Professional Documents
Culture Documents
6es7 134-6gf00-0aa1
6es7 134-6gf00-0aa1
General information
Product type designation AI 8xI 2-/4-wire BA
HW functional status from FS04
Firmware version
● FW update possible Yes
usable BaseUnits BU type A0, A1
Color code for module-specific color identification CC01
plate
Product function
● I&M data Yes; I&M0 to I&M3
● Isochronous mode No
● Measuring range scalable No
Engineering with
● STEP 7 TIA Portal configurable/integrated as of V13 SP1
version
● STEP 7 configurable/integrated as of version V5.5 SP3 / -
● PROFIBUS as of GSD version/GSD revision GSD Revision 5
● PROFINET as of GSD version/GSD revision GSDML V2.3
Operating mode
Supply voltage
Rated value (DC) 24 V
permissible range, lower limit (DC) 19.2 V
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes
Input current
Current consumption, max. 25 mA; without sensor supply
Encoder supply
24 V encoder supply
● 24 V Yes
● Short-circuit protection Yes
● Output current, max. 0.7 A; total current of all encoders/channels
Power loss
Power loss, typ. 0.7 W; Without encoder supply voltage
Address area
Address space per module
● Address space per module, max. 16 byte
Hardware configuration
Automatic encoding
● Mechanical coding element Yes
Selection of BaseUnit for connection variants
● 1-wire connection BU type A0, A1
● 2-wire connection BU type A0, A1
● 4-wire connection BU type A0, A1 + potential distributor module
Analog inputs
Number of analog inputs 8; Single-ended
● For current measurement 8
permissible input current for current input (destruction 50 mA
limit), max.
Cycle time (all channels), min. 1 ms; per channel
Input ranges (rated values), currents
● 0 to 20 mA Yes
— Input resistance (0 to 20 mA) 100 Ω; 15 bit
● -20 mA to +20 mA Yes
Encoder
Connection of signal encoders
● for voltage measurement No
● for current measurement as 2-wire transducer Yes
— Burden of 2-wire transmitter, max. 650 Ω
● for current measurement as 4-wire transducer Yes
Errors/accuracies
Linearity error (relative to input range), (+/-) 0.01 %
Temperature error (relative to input range), (+/-) 0.005 %/K
Crosstalk between the inputs, min. 50 dB
Repeat accuracy in steady state at 25 °C (relative to 0.05 %
input range), (+/-)
Operational error limit in overall temperature range
● Current, relative to input range, (+/-) 0.5 %
Basic error limit (operational limit at 25 °C)
● Current, relative to input range, (+/-) 0.3 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
● Series mode interference (peak value of 70 dB; With conversion time 67.5 / 22.5 / 18.75 ms: 40 dB
interference < rated value of input range), min.
Interrupts/diagnostics/status information
Diagnostics function Yes
Alarms
● Diagnostic alarm Yes
● Limit value alarm No
Diagnostic messages
Potential separation
Potential separation channels
● between the channels No
● between the channels and backplane bus Yes
● between the channels and the power supply of No
the electronics
Isolation
Isolation tested with 707 V DC (type test)
Ambient conditions
Ambient temperature during operation
● horizontal installation, min. -30 °C
● horizontal installation, max. 60 °C
● vertical installation, min. -30 °C
● vertical installation, max. 50 °C
Altitude during operation relating to sea level
● Installation altitude above sea level, max. 5 000 m; Restrictions for installation altitudes > 2 000 m, see
manual
Dimensions
Width 15 mm
Height 73 mm
Depth 58 mm
Weights
Weight, approx. 31 g