument panel.
3.5 Procedure with Compressor Disconnected
CAUTION: Before Starting the Compressor:- from Power
(a) Remove desiccant bags from moisture
Use the same equipment and inhibitor as described
separator and replace flange.
in para 3.4.
(b) Remove waterproof sealing tape from air
intake filter and gearbox air filter. 1. Disconnect the delivery pipework at the
baseframe connection.
14. Shut off water supply, and drain water circuit.
If possible disconnect pipework from water 2. Remove the inlet filter element and silencer.
supply. If anti-freeze has not been used in the
cooling water and if ambient temperature is
page 34
3. Remove the first stage moisture separator top
flange complete with the air pressure safety
valve.
page 35
CompAir
page 36
Oil Free Screw User Manual
5
COMMISSIONING
Page
Commissioning Procedure 38
Preliminary Mechanical Checks 38
Entering the Access Code 39
System Checks and Calibration 39
Checking/Altering Commissioning Parameters 43
Checking/Altering Operating Parameters 45
Re-setting Service Interval Timer 46
Final Mechanical Checks 47
Commissioning Parameters (compressor running on-load) 49
Commissioning Checklist 51
page 37
CompAir
COMMISSIONING
! WARNING
● Refer to the safety procedures before ● Lethal voltages are used in this equipment.
commissioning the compressor unit. Use extreme caution when carrying out
electrical checks. Isolate the power supply
before starting any maintenance work.
Note: We recommend that commissioning is Motor 220V/ 400V/ 220V/ 460V/ 575V/
carried out by a CompAir distributor. 50Hz 50Hz 60Hz 60Hz 60Hz
3. Open the access panel to the starter 11. Remove panels as required to gain access to
compartment. Check all screws and starter motor connections.
connections for security. Check all electrical
connections are correct and secure. 12. Inspect the motor and control wiring
connections to make sure they are correct
4. Ensure the controller to Extension module unit and secure. Replace all panels.
interface cable connections are correct and
secure. 13. Check that all protection blanks, air filter
covers and tapes have been removed.
5. Ensure the main supply cables and fuse
ratings comply with regulations. 14. Remove the four air-end/motor transportation
bolts (if fitted). These are coloured red for
6. Ensure the control transformer primary identification.
tapping connections are correct for supply
voltage. 15. Open the isolating valve to the user’s
pipework.
7. Ensure main motor thermal overload is set
correctly for motor F.L.C. and supply voltage, 16. Check that the air end and motor rotate freely.
as shown on the motor data plate.
17. Check oil level and top up if required.
8. Ensure MCB Q101 (MMS) is set correctly.
page 38
Oil Free Screw User Manual – Commissioning
1.2 Entering the Access Code Note: A guide to using the menu routines and
control unit menu structure diagrams is shown in
When an attempt to alter a parameter or Section 6 – Operation
option is made for the first time after entering
the menu routines, the controller will request
an access code. When this occurs the
following procedure should be followed.
Note: The values shown throughout these procedures are examples only.
Ready to start
Oil temperature 20°C
page 39
CompAir
(Steady display)
13. Press DOWN and repeat To scroll to the Test digital outputs
until the option shown on required option. Fan contactor 0
the right is displayed.
page 40
Oil Free Screw User Manual – Commissioning
24. Press ENTER. To set the zero pressure Set pressure > 5.51bar
measurement in the
controller.
page 41
CompAir
27. Press (+) or (-) as To adjust the LCD Adjust +/- :- 7.0bar
required to adjust the display reading to Press enter when ready
value shown on the match the slave
display. air gauge. (Pulsing display)
28. When the gauge and To store the pressure Commissioning - config.
display pressures are calibration value in
equal press ENTER. the controller. (After a delay the display
reverts to:)
Service diagnostics
Reset service hours
Service diagnostics
Reset service hours
page 42
Oil Free Screw User Manual – Commissioning
Note: The values shown throughout these procedures are examples only.
Refer to the Control Unit Menu Structure diagrams and check/set the commissioning parameters
page 43
CompAir
page 44
Oil Free Screw User Manual – Commissioning
Note: The values shown throughout these procedures are examples only.
page 45
CompAir
Note: The values shown throughout these procedures are examples only.
Service diagnostics
Reset service hours
page 46
Oil Free Screw User Manual – Commissioning
Notes:
2. Ensure that the air discharge pipe is disconnected from the user’s system.
3. Ensure that the discharge air is directed away from all persons in the area.
6. If electrical work
has to be carried
out switch power to
the compressor ‘OFF’.
Establish the correct
starting conditions.
Go to step 2.
page 47
CompAir
page 48
Oil Free Screw User Manual – Commissioning
18. Fully open water flow control To achieve full water flow.
valves.
page 49
CompAir
Note: The temperature guidelines are for compressors working in an ambient temperature of approximately
20°C and cooling water inlet temperature of 15°C with the correct water flow.
In higher ambient temperatures, higher cooling water inlet temperatures and/or low water flow conditions the
temperatures given may be higher. In this case the temperature alarm and trip levels may need to be raised.
page 50
Oil Free Screw User Manual – Commissioning
2. Cable, fuse ratings OK ............ 21. Maximum compressor pressure set. ............
15. Display units set. ............ 34. Emergency stop correct. ............
16. Compressor number set. (if comms 35. Temperatures and pressures in limits.............
facility available/fitted) ............
36. Oil level topped up. ............
17. Pressure control set points set. ............
37. All parameters recorded from
18. Run-on time set. ............ controller menu routines. ............
page 51
CompAir
page 52
6
OPERATION
Page
Routine Operation 54
Starting 54
Pressure Control 55
Displaying the Number of Hours Run 55
Changing the Displayed Value 56
Stopping 56
Emergency Stopping 56
Condensate Drain Operation 56
Service Interval Timer 56
Warnings 57
Shutdowns 57
Fault History Recall 57
Standby Operations 58
Default Values 66
page 53
CompAir
OPERATION
! WARNING
● Refer to the safety procedures before ● Lethal voltages are used in this equipment.
operating the compressor unit. Use extreme caution when carrying out
electrical checks. Isolate the power supply
before starting any maintenance work.
Note 1: If the compressor has been out of Note: Oil temperature is used as an example
operation for a prolonged period it is advisable to only. Actual display can be any of the
check performance and all regulation functions by displayed values in para 1.4.
carrying out the full commissioning procedure
before starting. See ‘Fault Messages’ for possible start-up
faults. If a fault exists and a repair is
necessary, power to the compressor must be
1. ROUTINE OPERATION (Refer to Control Panel isolated and the fault rectified.
diagram in Chapter 2, ‘General Description’)
If the reset indicator is lit, RESET must be
Note: The temperatures and pressures given in pressed following rectification of the fault,
the procedures are shown as examples only. before the compressor will start.
a) The POWER ON indicator (22) is lit. a) Certain menu routines are in use.
b) The status display (5) shows: b) The remote starting facility has been
enabled. In this instance the display
C20627/nn/xx/nn panel REMOTE CONTROL indicator (20)
will be lit and the display will show:
SF3LFnnUN_ddmmmyy
Unable to start
c) Either or both the REMOTE (20) and
AUTO RESTART (21) indicators are lit if Remote start enabled
these facilities have been selected. See
also ‘Remote Control’ and ‘Automatic 5. During the initial starting period, the drive
Restart’ in Appendix 1, Remote Options. motor starts in Star connection and the status
display will show:
3. After a few seconds, provided no fault exists,
the status display will show: Starting
Oil temperature 20°C
Ready to start
Oil temperature 20°C
page 54
Oil Free Screw User Manual – Operation
6. Following the motor Star/Delta switch-over 2. If the compressor is off-load for longer than
and during the subsequent load delay period, the ‘Run-on Time’, the compressor will stop
the status display will show: and the status display will change to:
Offload Stopping
Oil temperature 20°C Oil temperature 40°C
7. Provided the delivery pressure is below the 3. After the stopping period the display will
lower set point (P2) the compressor runs on change to:
load.
Standby
Onload
Oil temperature 40°C
Oil temperature 25°C
Note: If the START button is pressed whilst the
8. Fault conditions and service requirements are compressor is stopping the display changes to
continuously monitored (from start-up) and ‘Standby’ immediately.
warning and the appropriate status messages
are displayed. 4. When air demand lowers the pressure below
the lower set point P2 the compressor will
9. To interrogate other temperature or interstage restart and run on-load. The display will show:
pressure information press VALUE (see para
2, Using The Menu Routines). Starting
Oil temperature 20°C
10. To interrogate the hours run and service
hours information press HOURS. (see para 2, changing to:
Using The Menu Routines).
