#24 G.I. ROOF SHTS. #24 G.I. RIDGE HOOD


GENERAL CONSTRUCTION NOTES:
50mm X 50mm X 1.5mm
TUBULAR STEEL
1 A.GENERAL NOTES:
1. ALL STRUCTURAL WORKS SHALL BE EXECUTED IN
ACCORDANCE WITH THA NATIONAL STRUCTURAL CODE
C. NOTES ON BEAMS:
1. UNLESS OTHERWISE NOTED IN PLANS OR SPECIFICATIONS ALL BEAMS
50mm X 100mm X 1.5mm SHALL BE CAMBERED AT LEAST 6MM OF THE CLEAR SPAN EXCEPT
OF THE PHILIPPINES (NSCP) 2001 FIFTH EDITION, VOLUME 1. CANTILEVER WHICH SHALL BE 3000MM FOR CLEAR SPAN.
TUBULAR STEEL THE DOCUMENT ACI-318-95 FOR RREINFORCED CONCRETE
SUPPLEMENTS THE NSCP. 2. FOR BEAMS REINFORCING THAT THE END WALL THE CLEAR DISTANCE
#24 G.I. BOX GUTTER FROM THE BAR TO THE FARTHER FACE OF THE WALL SHALL NOT BE LESS
3 2. MATERIAL STRENGTH: THAN 5 BAR DIAMETER. THE REINFORCING BAR SHALL BE TERMINATED ON A
4" X 12" FACIA BOARD UNLESS OTHERWISE INDICATED IN THE PLANS OR NOTED
RB FCL STANDARD 90 DEGREE HOOK. MINIMUM EMBEDMENT SHALL BE 40 BAR DIAMETER
IN SPECS. THE MINIMUM 28 DAYS STRENGTH OF CONCRETE FOR TENSION AND 20 BAR DIAMETER FOR COMPRESSION BARS.

CEILING EAVES
2 ARE AS FOLLOWS:

COLUMN, BEAM, SLAB 3000 psi


3. FOR TWO OR MORE LAYER OF REINFORCING BARS 25MM SEPARATORS
SHALL BE USED.
SLAB ON FILL 2500 psi
4. GENERALLY NO SPLICED SHALL BE PERMITTED ON BEAMS AT POINTS
3. DESIGN LOADS: WHERE CRITICAL BENDING OCCURS. SPLICED WHERE SO PERMITTED
SHALL BE AS SHOWN IN TABLE 1.0.
LIVE LOAD: ROOF 15 psi
D. NOTES ON COLUMN:
DEAD LOAD: AS PER NSCP
1. CONCRETE SHALL BE DEPOSITED IN THE FINAL POSITION WITHOUT
4. IN THE INTERPRETATION OT THESE DRAWING INDICATED SEGREGATION, REHANDLING OR FLOWING. PLACING SHALL BE DONE
FFL DIMENSIONS SHALL GOVERN AND THE DISTANCE OR SIZES WITH BUGGIES BUCKETS OR BY PUMPING. NO CHUTE SHALL BE ALLOWED
ARE NOT TO BE SCALED FOR CONSTRUCTION PURPOSES. EXCEPT TO TRANSFER CONCRETE FROM HOPPERS TO BUGGIES.

3 5. IT SHALL BE THE CONTRACTORS' RESPONSIBILITY TO PROVIDE


ADEQUATE SHORING AND BRACINGS OF THE STRUCTURE FOR
ALL LOADS THAT MAY BE IMPOSED DURING CONSTRUCTION.
WHEELBORROWS OR BUCKETS IN WHICH CASE THEY SHALL NOT
EXCEED 6100MM IN AGGREGATE LENGTH.

E. NOTES ON CONCRETE HOLLOW BLOCKS (CHB):


6. ALL DIMENSIONS ARE IN METERS, UNLESS OTHERWISE SPECIFIED.
1. REINFORCEMENT FOR CONCRETE HOLLOW BLOCKS (CHB) SHALL BE
B. NOTES ON REINFORCING BARS: 10MM DIAMETER BAR SPACED AT 0.80 M ON VERTICAL BARS AND 0.60M
1. UNLESS OTHERWISE SPECIFIED IN THE PLANS THE MINIMUN ON HORIZONTAL BARS.
YIELD STRENGTH OF REINFORCEMENT TO BE USED
CORRESPONDING TO THE STRUCTURAL MEMBER ARE AS 2. CHB SHALL BE "CONVENTIONAL" OR ANY APPROVED EQUAL AND MUST
FOLLOWS: DEVELOP A MINIMUM COMPRESSIVE STRENGTH OF 72.5 KPa.
COLUMNS 40,000 psi 3. PROVIDE 1-12MM DIAMETER BAR ON CORNERS, INTERSECTIONS, END WALLS
BEAMS 40,000 psi AND EACH SIDE OPENING.

