Download as pdf or txt
Download as pdf or txt
You are on page 1of 90

Hilti CP 606 Firestop Acrylic

Sealant Submission Folder


Product Information and Method Statement 2

Test Reports

Top of Wall Joint

- RED No. R22D26-1A 7

Pipe Penetration

- RED No. R23A14-1A 31

- IA23-036 51

Door Frame

- RED No. R22D25-1A 64

General

- VOC Content 76

Letters

Government Letters 77

Country of Origin 80

LEED Letter 81

BEAM Plus Information 82

Material Safety Data Sheet 83

Job Reference 90

 Recycling one ton of paper saves 17 trees and 7000 gallons of water.
Please consider your environmental responsibility before using the hard copy version!

工程師技術支援平台 香港客戶熱線 澳門客戶熱線(免費) 香港門市 : 大角咀洋松街1號形品星寓地下2號舖 電郵 : hksales@hilti.com


Hilti (HK)
ask.hilti.com.hk +852 8228 8118 00800 8228 8118 澳門門市 : 澳門布魯塞爾街70號建興龍廣場地下W座地鋪 傳真 : +852 2954 1751

CP 606 Firestop Acrylic Sealant Page 1 of 90 Oct 2023


Flexible firestop sealant CP 606

APPLICATIONS Technical data


● Sealant rigid or low movement ceiling / wall joints, up to 30mm Chemical basis Water-based acrylic dispersion
● Sealing metal pipe penetrations Base materials Concrete, Masonry, Drywall, Steel
● For use in various base materials such as masonry, concrete, Movement1) ±12.5% (ISO 11600)
drywall and metal Approx. tack-free time (ventilated 20 min
at 77°F, 80% rel. humidity)
Approx. curing time2) 3 mm/3 days
Average volume shrinkage 22.2%
ADVANTAGES
Application temperature range 5 - 40 °C
● Paintable
Temperature resistance range -30 - 80 °C
● Easy to clean up with water
Storage and transportation 5 - 25 °C
● Smoke, fume and water resistant temperature range
Shelf life3) 24 Months
1)
according to HTC 1250
2)
at 75°F/24°C, 50% relative humidity
3)
at 77°F/25°C and 50% relative humidity; from date of manufacture
Water
Smoke Acoustic Siesmic
Tight

Mould &
Mildew

Consumption Guide
Cartridge volume = 310 ml (CP 606)
a = Joint width in mm
b = Sealant depth in mm
Linear metre per cartridge = Cartridge volume in ml
a x b
e.g.a floor 20mm wide with product depth of 10mm; with 310ml cartridge
Therefore linear metres per cartridge = 310/(20 x 10) = 1.55 metre per cartridge
for one side of the floor

Order Now

Ordering designation Colour Volume per unit Packaging Sales pack Item number
quantity
CP 606 310ml INT grey Grey 310 ml Cartridge 1 pc 209630
CP 606 580ml INT grey Grey 580 ml Foil pack 1 pc 209633
CP 606 310ml white white 310 ml Cartridge 1 pc 209625
CP 606 580ml white white 580 ml Foil pack 1 pc 209632

Please visit Hilti website for the latest item numbers and related products

CP 606 Firestop Acrylic Sealant Page 2 of 90 Oct 2023


Subject: Method Statement of CP 606 for Penetration Seal.
Material: CP 606 firestop sealant
Accessory: Hilti Dispenser CFS-DISP or Hilti Dispenser CS 270-P1 or equivalent.

Setting Operation
1 Clean the opening. Joint sides and surfaces to
which CP 606 will be applied must be sound,
dry and free from dust, oil and grease.

2 Insert the required fill of mineral wool and


backer.

3 Apply firestop CP 606 over backer.

Joint width (mm) 0-15 16-20 21-30


Sealant thickness (mm) 6 10 15

Hilti (Hong Kong) Ltd.


701-704 | Tower A | Manulife Financial Centre
223 Wai Yip Street | Kwun Tong
Kowloon | Hong Kong
P +852-8228 8118 I F +852-2954 1751
www.hilti.com.hk

CP 606 Firestop Acrylic Sealant Page 3 of 90 Oct 2023


4 Smooth the firestop sealant with a trowel
before the skin forms. Once cured, CP 606
can only be removed mechanically.

5 For maintenance reasons, a penetration seal


could be permanently marked with an
identification plate. In such a case, mark the
identification plate and fasten it in a visible
position next to the seal.