Offload
11. To show operating parameters, fault history, Oil temperature 20°C
etc. or to alter programmed settings, press
during load delay time, then:
ENTER (10) to access the menu routine (see
para 2, Using The Menu Routines). On load
Oil temperature 25°C
1.2 Pressure Control
1.3 Displaying the Number of Hours Run.
1. The compressor will unload and load in
response to varying air demand when the
1. The HOURS button (30) is used to display the
upper and lower set points P1 and P2 are
hours run by the compressor and the hours to
reached. When the compressor goes off-load
run before a service is due.
the system blows down. The controller loads
and unloads the compressor by fully opening
2. Successive presses of the HOURS button
or fully closing the suction regulator inlet
give the following display sequence:
valve. The display alternates, as appropriate,
between:
Total hours 1000
Offload Hours on load 800
Oil temperature 45°C Service hrs to run 3000
and
3. The display will cancel itself after a short
Onload period or it can be cancelled immediately by
pressing RESET.
Oil temperature 45°C
page 55
CompAir
1. TheVALUE button (33) is used to step through 1. When the EMERGENCY STOP (17) is
the compressor operating temperatures and pressed, the compressor will stop
interstage pressure displays. immediately and the system will blow down.
2. Successive presses of the VALUE button give 2. The RESET indicator will pulse and the
the following display sequence. display will show:
Ready to start
Oil temperature 40°C
page 56
Oil Free Screw User Manual – Operation
2. When the compressor has reached the 4. The occurrence of another warning after any
running hours at which a service is required, previous warning has been acknowledged will
the SERVICE indicator (35) will flash. If again cause the SERVICE indicator to flash
SERVICE (34) is now pressed the SERVICE continuously and the mimic diagram indicator
indicator (35) will stop flashing and remain lit. appropriate to the second fault will also light.
The RESET indicator (32) will then flash
continuously and the status display will show 5. It may not be convenient to respond to a
the service advice message below: warning immediately. In this case press
RESET to cancel the flashing service
Onload indicator and to restore the status and
selected value displays. The mimic diagram
Service due
indicator will remain lit to indicate that
attention is required.
3. The compressor must be stopped and
isolated to carry out the required service (see
‘Safety Procedures’). On completion of the
1.10 Shutdowns
service the ‘service hrs to run’ value must be
reset to maximum by using the Service
1. If a shutdown occurs, the compressor will
Diagnostics menu routine.
stop. This can occur at any time after the
compressor has been started.
4. It may not be convenient to respond to the
service due message immediately. In this
Both RESET and the appropriate mimic
case press RESET (31) to cancel the flashing
diagram indicator will flash continuously and
RESET indicator and restore the status and
the SERVICE indicator will light. If the menu
selected value display. The service indicator
routine is in use when a shutdown occurs the
will remain lit to indicate that a service is
appropriate panel and mimic diagram
required.
indicators will light and flash as normal. The
current message will not be overwritten until
RESET is pressed or the display reverts to
1.9 Warnings
the fault message after a period of time.
1. If a service is required, the SERVICE indicator
2. The display will show:
(35) and the appropriate mimic diagram
indicator will flash continuously. If SERVICE
Fault shutdown
(34) is pressed the SERVICE indicator will
stop flashing and stay lit in acknowledgement. (Relevant shutdown message) See Display
The RESET indicator (32) will flash messages
continuously and the display will show the
required action (e.g. an air filter change) as
below: 1.11 Fault History Recall
page 57
CompAir
1.12 Stand-by Operations With the mains power on and ENTER pressed, the
text display on the control panel will show two lines
A compressor on stand-by duty must be started of text. The top line indicates the menu in use and
and run for 10 minutes per week. the bottom line the parameters in use.
If the user’s air usage is insufficient to allow the The diagrams at the end of this section show the
compressor to run for 10 minutes the compressor sequence of messages available and the buttons
should be run Off-load as follows: to press to obtain the required message.
1. Ensure the Run On time on the controller is In the diagrams the solid line boxes represent the
set to 10 minutes. message window and the broken line boxes are
reader information or instructions.
2. At the remote inputs, ensure Remote Load
Input is open, then close the Remote Load Notes for use with SureScan menu diagrams
Enable.
1. Show program variant – Displays a reference
3. If the compressor is not already in standby, number for the controller program variant, for
start the compressor which will then go into reference only. Press Return to return to
stand by. main menu.
4. Momentarily close the Remote Load input. 2. Test digital inputs – Test routine for each
The compressor will start . individual input. Input cards test routine.
Note: Ensure that the Remote Load input is 3. Test analogue inputs – Test routine for
opened before the delta contact is closed or the pressure and temperature inputs.
compressor may load. Preconditioner card PT1000 conditioner units
and pressure transmitters test routine.
5. Open the Remote Load Enable to put control
back to the transducer. 4. Test keypad – Keypad test routine. Each key
pressed will be displayed to establish
6. The compressor will now run for the time set. operation. Press RESET to exit routine.
page 58
Status Message
Oil temperature 25°C
Main Menu Go to 2 of 7
To continue
PI/97/094
page 59
Oil Free Screw User Manual – Operation
From 1 of 7
page 60
CompAir
Main Menu
Operational settings
Go to 3 of 7
Service diagnostics
Go to 3 of 7
Fault history recall 2 Total hours 1000 St2 intake temp 45°C
Fault message
Commissioning - config
Go to 6 of 7
Pressure 7.0bar St2 delivery temp 165°C
Commissioning - values
Go to 7 of 7
Interstage Press 2.0bar Plant del temp 30°C
Fault history recall 0 St1 delivery temp 160°C Water out temp 31°C
Return to previous menu
PI/97/095
Drain open time 25sec Drain open time 15sec Test digital inputs
See Note 2
Drain shut time 125sec Drain shut time 200sec Test analogue inputs
See Note 3
Test display
See Note 5
PI/97/096
page 61
page 62
CompAir
Adjust pressure up/down Adjust until display tracks Calibration complete 2 sec
Press enter when ready pressure variations correctly
PI/97/097
PI/97/098
page 63
page 64
CompAir
From 1 of 7 Commissioning-Config
Language: English Language: Option
Trip type 1
Alarm type 3
Remote fault 5
Trip type 2
Start inhibit
Return to previous menu
PI/97/099
Max. overpress 10.6bar Oil temp alarm 70°C Plant del alarm 40°C
Star/delta time 25sec St1 delivery trip 200°C Water in trip 30°C
Load delay time 60sec St1 delivery alarm 180°C Water in alarm 27°C
Max. service hrs 4000 St2 intake trip 65°C Water out trip 65°C
Autorestart delay 100sec St2 intake alarm 60°C Water out alarm 55°C
Interstage trip 4.0bar St2 delivery trip 200°C Load default values Default values loaded 2 sec
Interstage alarm 3.8bar St2 delivery alarm 180°C Return to previous menu
PI/97/100
page 65
CompAir
page 66
Oil Free Screw User Manual – Operation
No reset indicated The ‘Reset’ button has been pressed when there is no reset required.
No service indicated The ‘Service’ button has been pressed when there is no service action
required.
Remote start enabled Starting has been attempted via the Control Panel when the remote start
facility is enabled (Panel starting is disabled).
Stop compressor first The compressor is running and a menu selection has been attempted which
can only be used when the compressor is stopped.
4.2 Shutdowns
Rotation fault Main supply phase rotation is detected to be incorrect or voltage is below
acceptable limits.
Main motor fault The compressor has shut down because of main motor overcurrent or high
temperature.
Fan motor fault The compressor has shut down because of fan motor overcurrent.
Oil pump fault The compressor has shut down because of oil pump motor overcurrent.
MPCB Q101 tripped The protection circuit breaker Q101 is in the tripped condition.
High air pressure The compressor has shut down because the delivery pressure has
exceeded the maximum pressure setting.
Interstage press trip The interstage pressure has exceeded the maximum set pressure limit.
Oil pressure low The compressor has shut down because the oil pressure has fallen below
the minimum pressure limit.
page 67
CompAir
Shutdowns (continued)
Oil temperature trip The compressor has shut down because the oil temperature has exceeded
the upper (trip) limit.
St1 delivery temp trip The compressor has shut down because the first stage delivery temperature
has exceeded the upper (trip) limit.
