Double Pulse Test Method For Neutral Point Clamped Inverter Switches at The Nominal Rating While Using Only Half of The Nominal DC Link Voltage

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 6

2022 International Symposium on Power Electronics,

Electrical Drives, Automation and Motion

Double pulse test method for neutral point clamped


2022 International Symposium on Power Electronics, Electrical Drives, Automation and Motion (SPEEDAM) | 978-1-6654-8459-6/22/$31.00 ©2022 IEEE | DOI: 10.1109/SPEEDAM53979.2022.9842036

inverter switches at the nominal rating while using


only half of the nominal DC link voltage
Juhamatti Korhonen, Aleksi Mattsson, Pasi Nuutinen, Riku Pöllänen
Pasi Peltoniemi, Olli Pyrhönen, and Pertti Silventoinen The Switch Drive Systems Oy
School of Energy Systems Lappeenranta, Finland
Lappeenranta-Lahti University of Technology
Lappeenranta, Finland

Abstract—Double pulse test is the industry standard for


determining the switching characteristics of a semiconductor sw 1
switch. The component manufacturers implement the double + d 5
H
pulse test with a dedicated test setup with favorable layout for
sw 2
minimizing the switching loop inductance. Such layout and min-
K n
imized loop inductances may not be implemented with different D C K l-n
inverter topologies. Therefore, independent tests must be done for + L d 6
sw 3
each switch of the phase-leg to ensure the switching behavior for
each possible commutation loop. This procedure becomes more
critical with more complex phase-leg structures of multilevel sw 4
inverters. This paper presents a double pulse testing method
dedicated for a phase-leg of a three-level neutral point clamped
inverter. With the proposed method, all of the commutation loops Fig. 1. Single phase-leg of a three-level NPC.
within the phase-leg can be tested at nominal voltage rating with
half of the nominal DC link voltage as input. The method is
verified with experimental results using a phase-leg of a medium optimized for a low stray inductance for ideal switching
voltage three-level neutral point clamped inverter using 4.5 kV
rated insulated-gate bipolar transistors. waveforms. This type of dedicated DPT testbeds can be used
Index Terms—Pulse width modulation inverters, insulated gate with varying pulse lengths to switching characteristics and
bipolar transistors, semiconductor device testing losses over the full current range of the switch [3]. This
feature of DPT can be extended to test the switch at different
I. I NTRODUCTION operational temperatures [4]–[6]. This can be done for example
Multilevel inverters are considered a viable solution for by adjusting the temperature of the base plate of the switch
high-power medium voltage applications and as a result several module either with a hot plate [5], heating the case [4], or by
multilevel inverter topologies have been adopted by the indus- using a cryogenic chamber [6].
try [1], [2]. Multilevel inverters have attractive features over DPT has been used to compare the variations with different
the two-level inverter with the ability to increase the inverter samples of the same component, to test different switch
nominal voltage, reach a higher apparent switching frequency, modules or housings, or different switch technologies and
and have an improved output power quality. semiconductors materials [4], [6]. The device under test (DUT)
Reliability of power electronic converters is determined by of a typical dedicated DPT is the bottom switch of a phase
testing at different stages of prototyping. A key test at an with an individual switch [6] or a half-bridge module [5], [7].
early stage is the double pulse test (DPT). DPT is a standard The switching characteristics of both upper and lower switch
test for determining the switching behavior of semiconductor can be tested for example in an H-bridge configuration [8].
switches. The primary outcomes of DPT are the reverse Switching characterization may require topology specific DPT
recovery peak current at the turn-on, collector-emitter over set-ups, as for current source inverter with reverse-blocking
voltage during turn-off, and the calculation of the switching switches [9].
losses of the turn-on and turn-off based on the collector current When an inverter or a converter is designed and built,
(iC ) and collector-emitter voltage (uCE ). the switching loops for the commutations are defined by
DPT can be implemented to serve different purposes. The the layout. Mutual coupling mechanisms will have an effect
first method is to have a dedicated testbed for testing different on the actual loop inductance [10]. Therefore, the switching
switches with the same module type. This is used especially characteristics of each switch should be tested for the inverter.
by component manufacturers. The layout is conventionally This approach has been studied with two-level inverters [11],

978-1-6654-8459-6/22/$31.00
Authorized ©2022 IEEE
licensed use limited to: ULAKBIM 511
UASL - CUKUROVA UNIVERSITESI. Downloaded on February 19,2024 at 21:18:57 UTC from IEEE Xplore. Restrictions apply.
sw 1 sw 1

