E6582062

The wiring of the power supply and motor is connected to the power terminal block and the wiring of
external control equipment such as control signals to the control terminal block.

■ Connection to power supply and motor


This diagram shows a standard wiring of the power circuit.
Connection to the power supply and motor wiring is common to all the types.

VF-AS3
Power supply Connect the power supply Connect the motor to [U/T1],
to [R/L1], [S/L2], and [T/L3]. [V/T2], and [W/T3].

2 R/L1 S/L2 T/L3 U/T1 V/T2 W/T3 Motor


Molded-case
circuit breaker
or
Earth leakage
circuit breaker

■ Connection to peripheral devices


This diagram shows an example of connection to peripheral devices.
Molded-case
circuit breaker Magnetic Input Motor-end surge voltage
Note 2) contactor reactor suppression filter
VF-AS3 Motor
R/L1 U/T1
Power
supply
S/L2 V/T2 M
T/L3 W/T3
PA/+ PO PA PB Zero-phase
reactor

Note 1) Braking unit is needed for frame

9 size A6 and A8. [PA] and [PB]


terminals are in the braking unit.

DC reactor Braking resistor Note 2) Or Earth leakage circuit breaker.


(frame size A7 and A8 Note 1)
attached in the package)

For details of the peripheral devices, refer to [Chapter 10].


DC reactor
• DC reactor is built in as standard for frame size A1 to A6
• DC reactor is attached for frame size A7 and A8, mount the DC reactor with the inverter securely.

Braking resistor
• To VFAS3-2004P to 2370P, VFAS3-4004PC to 4750PC, and VFAS3-4160KPC, connect only the
braking resistor (optional) because a dynamic braking circuit is built in them as standard.
• When a braking resistor (optional) is installed for VFAS3-4900PC to 4132KPC and VFAS3-
4200KPC to 4280KPC, a braking unit (optional) is also required.
For details, refer to [10. 3. 2].

DC power supply
• To supply DC power, connect the inverter between terminals [PA/+] and [PC/-].
• When VFAS3-2110P to VFAS3-2550P or VFAS3-4220PC to VFAS3-4280KPC are used with a DC
power supply, a circuit to suppress an inrush current should be required.
• When VFAS3-4160KPC to 4280KPC are used with a DC power supply, three-phase power supply
for cooling fan driving should be prepared separately.
For details, refer to application manual "DC power supply connect to inverter" (E6582156).

2. Installation and wiring 2-30