St2 intake temp trip The compressor has shut down because the second stage intake
temperature has exceeded the upper (trip) limit.
St2 delivery temp trip The compressor has shut down because the second stage delivery
temperature has exceeded the upper (trip) limit.
Plant delivery t trip The compressor has shut down because the plant air delivery temperature
has exceeded the upper (trip) limit.
Del press probe fault The compressor has shut down because the air delivery pressure transmitter
is indicating a pressure outside of normal limits.
Int.St press probe fault The compressor has shutdown because the interstage pressure transmitter
is indicating a pressure outside of normal limits.
Oil temp probe fault The temperature sensor is indicating a temperature outside of normal limits.
St1 del temp probe fault The temperature sensor is indicating a temperature outside of normal limits.
St2 in temp probe fault The temperature sensor is indicating a temperature outside of normal limits.
St2 del temp probe fault The temperature sensor is indicating a temperature outside of normal limits.
Plant del t probe fault The temperature sensor is indicating a temperature outside of normal limits.
Remote fault The compressor has shutdown because one of the remote fault inputs has
been activated.
Water in temp trip The water inlet temperature has exceeded the upper (trip) limit.
Water out temp trip The water outlet temperature has exceeded the upper (trip) limit.
Oil level low The sump oil level is detected to be low while the compressor is stopped.
(start inhibit)
page 68
Oil Free Screw User Manual – Operation
4.3 Warnings
Change air filter A high differential pressure has been detected across the air filter indicating
the need for an air filter element change.
Change oil filter A high differential pressure has been detected across the oil filter indicating
the need for an oil filter change.
Interstage press alarm The interstage pressure has reached the programmed warning value.
Oil temperature alarm The oil temperature has reached the programmed warning value.
St1 delivery temp alarm The first stage delivery temperature has reached the programmed warning
value.
St2 intake temp alarm The second stage intake temperature has reached the programmed warning
value.
St2 delivery temp alarm The second stage delivery temperature has reached the programmed
warning value.
Plant delivery t alarm The plant air delivery temperature has reached the programmed warning
value.
Water in t probe fault The temperature sensor is indicating a temperature outside of normal limits.
Water out t probe fault The temperature sensor is indicating a temperature outside of normal limits.
Water in temp alarm The water inlet temperature has reached the programmed warning value.
Water out temp alarm The water outlet temperature has reached the programmed warning value.
Remote alarm One of the remote alarm inputs has been activated.
Service due The service interval countdown timer has reached zero hours indicating a
service is now due.
page 69
CompAir
Total hours Shows the recorded total number of compressor running hours on and off
load.
Hours on load Shows the recorded total number of compressor running hours on load only.
Max. service hrs Shows the maximum programmed hours before a service is required.
Service hrs to run Indicates the number of running hours remaining before a service is
required.
Reset service hours Invitation to reset the service interval hours to the maximum programmed
service hours.
Offload The compressor is running off load (the run-on time has not expired).
Ready to start The compressor is waiting for a start signal (keypad or external) and no fault
has been detected.
Remote stopped Starting is inhibited by the remote stop input being open circuit.
Standby The compressor has been ‘started’ but is waiting for the delivery pressure to
fall below the lower setpoint, before the motor is energised.
Stopping The stop button has been pressed but the oil pump motor, canopy cooling fan
and the water solenoid will remain energised for 30 seconds.
page 70
Oil Free Screw User Manual
7
MAINTENANCE
Page
Routine Maintenance 72
Cleanliness 72
Recording Pressures and Temperatures 72
Maintenance Record 72
Electrical Connections 72
Leaks 73
Regular Checks 73
Lubricating Oil 73
Maintenance Schedule 73
Torque Schedule 75
Maintenance Procedures 81
Enclosure Filters 81
Condensate Drain 81
Regulation Air Line Filter 82
Intake Air Filter 82
Water Strainer and Condensate Strainers 83
Oil System 83
Balance Piston Diaphragms 84
Non-Return Check Valve (NRV) 84
Expansion Compensator Seal 84
Electrical System 85
Electric Motors 85
Moisture Separator 86
Flexible Drive Coupling 86
page 71
CompAir
MAINTENANCE
1. ROUTINE MAINTENANCE
! WARNING
● Refer to the safety procedures before ● Lethal voltages are used in this equipment.
carrying out any maintenance or servicing Use extreme caution when carrying out
work on the compressor unit. . electrical checks. Isolate the power supply
before starting any maintenance work.
To ensure the efficient operation of the 1.2 Recording Pressures and Temperatures
compressor unit the user must check performance
regularly and carry out the necessary adjustments Keep a regular record of the compressor operating
to maintain correct settings. This section gives the pressures and temperatures by noting the value
information needed by the user for this purpose. readings, together with ambient air temperature, in
a record book. The readings should be taken when
It is a condition of the Warranty cover that the unit conditions are stable and with the compressor
is properly maintained and adjusted, that all running on full load.
checks, routine maintenance and regular servicing
listed in the Maintenance Schedule are carried out
at the specified intervals and that an accurate 1.3 Maintenance Record
record is kept of the work.
Keep a careful record of all servicing, maintenance
It is recommended that service and maintenance is and repair work carried out on the compressor.
carried out by your local CompAir Distributor. This record will form a useful reference. Any
variation from normal operation will be noticeable
All CompAir compressors are fitted with high immediately, alerting the user to a possible need
performance filtration equipment. However, if the for servicing or maintenance. The frequency of
working environment is particularly hostile the filter recurrence of a particular repair task could reveal
elements and the heat exchangers will require an unsatisfactory operating condition which should
attention at more frequent intervals than specified be corrected.
in the schedule.
page 72
Oil Free Screw User Manual – Maintenance
page 73
CompAir
Item Action
Weekly Checks
Service A plus:
Oil breather filter element Replace.
Oil system Change oil.
Oil filter element Renew.
Intake air filter element Renew.
Balance piston diaphragms Renew. (Models 509–515 and 609–615 Only)
Regulation air line filter element Renew.
Intercooler tubestack Check condition.
Clean.✻
Aftercooler tubestack Check condition.
Clean.✻
Oil cooler Check condition.
Clean.
Drive motor connections Ensure secure.
Starter connections Ensure secure.
2nd stage non-return valve Inspect and renew if necessary.
Cooling Water Quality Inspect the cooling water quality against the specification
detailed in Appendix 5.
Service B plus:
Balance piston diaphragms Renew. (Models 504–508 and 604–608 Only)
★Suction regulator valve diaphragm Renew.
★Drive coupling inserts Examine and renew if necessary.
▲Starter contactors Examine and renew if necessary.
page 74
Oil Free Screw User Manual – Maintenance
✻ Increases in temperature noted during weekly checks will indicate that the tubestacks may require
cleaning at more frequent intervals.
★ The servicing of these items should normally be carried out by a local CompAir Distributor.
▲ The servicing of these items is not covered in the Repair Manual and must only be carried out by a
qualified technician.
Note: For information on lubrication of motor bearings refer to para 4.11 ‘Electric Motors’.
Incorrect tightening of air pipework flange bolts may cause premature failure of the gaskets. All flange bolts
should be tightened in accordance with the torque schedules below and re-checked at every 4000 hour
service. The bolts should be tightened in a sequence of diametrically opposite pairs to ensure even loading.
page 75
CompAir
page 76
Oil Free Screw User Manual – Maintenance
page 77
CompAir
page 78
Oil Free Screw User Manual – Maintenance
Models 504–508/604–608
Models 504–505/604–605
Intercooler joint kit C11158–5910 2
Aftercooler joint kit C11158–5911 2
Models 506–508/606–608
Intercooler joint kit C11158–5912 2
Aftercooler joint kit C11158–5913 2
page 79
CompAir
Models 509–515/609–615
page 80
Oil Free Screw User Manual – Maintenance
4. MAINTENANCE PROCEDURES
! WARNING
● Refer to the safety procedures before 3. Attach a label carrying the warning
carrying out any maintenance or servicing ‘WORK IN PROGRESS – DO NOT
work on the compressor unit. APPLY VOLTAGE’ to the isolator switch
and to the display panel. Do not switch on
● Lethal voltages are used in this equipment. electrical power or attempt to start the unit
Use extreme caution when carrying out if such a warning label is attached.
electrical checks. Isolate the power supply
before starting any maintenance work. 4. Bleed down all air pressure in the delivery
pipe between the non-return valve and the
● Where a maintenance procedure below shut-off valve by carefully slackening the
includes the warning ‘The compressor aftercooler condensate drain connection at
must be stopped’ the following steps must the strainer inlet.
be taken before work is commenced:
5. First and second stage pressure will
1. Close the isolating shut-off valve to the exhaust through the dump silencers by the
user’s pipework. Close the isolating valves action of the unloader solenoid valve. As
in the cooling water inlet and outlet pipes. an additional precaution, slacken the drain
Attach a label carrying the warning ‘WORK plug at the base of the regulation air line
IN PROGRESS – DO NOT OPEN’ to each filter to release any residual pressure and
isolating valve. leave it slack while work is in progress.
