0 INTERFACES BETWEEN 33kV SWITCHGEAR AND EXISTING PROTECTION PANEL OF ICT


Sl. Signal From Equipment To Equipment
No. Description Tag No. Description Comp. Terminal Tag Description Terminal Purpose
No. No. No. No.
4 33kV 00BBA54 33kV 06A XI-29 ICT-1 TB2-49 NO contact
Incomer Switchgear XI-30 Protection TB2-50 for Tripping
Panel interlock to
breaker (4RTB)(BI-2, ICT
failure D4-D3) (SHT:27 OF
OF 64 KY8G SCO1)
RELAY
FOR INITIATION OF TRIP DUE TO 33KV BKR-FAIL, THERE SHALL BE REQUIREMENMT OF 02 Nos NO-CONTACTS OF
33KV-SWGR AS FOR 400KV & 220KV CB (OR 86A & 86B).
IF 02 Nos SPARE NO-CONTACTS ARE NOT AVL.; THEN FOLLOWING WIRING SHALL ALSO BE INCORPORATED BY
EPC(FGD) AT ICT-PROTN PANEL FOR TRIP-INITIATION TO 86A & 86B:-
4A ICT-1 TB3-44 ICT-1 TB4-11 FOR 86A
Protection TB3-45 Protection TB4-12 OPERATION
Panel Panel DUE TO 33KV
(4RTB) (4RTB) CBF

(SHT:15, 27 OF
KY8G SCO1)

4B ICT-1 TB3-48 ICT-1 TB4-21 FOR 86B


Protection TB3-49 Protection TB4-22 OPERATION
Panel Panel DUE TO 33KV
(4RTB) (4RTB) CBF

(SHT:17, 27 OF
KY8G SCO1)
NO-CONTACT OF
33KV BKR-FAIL

TO 86A (FOR 33KV


BKR-FAIL INTERTRIP)

TO 86B (FOR 33KV


BKR-FAIL INTERTRIP)
64(33KV BKR-FAIL)
64(33KV BKR-FAIL)
Sl. Signal From Equipment To Equipment
No. Description Tag No. Description Comp. Terminal Tag Description Terminal Purpose
No. No. No. No.
5 Earth truck 00BBA54 33kV 06A XI-31 ICT-1 TBIO-4 NC contact
not in Switchgear XI-32 Protection TBIO-19 for Closing
service or Panel interlock to
Isolator (4RTA) (BI-15 OF ICT
open BCU-HV)
(SHT:33 OF
KY8G SCO1)

FOR CLOSE INTERLOCK IN 400KV SIDE CB & 220KV SIDE CB DUE TO EARTH-TRUCK IN SERVICE(33KV SWGR),
THERE SHALL BE REQUIREMENT OF 02 Nos SPARE-NC-CONTACTS OF EARTH-TRUCK (SWGR).
IF 02 Nos SPARE NC-CONTACTS ARE NOT AVL., THEN FOLLOWING WIRINGS ALONGWITH BI-BO MAPPING IN BCU-
HV SHALL BE INCORPORATED FOR NECESSARY CLOSE-I/L:-

MAPPING REQD:- UPON BI-15 HIGH (i.e. WHEN EARTH-TRUCK IN SERIVICE : NC CONTACT), THE BO7 OF BCU-HV
(DOUE,13-14) AND BO8 OF BCU-HV (DOUF, 15-16) WILL ALSO BE HIGH AND THEY WIIL BE USED
IN CLOSE0I/L PATH OF 400KV-CB & 220KV-CB RESPECTIVLEY.

SIMPLIFIED SCHEME:-

400KV C/PNL (4RTA)


BCU-HV IN 4RTA PNL
TBOE-13 TBOE-2
BO-7 (DOUE) OPEN THIS
BI-15 (DIUO) SHORT-WIRE
TBIO-4 TBIO-19 (400KV CB I/L)
TBOE-14 TB3-3
XI-31 XI-32
DOUD OF BCUMV
(CLOSE COMMAND
33KV FROM BCU)
BO-8 (DOUF) TBOF-15 (K29L)
SWGR
(220KV CB I/L) (K19L)

TBOF-16 TB4-18

220KV CONTROL PNL

5A ICT-1 TBOE-2 ICT-1 TBOE-13 FOR CLOSE


Protection TB3-3 Protection TBOE-14 I/L OF 400KV-
Panel Panel CB
(4RTA) (4RTA) (OPEN (SHT:21, 35 OF
EXSTG KY8G SCO1)
WIRE
BETWEE
N TBOE-2
& TB3-3)
5B ICT-1 TBOF-15 220KV ICT- TB4-18 FOR CLOSE
Protection TBOF- 16 1 & I/L OF 220KV-
Panel CONTROL (DO1 OF CB
(4RTA) PNL DOUD OF (SHT:36 OF
(2RZ1AM) BCUMV KY8G SCO1
WIRE & SHT:31 OF
K29L) KZG7 SC01))
EARTH-TRUCK IN (33KV SWGR)

