Download as pdf or txt
Download as pdf or txt
You are on page 1of 7

PWPS Project # 0301 PRATT & WHITNEY FT8 0301-189-C003L

Greenport Power LLC; NGS Rev - Orig: 12-May-03


Control System I/O BOP List
Rack Slot Channel Type ID (Tag Name) Description State

1 11 1-2 WG 9905-969 LN AI 4-20 mA 6 channel


1 11 1-2-1 AI ET-2020 (VA) GEN: VXA VOLT PHASE A 0-18,000 Volts
1 11 1-2-2 AI ET-2021 (VB) GEN: VXB VOLT PHASE B 0-18,000 Volts
1 11 1-2-3 AI ET-2022 (VC) GEN: VXC VOLT PHASE C 0-18,000 Volts
1 11 1-2-4 AI reserved: IXA
1 11 1-2-5 AI reserved: IXB
1 11 1-2-6 AI reserved: IXC
NOTE: The above Module is not located in the BOP Cabinet

1 11 1-5 WG 9905-969 LN AI 4-20 mA 6 channel


1 11 1-5-1 AI spare
1 11 1-5-2 AI spare
1 11 1-5-3 AI spare
1 11 1-5-4 AI spare
1 11 1-5-5 AI spare
1 11 1-5-6 AI spare
1 11 1-6 WG 9905-972 LN AO 4-20 mA 6 channel
1 11 1-6-1 AO ET-2023 GEN: Generator MWs 0 - 96 Mwatts
1 11 1-6-2 AO ET-2024 GEN: Generator MVARs -96 to +96 Mvars
1 11 1-6-3 AO ET-2025 GEN: Generator Current 0-4000 Amps
1 11 1-6-4 AO ET-2026 GEN: Generator Power Factor " -1 to +1 dimensionless
1 11 1-6-5 AO FT-1502A SCR: Fuel Oil Flow - Turbine A 0 - 35 GPM
1 11 1-6-6 AO FT-1503A SCR: Fuel Oil Flow - Turbine B 0 - 35 GPM
1 11 1-7 WG 9905-969 LN AI 4-20 mA 6 channel
1 11 1-7-1 AI spare
1 11 1-7-2 AI spare
1 11 1-7-3 AI spare
1 11 1-7-4 AI spare
1 11 1-7-5 AI spare
1 11 1-7-6 AI spare
1 11 1-8 WG 9905-971 LN Discrete Inputs 16 channel
1 11 1-8-01 DI XS-2001 GEN: 69 kV Disconnect Switch 613 Position Open Closes when in position
1 11 1-8-02 DI XS-2004 GEN: 69 kV Breaker 610 Status Open Closes when in position
1 11 1-8-03 DI XS-2005 GEN: 69 kV Breaker 610 Status Closed Closes when in position
1 11 1-8-04 DI XS-2006 GEN: 69 kV Lockout A Operated Closes on lockout operation
whs
Rev: 12-May-03 0301-189-c003L .xls
1/7 BOP IO List