4 SLAB 40,000 psi

2. THE FOLLOWING MINIMUM CLEAR CONCRETE COVER


4. LINTEL BEAM SHALL BEAR AT LEAST 0.60M ON EACH SIDE OF THE WALL.
SHALL BE PROVIDED: 5. REINFORCEMENT SHALL BE SPLICE AT MINIMUM OF 400MM.
FOOTING, WALL FOOTING 50MM 6. WHERE CHB WALLS ADJOIN REINFORCED COLUMNS, BEAMS, AND SLABS,
COLUMN 25MM 10MM DIAMETER DOWELS SHALL BE PROVIDED.
BEAMS 25MM

SCALE
ROOF FRAMING PLAN
1:100
5 SLABS 20MM F. NOTES ON STRUCTURAL STEEL:

1. ALL STRUCTURAL STEEL TO BE USED FOR FABRICATION AND ERECTION


TABLE 1.0 OF THE STRUCTURE SHALL COMPLY WITH ALL THE PERTINENT PROVISION
MINIMUM SPLICES
10mmØ DRB.
@ 0.60m O.C, BOTHWAYS
ROOF PLAN BEAMS
OF AISC SPECIFICATION FOR ITS DESIGN.

BAR SIZE TOP BARS BOTTOM BARS


BAR SIZE 2. ALL STRUCTURAL STEEL SHALL CONFORM TO ASTM A-36 , fy=248 MPa.
SCALE 1:100
16 MM 400 MM 250 MM 400 MM
10mmØ DRB. 3. WELDING SHALL CONFORM TO AWS STANDARDS.
12 MM 300 MM 200 MM 300 MM
@ 0.60m O.C, BOTHWAYS 10 MM 300 MM 200 MM 300 MM 4. SAGRODS AND CROSS BRACING SHALL BE INSTALLED AND TIGHTENED
BEFORE INSTALLATION OF ROOFING OR WALL CLADDING.
L L L
10mmHORBAR 10mmHORBAR MAIN REINFORCEMENT 5. ALL CONNECTIONS SHOWN IN DRAWING SHALL BE ABLE TO DEVELOP
EVERY3CHBLAYER
EVERY3CHBLAYER with TIES B THE FULL TENSILE CAPACITY OF THE CONNECTED MEMBERS.
NGL. NGL. 5"CHBWALL B
5"CHBWALL
MAIN REINFORCEMENT

D
B
with TIES
0.60m

10mmVERTDOWELS
0.60

SPACED@800mmO.C. MAIN
0.80m

D
W
0.80

10mmVERTDOWELS REINFORCEMENT

D
SPACED@800mmO.C. CONCRETE COUNTER

W
with TIES

W
FORTS
3$-$12mmØ$HOR$BARS$&
3$-$12mmØ$HOR$BARS$&
10mmØ$STIRRUPS$SPACED
10mmØ$STIRRUPS$SPACED
@EVERY50mmO.C.
@EVERY50mmO.C.

PLAN C1/F1 PLAN C1/F1 PLAN C1/F1


0.20

0.20m

WALL REINFORCEMENT DETAILS WF-1 WF-2 TYPICAL COLUMN / WALL FOOTING


SCALE 1:100 DETAILS
SCALE 1:100

SCHEDULE OF BEAM
MAIN REINFORCEMENT BAR
DIMENSION
AT SUPPORTS AT MIDSPAN SIZE OF SPACING OF
MARK
STIRRUPS STIRRUPS B

EXTRA EXTRA
B D TOP BARS BOTTOM BARS TOP BARS BOTTOM BARS MAIN BARS
TOP BARS BOTTOM BARS

D
3@100mm, 3@150mm, TIES
PB-1 0.25m 0.30m 4-12mmØ RSB 2-12mmØ RSB 2-12mmØ RSB 2-12mmØ RSB 4-12mmØ RSB 2-12mmØ RSB 10mmØ RSB
REST 200mm

3@100mm, 3@150mm,
LB-1 0.20m 0.25m 3-12mmØ RSB 2-12mmØ RSB 2-12mmØ RSB 2-12mmØ RSB 3-12mmØ RSB 2-12mmØ RSB 10mmØ RSB
REST 200mm

3@100mm, 3@150mm,
RB-1 0.20m 0.25m 3-12mmØ RSB 2-12mmØ RSB 2-12mmØ RSB 2-12mmØ RSB 3-12mmØ RSB 2-12mmØ RSB 10mmØ RSB
REST 200mm