When work is completed remember to re-
2. Switch the power supply ‘OFF’ at the tighten the plug before starting the
isolator. compressor.
The compressor is provided with two coarse Moisture present in the compressed air condenses
screen filters in the panels of the enclosure. One in the interstage and second stage moisture
acts as a pre-filter for the intake air and the other separators and is drained by solenoid operated
to filter the ventilation air. valves.
page 81
CompAir
4.3 Regulation Air Line Filter It is always better to renew the intake air filter
element rather than to try to clean it. In any
This filter separates moisture and solid impurities cleaning operation, however carefully done, there
from the regulation air system. The moisture and is a risk of critical damage to filter efficiency and
other contaminants collect in the filter bowl and dirt particles remaining on the element or being
must be cleared regularly. carried over to the clean side.
2. When the air being discharged is clean, close 1. Remove panels as required to gain access to
the drain plug. the intake air filter.
The compressor must be stopped. 3. Clean the inside of the filter body.
CAUTION: Avoid excessive strain on the pipework 4. Fit the new element in the filter body and refit
when removing or refitting the filter bowl. the cover.
1. Hold the filter housing securely and unscrew Always fit a new filter element at the specified
the bowl from the housing. service intervals. However, if cleaning must be
resorted to, carry out the following procedure.
2. Unscrew the retainer assembly, remove the
collar and withdraw the element from
retainer. 4.4.2 To Clean the Element by Air Blast:
3. Clean out the bowl with a mild detergent CAUTION: Do not use high
solution. Rinse and dry it thoroughly. ! pressure air supply.
4. Clean the filter housing by blowing with low 1. Using an air line supplying dry, low-pressure
pressure (max. 0·5 bar) compressed air. air (maximum 0·5 bar) carefully blow out the
inner cavity, ensuring that the air stream
5. Fit new element over retainer, fit the collar passes through the element from the clean
and screw firmly by hand into the housing. side.
6. Hold the filter housing securely and screw the 2. When all contamination has been removed,
filter bowl firmly by hand into the housing. inspect the element for cracks, holes or other
damage by holding the element up against a
light source. If any damage is evident the
4.4 Intake Air Filter element must be discarded and a new one
fitted.
The servicing intervals required by the intake air
filter will depend on the dust conditions prevailing 3. Re-install the clean element in the filter body
on site. and refit the cover.
page 82
Oil Free Screw User Manual – Maintenance
4.5 Water Strainer And Condensate Strainers 1. Remove enclosure panels as required.
The compressor must be stopped 8. Ensure that breather is dry and refit to filler
pipe.
Note: Allow a minimum of 30 minutes after
stopping for the oil in the system to settle. 9. Start and run unit for 60 seconds to circulate
oil, check for leaks, then press STOP button.
1. Open the enclosure to gain access to the oil
filler and sightglass. 10. Allow 30 minutes for oil to settle, check oil
level and top up as necessary.
2. Check the sightglass visually. The oil level
should be on the ‘H’ or ’MAX’ mark. 11. Refit enclosure panels.
3. If the oil level is low, remove the canister Note: The oil filter element should be renewed
from the oil breather pipe and gradually top after every 8000 operating hours or every year,
up the reservoir to the correct level with whichever is sooner or when indicated by the
recommended or approved oil of the type in control system CHANGE OIL FILTER message
use. After each small quantity has been
added allow time for the change in level to be The compressor must be stopped.
indicated on the sightglass. This will prevent
overfilling. 1. Unscrew and discard the old oil filter element.
4. Refit the oil breather filter canister. 2. Carefully clean out the filter housing.
5. Close the enclosure panel. 3. Apply a thin film of clean oil to the element
seal.
4.6.2 To Change the Oil: 4. Screw in the new element by hand until seal
contact is made and then continue tightening
The compressor must be stopped for a further quarter of a turn.
page 83
CompAir
4.6.4 To Clean the Oil Breather Element: Note: The valve is secured between the flanges by
pressure exerted by the securing screws and nuts.
1. Remove the canister from oil filler/breather It is not positively located.
pipe.
2. Slacken the lower screws and nuts securing
2. Wash the element in warm (50°C) mild the valve between the discharge pipe
detergent solution. flanges. Remove the upper screws, washers
and nuts. Slacken the screws and nuts at the
3. Rinse thoroughly and dry. aftercooler flange if necessary.
4. Refit the canister to oil filler/breather pipe. 3. Remove the valve and renew any worn or
damaged parts. CAUTION: Do not lubricate.
4.7 Balance Piston Diaphragms 4. Fit new joints to the valve and refit between
the flanges. Ensure that the valve is correctly
4.7.1 To Renew the Diaphragms: positioned, that the lifting eye is uppermost
and that the direction of flow arrow is pointing
1. Remove the rear fill-in panel from the in the correct direction.
enclosure.
5. Refit the screws, nuts and washers and
2. Remove the regulation air pipe from the first tighten in sequence using the correct torque
stage diaphragm cover. Disconnect the loading.
regulation air pipe from the second stage
diaphragm cover. 6. Start and run the compressor until working
temperatures are reached. Stop and re-
3. Remove the screws and washers securing tighten the flange bolts.
the covers to the casing. Remove the covers.
Remove and discard the diaphragms. 7. Refit the enclosure panel.
6. Refit the regulation air pipe to the first stage 2. Remove the screws, nuts and washers
diaphragm cover. Re-connect the regulation securing the compensator to the intercooler.
air pipe to the second stage diaphragm
cover. 3. Remove the four bolts securing the first stage
discharge pipe flange to the compensator.
7. Refit the enclosure panel.
4. Remove the compensator from the
intercooler. Withdraw the flanged pipe from
4.8 Non-Return Check Valve (NRV) the discharge pipe. Remove and discard the
‘O’ ring.
4.8.1 To Inspect the Valve:
5. Ensure that the ‘O’ ring groove is clean and
Stop the compressor, isolate from air main without sharp edges. Ensure that all pipes
and release all pressure and component parts are free from dirt and
contaminates. Fit a new ‘O’ ring into the
1. Remove the enclosure side panel. groove. Coat the exposed part of the ‘O’ ring
with soft soap.
page 84
Oil Free Screw User Manual – Maintenance
6. Slide the flanged pipe into the discharge pipe. 4.10.1 To Check the Electrical Connections:
Renew the joints and refit the compensator to
the intercooler. Refit the screws, washers and Carefully examine the electrical wiring and check
nuts. the security of all connections and terminals.
8. Refit the enclosure panel. The main drive motor may have provision for
lubrication of the bearings at both ends of the shaft
or may be fitted with pre-packed shielded bearings
4.10 Electrical System which require attention only at major service
intervals. The cooling fan and oil pump motors are
fitted with sealed bearings and should not need
WARNING attention.
!
If a non-standard motor is fitted the user should
● Lethal voltages are used in this take advice from the local CompAir BroomWade
equipment. Use extreme caution when distributor before the compressor is put into
carrying out electrical checks. Isolate extended operation.
the power supply before starting any
maintenance work.
4.11.2 Lubricated Bearings
Note 1: For motors above 132 kW rating it is recommended that at every second service the bearing
housings are completely cleaned of old grease before refilling
Note 2: The intervals stated may have to be reduced by up to 50% when operating in ambient temperatures
consistently above 30°C.
page 85
CompAir
Where no grease nipples are provided the 4.13.1 To Check the Coupling Backlash:
bearings are either single or double shielded
and pre-packed with grease. These bearings do The compressor must be stopped and isolated
not require periodic re-lubrication but should be from both the electrical supply and air pipework.
renewed after 25000 hours of operation in
normal environments. Reach through the access opening in the
bellhousing and hold the drive shaft on each side
Note: We recommend that this work is carried of the coupling. Check the coupling backlash
out by a CompAir distributor. which should not exceed 6 mm. If the backlash is
excessive it will be necessary to change the
coupling inserts.