Safety precautions:

 Never use in areas immersed in water


 Keep out of reach of children
 Read the Material Safety Data Sheet
 Eyes sand hands must be suitably protected
 Avoid contact with eyes or skin
 Only use in well ventilated areas

CP 606 Firestop Acrylic Sealant Page 4 of 90 Oct 2023


Subject: Method Statement of CP 606 for Linear Joint Seal
Material: CP 606 firestop sealant
Accessory: Hilti Dispenser CFS-DISP or Hilti Dispenser CS 270-P1 or equivalent.

Setting Operation
1 Clean the opening. Joint sides and surfaces to which CP
606 will be applied must be sound, dry and free from
dust, oil and grease.

2 Insert fill of mineral wool or backing material (if required)

3 Apply CP 606 over the backing material .

Joint width (mm) 0-15 16-20 21-30


Sealant thickness (mm) 6 10 15

Hilti (Hong Kong) Ltd.


701-704 | Tower A | Manulife Financial Centre
223 Wai Yip Street | Kwun Tong
Kowloon | Hong Kong
P +852-8228 8118 I F +852-2954 1751
www.hilti.com.hk

CP 606 Firestop Acrylic Sealant Page 5 of 90 Oct 2023


4 Smooth CP 606 using a trowel before the skin forms. It
can only be removed mechanically once it is cured.

5 For maintenance reasons, a penetration seal would be


permanently marked with an identification plate. In such
a case, mark the identification plate and fasten it in a
visible position next to the seal

Safety precautions:
• Never use in areas immersed in water
• Keep out of reach of children
• Read the Material Safety Data Sheet
• Eyes and hands must be suitably protected
• Avoid contact with eyes or skin
• Only use in well ventilated areas