D U T

D U T
sw 1 sw 1

C d 5 C d 5
C d 5 C d 5 H H

D U T
D U T
H H
sw 2 sw 2
sw 2 sw 2
n n n n
L L L L
d 6 d 6 d 6 d 6
sw 3 sw 3 sw 3 sw 3
C C C L C L
L L

sw 4 sw 4 sw 4 sw 4

(a) Device under test sw1 (a) Device under test sw2

sw 1 sw 1 sw 1 sw 1

C d 5 C d 5 C C d 5
H H
H d 5 H
sw 2 sw 2 sw 2 sw 2

n n n n
L L
d 6 d 6 L L
sw 3 sw 3 d 6 d 6

D U T
D U T
sw 3 sw 3
C C
L L
C L C L
D U T

D U T

sw 4 sw 4
sw 4 sw 4

(b) Device under test sw4 (b) Device under test sw3

Fig. 2. Short loop double pulse test configurations. The current paths are Fig. 3. Long loop double pulse test configurations. The current paths are
illustrated with red traces. The figures on the left illustrate the current path illustrated with red traces. The figures on the left illustrate the current path
when DUT is conducting and the figures on the right when DUT is not when DUT is conducting and the figures on the right when DUT is not
conducting. conducting.

T-type inverter [12], and active neutral point clamped inverter NPC using 4.5 kV rated insulated-gate bipolar transistors.
(ANPC) [10], [13]–[15]. II. NPC PHASE - LEG DOUBLE PULSE TEST PRINCIPLE
The measurement results from DPT may be used for im- The three-level NPC inverter is able to produce three line-
proving simulation models [16] or simulation of switching to-neutral voltage levels. The three output voltages of the
losses of different inverter topologies using DUT data [7]. phase-leg are produced with the three switching states shown
They can also be used for calculation of the effective switching in Table I. Even though the switching states do not have
loop stray inductances [10]. any redundancy, the current path of the zero output voltage
With different inverter topologies and with different layouts, state depends on the current polarity. These current loops
the commutation path stray inductances may vary significantly. are referred to as short and long loops. For example, when
For example, with a three-level neutral point clamped (NPC) transitioning from the state ul-n = +uDC /2 to ul-n = 0, with
inverter this characteristic was simulated in [17], and demon- positive output current the short loop through diode d5 and
strated with measurements for NPC and ANPC in [10], [18]. sw2 will take place. Alternatively, the same transition with
This paper focuses on testing of the individual switches negative output current will result in the long current loop
within a three-level NPC [19]. A single phase-leg of NPC is through d6 and sw3.
composed of four semiconductor switches and two diodes. The
single-phase presentation of the topology is shown in Fig. 1. TABLE I
NPC has an inherent characteristic in asymmetric loading of NPC SWITCHING STATES
the inner switches (sw2 and sw3) and the outer switches (sw1 ul-n sw1 sw2 sw3 sw4
and sw4) [20]. This asymmetry does not take into account the +uDC /2 1 1 0 0
potential asymmetry caused by the layout and coupling effects. 0 0 1 1 0
−uDC /2 0 0 1 1
This paper proposes a new test set-up for DPT of three-level
NPC. The proposed test configuration uses only half of the
nominal DC link voltage as the input, while being able to test DPT can be performed on each of the four switches of the
all of the phase-leg switches at nominal voltage. The proposed NPC phase-leg. The test can be implemented with either a full
method is verified with DPT of a medium voltage three-level DC link voltage connected to the DC bus, or as proposed in

