Load - Calculation - Carrier
Load - Calculation - Carrier
CHAP CHAP
TABLE REFERENCE TABLE REFERENCES
REF REF
AREA OR SUNGAIN OR LOCAL TIME LOCAL TIME
ITEM TEMP. DIFF FACTOR ESTIMATE FOR 15.00 PM PEAK LOAD 12.00 AM
QUANTITY SUN TIME SUN TIME
SOLAR GAIN-GLASS (Btu/hr) 25,436 HOUR OF OPERATION 16
GLASS 50 SQ FT X 108.24 X 0.94 CONDITIONS DB WB % RH DP GR/LB
3&4
2
GLASS 50 SQ FT X 108.24 X 0.94 ROOM (RM) 76 50 0 0 0
GLASS 50 SQ FT X 108.24 X 0.94 DIFFERENCE 19 XXX XXX XXX 0
SKYLIGHT 50 SQ FT X 108.24 X 0.94 OUTDOOR AIR
SOLAR & TRANS. GAIN-WALLS & ROOF (Btu/hr) 9,956 VENTI- 40 PEOPLE X 50 CFM/PERSON = 2000
WALL 200 SQ FT X 19 X 0.32 LATION 1000 SQ FT X 5 CFM/SQ FT = 5000
WALL 200 SQ FT X 19 X 0.32 CFM VENTILATION = 5000
WALL 200 SQ FT X 19 X 0.32 SWINGING
WALL 200 SQ FT X 19 X 0.32 REVOLVING DOORS 50 PEOPLE X 12 CFM/PERSON = 600
6
ROOF-SUN 200 SQ FT X 19 X 0.67 INFIL- OPEN DOORS 3 DOORS X 100 CFM/DOOR = 300
5
STORAGE 25 SQ FT X 2 X 0.4
SUPPLY AIR QUANTITY
8
SUB TOTAL 2 (Btu/hr) 50,560 SUPPLY ROOM SENS. HEAT = 6,058 CFMSA
SAFETY FACTOR 10 % CFM 1.08 X 8.50 FDESIRE DIFF
SUPPLY DUCT + SUPPLY DUCT + FAN BYPASS 6058 CFM SA - 6,058 CFMDA = - CFMBA
HEAT GAIN % 15 LEAK LOSS % 10 H.P. 10 % CFM
OUTDOOR AIR 15 CFM X 19 F X 0.5 BF X 1.08 RESULTING ENT & LVG CONDITIONS AT APPARATUS
8
EFFECTIVE ROOM SENSIBLE HEAT(Btu/hr) 75,236 EDB TRM 76 F+ 0.83 CFMOA X (TOA 95 F -TRM 76 F) = TEDB 92 F
LATENT HEAT (Btu/hr) 7,560 CFM+
6
INFILTRATION 300 CFM X 15 GR/LB X 0.68 LDB TADP 53 F+ 0.5 BF X (TEDB 92 F -TADP 53 F) = TLD 72 F
PEOPLE 30 PEOPLE X 0 B
8 0
3&7
SUPPLY AIR DUCT LEAK LOSS 10 % 3. NORMALLY. USE "CFM VENTILATION" FOR "CFM OUTDOOR AIR" HOWEVER
OUTDOOR AIR 0 CFM X 0GR/LbX 0.5 BF X 0.68 WHEN INFILTRATION IS TO BE OFFSET, REFER TO PAGE 92 TO DETERMINE
EFFECTIVE ROOM LATENT HEAT (Btu/hr) 8,316 "CFM OUTDOOR AIR."
EFFECTIVE ROOM TOTAL HEAT (Btu/hr) 83,552 4. WHEN INFILTRATION IS NOT TO BE OFFSET, AND "CFM VENTILATION IS LESS THAN
8
OUTDOOR AIR HEAT 1,635 "CFM INFILTRATION," THEN THE EXCESS INFILTRAITON IS ACCOUNTED FORHERE.
FX (1 -
SENSIBLE : 450 CFM X 5 0.5 BF)X1.08
LATENT : 510 CFM X X(1--
2 GR/Lb XB(1 0.5 BF)X0.68
RETURN DUCT RETURN DUCT
10 10
HEAT GAIN % + LEAK GAIN %
HP DEHUM. &
7
5 5
PUMP % + PIPE LOSS % * IF THIS DIFF TEMP IS TOO HIGH, DETERMINE SUPPLY CFM FOR DESIRED DIFFERENCE BY SUPPLY
SUB TOTAL 4 (Btu/hr) 2,126 AIR QUANTITY FORMLA.
#
WHEN BYPASSING MIXTURE OF OUTDOOR AND RETURN AIR, USE SUPPLY CFM WHEN BYPASSING
GRAND TOTAL HEAT (Btu/hr) 85,677
RETURN AIR ONLY, USE DEHUMIFIED CFM.
C32: Power, kw
Grossory of power of operating motor in the A/C area. It can generate heat to be the cooling load.
C33: Power, kw
Grossory of power of lighting in the A/C area. It can generate heat to be the cooling load.
L21: Door,
The numbe of open door of the A/C area.