CP 606 Firestop Acrylic Sealant Page 6 of 90 Oct 2023


CP 606 Firestop Acrylic Sealant Page 7 of 90 Oct 2023
CP 606 Firestop Acrylic Sealant Page 8 of 90 Oct 2023
CP 606 Firestop Acrylic Sealant Page 9 of 90 Oct 2023
CP 606 Firestop Acrylic Sealant Page 10 of 90 Oct 2023
CP 606 Firestop Acrylic Sealant Page 11 of 90 Oct 2023
CP 606 Firestop Acrylic Sealant Page 12 of 90 Oct 2023
CP 606 Firestop Acrylic Sealant Page 13 of 90 Oct 2023
CP 606 Firestop Acrylic Sealant Page 14 of 90 Oct 2023
CP 606 Firestop Acrylic Sealant Page 15 of 90 Oct 2023
CP 606 Firestop Acrylic Sealant Page 16 of 90 Oct 2023
CP 606 Firestop Acrylic Sealant Page 17 of 90 Oct 2023
CP 606 Firestop Acrylic Sealant Page 18 of 90 Oct 2023
CP 606 Firestop Acrylic Sealant Page 19 of 90 Oct 2023
CP 606 Firestop Acrylic Sealant Page 20 of 90 Oct 2023
CP 606 Firestop Acrylic Sealant Page 21 of 90 Oct 2023
CP 606 Firestop Acrylic Sealant Page 22 of 90 Oct 2023
CP 606 Firestop Acrylic Sealant Page 23 of 90 Oct 2023
CP 606 Firestop Acrylic Sealant Page 24 of 90 Oct 2023
CP 606 Firestop Acrylic Sealant Page 25 of 90 Oct 2023
CP 606 Firestop Acrylic Sealant Page 26 of 90 Oct 2023
CP 606 Firestop Acrylic Sealant Page 27 of 90 Oct 2023
CP 606 Firestop Acrylic Sealant Page 28 of 90 Oct 2023
CP 606 Firestop Acrylic Sealant Page 29 of 90 Oct 2023
CP 606 Firestop Acrylic Sealant Page 30 of 90 Oct 2023
CP 606 Firestop Acrylic Sealant Page 31 of 90 Oct 2023
CP 606 Firestop Acrylic Sealant Page 32 of 90 Oct 2023
CP 606 Firestop Acrylic Sealant Page 33 of 90 Oct 2023
CP 606 Firestop Acrylic Sealant Page 34 of 90 Oct 2023
CP 606 Firestop Acrylic Sealant Page 35 of 90 Oct 2023
CP 606 Firestop Acrylic Sealant Page 36 of 90 Oct 2023
CP 606 Firestop Acrylic Sealant Page 37 of 90 Oct 2023
CP 606 Firestop Acrylic Sealant Page 38 of 90 Oct 2023
CP 606 Firestop Acrylic Sealant Page 39 of 90 Oct 2023
CP 606 Firestop Acrylic Sealant Page 40 of 90 Oct 2023
CP 606 Firestop Acrylic Sealant Page 41 of 90 Oct 2023
CP 606 Firestop Acrylic Sealant Page 42 of 90 Oct 2023
CP 606 Firestop Acrylic Sealant Page 43 of 90 Oct 2023
CP 606 Firestop Acrylic Sealant Page 44 of 90 Oct 2023
CP 606 Firestop Acrylic Sealant Page 45 of 90 Oct 2023
CP 606 Firestop Acrylic Sealant Page 46 of 90 Oct 2023
CP 606 Firestop Acrylic Sealant Page 47 of 90 Oct 2023
CP 606 Firestop Acrylic Sealant Page 48 of 90 Oct 2023
CP 606 Firestop Acrylic Sealant Page 49 of 90 Oct 2023
CP 606 Firestop Acrylic Sealant Page 50 of 90 Oct 2023
CP 606 Firestop Acrylic Sealant Page 51 of 90 Oct 2023
CP 606 Firestop Acrylic Sealant Page 52 of 90 Oct 2023
CP 606 Firestop Acrylic Sealant Page 53 of 90 Oct 2023
CP 606 Firestop Acrylic Sealant Page 54 of 90 Oct 2023
CP 606 Firestop Acrylic Sealant Page 55 of 90 Oct 2023
CP 606 Firestop Acrylic Sealant Page 56 of 90 Oct 2023
CP 606 Firestop Acrylic Sealant Page 57 of 90 Oct 2023
CP 606 Firestop Acrylic Sealant Page 58 of 90 Oct 2023
CP 606 Firestop Acrylic Sealant Page 59 of 90 Oct 2023
CP 606 Firestop Acrylic Sealant Page 60 of 90 Oct 2023
CP 606 Firestop Acrylic Sealant Page 61 of 90 Oct 2023
CP 606 Firestop Acrylic Sealant Page 62 of 90 Oct 2023
CP 606 Firestop Acrylic Sealant Page 63 of 90 Oct 2023
CP 606 Firestop Acrylic Sealant Page 64 of 90 Oct 2023
CP 606 Firestop Acrylic Sealant Page 65 of 90 Oct 2023
CP 606 Firestop Acrylic Sealant Page 66 of 90 Oct 2023
CP 606 Firestop Acrylic Sealant Page 67 of 90 Oct 2023
CP 606 Firestop Acrylic Sealant Page 68 of 90 Oct 2023
CP 606 Firestop Acrylic Sealant Page 69 of 90 Oct 2023
CP 606 Firestop Acrylic Sealant Page 70 of 90 Oct 2023
CP 606 Firestop Acrylic Sealant Page 71 of 90 Oct 2023
CP 606 Firestop Acrylic Sealant Page 72 of 90 Oct 2023
CP 606 Firestop Acrylic Sealant Page 73 of 90 Oct 2023
CP 606 Firestop Acrylic Sealant Page 74 of 90 Oct 2023
CP 606 Firestop Acrylic Sealant Page 75 of 90 Oct 2023
88 Empire Drive • St. Paul, Minnesota • 55103
(651) 642-1150 • fax (651) 642-1239


VOC Content Test Certificate

October 26, 2009

Supplier: Hilti Entwicklungsgesellschaft mbH


BU Chemicals
Hiltistrasse 6
86916 Kaufering
GERMANY

Sample Description: Hilti CP 606

Date tested: July 20, 2009

Test Method: SCAQMD method 304-91 Determination of Volatile Organic Compounds


(VOC) in various materials as referenced by South Coast Air Quality
Management District (SCAQMD) rule 1168. The values also comply with the
requirements of EPA test method #24.