Homepage Previous Document


PWPS Project # 0301 PRATT & WHITNEY FT8 0301-189-C003L
Greenport Power LLC; NGS Rev - Orig: 12-May-03
Control System I/O BOP List
Rack Slot Channel Type ID (Tag Name) Description State
1 11 1-8-05 DI XS-2007 GEN: 69 kV Lockout B Operated Closes on lockout operation
1 11 1-8-06 DI XS-2008 GEN: GSU Transformer Common Trouble Closes on alarm
1 11 1-8-07 DI XS-2009 GEN: 69 kV/Transformer Disconnect Switch Open Closes when in position
1 11 1-8-08 DI XS-2010 GEN: Generator Breaker Trip Closes on occurrence
1 11 1-8-09 DI XS-2014 GEN: HOA Not Auto Position Opens when in position
1 11 1-8-10 DI spare
1 11 1-8-11 DI spare
1 11 1-8-12 DI spare
1 11 1-8-13 DI spare
1 11 1-8-14 DI spare
1 11 1-8-15 DI spare
1 11 1-8-16 DI spare
1 11 1-9 WG 9905-973 LN Relay Outputs 8 channel
1 11 1-9-01 DO XS-2002 GEN: 69 kV Breaker 610 Control Open Closes to open bkr
1 11 1-9-02 DO XS-2003 GEN: 69 kV Breaker 610 Control Close Closes to close bkr
1 11 1-9-03 DO XS-2011 GEN: Generator Breaker Status Open Closes when in position
1 11 1-9-04 DO XS-2012 GEN: Generator Breaker Status Closed Closes when in position
1 11 1-9-05 DO XS-2013 GEN: Generator Breaker Lockout Closes on occurrence
1 11 1-9-06 DO spare
1 11 1-9-07 DO spare
1 11 1-9-08 DO spare
1 11 1-10 WG 9905-969 LN AI 4-20 mA 6 channel
1 11 1-10-01 AI PT-1101 AIR: Air Receiver Discharge Pressure 0-200 PSIG
1 11 1-10-02 AI spare
1 11 1-10-03 AI spare
1 11 1-10-04 AI spare
1 11 1-10-05 AI spare
1 11 1-10-06 AI spare
1 11 1-11 WG 9905-969 LN AI 4-20 mA 6 channel
1 11 1-11-01 AI LIT-1010 WD: Demineralized Water Tank Level 0-100 %
1 11 1-11-02 AI LIT-1011 WR: Raw Water Tank Level 0-100 %
1 11 1-11-03 AI spare
1 11 1-11-04 AI spare
1 11 1-11-05 AI spare
1 11 1-11-06 AI AT-1025 WR: Raw Water Turbidity Level 0-50 NTU
1 11 12 WG 9905-973 LN Relay Outputs 8 channel
1
whs 11 1-12-01 DO spare
Rev: 12-May-03 0301-189-c003L .xls
2/7 BOP IO List

Homepage Previous Document


PWPS Project # 0301 PRATT & WHITNEY FT8 0301-189-C003L
Greenport Power LLC; NGS Rev - Orig: 12-May-03
Control System I/O BOP List
Rack Slot Channel Type ID (Tag Name) Description State
1 11 1-12-02 DO spare
1 11 1-12-03 DO HS-1012A WR: RW Pump A Start Close to run
1 11 1-12-04 DO HS-1018A WD: Demin Pump A Start Close to run
1 11 1-12-05 DO spare
1 11 1-12-06 DO HS-1006A WR: RW Booster Pump Start Close to run
1 11 1-12-07 DO SOV-1008 WD: Demin Inlet SOV Contact closes to energize SOV
1 11 1-12-08 DO SOV-1009 WR: RW Inlet SOV Contact closes to energize SOV
1 11 13 WG 9905-973 LN Relay Outputs 8 channel
1 11 1-13-01 DO spare
1 11 1-13-02 DO spare
1 11 1-13-03 DO HS-1013A WR: RW Pump B Start Close to run
1 11 1-13-04 DO HS-1019A WD: Demin Pump B Start Close to run
1 11 1-13-05 DO spare
1 11 1-13-06 DO XS-1010 WD: Demin Water Tank Lo-Lo Level Heater Cut-Off Open on Lo-Lo Level
1 11 1-13-07 DO XS-1011 WR: Raw Water Tank Lo-Lo Level Heater Cut-Off Open on Lo-Lo Level
1 11 1-13-08 DO SOV-306 LW: Waste Drains Isolation SOV Contact closes to energize SOV
1 11 14 WG 9905-973 LN Relay Outputs 8 channel
1 11 1-14-01 DO XS-1303 SCR: Unit Start - Purge Fan Start Command Close to Start
1 11 1-14-02 DO spare
1 11 1-14-03 DO XS-1305 SCR: EGT increase lightoff sensed / Start SCR Blower 1 Close to run
1 11 1-14-04 DO XS-1306 SCR: Water On/Ammonia Injection Pump Start Close to run
1 11 1-14-05 DO spare
1 11 1-14-06 DO UA-1506 CEMS: Turbine A : Flame / On Closed when on
1 11 1-14-07 DO UA-1507 CEMS: Turbine B : Flame / On Closed when on
1 11 1-14-08 DO UA-1508 CEMS: Generator Breaker Closed Closed on occurrence