4.11.4 To Lubricate the Motor Bearings:
The recommended grease for lubrication of the 4.13.2 To Renew the Inserts:
motor bearings is Esso (Exxon) Unirex N3 or an
equivalent lithium complex grease. It is recommended that this work is carried out by a
CompAir distributor.
Note: It is important that the motor bearings are
not over-lubricated.
page 86
Oil Free Screw User Manual
8
FAULT FINDING
Page
Shutdown Messages 88
Warning Messages 92
page 87
CompAir
FAULT FINDING
The controller has a memory facility that retains a In operation the compressor is protected by
fault history. Details of 15 previous situations can circuits which are triggered when a fault arises and
be displayed, including the fault message together either cause the compressor to shut down or
with recorded hours, compressor state (standby, indicate that a servicing action is required.
on-load, off-load etc.), plant temperatures and
pressures.
! WARNING
● Refer to the safety procedures before ● Lethal voltages are used in this
carrying out any fault finding equipment. Use extreme caution when
investigation. carrying out electrical checks. Isolate
the power supply before starting any
maintenance work.
1. SHUTDOWN MESSAGES
Emergency stop (1) Emergency Stop (1) Check cause of fault and
switch operated. rectify. Turn Emergency Stop
switch to release latch. Press
RESET.
(2) Starter circuit fuse F1 blown. (2) Check cause and rectify.
Main motor fault (1) High ambient temperature. (1) Check room ventilation.
(2) Insufficient cooling air flow. (2) Inspect/clean: enclosure
filter; ducting; motor cooling
air intake.
(3) Fan operation/rotation incorrect. (3) Check and rectify electrical
circuit.
(4) Low voltage/high current. (4) Check power supply.
(5) Thermal overload F101 (5) Check setting and reset.
incorrectly set.
page 88
Oil Free Screw User Manual – Fault Finding
Fan motor fault (1) High ambient temperature. (1) Check room ventilation.
(2) Insufficient cooling air flow. (2) Inspect/clean: enclosure
filter; ducting; motor cooling
air intake.
(3) Low voltage/high current. (3) Check power supply.
(4) Circuit breaker F102 (4) Check setting and reset.
incorrectly set.
Oil pump fault (1) High ambient temperature. (1) Check room ventilation.
(2) Insufficient cooling air flow. (2) Inspect/clean: enclosure filter;
ducting; motor cooling
air intake.
(3) Low voltage/high current. (3) Check power supply.
(4) Circuit breaker F103 (4) Check setting and reset.
incorrectly set.
MPCB Q102 tripped (1) Circuit breaker incorrectly set. (1) Check setting and reset.
(2) Oil pump/fan motor circuit fault. (2) Check cause and rectify.
Oil temperature trip (1) High ambient temperature. (1) Check room ventilation.
(2) Insufficient cooling water (2) Check water supply. Check
flow. adjustment of water valve.
Inspect/clean water strainer.
Inspect/clean oil cooler.
(3) Temperature sensor fault. (3) Rectify/renew.
(4) Sensor wiring fault. (4) Check wiring.
St1 delivery temp trip (1) High ambient temperature. (1) Check room ventilation.
(2) Insufficient cooling water flow. (2) Check water supply. Check
adjustment of water valve.
Inspect/clean water strainer.
(3) Temperature sensor fault. (3) Rectify/renew.
(4) High interstage pressure. (4) Inspect/clean air coolers.
St2 intake temp trip (1) Insufficient cooling water flow. (1) Check water supply. Check
adjustment of water valve.
Inspect/clean water strainer.
(2) High ambient temperature. (2) Check room ventilation.
(3) Temperature sensor fault. (3) Rectify/renew.
page 89
CompAir
St2 delivery temp trip (1) Insufficient cooling water flow. (1) Check water supply. Check
adjustment of water valve.
Inspect/clean water strainer.
(2) Air flow restriction. (2) Inspect/clean aftercooler.
(3) Temperature sensor fault. (3) Rectify/renew.
Plant delivery t trip (1) Insufficient cooling water flow. (1) Check water supply. Check
adjustment of water valve.
Inspect/clean water strainer.
Inspect/clean intercooler.
(2) Temperature sensor fault. (2) Rectify/renew.
Interstage press trip (1) Air flow restriction. (1) Inspect/clean air coolers.
Oil pressure low (1) Low oil level. (1) Investigate for leaks,
top up oil level.
(2) Oil pump fault. (2) Investigate and rectify.
(3) Relief valve failure. (3) Adjust/Renew valve.
(4) Pressure switch fault. (4) Renew pressure switch.
(5) Oil cooler restriction. (5) Clean cooler.
(6) Oil filter blocked. (6) Renew oil filter element.
High air pressure (1) Compressor is failing to unload. (1) (a) Check/renew solenoid
operated unloader valve.
(b) Check suction regulator
inlet valve closing fully.
Rectify if necessary.
(2) Pressure transmitter fault. (2) Check/renew pressure
transmitter.
Del press probe fault (1) Pressure transmitter fault. (1) Renew pressure transmitter.
(2) Transmitter wiring fault. (2) Check and rectify fault.
Int.St press probe fault (1) Pressure transmitter fault. (1) Renew pressure transmitter.
(2) Transmitter wiring fault. (2) Check and rectify fault.
St1 del temp probe fault (1) Temperature sensor fault. (1) Renew temperature sensor.
(2) Sensor wiring fault. (2) Check and rectify fault.
(3) PT1000 conditioner unit fault. (3) Renew conditioner unit.
page 90
Oil Free Screw User Manual – Fault Finding
St2 in temp probe fault (1) Temperature sensor fault. (1) Renew temperature sensor.
(2) Temperature sensor wiring fault. (2) Check and rectify.
(3) Preconditioner card fault. (3) Check/renew card.
St2 del temp probe fault (1) Temperature sensor fault. (1) Renew temperature sensor.
(2) Sensor wiring fault. (2) Check and rectify fault.
(3) PT1000 conditioner unit fault. (3) Renew conditioner unit.
Plant del t probe fault (1) Temperature sensor fault. (1) Renew temperature sensor.
(2) Temperature sensor wiring fault. (2) Check and rectify.
(3) Preconditioner card fault. (3) Check/renew card.
Remote fault (1) Remote fault loop open circuit. (1) Find cause and rectify.
Extension fault (1) Fuse F2 failed. (1) Check cause and rectify.
(2) Interface cable insecure. (2) Check interface cable.
(3) Extension module failure. (3) Renew Extension module.
Rotation fault (1) Supply wiring configuration (1) Check supply wiring
incorrect, motor rotation connections U, V and W.
will be incorrect.
(2) Supply voltage low. (2) Check supply voltage.
Water in temp trip (1) User cooling water system (1) Find cause and rectify.
fault.
Water out temp trip (1) Water flow restriction. (1) Check/clean coolers.
(2) Low water flow. (2) Check cooling water flow rate.
Oil level low (1) Low oil level. (1) Check for oil leaks and
(start inhibit) rectify. Top up reclaimer to
correct level.
(2) Oil level sensor fault. (2) Find cause and rectify.
(3) Sensor wiring fault. (3) Check and rectify.
page 91
CompAir
2. WARNING MESSAGES
Service due (1) Service countdown time (1) Service compressor then
expired. reset timer.
Change air filter (1) Intake air filter blocked. (1) Check/renew element.
(2) Filter pressure switch fault. (2) Check operation. Renew if
necessary.
(3) Filter pressure switch (3) Check and rectify.
wiring fault.
Change oil filter (1) Oil filter element blocked. (1) Renew oil filter.
(2) Differential pressure (2) Check operation. Renew if
switch fault. necessary.
(3) Filter pressure switch (3) Check and rectify.
wiring fault.
Oil level low (1) Low oil level. (1) Check for oil leaks and
rectify. Top up reclaimer to
correct level.
(2) Oil level sensor fault. (2) Find cause and rectify.
(3) Sensor wiring fault. (3) Check and rectify.
(4) Input card fault. (4) Check/renew input card.
Oil temperature alarm (1) High ambient temperature. (1) Check room ventilation.
(2) Insufficient cooling water flow. (2) Check water supply. Check
adjustment of water valve.
Inspect/clean water strainer.
Inspect/clean oil cooler.
(3) Temperature sensor fault. (3) Rectify/renew.
(4) Sensor wiring fault. (4) Check wiring.