Test Data: Legend Project Number 0903311

Specification Product
LEED 2009 (LEED 3.0)
LEED 2.2
IEQ-4.1: Low-Emitting Materials –
Architechtural Sealant Hilti
Green Building Council of Australia
Green Star Office Design 3.0, IEQ-13
CP 606
Green Star Office Design 2.0, IEQ-13
Green Star Office Interiors 1.1, IEQ-11

Architectural Sealant;
Product contains: 75 g/L of VOC
VOC Limit: 250 g/L

William Welbes Allen Noreen, Ph.D.


Vice President of Laboratory Operations Technical Director


CP 606 Firestop Acrylic Sealant Page 76 of 90 Oct 2023


CP 606 Firestop Acrylic Sealant Page 77 of 90 Oct 2023
CP 606 Firestop Acrylic Sealant Page 78 of 90 Oct 2023
CP 606 Firestop Acrylic Sealant Page 79 of 90 Oct 2023
Attn. : To whom it may concern

Date : 26 September 2023


Ref. : 080/FP/DY/23

Subject : Country of Origin- Hilti CP 606 Flexible Firestop Sealant

Dear Sir / Madam,

Enclosed please find the information of Hilti CP 606 Flexible Firestop Sealant

Brand Name : Hilti

Model Name : Hilti CP 606 Flexible Firestop Sealant

Manufacturer : Hilti Corporation

Address of Manufacturer : FL-9494, Principality of Liechtenstein.

Manufacturer Contact Person : Dennis Yeung

Supplier : Hilti (Hong Kong) Ltd

Address of Supplier : 701-704, 7/F, Tower A, Manulife Financial Centre,


223 Wai Yip Street, Kwun Tong, Kowloon, Hong Kong

Supplier Contact Person : Dennis Yeung (+852 9723 4621)

Country of Origin : Germany

Should you have further questions, please do not hesitate to contact our Technical
Representatives, Customer Service Hotline at 8228-8118, or email us at hksales@hilti.com.

Yours faithfully,

Dennis Yeung
Head of Product Leadership Strategy, F&P
Hilti (Hong Kong) Ltd.
701-704 | Tower A | Manulife Financial Centre
223 Wai Yip Street | Kwun Tong
Kowloon | Hong Kong
P +852-8228 8118 I F +852-2954 1751
www.hilti.com.hk

CP 606 Firestop Acrylic Sealant Page 80 of 90 Oct 2023


CP 606 Firestop Acrylic Sealant Page 81 of 90 Oct 2023
To whom it may concern

Date: 22nd April 2016

Dear Sir / Madam,

Subject: Hilti Firestop Products non-CFC and Ozone Confirmation

Referring to your enquiry about the captioned subject, please be advised that:

Hilti firestop products, CP606 Flexible Firestop Sealant is free of CFC, HCFC nor other
ozone depletion elements.

CFC, HCFC and ozone depletion elements were not used during the product process neither.

Should you have further questions, please do not hesitate to contact our
Technical Representatives or Customer Service Hotline at 8228-8118.

Yours sincerely,

Andrew Lau
Product Manger

Hilti (Hong Kong) Ltd.


701-704 & 708A&B | Tower A | Manulife Financial Centre
223 Wai Yip Street | Kwun Tong
Kowloon | Hong Kong
P +852-8228 8118 I F +852-2954 1751
www.hilti.com.hk

CP 606 Firestop Acrylic Sealant Page 82 of 90 Oct 2023


CFS-S ACR; CP 606
Safety Data Sheet
according to the United Nations GHS (Rev. 4, 2011)
Issue date: 08/02/2021 Revision date: 08/02/2021 Supersedes: 02/10/2019 Version: 4.7

SECTION 1: Identification
1.1. GHS Product identifier
Product form Mixture
Trade name CFS-S ACR; CP 606
Type of product Sealants
Product code BU Fire Protection

1.2. Other means of identification


No additional information available

1.3. Recommended use of the chemical and restrictions on use


Use of the substance/mixture Flexible firestop sealant
Recommended uses and restrictions For professional users only
Recommended use Adhesives, sealants