whs
Rev: 12-May-03 0301-189-c003L .xls
3/7 BOP IO List

Homepage Previous Document


PWPS Project # 0301 PRATT & WHITNEY FT8 0301-189-C003L
Greenport Power LLC; NGS Rev - Orig: 12-May-03
Control System I/O BOP List
Rack Slot Channel Type ID (Tag Name) Description State
1 11 4-4 WG 9905-971 LN Discrete Inputs 16 channel
1 11 4-4-01 DI LSL-223 LF: Fuel Tank #1 Low Level Contact opens when in alarm
1 11 4-4-02 DI LSH-223 LF: Fuel Tank #1 High Level Contact opens when in alarm
1 11 4-4-03 DI ZSC-212 LF: Fuel Tank #1 Recirc Isolation AOV-212 Closed Contact closes when in position
1 11 4-4-04 DI ZSC-215 LF: Fuel Tank #1 Inlet Isolation AOV-215 Closed Contact closes when in position
1 11 4-4-05 DI ZSO-215 LF: Fuel Tank #1 Inlet Isolation AOV-215 Open Contact closes when in position
1 11 4-4-06 DI ZSC-216 LF: Fuel Tank #1 Outlet Isolation AOV-216 Closed Contact closes when in position
1 11 4-4-07 DI spare
1 11 4-4-08 DI spare
1 11 4-4-09 DI XS-1315 SCR: High Inlet Pressure Open on alarm
1 11 4-4-10 DI XS-1316 SCR: High Inlet Temperature Open on alarm
1 11 4-4-11 DI XL-1012A WR: RW Pump A Running Closed when running
1 11 4-4-12 DI XL-1018A WD: Demin Pump A Running Closed when running
1 11 4-4-13 DI UA-1030 WD: Demineralized Trailer Alarm Open on alarm
1 11 4-4-14 DI XL-1006A WR: RW Booster Pump Running Closed when running
1 11 4-4-15 DI ZSC-1008 WD: Demin Inlet Isolation AOV-1008 Closed Contact closes when in position
1 11 4-4-16 DI ZSC-1009 WR: RW Inlet AOV-1009 Closed Contact closes when in position
1 11 4-5 WG 9905-971 LN Discrete Inputs 16 channel
1 11 4-5-01 DI LSL-218 LF: Fuel Tank #2 Low Level Contact opens when in alarm
1 11 4-5-02 DI LSH-218 LF: Fuel Tank #2 High Level Contact opens when in alarm
1 11 4-5-03 DI ZSC-211 LF: Fuel Tank #2 Recirc Isolation AOV-211 Closed Contact closes when in position
1 11 4-5-04 DI ZSC-214 LF: Fuel Tank #2 Inlet Isolation AOV-214 Closed Contact closes when in position
1 11 4-5-05 DI ZSO-214 LF: Fuel Tank #2 Inlet Isolation AOV-214 Open Contact closes when in position
1 11 4-5-06 DI ZSC-213 LF: Fuel Tank #2 Outlet Isolation AOV-213 Closed Contact closes when in position
1 11 4-5-07 DI spare
1 11 4-5-08 DI spare
1 11 4-5-09 DI XS-1320 SCR: Low Ammonia Pressure Open on alarm
1 11 4-5-10 DI spare
1 11 4-5-11 DI XL-1013A WR: RW Pump B Running Closed when running
1 11 4-5-12 DI XL-1019A WD: Demin Pump B Running Closed when running
1 11 4-5-13 DI FS-1302 WS: Safety Shower Activated Open on alarm
1 11 4-5-14 DI ZSC-1201 WF: Fire Water Valve FW-V-01 Status Open when in position
1 11 4-5-15 DI ZSC-1202 WF: Fire Water Valve FW-V-00 Status Open when in position
1 11 4-5-16 DI XS-1210 WF: Plant Fire Alarm Open when in alarm
1 11 4-6 WG 9905-973 LN Relay Outputs 8 channel
1 11 4-6-1 DO SOV-212 LF: Fuel Tank #1 Recirc Isolation SOV Contact closes to energize SOV
1 11 4-6-2 DO SOV-215 LF: Fuel Tank #1 Inlet Isolation SOV Contact closes to energize SOV
whs
Rev: 12-May-03 0301-189-c003L .xls
4/7 BOP IO List