512
Authorized licensed use limited to: ULAKBIM UASL - CUKUROVA UNIVERSITESI. Downloaded on February 19,2024 at 21:18:57 UTC from IEEE Xplore. Restrictions apply.
this paper by applying half of the DC link voltage to either the TABLE II
positive side capacitance CH or the negative side capacitance DPT GATE COMMANDS FOR EACH DUT
CL . DUT sw1 sw2 sw3 sw4
The proposed DPT requires modified connections to the sw1 1⇒0⇒1 1 0 0
phase-leg, as shown in Figs. 2 – 3. As only half of the DC link sw2 0 1⇒0⇒1 1 0
sw3 0 1 1⇒0⇒1 0
is used for the testing, the other DC link capacitance must sw4 0 0 1 1⇒0⇒1
be disconnected from the circuit. For example, when DUT is
sw1 or sw2, the negative side DC link capacitance CL must be
disconnected. As for the DPT results, disconnecting the other 4 0 0 V / 1 2 -p u ls e
1 0 0 0 V / re c tifie r
DC link capacitance will not have any effect on the resulting sw 1
1 0 0 0 V
current loop for the DUT. V a ria b le tra n s fo rm e r C H d 5
tra n s fo rm e r
The short loop commutations can be tested when DUT sw 2
is sw1 or sw4, as shown in Fig. 2. During these DPTs,
the load inductor is connected between the phase-leg output C d 6
L
sw 3 L
and the neutral point (n). The device under test runs the
pulse sequence of DPT, while the other switches use the sw 4
corresponding switching states from Table I, and the actual
switching states are given in Table II. For example, when DUT
Fig. 4. Double pulse test setup consisting of a variable transformer connecting
is sw1, the charge pulse of DPT starts when sw1 and sw2 are to the grid, 400V/1000V/1000V transformer, 12-pulse rectifier, NPC phase-
set to conduct. The charge pulse results in a positive output leg, and output inductor L. The connections of the rectifier with the DC link
current to the phase-leg, and corresponds to the switching state capacitors, and the output inductor connections are varied depending on the
device under test.
of ul-n = +uDC /2. The switch sw2 is left to conduct for the
whole duration of DPT. At the end of the charge pulse, DUT
is set to non-conductive state and the current path commutates
from sw1 to d5, through the short loop. The duration of the
rest period (time between the two pulses) and the second pulse
are set at the minimum pulse requirement of the switch, and
as a result sw3 should not be set to conduct. Once DPT is
finished, all of the switches are set to non-conductive states.
The double pulse tests of sw2 and sw3 form long loops,
as illustrated in Fig. 3. Now the load inductor is connected
between the inverter output and one of the DC rails (to DC−
when DUT is sw2, and to DC+ when DUT is sw3). For both
of these tests the starting output voltage state is the zero output
voltage state from Table I. The test for sw3 is as follows.
The pulses of DPT are formed with the long loop current
path, going through sw3 and d6. This pulse causes a negative
current to flow through the load. When the charge pulse ends
as sw3 is turned off, but again sw1 is not set to conduct due to Fig. 5. Double pulse test setup. 1. NPC phase-leg 2. DC link with laminated
the minimum pulse requirement. The current path during the bus bars 3. diode rectifier 4. load inductor L. The inductor L is in a separate
rest period flows through the freewheeling diodes of sw1 and cabinet, because a full back-to-back NPC inverter is to be completed in the
cabinet seen on the left.
sw2, and the switching sw1 to conduct during the rest period
would not contribute to the test. Therefore, the commutations
of the described DPT are identical to the states ul-n = 0 to allows the testing of the switching characteristics of all of the
ul-n = +uDC /2 and back to ul-n = 0 in case of a negative four switches with the actual commutation loops interfacing
load current. Again, when DPT sequence has finished, the gate the DC link capacitors.
commands of all of the switches are set to non-conductive The inverter was designed for 3.3 kV nominal voltage,
values. which means that the DC link voltage with a diode rectifier
will be uDC = 4.67 kV and with an active front-end with
III. E XPERIMENTAL VERIFICATION
a 10 % boost uDC = 5.13 kV. The designed PEBB structure
A. Test setup description allows both rectifier versions. In an ideal case, each switch of
The proposed DPT method was experimentally tested with the phase-leg should withstand half of the DC link voltage,
a three-level NPC phase-leg. The layout of the inverter was but the voltage fluctuations of the DC link capacitors require
implemented with a single NPC phase-leg being connected to an increased tolerance for the voltage over the switch. The
the DC link with laminated bus bars. This kind of a structure capacitor voltage fluctuations are caused by fluctuations on the
for the phase-leg power electronic building block (PEBB) bus voltage, as well as the neutral point voltage fluctuation.

513
Authorized licensed use limited to: ULAKBIM UASL - CUKUROVA UNIVERSITESI. Downloaded on February 19,2024 at 21:18:57 UTC from IEEE Xplore. Restrictions apply.
TABLE III
800 M EASURED PEAK COLLECTOR - EMITTER VOLTAGES DURING TURN - OFF
600 AND PEAK COLLECTOR CURRENTS AT TURN - ON .
i L (A)

400
200 DUT uCE,peak (V) iC,peak (A) iRR (A)
0 sw1 3327 1159 575
sw2 3280 1348 764
3000 sw3 3194 1187 603
sw4 3257 1075 491
u L (V)