EARTH-TRUCK IN
(33KV SWGR)
NC CONTACT
TO BE CONFIGURED WITH BI-15
(DIUO) AS TO BE USED FOR CLOSE-I/L
OF 400KV CB
TO BE CONFIGURED WITH BI-15
(DIUO) AS TO BE USED FOR CLOSE-I/L
OF 220KV CB
TB1/26

TBOE-13 TBOE-14
TB1/21
BO-7(DOUE)
{EARTH-TRUCK NOT
IN OF 33KV SWGR)
This document is confidential property of GE T&D India Limited and only for information of the intended recipient and shall not be used, copied or published without written authorization.

07

2RZAM

BASE FILE:
FOR GE REF:
TB4 +VE

.
-VE K701
+VE
1
-VE
K702
2
LKT11 TB4 X1A-7
K63 K701A
TC-1 COMM.DC (T1+)
2 1
2RZBM 3

SALES ORDER: 3269062855


86A X50-30
K63A
6 8
K63B 4 X50-25 PROTN TRIP/
K63

SCHEME TYPE: TRANSFORMER PROTECTION


19 10 12 19 POST CLOSE SUPVN
5 X50-20
K63C
14 16
6

ENGG.REF.NO.: KZG7
86B
6 8

20 6 8 20
17 19

96A
6 8 TB4 X50-30
K431
25 6 8 25 195RM 7
17 X50-32
19
96B K432

Dated 23.06.2022
21
B 22
6 8 8
X50-25
6 8 K433
29 29
195YM 9
17 19
X50-27
K434
21
B 22 10
X50-20
PRECLOSE SUPVN.

K435
195BM 11

CUSTOMER: DAMODAR VALLEY CORPORATION


PROJECT: ESTABLISHMENT OF 220KV INFRA AT MTPS & RTPS
X50-22
TBTC1 K436
TBTC1 21
B 22
2 12

P.O.NO.: DVC/TENDERING/HQ/SPE/CMM/WORK & SER/0040/542


K63 FUTURE
TRIP 3
1
4

g
TBTC1
TBTC1 ** FROM 86G
K63 7
TRIP
6 APPLICABLE ONLY FOR ICT-2 8 PB01
9 K47
195RM 1P3 1P4
13
CTD TRIP
REF DRG. GD06L001243 SHT:7,21,22

K63A
13
A 14 K49
195YM
14
CIRCUIT BREAKER 20X-52 (TC-1)

K63B
13
A
195BM 14

GE T&D India Ltd.


K63C
13 A 14

Grid Automation-Pallavaram India


TB4 X1A-8
K721
DC +VE
A/T A/C 15
T C

PANEL TYPES: 34 1P3 1P4


BCUMV(DOUF) L52CS TB4 X50-14
K723
3 4 REMOTE TRIPPING-1
41 16
FOR FUTURE PURPOSE
2RZBM
SCHEMATIC DRAWING

96B 96A TB4


2RZAM 2RZBM

K9L TB3 TB3 X1A-6


K7B K7A K7L
DC +VE
294 2 29 4 2 25 17
10 9
TITLE: 400/220KV ICT-220KV SIDE

OPEN THIS WIRE FROM TB4-18


2RZBR BCUMV(DOUF) TB4 X50-7
86A K11L 86B K19L K19L K29L
1 2
REMOTE CLOSE
1 3 19 32 30 20
41 18
TBOF-16
BO-8(DOUF) FOR EARTH-
A/T A/C TRUCK NOT IN 33KV SWGR
C TBOF-15
CIRCUIT BREAKER CONTROL CKT. (TC-1) -MV
FILE: DZG70131

195RM 34
A K702 S201
27
C 28 TC-1 FAIL
B 195RM S537 40
195YM
C
1 3
A K702 195RM
C 28 195RM .
27 195YM S537 C
APPROVED BY: SSS
CHECKED BY: GSS
PREPARED BY: SDK

B C 5 7 2 4
1 3
195BM
195YM
195YM .
A K702
195BM S537
C 5 C 7 2 4
27
C 28 1 3
B 195BM
LOC
TYPE

SCALE:

195BM .
EQPT

5 C 7 2 4
--
REVISION: Z
DATE: 17.10.2023
2RZAM
195 R,Y,B
MVAXM31

DRG. NO.: CPD KZG7 SC01 SHT 31 OF 50