1.4. Supplier's details


Supplier Department issuing data specification sheet
Hilti (Hong Kong) Ltd. Hilti AG
701-704, 7/F, Tower A, Manulife Financial Centre Feldkircherstraße 100
223 Wai Yip Street, Kwun Tong 9494 Schaan - Liechtenstein
Kowloon - Hong Kong T +423 234 2111
T +852 27734 700 chemicals.hse@hilti.com
hksales@hilti.com

1.5. Emergency phone number


Emergency number Schweizerisches Toxikologisches Informationszentrum – 24h Service
+41 44 251 51 51 (international)
+852 27734 700

SECTION 2: Hazard identification


2.1. Classification of the substance or mixture
Classification according to the United Nations GHS
Not classified

2.2. GHS Label elements, including precautionary statements


Labelling according to the United Nations GHS
0

2.3. Other hazards which do not result in classification


No additional information available

SECTION 3: Composition/information on ingredients


3.1. Substances
Not applicable

CP 606 Firestop Acrylic Sealant Page 83 of 90 Oct 2023


CFS-S ACR; CP 606
Safety Data Sheet
according to the United Nations GHS (Rev. 4, 2011)

3.2. Mixtures

This mixture does not contain any substances to be mentioned according to the applicable regulations

SECTION 4: First-aid measures


4.1. Description of necessary first-aid measures
First-aid measures general Never give anything by mouth to an unconscious person. If you feel unwell, seek medical
advice (show the label where possible).
First-aid measures after inhalation Get medical advice/attention if you feel unwell. Allow affected person to breathe fresh air.
Allow the victim to rest.
First-aid measures after skin contact Wash skin with plenty of water. If skin irritation occurs: Get medical advice/attention.
Remove affected clothing and wash all exposed skin area with mild soap and water,
followed by warm water rinse.
First-aid measures after eye contact Rinse cautiously with water for several minutes. Remove contact lenses, if present and easy
to do. Continue rinsing. If eye irritation persists: Get medical advice/attention. Rinse
immediately with plenty of water. Obtain medical attention if pain, blinking or redness
persists.
First-aid measures after ingestion Get medical advice/attention if you feel unwell. Rinse mouth. Do NOT induce vomiting.
Obtain emergency medical attention.

4.2. Most important symptoms/effects, acute and delayed


Symptoms/effects Not expected to present a significant hazard under anticipated conditions of normal use.
Potential adverse human health effects and Based on available data, the classification criteria are not met.
symptoms

4.3. Indication of immediate medical attention and special treatment needed, if necessary
No additional information available

SECTION 5: Fire-fighting measures


5.1. Suitable extinguishing media
Suitable extinguishing media Water spray. Dry powder. Foam. Carbon dioxide. Sand.
Unsuitable extinguishing media Do not use a heavy water stream.

5.2. Specific hazards arising from the chemical


Hazardous decomposition products in case of Carbon dioxide. Carbon monoxide.
fire

5.3. Special protective actions for fire-fighters


Firefighting instructions Use water spray or fog for cooling exposed containers. Exercise caution when fighting any
chemical fire. Prevent fire fighting water from entering the environment.
Protection during firefighting Self-contained breathing apparatus. Complete protective clothing. Do not enter fire area
without proper protective equipment, including respiratory protection.

SECTION 6: Accidental release measures


6.1. Personal precautions, protective equipment and emergency procedures
6.1.1. For non-emergency personnel
Emergency procedures Evacuate unnecessary personnel.

6.1.2. For emergency responders


Protective equipment For further information refer to section 8: "Exposure controls/personal protection". Equip
cleanup crew with proper protection.
Emergency procedures Ventilate area.

CP 606 Firestop Acrylic Sealant Page 84 of 90 Oct 2023


CFS-S ACR; CP 606
Safety Data Sheet
according to the United Nations GHS (Rev. 4, 2011)

6.2. Environmental precautions


Prevent entry to sewers and public waters. Notify authorities if liquid enters sewers or public waters.

6.3. Methods and materials for containment and cleaning up


Methods for cleaning up Mechanically recover the product. On land, sweep or shovel into suitable containers.
Minimise generation of dust. Store away from other materials.