2000
1000
0
0 10 20 30 40 50 60 70 80
where imax is the maximum current at the end of DPT. The
Time (μs)
test pulse pattern has a limitation of minimum pulse length
set by the switches. The minimum pulse duration is used for
Fig. 6. Measured DPT inductor current (iL ) (top) and the load voltage (uL ) the rest period (time between the two test pulses) and the
(bottom). duration of the second pulse t2 . The minimum pulse for the
used switches is 10 μs. Therefore, the first pulse has a duration
of t1 = ttot − 10 μs. The time between t1 and t2 is the
For this voltage rating 4.5 kV rated IGBTs were selected, as
minimum pulse length (10 μs), which is not included in ttot .
semiconductor switch manufacturers conventionally set their
With the maximum current of imax = 800 A of the chopper
testing voltage at uCE = 2.8 kV.
module, the pulse lengths are t1 = 38 μs and t2 = 10 μs. For
Based on the required voltage rating, the following semi-
the tests presented in this paper, the selected pulse times were
conductor modules were selected for the phase-leg PEBB:
t1 = 36 μs and t2 = 10 μs.
• ABB 800A chopper module, 5SNE 0800G450300
• ABB 1200A single switch module, 5SNA 1200G450350 C. Measurement instrumentation
The chopper modules are used to combine a switch that is For the double pulse test, the following measurements were
connected to a DC rail and a neutral point connected diode, used:
as follows: sw1 and d5 in one chopper module, and sw4 and d6 • Rohde & Schwarz RTH1004 oscilloscope
in the second chopper module. The switches sw2 and sw3 are • Tektronix P5210 differential voltage probes, 50 MHz
implemented with the single switch modules. The power rating bandwidth
of the phase-leg is defined by the chopper module current • CWT Rogowski coil, CWTUM/3/B, 6 kA peak current,
rating. 30 MHz bandwidth
The double pulse test setup consists of a variable trans-
For each DPT, the measurements were the voltage over
former, 400V/1000V/1000V step-up transformer, twelve-pulse
DUT (uCE ), the current of the switch (iC ), and the load
rectifier, DC link, NPC phase-leg, and an output inductor, as
voltage (uL ). The inductor current (iL ) was measured with
shown in Fig. 4. The 400V/1000V/1000V transformer has two
some double pulses, but the inductor current waveform was
secondary windings with a 30◦ phase-shift, and the secondary
assumed constant as the pulse sequence was not modified.
windings are used to form a 12-pulse rectifier. The output
voltage of the 12-pulse rectifier is 2.83 kV with the 400 V D. Measurement results
input. The variable transformer can be used to adjust the DPT The first measurements shown in Fig. 6 illustrate the induc-
voltage for the full voltage range. The DC link capacitances tor current (iL ) and the load voltage (uL ) measured between
are CH = CL = 680 μF. A picture of the double pulse test the NPC phase-leg output and the neutral point (n), as depicted
setup is shown in Fig. 5. in Fig. 2(a). The measured switching currents and switching
B. Double pulse test dimensioning instants from Fig. 6 are
The double pulse test switching pattern is dimensioned to • iP1,off = 619 A (t = 46 μs)

have two pulses: the first pulse is referred to as the charge • iP2,on = 584 A (t = 56 μs)

pulse with the duration t1 and the second test pulse with • iP2,off = 748 A (t = 66 μs)

the duration of t2 . The dimensioned maximum test DC link where iP1 refers to the charge pulse current and iP2 test pulse
voltage uDC /2 was 2.8 kV, and for the test pulse duration currents. Based on the measurements, the inductor current
calculation the voltage is assumed to be constant. In the actual dropped 35 A during the rest period between the pulses.
test, the DC link voltage is expected to drop, depending on the The DUT measurement results for all switches sw1–sw4
power losses during DPT. The test load inductor was selected are shown in Figs. 7 – 10, while using the proposed method as
to be L =170 μH. The duration of the pulses are calculated shown in Figs. 2 – 3. The key results of these measurements are
with the following procedure. First, the overall charge period shown in Table III with peak collector-emitter voltages during
ttot can be calculated with turn-off uCE,peak at the end of the test pulse, peak collector
2imax L currents at turn-on of the test pulse iC,peak , and the reverse
ttot = t1 + t2 = , (1) recovery current during the test iRR .
uDC

514
Authorized licensed use limited to: ULAKBIM UASL - CUKUROVA UNIVERSITESI. Downloaded on February 19,2024 at 21:18:57 UTC from IEEE Xplore. Restrictions apply.
1500 1500
1000 1000
i C (A)

i C (A)
500 500
0 0
3000 3000
u CE (V)

u CE (V)
2000 2000
1000 1000
0 0
0 10 20 30 40 50 60 70 80 0 10 20 30 40 50 60 70 80
Time (μs) Time (μs)

Fig. 7. Measured collector current iC and collector-emitter voltage uCE , Fig. 9. Measured collector current iC and collector-emitter voltage uCE ,
when DUT is sw1. when DUT is sw3.

