TO INSTALL A ROOF MOUNTED SOLAR PHOTOVOLTAIC SYSTEM AT THE OWNER RESIDENCE GOVERNING CODES SYSTEM RATING
LOCATED AT 4312 BEAL STREET FORT WORTH, TX 76105 2018 INTERNATIONAL RESIDENTIAL CODE 7.92 KWDC
THE POWER GENERATED BY THE PV SYSTEM WILL BE INTERCONNECTED WITH THE UTILITY 2015 INTERNATIONAL FIRE CODE
GRID THROUGH THE EXISTING ELECTRICAL SERVICE EQUIPMENT. 2017 NATIONAL ELECTRICAL CODE 6.49 KWAC
THE PV SYSTEM DOES NOT INCLUDE STORAGE BATTERIES
4K & ZAVALA
SHEET INDEX
EQUIPMENT SUMMARY PV-0
SOLAR LLC
COVER PAGE
22 SEG-360-BMB-HV MODULES PV-1 SITE PLAN
PV-2 ROOF PLAN & MODULES
22 ENPHASE IQ7 PLUS-72-2-US (240V) MICROINVERTERS
PV-2A STRING LAYOUT & BOM
PV-3 ATTACHMENT DETAIL
GENERAL NOTES: WIRING AND CONDUIT NOTES:
PV-3A ATTACHMENT DETAIL
· THESE CONSTRUCTION DOCUMENTS HAVE BEEN BASED ON FIELD INSPECTIONS AND · ALL CONDUIT SIZES AND TYPES, SHALL BE LISTED FOR ITS
PV-4 ELECTRICAL LINE DIAGRAM & CALCS. SYSTEM INFO.
OTHER INFORMATION AVAILABLE AT THE TIME. ACTUAL FIELD CONDITIONS MAY REQUIRE PURPOSE AND APPROVED FOR THE SITE APPLICATIONS
PV-4A (22)SEG-360-BMB-HV
MODIFICATIONS IN CONSTRUCTION DETAILS. · ALL PV CABLES AND HOMERUN WIRES BE #10AWG *USE-2, PV SPECIFICATIONS & CALCULATION
PV-5 (22) ENPHASE IQ7 PLUS-72-2-US (240V)
· ARCHITECT HAS NOT BEEN RETAINED TO SUPERVISE ANY CONSTRUCTION OR WIRE, OR PROPRIETARY SOLAR CABLING SPECIFIED BY MFR, SIGNAGE
DC SYSTEM SIZE: 7.92 KWDC
INSTALLATION OF ANY EQUIPMENT AT SITE. OR EQUIVALENT; ROUTED TO SOURCE CIRCUIT COMBINER PV-6+ EQUIPMENT SPECIFICATIONS
· CONTRACTOR SHALL FURNISH ALL LABOR, MATERIAL, EQUIPMENT, TOOLS, OBTAINS ALL BOXES AS REQUIRED AC SYSTEM SIZE: 6.49 KWAC
PERMITS, LICENSES AND PAY ALL REQUIRED FEES AND COMPLETE INSTALLATION. · ALL CONDUCTORS AND OCPD SIZES AND TYPES SPECIFIED REVISIONS
· CONTRACTOR HAS THE FULL RESPONSIBILITY TO CHECK AND VERIFY ALL DIMENSIONS ACCORDING TO [NEC 690.8 (A)(1) & (B)(1)], [NEC 240] [NEC PROJECT SITE
DESCRIPTION DATE REV
AND EXISTING CONDITIONS. ANY DISCREPANCIES SHALL BE REPORTED TO THE ENGINEER 690.7] FOR MULTIPLE CONDUCTORS REVISION 11/30/2021 A
BEFORE PROCEEDING WITH THE WORK. ANY WORK STARTED BEFORE CONSULTATION · ALL PV DC CONDUCTORS IN CONDUIT EXPOSED TO SUNLIGHT
AND ACCEPTANCE BY THE ENGINEER SHALL BE THE SOLE RESPONSIBILITY OF THE SHALL BE DERATED ACCORDING TO [NEC TABLE 310.15
CONTRACTOR AND SHALL BE SUBJECT TO CORRECTION BY THEM WITHOUT ADDITIONAL (B)(2)(C)] BLACK ONLY**
COMPENSATION. · EXPOSED ROOF PV DC CONDUCTORS SHALL BE USE-2, 90°C Signature with Seal
· DAMAGE CAUSED TO THE EXISTING STRUCTURE, PIPES, DUCTS, WINDOWS, WALL, RATED, WET AND UV RESISTANT, AND UL LISTED RATED FOR