SECTION 7: Handling and storage


7.1. Precautions for safe handling
Precautions for safe handling Wear personal protective equipment. Wash hands and other exposed areas with mild soap
and water before eating, drinking or smoking and when leaving work. Provide good
ventilation in process area to prevent formation of vapour.
Hygiene measures Wash contaminated clothing before reuse. Do not eat, drink or smoke when using this
product. Always wash hands after handling the product.

7.2. Conditions for safe storage, including any incompatibilities


Storage conditions Keep cool. Store in a dry place. Keep only in the original container in a cool, well ventilated
place away from : Keep container closed when not in use.
Incompatible products Strong bases. Strong acids.
Incompatible materials Sources of ignition. Direct sunlight.

Storage temperature 5 – 25 °C

SECTION 8: Exposure controls/personal protection


8.1. Control parameters
Additional information The product has a pasty consistency. Exposure limit values for respirable dusts are not
relevant for this product.

8.2. Appropriate engineering controls


Other information Do not eat, drink or smoke during use.

8.3. Individual protection measures, such as personal protective equipment (PPE)


Hand protection Protective gloves. EN 374. Wear protective gloves.

Type Material Permeation Thickness (mm) Penetration Standard


Disposable gloves Nitrile rubber (NBR) 1 (> 10 minutes) >0.4 EN ISO 374
Eye protection Chemical goggles or safety glasses

Type Use Characteristics Standard


Safety glasses EN 166, EN 170
Skin and body protection Wear suitable protective clothing

Personal protective equipment symbol(s)

8.4. Exposure limit values for the other components


No additional information available

CP 606 Firestop Acrylic Sealant Page 85 of 90 Oct 2023


CFS-S ACR; CP 606
Safety Data Sheet
according to the United Nations GHS (Rev. 4, 2011)

SECTION 9: Physical and chemical properties


9.1. Basic physical and chemical properties
Physical state Solid
Appearance Pasty

Molecular mass Not determined


Colour red. white. Grey.
Odour characteristic.
Odour threshold Not determined
Melting point Not applicable
Freezing point Not available
Boiling point Not available
Flammability (solid, gas) Not applicable,Non flammable.
Explosive limits Not applicable
Lower explosive limit (LEL) Not applicable
Upper explosive limit (UEL) Not applicable
Flash point Not applicable
Auto-ignition temperature Not applicable
Decomposition temperature Not available
pH ≈ 9 Not applicable
pH solution Not available
Viscosity, kinematic (calculated value) (40 °C) Not applicable
Partition coefficient n-octanol/water (Log Kow) Not available
Vapour pressure Not available
Vapour pressure at 50 °C Not available
Density 1.6 g/cm³
Relative density Not available
Relative vapour density at 20 °C Not applicable
Solubility Not available
Particle size Not available
Particle size distribution Not available
Particle shape Not available
Particle aspect ratio Not available
Particle specific surface area Not available

9.2. Data relevant with regard to physical hazard classes (supplemental)


No additional information available

SECTION 10: Stability and reactivity


10.1. Reactivity
The product is non-reactive under normal conditions of use, storage and transport.

10.2. Chemical stability


Stable under normal conditions. Not established.

10.3. Possibility of hazardous reactions


No dangerous reactions known under normal conditions of use. Not established.

CP 606 Firestop Acrylic Sealant Page 86 of 90 Oct 2023


CFS-S ACR; CP 606
Safety Data Sheet
according to the United Nations GHS (Rev. 4, 2011)

10.4. Conditions to avoid


None under recommended storage and handling conditions (see section 7). Direct sunlight. Extremely high or low temperatures.

10.5. Incompatible materials


Strong acids. Strong bases.

10.6. Hazardous decomposition products


Under normal conditions of storage and use, hazardous decomposition products should not be produced. fume. Carbon monoxide. Carbon dioxide.

