44mm Fire Door

CF5143
FD30 Fire Door
Installation Instructions
This door is to be installed as FD30 Doorset.
Maximum leaf size 2040mm x 926mm.

ALLOWED ALLOWED NOT ALLOWED

Double acting, single


Single leaf, single acting Double leaf, single acting or double leaf

GLAZING

For other configurations,


closers and glazing of
apertures, see the specific
manufacturer’s technical
data sheet from
Aperturing to be completed www.jeld-wen.co.uk
by an approved third party or phone the company
BWF CERTIFIRE member only helpline on 0845 122 2890

CF 5143

30
33013

NEVER REMOVE THIS TAMPER EVIDENT LABEL FROM THE TOP EDGE OF THE DOOR LEAF
Installation Instructions
All Dimensions are in Millimetres (mm)

1. Door Frame 4. Door Seals


Single leaf 20mm Max.
Double leaf 15mm x 4mm
Alternative Seal Position Wall
Frame Head
Any CERTIFIRE approved intumescent
Door Leaf
77mm

Frame
5. Hinges & Screws
Door Leaf 3 X per door

25mm
Seals to run though
10mm the frame head and 8 screws per hinge
The frame to wall gap must be filled with top of the door. Min. 50mm long
stone wool or sealed with intumescent These are to be offset

100mm
from each other.
mastic if less than 6mm wide.
Diameter: 3mm

2. Hinge Position & OR


No.08
Hinges must be
Fixing Locations CE marked

150mm 25mm - 30mm 2mm - 3mm


Pilot holes required. Screws to door leaf must be chipboard thread pattern.

Note:
Where smoke seals are
required the threshold gap 6. Lock or Latch 25mm
19mm
1981mm / 2040mm

shall be 3mm maximum All dimensions are maximum.


Min. 6 frame to unless a threshold seal is
wall fixings on
fitted. 19mm
each side

120mm
25mm
120mm

165mm

Central in Height
165mm

225mm - 250mm 75mm


Max. 8mm Max. 4mm 75mm

Measure from the top of the floor covering to the Any CERTIFIRE approved
underside of the door. Pilot holes required. Screws to door leaf must be chipboard thread pattern.

3. Trimming of the door 7. Door Closer, handles & any other


surface mounted hardware

Minimum 38mm long


Max. 3mm

Max. 3mm

Jamb mounted closer may be used


No limit on internal doors to dwelling with
single family occupancy.

Any CERTIFIRE approved to BS EN 1154


Pilot holes required. Screws to door leaf must be chipboard thread pattern.

You might also like