FLOORS, ETC. SHALL BE REPAIRED TO THE ORIGINAL CONDITION OR REPLACED BY THE 600V, UV RATED SPIRAL WRAP SHALL BE USED TO PROTECT
CONTRACTOR AT NO ADDITIONAL COST. WIRE FROM SHARP EDGES
· THE CONTRACTOR SHALL BE HELD RESPONSIBLE FOR THE PROPER INSTALLATION AND · PHASE AND NEUTRAL CONDUCTORS SHALL BE DUAL RATED
COMPLETION OF THE WORK WITH APPROVED MATERIALS. THHN/THWN-2 INSULATED, 90°C RATED, WET AND UV
· NO CHANGES ARE TO BE MADE WITHOUT THE CONSULTATION AND APPROVAL OF THE RESISTANT, RATED FOR 600V PER NEC 2008 OR 1000V PER
ARCHITECT. NEC 2011 DATE: 11/30/2021
· CONTRACTOR SHALL OBTAIN BULDING PERMIT. NO WORK TO START UNLESS BUILDING · 4-WIRE DELTA CONNECTED SYSTEMS HAVE THE PHASE WITH PROJECT NAME & ADDRESS
PERMIT IS PROPERLY DISPLAYED. THE HIGHER VOLTAGE TO GROUND MARKED ORANGE OR
· ALL WORKMANSHIP AND MATERIALS SHALL BE OF FIRST QUALITY AND IN COMPLIANCE IDENTIFIED BY OTHER EFFECTIVE MEANS
WITH THE REQUIREMENTS OF THE TX BUILDING CODE, THE DEPARTMENT OF
Email: andressolar1960@gmail.com
· ALL SOURCE CIRCUITS SHALL HAVE INDIVIDUAL SOURCE
ENVIRONMENTAL PROTECTION AND ALL PERTINENT AGENCIES. CIRCUIT PROTECTION
· IT IS ESSENTIAL THAT ALL WORK PROCEED WITH THE MAXIMUM COOPERATION OF ALL
RESIDENCE
PV-0 SCALE: NTS
· ALL EXPOSED PLUMBING, HVAC, ELECTRICAL DUCTWORK, PIPING AND CONDUITS ARE TO RED), DC NEGATIVE - GREY (OR MARKED GREY)
BE PAINTED BY GENERAL CONTRACTOR. · POSITIVE GROUNDED SYSTEMS DC CONDUCTORS COLOR
· THE CONTRACTOR SHALL PERFORM THE WORK IN STRICT CONFORMANCE WITH THE CODED: DC POSITIVE - GREY (OR MARKED GREY), DC
LOCAL LAWS, REGULATIONS AND THE NATIONAL ELECTRIC CODE. NEGATIVE - BLACK (OR MARKED BLACK) PROJECT SITE
· THE CONTRACTOR SHALL OBTAIN ALL PERMITS, APPROVALS, AFFIDAVITS, · AC CONDUCTORS >4AWG COLOR CODED OR MARKED: PHASE
CERTIFICATIONS, ETC. AND PAY ALL FEES AS REQUIRED BY THE LOCAL AUTHORITIES. A OR L1- BLACK, PHASE B OR L2- RED, PHASE C OR L3- BLUE,
· CONTRACTORS SHALL OBTAIN FIRE CERTIF. UPON COMPLETION OF WORK. NEUTRAL- WHITE/GRAY
ELECTRICAL NOTES:
· THE EQUIPMENT AND ALL ASSOCIATED WIRING AND INTERCONNECTION SHALL BE INSTALLED ONLY BY QUALIFIED PEOPLE. A QUALIFIED PERSON IS
ONE WHO HAS SKILLS AND KNOWLEDGE RELATED TO THE CONSTRUCTION AND OPERATION OF THE ELECTRICAL EQUIPMENT AND INSTALLATIONS
AND HAS RECEIVED SAFETY TRAINING TO RECOGNIZE AND AVOID THE HAZARDS INVOLVED. (NEC 690.4(E) AND 705.6)
· LOCAL UTILITY PROVIDER SHALL BE NOTIFIED PRIOR TO USE AND ACTIVATION OF ANY SOLAR PHOTOVOLTAIC INSTALLATION. FOR A LINE SIDE TAP
CONNECTION, UTILITY NEEDS TO BE NOTIFIED WELL IN ADVANCE TO COORDINATE BUILDING ELECTRICAL SHUT OFF.