Homepage Previous Document


PWPS Project # 0301 PRATT & WHITNEY FT8 0301-189-C003L
Greenport Power LLC; NGS Rev - Orig: 12-May-03
Control System I/O BOP List
Rack Slot Channel Type ID (Tag Name) Description State
1 11 4-6-3 DO SOV-216 LF: Fuel Tank #1 Outlet Isolation SOV Contact closes to energize SOV
1 11 4-6-4 DO spare
1 11 4-6-5 DO spare
1 11 4-6-6 DO spare
1 11 4-6-7 DO spare
1 11 4-6-8 DO HS-1106B AIR: Compressor A Start Closes to start compressor
1 11 4-7 WG 9905-969 LN AI 4-20 mA 6 channel
1 11 4-7-1 AI LIT-223 LF: Fuel Tank #1 Level 0-100%
1 11 4-7-2 AI LIT-218 LF: Fuel Tank #2 Level 0-100%
1 11 4-7-3 AI PT-201 LF: Inlet Press. Fuel Metering & Filter Skid 0-100 PSIG
1 11 4-7-4 AI FT-226 LF: Fuel Flow tbd
1 11 4-7-5 AI spare
1 11 4-7-6 AI spare
1 11 4-8 WG 9905-969 LN AI 4-20 mA 6 channel
1 11 4-8-1 AI AT-1401 CEMS: Stack NOx correction to 15% O 2 0-200 ppmvd
1 11 4-8-2 AI AT-1402 CEMS: Stack CO correction to 15% O2 0-250 ppmvd
1 11 4-8-3 AI AT-1403 CEMS: Stack O2 0-25%
1 11 4-8-4 AI AT-1404 CEMS: Stack SO2 correction to 15% O2 0-10 ppmvd
1 11 4-8-5 AI AT-1405 CEMS: Stack NH3 correction to 15% O2 0-30 ppmvd
1 11 4-8-6 AI spare
1 11 4-9 WG 9905-973 LN Relay Outputs 8 channel
1 11 4-9-01 DO SOV-211 LF: Fuel Tank #2 Recirc Isolation SOV Contact closes to energize SOV
1 11 4-9-02 DO SOV-213 LF: Fuel Tank #2 Outlet SOV Contact closes to energize SOV
1 11 4-9-03 DO SOV-214 LF: Fuel Tank #2 Inlet Isolation SOV Contact closes to energize SOV
1 11 4-9-04 DO spare
1 11 4-9-05 DO spare
1 11 4-9-06 DO spare
1 11 4-9-07 DO spare
1 11 4-9-08 DO HS-1107B AIR: Compressor B Start Closes to start compressor
1 11 4-10 WG 9905-969 LN AI 4-20 mA 6 channel
1 11 4-10-01 AI spare
1 11 4-10-02 AI spare
1 11 4-10-03 AI FI-1317 SCR: Ammonia Flow Rate 0-40 GPM
1 11 4-10-04 AI LIT-1318 SCR: Ammonia Tank Level 0-100%
1 11 4-10-05 AI spare
1 11 4-10-06 AI spare
whs
Rev: 12-May-03 0301-189-c003L .xls
5/7 BOP IO List