(5) Preconditioner card fault. (5) Renew card.
St1 delivery temp alarm (1) High ambient temperature. (1) Check room ventilation.
(2) Insufficient cooling water flow. (2) Check water supply. Check
adjustment of water valve.
Inspect/clean water strainer.
(3) High interstage pressure. (3) Inspect/Clean air coolers.
St2 intake temp alarm (1) Insufficient cooling water flow. (1) Check water supply. Check
adjustment of water valve.
Inspect/clean water strainer.
Inspect/clean intercooler.
(2) High ambient temperature. (2) Check room ventilation.
page 92
Oil Free Screw User Manual – Fault Finding
St2 delivery temp alarm (1) Insufficient cooling water flow. (1) Check water supply. Check
adjustment of water valve.
Inspect/clean water strainer.
(2) Air flow restriction. (2) Inspect/Clean aftercooler.
Plant delivery t alarm (1) Insufficient cooling water flow. (1) Check water supply. Check
adjustment of water valve.
Inspect/clean water strainer.
Inspect/clean aftercooler.
Water in temp alarm (1) Supply water temperature high. (1) Check supply
water temperature.
(2) Low water flow. (2) Check water flow.
Water out temp alarm (1) Supply water temperature high. (1) Check supply
water temperature.
(2) Low water flow. (2) Check water flow.
Inspect/clean air coolers.
Interstage press alarm (1) Air flow restriction. (1) Inspect/clean air coolers.
Water in t probe fault (1) Temperature sensor fault. (1) Renew temperature sensor.
(2) Sensor wiring fault. (2) Check and rectify fault.
(3) PT1000 conditioner fault. (3) Renew conditioner unit.
Water out t probe fault (1) Temperature sensor fault. (1) Renew temperature sensor.
(2) Sensor wiring fault. (2) Check and rectify fault.
(3) PT1000 conditioner fault. (3) Renew conditioner unit.
Remote Alarm (1) Remote alarm loop open circuit. (1) Find cause and rectify.
Start inhibit (1) Remote start inhibit loop (1) Find cause and rectify.
open circuit.
page 93
CompAir
page 94
Oil Free Screw User Manual
APPENDIX 1
CONTROL/REMOTE OPTIONS
Page
Condensate Drain 96
Condensate Drain Operation 96
Inputs 96
Description 96
Input Designations 97
Input Functions 97
Outputs 102
Description 102
Output Relay 102
Output Designations 103
Output Functions 103
page 95
CompAir
APPENDIX 1
WARNING
!
● Lethal voltages are used in this ● Refer to the safety procedures before
equipment. Use extreme caution when carrying out any of the following
carrying out electrical checks. Isolate operations.
the power supply before starting any
maintenance work.
page 96
Oil Free Screw User Manual – Appendix 1
X01
1 2 3 4 5 6 7 8 9
REMOTE LOAD
COMMS CONTROL ENABLE
START
STOP
500
PRESSURE SWITCH
OR CASCADE
PANEL CONNECTION
Pin No. Function X02-1 Common (20V dc) for X02 inputs
X02-5 Remote Fault Input 1
X01-1 Common (20V dc) for X01 inputs X02-6 Remote Fault Input 2
X01-2 Comms Control Enable X02-7 Remote Fault Input 3
X01-3 Auto Restart Enable X02-8 Remote Fault Input 4
X01-4 Remote Load Enable X02-9 Remote Fault Input 5
X01-5 Remote Load/Unload
X01-6 Remote Start Enable
X01-7 Remote Start 2.3 Input Functions
X01-8 Remote Stop
X01-9 No Standard Function 2.3.1 Input X01-2 RS485 Communications
Control Enable
page 97
CompAir
The communications link can either be connected 3. When power is restored the following
point-to-point or networked with up to 31 message is displayed and the Auto Re-start
compressors and one master. enable indicator will flash.
page 98
Oil Free Screw User Manual – Appendix 1
2.3.4 Input X01-5 Remote Load/Unload 2.3.6 Input X01-7 Remote Start
1. If input X01-5 is activated, via a remote 1. When the remote start enable and remote
pressure switch, relay, programmable logic stop inputs are activated the compressor will
controller (P.L.C.) output etc, the compressor start when the remote start input is activated.
will load. When the input is de-activated the This input reqires a sngle pulse of at least 0·5
compressor will unload. seconds to activate it. The pulse length can
be between 0·5 seconds and continuous.
2. The compressor will shutdown and the
display will show a High air pressure trip if 2. When the remote start input is continuously
the Max overpress setting of the activated the SureScan panel stop button or
Commissioning - values menu is exceeded the remote stop input will override the remote
while using this facility. The compressor ‘Max start signal and the compressor will stop.
overpress’ setting must be set above the
working pressure of the remote pressure When the compressor is stopped, the remote
control system. Where the remote pressure start signal must be de-activated before the
control system is detecting air system compressor can be re-started.
pressure downstream of dryers, filters or long
lengths of pipework, an allowance for any Note: This facility is inhibited if the RS485
pressure differential should be taken into communications control input is activated.
account.
3. Remote Timer Control
2.3.5 Input X01-6 Remote Start Enable The remote start/stop facility can also be
used to achieve automatic seven day timer
1. The compressor can be connected to accept control. Any commercially available timer with
a remote start signal. When this input is a single switching contact can be used for
activated the REMOTE CONTROL indicator this purpose. Alternatively a timer with a 24v
will be lit and the SureScan panel START ac power supply can be mounted within the
button is disabled. starter area A 24vac power supply for this
purpose is available on compressors
The SureScan panel stop button and the terminals X2/1 and X2/2. The timer unit
remote stop input are always active, should be battery backed.
regardless of remote start enable being
activated.
EXTENSION MODULE
7 DAY TIMER
X01
1 2 3 4 5 6 7 8 9
REMOTE START ENABLE
X5/1 X5/1 X5/1 X5/1 X5/1 X5/1 X5/1 X5/1 CLOSED - START
OPEN - STOP
PI/97/136
TIMER CONTROL
page 99
CompAir
2.3.7 Input X01-8 Remote Stop 2.3.9 Inputs X02-5 to 9 - Remote Faults 1 to 5
1. The remote stop input is always active, There are five remote fault input functions
regardless of remote start enable being available that can be individually programmed to
activated. function as remote alarm, remote trip or start
inhibit inputs. A remote fault input can be
2. The remote stop input must be active to connected to a remote switch, relay contact,
enable the compressor to be started. The programmable logic controller (PLC) output or any
compressor will stop when the remote stop switching contact device. Each input function will
input is de-activated. operate when the connection between the
appropriate input terminal, X02-5 to X02-9, and the
3. A remote stop signal will override a remote common terminal X5/2 is broken.
start signal. When the remote stop input is
de-activated the display will show: When a remote fault input is de-activated the
appropriate remote fault number will be displayed
Remote stopped by the SureScan controller and the fault will be
stored in the fault history. The remote fault can be
Oil temperature 20°C
reset normally using the RESET button.
4. The STOP button on the SureScan panel is
1. Remote Fault Input Configuration
not affected and will remain active at all
times.
Each remote fault input can be pre-
programmed using the SureScan controller
5. If this facility is not used the input must be
menu routines to function as a remote alarm,
continuously activated by connecting a wire
remote shutdown trip or start inhibit when the
from the input pin to terminal connection X5/
fault input is de-activated. Remote alarm and
1, to enable the compressor to be started and
shutdown trip functions can also be pre-
run.
programmed to operate only under pre-
determined conditions to suit a particular
application depending on the remote fault
2.3.8 Inputs X01-9 and X02-2 to 4
input type selected.
CAUTION: These inputs are used by the controller
Note: When a remote fault input is configured to
to monitor the operation of the compressor and
any option other than ‘Disabled’ the input must,
must not be used for any other function.
under normal circumstances, be continuously
activated to enable the compressor to operate
without indicating a remote alarm, trip or start
inhibit condition.
page 100
Oil Free Screw User Manual – Appendix 1
Start inhibit Will prevent a compressor from starting but will not stop a
compressor if already started. When activated the display will show
‘Start inhibited’. This function is not a shutdown trip or alarm and will
only function while the input is de-activated.
All remote fault inputs will be ‘Disabled’ when the compressor is first commissioned. To enable a
remote fault input, and select a required fault input function from the Configuration Options table , use
the SureScan menu routines procedure as described below :-
page 101
CompAir
The display will automatically return to the fault input selection menu.