SECTION 11: Toxicological information


11.1. Information on toxicological effects
Acute toxicity (oral) Not classified
Acute toxicity (dermal) Not classified
Acute toxicity (inhalation) Not classified

Skin corrosion/irritation Not classified


pH: ≈ 9 Not applicable
Serious eye damage/irritation Not classified
pH: ≈ 9 Not applicable
Respiratory or skin sensitisation Not classified
Germ cell mutagenicity Not classified
Carcinogenicity Not classified
Reproductive toxicity Not classified
STOT-single exposure Not classified

STOT-repeated exposure Not classified

Aspiration hazard Not classified

Potential adverse human health effects and Based on available data, the classification criteria are not met.
symptoms

SECTION 12: Ecological information


12.1. Toxicity
Ecology - general The product is not considered harmful to aquatic organisms nor to cause long-term adverse
effects in the environment.
Hazardous to the aquatic environment, short- Not classified
term (acute)
Hazardous to the aquatic environment, long-term Not classified
(chronic)

12.2. Persistence and degradability


CFS-S ACR; CP 606
Persistence and degradability Not established.

CP 606 Firestop Acrylic Sealant Page 87 of 90 Oct 2023


CFS-S ACR; CP 606
Safety Data Sheet
according to the United Nations GHS (Rev. 4, 2011)

12.3. Bioaccumulative potential


CFS-S ACR; CP 606
Bioaccumulative potential Not established.

12.4. Mobility in soil


CFS-S ACR; CP 606
Mobility in soil No additional information available

12.5. Other adverse effects


Ozone Not classified
Other adverse effects No additional information available

Other information Avoid release to the environment.

SECTION 13: Disposal considerations


13.1. Disposal methods
Waste treatment methods Dispose in a safe manner in accordance with local/national regulations.
Product/Packaging disposal recommendations Recycle the material as far as possible.
Additional information European waste catalogue: 08 04 10 waste adhesives and sealants other than those
mentioned in 08 04 09.

SECTION 14: Transport information


In accordance with ADR / RID / IMDG / IATA / ADN

ADR IMDG IATA RID


14.1. UN number
Not regulated Not regulated Not regulated Not regulated

14.2. UN proper shipping name


Not regulated Not regulated Not regulated Not regulated

14.3. Transport hazard class(es)


Not regulated Not regulated Not regulated Not regulated

14.4. Packing group


Not regulated Not regulated Not regulated Not regulated

14.5. Environmental hazards


Not regulated Not regulated Not regulated Not regulated
No supplementary information available

14.6. Special precautions for user


Overland transport
Not regulated
Transport by sea
Not regulated

CP 606 Firestop Acrylic Sealant Page 88 of 90 Oct 2023


CFS-S ACR; CP 606
Safety Data Sheet
according to the United Nations GHS (Rev. 4, 2011)

Air transport
Not regulated
Rail transport
Not regulated

14.7. Transport in bulk according to Annex II of Marpol and the IBC Code
Not applicable

SECTION 15: Regulatory information


15.1. Safety, health and environmental regulations specific for the product in question
No additional information available

SECTION 16: Other information


SDS Major/Minor None
Issue date 08/02/2021
Revision date 08/02/2021
Supersedes 02/10/2019

Other information None.

SDS_UN_Hilti
This information is based on our current knowledge and is intended to describe the product for the purposes of health, safety and environmental
requirements only. It should not therefore be construed as guaranteeing any specific property of the product.