1500 1500
1000 1000
i C (A)

i C (A)
500 500
0 0
3000 3000
u CE (V)

u CE (V)

2000 2000
1000 1000
0 0
0 10 20 30 40 50 60 70 80 0 10 20 30 40 50 60 70 80
Time (μs) Time (μs)

Fig. 8. Measured collector current iC and collector-emitter voltage uCE , Fig. 10. Measured collector current iC and collector-emitter voltage uCE ,
when DUT is sw2. when DUT is sw4.

The test results are evident, that the phase-leg commutation voltage was proposed and it was verified with experimental
loops have mutual coupling mechanisms, which effect the loop results. The proposed method demonstrates how a PEBB
inductance, regardless of the symmetrical physical dimensions switching behavior can be tested comprehensively at nominal
of the layout. Even though the same modules were used for voltage of each semiconductor switch, even though a scaled
the outer switches and the neutral point diodes (sw1 with d5 input voltage is used. Further, the acquired test results show the
and sw4 with d6), and for the inner switches (sw2 and sw3), importance of switch and commutation loop specific tests in
the resulting uCE,peak and iC,peak were not the same in any order to determine the peak values of collector-emitter voltage
of the measurements. and collector current during switching operations, as they may
The proposed method was found feasible and the required vary among the phase-leg switches.
voltage rating of 2.8 kV per NPC phase-leg semiconductors
was achieved conveniently with the step-up transformer 1 kV R EFERENCES
secondary windings. With the proposed method it is possible [1] L. Franquelo, J. Rodriguez, J. Leon, S. Kouro, R. Portillo, and M. Prats,
to test all of the commutation loops and to provide the full “The age of multilevel converters arrives,” IEEE Ind. Electron. Mag., vol.
2, Issue 2, pp. 28–39, June 2008.
voltage stress to the switches even when only half of the DC [2] S. Kouro, M. Malinowski, K. Gopakumar, J. Pou, L. Franquelo, B. Wu,
link voltage is available. J. Rodriguez, M. Perez, and J. Leon, “Recent advances and industrial ap-
plications of multilevel converters,” IEEE Trans. Ind. Electron., vol. 57,
IV. C ONCLUSIONS no. 8, pp. 2553–2580, Aug. 2010.
[3] M. H. Ahmed, M. Wang, M. A. S. Hassan, and I. Ullah, “Power loss
Testing of power electronic converters is crucial for model and efficiency analysis of three-phase inverter based on SiC
determining safe operation. As for the semiconductor switches, MOSFETs for PV applications,” IEEE Access, vol. 7, pp. 75 768–75 781,
double pulse test is used for measuring transient peak values 2019.
[4] R. Alvarez, F. Filsecker, M. Buschendorf, and S. Bernet, “Characteri-
during switching commutations within the converter. The zation of 4.5 kV/2.4 kA press pack IGBT including comparison with
layout of the converter affects the switching behaviour, and IGCT,” in 2013 IEEE Energy Conversion Congress and Exposition,
as a result it is important to test each commutation loop of the 2013, pp. 260–267.
[5] A. Marzoughi, J. Wang, R. Burgos, and D. Boroyevich, “Characteriza-
converter. In this paper a method for testing each commutation tion and evaluation of the state-of-the-art 3.3-kV 400-A SiC MOSFETs,”
loop of a three-level NPC phase-leg PEBB with half input IEEE Trans. Ind. Electron., vol. 64, no. 10, pp. 8247–8257, 2017.