3.1 Description
Qty Description Part Number
Two sets of six outputs are available on extension
module terminal connections X05 and X06. Each 1 Relay - 24 V dc 98475-64
output is designated a particular function which 1 Relay Base 98475-65
may be used if required. Outputs which are not
used should be left unconnected.
3.2.1 Relay Specification
page 102
Oil Free Screw User Manual – Appendix 1
K405
K404
K403
K402
K401
5 3
+ 2
5 5 5 5 5 5
24V d.c.
- 4
406 1 1 1 1 1 1 1
405
404
403
402
401
400
7 6 5 4 3 2 1
X05
2. Relay terminal ‘1’ must be connected to the 3.3.2 Output Terminal X06
pin of the output terminal appropriate for the
required output function.
Pin No. Function
The relay base can be screw mounted or secured
to a standard type DIN rail (available from X06-1 Common (20V dc) for X06 outputs
CompAir).
X06-2 Remote Fault 1 Repeat
X06-3 Remote Fault 2 Repeat
3.3 Output Designations
X06-4 Remote Fault 3 Repeat
3.3.1 Output Terminal X05 X06-5 Remote Fault 4 Repeat
X06-6 Remote Fault 5 Repeat
Pin No. Function X06-7 No Standard Function
page 103
CompAir
3.4.2 Output X05-3 Group Fault 3.4.6 Output X05-7 Service Due
The group fault output will de-energise when an The service due output will energise when the
alarm, shutdown trip or power loss occurs. service hours countdown timer has reached zero
The output will be energised when power is hours and a routine service is due.
applied and no alarm or trip conditions are
detected. The contacts of relay K406 must be used for
remote connections to this facility.
The contacts of relay K402 must be used for
remote connections to this facility.
3.4.7 Outputs X06-2 to 6
3.4.3 Output X05-4 Running Remote fault repeat outputs 1 to 5 will be normally
energised and will de-energise if a fault condition
The running output will energise when the on the appropriate remote fault input, 1 to 5, is
compressor main motor is running. detected or a power loss occurs. The output will
remain de-energised until the SureScan controller
The contacts of relay K403 must be used for is reset. See remote fault inputs.
remote connections to this facility.
If start inhibit is selected, the output will de-
energise when the input is de-activated and
3.4.4 Output X05-5 On Load automatically re-set when the input is re-activated.
The on load output will energise when the Note: An additional relay module, as specified in
compressor is on load. para 3.2, must be added if these outputs are used.
page 104
Oil Free Screw User Manual – Appendix 2
APPENDIX 2
Electrical Connections
page 105
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35
CompAir
page 106
U (01) U
[BK] <2/2>
V (02)
[BK]
W (03) W
[BK] <2/2>
PE
FUSED ISOLATOR
m 3
INCOMING SUPPLY
FROM CUSTOMERS
T1 T2 T3
K101
L1
Q101
L3 U V W
L1 L2 L3
[BK]
[BK]
[BK]
[BK]
[BK]
[BK]
(101A)
(102A)
(103A)
(101C)
(102C)
(103C)
(101B)
[BK]
(102B) F101 Main Motor Thermal Overload Relay
[BK]
(103B)
[BK] F102 Fan Motor Thermal Overload Relay
F103 Oil Pump Motor Thermal Overload
KM201
KM203
KM202
KM204
KM204
Relay
K101 Phase Rotation Relay
F101
F102
F103
[BK]
M101 Main Motor
[BK]
M102 Fan Motor
[BK]
U1 V1 W1 U1 V1 W1 U1 V1 W1 M103 Oil Pump Motor
R
Q101 M.C.B. 3 Pole
(104)
M101 a M103
E [BL] <3/14> E M102 E S201/1 Emergency Stop Contact
R
3~ (105) 3~ 3~
b
R [BL] <3/14> Y201 Unloader Solenoid
[BK]
[BK]
[BK]
U2 V2 W2
E
<2/2>
E
<2/2>
[G/Y] E
<2/2>
PI/97/148
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35
280VA T201
F1 1.6A (209)
575V 24V (203)
30VA [R] [R]
F2 1.6A (224)
440/460V 0V (204)
[R] [R]
Q201 F3 3.15A 24V~
U (01) (201) 415/380V 24V (205) (210) (210)
24V~ SUPPLY TO
<1/26> [BK] 1 2 [BK] 50VA [R] [R] [R] <4/2>
F4 3.15A EXTENSION
220/230V 0V (206) (225) (225) OV (24V~)
MODULE
[R] [R] [R] <4/2>
F5 10A
W (03) 3 4 (202) 0V 24V (207)
<1/26> [BK] [BK] 200VA [R]
<4/2>
3A 0V (208)
[R]
[R]
AND
<4/2>
(211)
INTERCONNECTING
CABLE
<4/2>
[R]
[R]
(E)
[G/Y]
(224)
(209)
CABLE No.
98140/264
1 2
[R]
AC1 AC2 CONTROLLER
(208)
CONTROLLER
1 X03 X04
RELAY OUTPUT DIGITAL OUTPUTS
~
X08 X09
S201/1
2
R1 R2 R3 R4 R5 VC1 OC1 OC2 OC3
1 2 3 4 5 6 7 8 9 10 1 2 3 4
K201/1
4 3
[R]
[R]
[R]
[R]
[R]
(223C)
(223D)
(223E)
(223F)
(223B)
(223) A (223G)
[R] [R]
X2/1 X2/1 X2/1 X2/1 X2/1
[R]
[R]
(219)
(220A)
X/26
CL1/1
CL1/2
CL1/3
[R]
(218)
EARTH
X/26
X/26
BAR
[R]
[R]
[R]
(212)
(214)
(216)
[R]
[R]
[R]
(220C)
(E)
(220B)
(220D)
[R]
[R]
96
96
(219)
(219)
[G/Y]
[BL]
[BL]
(230A)
(231)
F101
(E)
95
95
[G/Y]
ML1/5
ML1/7
ML1/1
ML1/3
[R]
[R]
[R]
[R]
[R]
(213)
(215) KM203
(217) KM202
(E)
A1 (221) F102
A1 (222) F103
A2
[G/Y] <4/2>
E [G/Y]
K201
Y201
Y202
Y203
Y204
KM201
KM202
KM203
KM204
KM205
<1/26>
A1
A2
A2
E [G/Y]
<1/26>
E [G/Y]
ML1/4
ML1/6
ML1/8
ML1/2
<1/26>
E [G/Y]
<1/26>
[R]
[R]
[R]
[R]
[R]
[R]
[R]
[R]
[R]
[BL]
[BL]
(208)
(208)
(208)
(208B)
(208C)
(208D)
(208E)
(208F)
(208G)
(230)
(230B)
(208)
20V-
[R]
X2/2 X2/2 X2/2 X2/2 X2/2 X2/2 X2/2 X2/2 X2/2 X2/2 X2/4 X2/4 X2/4 X2/4
(305) [BL] d
page 107
Oil Free Screw User Manual – Appendix 2
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35
CompAir
page 108
CONTROLLER CONTROLLER
DIGITAL INPUTS ANALOG INPUTS
X01 X02
VCONT CONT1 CONT2 CONT3 CONT4 CONT5 CONT6 CONT7 CONT8 VA+ ANA1 ANA2 ANA3 ANA4 VA-
1 2 3 4 5 6 7 8 9 1 2 3 4 5 6
[BL]
[BL]
[BL]
[BL]
[BL]
[BL]
[BL]
[BL]
[BL]
[BL]
[BL]
[BL]
(321)
(322)
(301)
(302)
(303)
(304)
(306)
(307)
(308)
(309)
(300A)
(320A)
R301
X3/2
CL1/4
[BL]
[BL]
[BL]
(320C)
(320B)
(304B)
11
14
14
14
ML1/9
ML1/11
ML1/15
K101
KM205
KM201
KM204
12
13
13
13
1 4
2
2
3 S303
~
S301
S302
S201/2
2 2
P301
P302
(104)
1
1
1
<1/12> [BL]
R301
b
ML1/14
ML1/10
ML1/12
ML1/13
<1/12>
[BL]
[BL]
[BL]
[BL]
[BL]
[BL]
[BL]
[BL]
[BL]
[BL]
[BL]
(305)
(300A)
(300B)
(300C)
(300D)
(300H)
(300E)
(300F)
(300G)
(105)
(300I)
20V-
X3/1 X3/1 X3/1 X3/1 X3/1 X3/1 X3/1 X3/1 X3/1 X3/1
PI/97/149
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35
(E)
<2/7> [G/Y]
24V~ (210)
<2/25> [R]
OV (24V~) (225)
<2/25> [R]
<2/25>
<2/25>
<2/25>
CABLE No.