CP 606 Firestop Acrylic Sealant Page 89 of 90 Oct 2023


Hilti CP 606 Firestop Acrylic Sealant Job Reference
Year Project Name Customer Name Project type
2020 Refurbishment - Residential - 380 Hiram's Highway, Sai Kung KIN HING DOOR ENGINEERING LIMITED Residential
2020 WANG WO TSAI ST, TWTL 126, 137, 160 & 363 BILLION BUILDING MATERIALS LIMITED Residential
2020 TAI PO LAI CHI SHAN (221) LAHINE ENGINEERING LIMITED Residential
2020 NW KLN RECLAM 6 & FAT TSEUNG ST W KWONG YIN WING KOO TIMBER CO LTD Residential
2020 TKO LOHAS PARK PH9 (SITE J) CHEUNG WAH BUILDING MATERIAL LTD Residential
2020 TIN SHUI WAI AREA 112 LOT 33 WING FAT PLUMBING LIMITED Residential
2020 TKO LOHAS PARK PH8 (SITE H) YUN KEE SHUI TUNG WOODEN WORK Residential
2020 KWUNTONG YUE MAN SQUARE DEVELOPMENT EASY SMART ENGINEERING LIMITED Residential
2020 TUEN MUN AREA 56 (500),KWUN CHUI RD LEUNG'S WOODEN CO. Residential
2020 7 MUK TAI ST, KAI TAK 1K3 (6565) EVER GAIN AIR CONDITION ENGINEERING Residential
2021 Refurbishment - Residential - 380 Hiram's Highway, Sai Kung KIN HING DOOR ENGINEERING LIMITED Residential
2021 AREA 54 TUNG CHUNG HOUSING KWONG YIN WING KOO TIMBER CO LTD Residential
2021 KAI TAK SPORTS PARK SHUN HING WOOD WORKING CO LTD Sport & Recreation
2021 KAI TAK SPORTS PARK WELLYSON CONSTRUCTION COMPANY Sport & Recreation
2021 TAIKOO PLACE PH 2B LEE SHING MASONRY ENGINEERING Office
2021 HANG TAI RD, MA ON SHAN AREA 86B PH 1&2 - HOUSING KWONG YIN WING KOO TIMBER CO LTD Residential
2021 Refurbishment - Residential - Various District SHUNING BUILDING MATERIALS Residential
2021 TAI WAI STATION NW RES HOI SING DECORATION Residential
2021 1-11 AU PUI WAN ST, FO TAN LAHINE ENGINEERING LIMITED Residential
2021 NW KLN RECLAM 6 & FAT TSEUNG ST W ` Residential
2021 HKIA SKYCITY COMPLEX BLDG A2&A3 SAN WO COMPANY Retail
2022 HKIA 3508 TERMINAL 2 EASY SMART ENGINEERING LIMITED Transport
2022 KAI TAK SPORTS PARK WELLYSON CONSTRUCTION COMPANY Sport & Recreation
2022 ORGANIC RESOURCES RECOVERY CENTRE PH2 (WASTE TREA KWONG YIN WING KOO TIMBER CO LTD Utilities
2022 New - Residential - Lots No. 2281 S.A, 2282 RP, 2283 RP, 296 SUNNY FIRE BUILDING MATERIALS LTD Residential
2022 POLICE SCHOOL RD HKU DORM (459) PAUL Y. CONSTRUCTION CO LTD Residential
2022 KWONG WAH HOSPITAL PH2 KWAN TAI ENGINEERING CO. LIMITED Health
2022 HING WAH ST WEST LOT 6550 HOTEL LAHINE ENGINEERING LIMITED Hospitality
2022 HKIA SKYCITY COMPLEX BLDG A2&A3 SHEREX ENGINEERING LIMITED Retail
2022 SIU HONG, AREA 54 DD 132 TMTL 483 RIDGID PLUMBING LIMITED Residential
2022 KAI TAK AREA 4B, SITE 3, NKIL 6574 CHIT TAT ELECTRICAL ENGINEERING LTD Residential
2023 KAI TAK SPORTS PARK A & R ENGINEERING COMPANY LIMITED Sport & Recreation
2023 HKIA 3508 TERMINAL 2 GAMMON ENGINEERING & CONSTRUCTION Transport
2023 ASIAWORLD-EXPO PH 2 PAPEPO CONSULTING GROUP LIMITED Community & Cultural
2023 WANG WO TSAI ST, TWTL 126, 137, 160 & 363 BILLION BUILDING MATERIALS LIMITED Residential
2023 KAI TAK AREA 4A, SITE 2, NKIL 6554 CHIT TAT ELECTRICAL ENGINEERING LTD Residential
2023 KWAI CHUNG HOSPITAL PH2 & 3 ANTOP ENGINEERING COMPANY LIMITED Health
2023 UNITED CHRISTIAN HOSPITAL HIN TAT ENGINEERING LIMITED Health
2023 KAI TAK AREA 4C, SITE 2, NKIL 6552 CHIT TAT ELECTRICAL ENGINEERING LTD Residential
2023 IMMIGRATION HEADQUARTERS, TKO LAHINE ENGINEERING LIMITED Office
2023 SIU HONG, AREA 54 DD 132 TMTL 483 SHUN TUNG ENGINEERING CO LTD Residential

CP 606 Firestop Acrylic Sealant Page 90 of 90 Oct 2023