515
Authorized licensed use limited to: ULAKBIM UASL - CUKUROVA UNIVERSITESI. Downloaded on February 19,2024 at 21:18:57 UTC from IEEE Xplore. Restrictions apply.
[6] J. Qi, X. Yang, X. Li, K. Tian, Z. Mao, S. Yang, and W. Song, “Tem- wind turbines,” IEEE Trans. Ind. Appl., vol. 47, no. 6, pp. 2505–2515,
perature dependence of dynamic performance characterization of 1.2- 2011.
kV SiC power mosfets compared with Si IGBTs for wide temperature [14] Y. Jiao, S. Lu, and F. C. Lee, “Switching performance optimization of
applications,” IEEE Trans. Power Electron., vol. 34, no. 9, pp. 9105– a high power high frequency three-level active neutral point clamped
9117, 2019. phase leg,” IEEE Trans. Power Electron., vol. 29, no. 7, pp. 3255–3266,
[7] A. Kumar, S. Bhattacharya, J. Baliga, and V. Veliadis, “Performance 2014.
comparison and demonstration of 3-L voltage source inverters using [15] M. Chen, D. Pan, H. Wang, X. Wang, F. Blaabjerg, and W. Wang,
3.3 kV SiC MOSFETs for 2.3 kV high speed induction motor drive “Switching characterization of SiC MOSFETs in three-level active
applications,” in 2021 IEEE Applied Power Electronics Conference and neutral-point-clamped inverter application,” in 2019 10th International
Exposition (APEC), 2021, pp. 1103–1110. Conference on Power Electronics and ECCE Asia (ICPE 2019 - ECCE
[8] S. S. Ahmad and G. Narayanan, “Double pulse test based switching Asia), 2019, pp. 1793–1799.
characterization of SiC MOSFET,” in 2017 National Power Electronics [16] T. Musikka, L. Popova, R. Juntunen, M. Lohtander, P. Silventoinen,
Conference (NPEC), 2017, pp. 319–324. O. Pyrhönen, J. Pyrhönen, and K. Maula, “Improvement of IGBT
[9] X. Han, L. Zheng, R. P. Kandula, K. Kandasamy, D. Divan GAE, model characterization with experimental tests,” in 2013 15th European
and M. Saeedifard, “Characterization of 3.3 kV reverse-blocking SiC Conference on Power Electronics and Applications (EPE), 2013, pp.
modules for use in current-source zero-voltage-switching converters,” 1–10.
IEEE Trans. Power Electron., pp. 1–1, 2020. [17] L. Popova, T. Musikka, R. Juntunen, M. Lohtander, P. Silventoinen,
[10] Mayor, M. Rizo, A. Rodrı́guez Monter, and E. J. Bueno, “Commutation O. Pyrhönen, and J. Pyrhönen, “Modelling of low inductive busbars
behavior analysis of a dual 3L ANPC-VSC phase-leg PEBB using for medium voltage three-level NPC inverter,” in 2012 IEEE Power
4.5-kV and 1.5-kA HV-IGBT modules,” IEEE Trans. Power Electron., Electronics and Machines in Wind Applications, 2012, pp. 1–7.
vol. 34, no. 2, pp. 1125–1141, 2019. [18] A. Mattsson, J. Korhonen, P. Nuutinen, P. Peltoniemi, P. Silventoinen,
[11] Z. Zhang, F. Wang, L. M. Tolbert, B. J. Blalock, and D. J. Costinett, O. Pyrhönen, and R. Pöllänen, “Design considerations for the interme-
“Evaluation of switching performance of SiC devices in PWM inverter- diate circuit of a multimegawatt medium-voltage neutral-point-clamped
fed induction motor drives,” IEEE Trans. Power Electron., vol. 30, inverter,” in International Power Electronics Conference (IPEC-Himeji
no. 10, pp. 5701–5711, 2015. 2022- ECCE Asia), 2022.
[12] Y. Shi, R. Xie, L. Wang, Y. Shi, and H. Li, “Switching characterization [19] A. Nabae, I. Takahashi, and H. Akagi, “A new neutral-point-clamped
and short-circuit protection of 1200 V SiC MOSFET T-type module in PWM inverter,” IEEE Trans. Ind. Appl., vol. IA-17, pp. 518–523, Sept.
PV inverter application,” IEEE Trans. Ind. Electron., vol. 64, no. 11, pp. 1981.
9135–9143, 2017. [20] T. Brückner, S. Bernet, and H. Güldner, “The active NPC converter and
[13] O. S. Senturk, L. Helle, S. Munk-Nielsen, P. Rodriguez, and R. Teodor- its loss-balancing control,” IEEE Trans. Ind. Electron., vol. 52, no. 3,
escu, “Converter structure-based power loss and static thermal modeling pp. 855–868, June 2005.
of the press-pack IGBT three-level ANPC VSC applied to multi-MW

516
Authorized licensed use limited to: ULAKBIM UASL - CUKUROVA UNIVERSITESI. Downloaded on February 19,2024 at 21:18:57 UTC from IEEE Xplore. Restrictions apply.

You might also like