Homepage Previous Document


PWPS Project # 0301 PRATT & WHITNEY FT8 0301-189-C003L
Greenport Power LLC; NGS Rev - Orig: 12-May-03
Control System I/O BOP List
Rack Slot Channel Type ID (Tag Name) Description State
1 11 4-11 WG 9905-971 LN Discrete Inputs 16 channel
1 11 4-11-01 DI XS-1307 SCR: Purge Fan #1 Fault Open on fault
1 11 4-11-02 DI XS-1308 SCR: Purge Fan #2 Fault Open on fault
1 11 4-11-03 DI XS-1309 SCR: Purge Cycle Complete Close when complete
1 11 4-11-04 DI XS-1310 SCR: General Trouble Alarm Open on fault
1 11 4-11-05 DI XS-1311 SCR: Blower #1 Fault Open on fault
1 11 4-11-06 DI XS-1312 SCR: Blower #2 Fault Open on fault
1 11 4-11-07 DI XS-1313 SCR: Ammonia Pump #1 Fault Open on fault
1 11 4-11-08 DI XS-1314 SCR: Ammonia Pump #2 Fault Open on fault
1 11 4-11-09 DI LSHH-1319 SCR: Ammonia Tank Hi-Hi Level Open on high high level
1 11 4-11-10 DI UA-1406 CEMS: System Trouble Open on fault
1 11 4-11-11 DI UA-1407 CEMS: Shelter Fire Detection Open on fire
1 11 4-11-12 DI UA-1408 CEMS: High Emissions Open on high emissions
1 11 4-11-13 DI UA-1409 CEMS: in Operation Open on occurrence
1 11 4-11-14 DI UA-1410 CEMS: in Calibration Open on occurrence
1 11 4-11-15 DI spare
1 11 4-11-16 DI UA-1109 AIR: Compressor A Malfunction Alarm Opens on alarm
1 11 4-12 WG 9905-971 LN Discrete Inputs 16 channel
1 11 4-12-01 DI LSH-301 LW: Ammonia Area Sump High Level Open on high level
1 11 4-12-02 DI LSHH-302 LW: Clean Waste Water Sump Hi-Hi Level Open on high high level
1 11 4-12-03 DI LSH-303 LW: Liquid between walls of Oil/Water Separator Open on high level
1 11 4-12-04 DI LSH-304 LW: High Oil Level in Oil/Water Separator Open on high level
1 11 4-12-05 DI LS-305 LW: Leak in Inlet Double Wall Pipe to Oil Water Separater Open when in position
1 11 4-12-06 DI ZSC-306 LW: Waste Drains Isolation AOV-306 Closed Closes when in position
1 11 4-12-07 DI LSH-307 LW: Fuel Unloading Area Sump High Level Open on high level
1 11 4-12-08 DI LSH-308 LW: Dry Valve Pit High Level Open on high level
1 11 4-12-09 DI LSH-309 LW: Fuel Tank Containment Sump High Level Open on high level
1 11 4-12-10 DI LSHH-309 LW: Fuel Tank Containment Sump Hi-Hi Level Open on high high level
1 11 4-12-11 DI LSH-311 LW: Transformer Area Sump High Level Open on high level
1 11 4-12-12 DI LSH-312 LW: Turbine Water Wash Tank High Level Open on high level
1 11 4-12-13 DI LSH-313 LW: Ammonia Skid Containment High Level Open on high level
1 11 4-12-14 DI LSH-202 LW: Leak Detection Sump High Level Contact open when in alarm
1 11 4-12-15 DI LSH-220 LW: Waste Oil Tank High Level Contact open when in alarm
1 11 4-12-16 DI UA-1111 AIR: Compressor B Malfunction Alarm Opens on alarm
1 11 4-13 WG 9905-972 LN AO 4-20 mA 6 channel
1 11 4-13-1 AO JT-1501 CEMS: Turbine A & B Gross Operating Load 0 - 96 Mwatts
1 11 4-13-2 AO FT-1502 CEMS: Fuel Oil Flow - Turbine A 0 - 35 GPM
whs
Rev: 12-May-03 0301-189-c003L .xls
6/7 BOP IO List

Homepage Previous Document


PWPS Project # 0301 PRATT & WHITNEY FT8 0301-189-C003L
Greenport Power LLC; NGS Rev - Orig: 12-May-03
Control System I/O BOP List
Rack Slot Channel Type ID (Tag Name) Description State
1 11 4-13-3 AO FT-1503 CEMS: Fuel Oil Flow - Turbine B 0 - 35 GPM
1 11 4-13-4 AO FT-1504 CEMS: Water Injector Flow - Turbine A 0 - 72 GPM
1 11 4-13-5 AO FT-1505 CEMS: Water Injector Flow - Turbine B 0 - 72 GPM
1 11 4-13-6 AO FT-1301 CEMS: NH3 Flow Rate 0 - 40 GPM

NOTES

BOP System Abbreviations are as follows:


AIR: Air Compressor
CEMS: Continous Emissions Monitor System
GEN: Generator, Transformer and Switch Yard
LF: Liquid Fuel
LW: Liquid Waste
SCR: Selective Catalytic Reduction
WD: Demin Water
WF: Fire Water
WR: Raw Water
WS: Safety Shower Water
WW: Well Water

* present intent to output Fuel flow separately to CEMS & to SCR


Polarity disagreement (I/O vs Logic): As provided by Framatome documents