98140/264
1 2
AC1 AC2 EXTENSION
EXTENSION X03 X04 DIGITAL OUTPUTS
DIGITAL OUTPUTS X06
X05
VC1 OC1 OC2 OC3 OC4 OC5 OC6 VC2 OC7 OC8 OC9 OC10 OC11 OC12
1 2 3 4 5 6 7 1 2 3 4 5 6 7
[BL]
[BL]
[BL]
[BL]
[BL]
[BL]
[BL]
[BL]
(400)
(401)
(402)
(403)
(404)
(405)
(406)
(410)
3
3
3
3
3
3
A2
A2
A2
A2
A2
A2
K401/1 2
K402/1 2
K403/1 2
K404/1 2
K405/1 2
K406/1 2
K401
K402
K403
K404
K405
K406
A1
A1
A1
A1
A1
A1
4
4
4
4
4
4
[BL]
[BL]
[BL]
[BL]
[BL]
[BL]
[BL]
(400A)
(400B)
(400C)
(400D)
(400E)
(400F)
(400G)
[BL]
(410)
20V- 20V-
X4/1 X4/1 X4/1 X4/1 X4/1 X4/1 X4/1 X4/2 X4/2 X4/2 X4/2 X4/2 X4/2 X4/2
PI/97/150
page 109
Oil Free Screw User Manual – Appendix 2
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35
CompAir
page 110
EXTENSION EXTENSION
DIGITAL INPUTS DIGITAL INPUTS
X01 XO2
VCONT CONT1 CONT2 CONT3 CONT4 CONT5 CONT6 CONT7 CONT8 VCONT CONT9 CONT10 CONT11 CONT12 CONT13 CONT14 CONT15 CONT16
1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9
[BL]
[BL]
[BL]
[BL]
[BL]
(500)
(511)
(512)
(513)
(LK1)
(510)A
ML1/32
ML1/30
S501
S502
13 Q101 14
ML1/31
ML1/33
[BL]
[BL]
[BL]
[BL]
[BL]
(LK1)
(500)
(510A)
(510B)
(510C)
(510D)
X5/1 X5/1 X5/1 X5/1 X5/1 X5/1 X5/1 X5/1 X5/2 X5/2 X5/2 X5/2 X5/2 X5/2 X5/2 X5/2 X5/2
PI/97/151
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35
EXTENSION EXTENSION
ANALOG INPUTS ANALOG INPUTS
X08 X07
VA18_1 ANA1 ANA2 ANA3 ANA4 GA_1 VA18_2 ANA5 ANA6 ANA7 ANA8 GA_2
1 2 3 4 5 6 1 2 3 4 5 6
[BL]
[BL]
[BL]
[BL]
[BL]
[BL]
[BL]
[BL]
[BL]
(601)
(602)
(603)
(611)
(612)
(613)
(614)
(605A)
(615A)
ML1/24
ML1/22
ML1/26
ML1/28
ML1/16
ML1/20
ML1/18
R601 Plant Delivery Temp.
R605
R606
R607
R608
R601
R602
R603
R602 St.2 Intake Temp.
R603 Oil Temp.
R605 Water In Temp
ML1/17
ML1/19
ML1/21
ML1/25
ML1/23
ML1/27
ML1/29
R606 Water Out Temp.
R607 St.1 Out Temp.
[BL]
[BL]
[BL]
[BL]
[BL]
[BL]
[BL]
[BL]
[BL]
(605B)
(605C)
(605D)
(605A)
(615B)
(615D)
(615C)
(615E)
(615A)
X6/1 X6/1 X6/1 X6/1 X6/1 X6/2 X6/2 X6/2 X6/2 X6/2
page 111
CompAir
page 112
Oil Free Screw User Manual – Appendix 3
APPENDIX 3
page 113
CompAir
APPENDIX 3
THE PRESSURE SYSTEMS AND Note: The intervals between examination and
TRANSPORTABLE GAS CONTAINER calibration of components, e.g. pressure vessels,
REGULATIONS 1989 pressure relief valves etc., will be defined by the
‘competent person’ preparing the written scheme.
The circuit diagram shown below is provided to
assist a ‘competent person’ in preparing a written In defining these periods the ‘competent person’
scheme of examination for a system incorporating must take into account the recommendations of
the air compressor(s). the component part manufacturer, the Health and
Safety Executive (H & SE) and the British
Compressed Air Society (BCAS).
12 13 14
1 2
15 16
4
5
17 6
18
3
+ -
11
19
21
M + -
20
10
7 8 9
16
15
PI/97/093
1. Intake Air Filter
2. Suction Regulator 12. Unloader Solenoid Valve
3. First Stage Air-end 13. Regulation Air Line Filter
4. Intercooler 1st Stage 14. Shuttle Valve
5. Pressure Relief Valve 15. Strainer (2)
6. Pressure Transmitter 16. Condensate Drain Valve (2)
7. Second Stage Air-end
17. Air Filter Switch
8. Non-return Valve 18. Temperature Sensor
9. Aftercooler
19. Temperature Sensor
2nd Stage
10. Pressure Relief Valve 20. Temperature Sensor
11. Pressure Transmitter 21. Temperature Sensor
page 114
Oil Free Screw User Manual – Appendix 4
APPENDIX 4
Page
Introduction 116
Values at Commissioning 117
Commissioning Configurations 118
Operational Settings 118
Weekly Checks 119
Performance Log 120
4000 hr Service (Service A) 120
8000 hr Service (Service B) 121
16000 hr Service (Service C) 121
Compressor History Log 122
page 115
CompAir
APPENDIX 4
Introduction
page 116
Oil Free Screw User Manual – Appendix 4
VALUES AT COMMISSIONING
Note: All readings to be taken from SureScan except oil and interstage pressures which are taken from the
gauges.
Water in trip °C
Water in alarm °C
page 117
CompAir
COMMISSIONING CONFIGURATIONS
Language
Unit of Pressure
Unit of Temperature
Compressor Number
OPERATIONAL SETTINGS
P1 Set Point
P2 Set Point
Run On Time
page 118
Oil Free Screw User Manual – Appendix 4
WEEKLY CHECKS
Date
Hours On Load
Enclosure Filters
Status Display
page 119
CompAir
PERFORMANCE LOG
This log is provided to enable the user to keep a written record of compressor performance and as an aid to
fault diagnostics. It is recommended that the readings are recorded regularly, as part of the weekly service,
with the compressor in normal operating condition.
°
Oil Temp C
°
St 1 delivery temp. C
°
St 2 intake temp. C
°
St 2 delivery temp. C
°
Plant del temp. C
°
Water in temp. C
°
Water out temp. C
Item Value/Completed
Date
Total Hours
Hours On Load
Water Strainer
page 120
Oil Free Screw User Manual – Appendix 4
Item Value/Completed
Date
Total Hours
Oil Change
Intercooler Tubestack
Aftercooler Tubestack
Oil Cooler
Starter Connections
Item Value/Completed
Date
Total Hours
Hours On Load
Starter Contacts
page 121
CompAir
Introduction
Serial 1 2 3 4 5 6 7 8 9 10 11
Date
By
Fault Message
Status Message
Total Hours
Discharge P bar
Interstage P bar
Oil Temp °C
LP Dely Temp °C
HP Inlet Temp °C
HP Dely Temp °C
Water In Temp °C
page 122
Oil Free Screw User Manual – Appendix 4
12 13 14 15 16 17 18 19 20 21 22 23 24 25
page 123
CompAir
page 124
Oil Free Screw User Manual – Appendix 5
APPENDIX 5
page 125
CompAir
APPENDIX 5
Introduction
To ensure that the cooling water system does not foul prematurely, it is recommend that cooling water is
provided from a closed circuit radiator system and that the water quality meets the Quality (A) requirements
below. If cooling water is to be provided from another source, the cooling water should be checked
periodically to ensure that it meets the Quality (A) requirements.
Sulphuric acid ion; SO42- (ppm) Less than 200 Less than 50
* Where Quality (A) refers to the circulating water and Quality (B) refers to the replenishment water.
Inspect the circulating water regularly to confirm that it meets Quality (A) as the quality will gradually
deteriorate.
page 126