· NEW CONDUIT ROUTING SHOWN IS ESSENTIALLY SCHEMATIC. SUBCONTRACTOR SHALL LAY OUT RUNS TO SUIT FIELD CONDITIONS AND THE
COORDINATION REQUIREMENTS OF OTHER TRADES. SHEET NAME
· ARRAY WIRING SHOULD NOT BE READILY ACCESSIBLE EXCEPT TO QUALIFIED PERSONNEL. COVER PAGE
· ALL EXTERIOR CONDUIT, FITTINGS, AND BOXES SHALL BE WATERTIGHT AND APPROVED FOR USE IN WET LOCATIONS. (NEC 314.15A).
· WIRING METHODS FOR PV SYSTEM CONDUCTORS AREN'T PERMITTED WITHIN 10 IN. OF THE ROOF DECKING OR SHEATHING EXCEPT WHERE LOCATED
SHEET SIZE
DIRECTLY BELOW THE ROOF SURFACE THAT'S COVERED BY PV MODULES AND ASSOCIATED EQUIPMENT WIRING
· BACK-FED BREAKER MUST BE AT THE OPPOSITE END OF BUS BAR FROM THE MAIN BREAKER OR MAIN LUG SUPPLYING CURRENT FROM THE UTILITIES.
· ALL CONDUCTORS AND WIRE TIES EXPOSED TO SUNLIGHT ARE LISTED AS UV RESISTANT. ANSI B
· CONTRACTOR SHALL FOLLOW ALL ELECTRICAL EQUIPMENT LABELING REQUIREMENTS IN NEC 690 AND IFC 2015 11" X 17"
· PV SOURCE, OUTPUT AND INVERTER CIRCUITS SHALL BE IDENTIFIED AT ALL POINTS OF TERMINATION, CONNECTION, AND SPLICES. THE MEANS OF ID
CAN BE SEPARATE COLOR CODING, MARKING TAPE, TAGGING ETC. (NEC 690.4).
1
PV-0 VICINITY MAP SCALE: NTS
SHEET NUMBER
· MEASURE THE LINE-TO-LINE AND LINE-TO-NEUTRAL VOLTAGE OF ALL SERVICE ENTRANCE CONDUCTORS PROIR TO INSTALLING ANY SOLAR
EQUIPMENT. THE VOLTAGES FOR THE 240VAC RATED. PV-0
SITE NOTES
· A LADDER SHALL BE IN PLACE FOR INSPECTION IN COMPLIANCE WITH OSHA REGULATIONS.
· THE PV MODULES ARE CONSIDERED NON-COMBUSTIBLE AND THIS SYSTEM IS AN UTILITY INTERACTIVE SYSTEM WITH NO STORAGE BATTERIES.
· THE SOLAR PV INSTALLATION SHALL NOT OBSTRUCT ANY PLUMBING, MECHANICAL, OR BUILDING ROOF VENTS.
· PROPER ACCESS AND WORKING CLEARANCE AROUND EXISTING AND PROPOSED ELECTRICAL EQUIPMENT WILL BE PROVIDED AS PER SECTION [NEC 110.26]
4K & ZAVALA
BEAL STREET SOLAR LLC
PROPERTY LINE
PROPERTY LINE
SYSTEM INFO.
29'-4"
(22)SEG-360-BMB-HV
(22) ENPHASE IQ7 PLUS-72-2-US (240V)
DC SYSTEM SIZE: 7.92 KWDC
REVISIONS
ROOF #2
120'-7"
(16) SEG-360-BMB-HV MODULES
Email: andressolar1960@gmail.com
1-STORY
LC
AC
MSP
ANDRES MIER
(N) VISIBLE LOCKABLE LABELED DISCONNECT
<10FT
RESIDENCE
(E) DETACH (E) MAIN SERVICE PANEL
(E) UTILITY METER
TREES
36'-5"
(E) FENCE
SHEET NAME
SITE PLAN
SHEET SIZE
PROPERTY LINE
56'-6" ANSI B
11" X 17"
1 PLOT PLAN WITH ROOF PLAN VISIBLE LOCKABLE LABELED DISCONNECT LOCATED ON
SHEET NUMBER
PV-1 SCALE: 1/16" = 1'-0" ACCESSIBLE EXTERIOR WALL WITHIN 10 FEET OF ONCOR METER PV-1
DESIGN SPECIFICATION ROOF DESCRIPTION
ROOF RAFTER RAFTER
RISK CATEGORY: II ROOF AZIMUTH ROOF MATERIAL
TILT SIZE SPACING
CONSTRUCTION: SFD #1 18° 180° 2"X6" 16" o.c. ASPHALT SHINGLE
#2 18° 360° 2"X6" 16" o.c. ASPHALT SHINGLE
ZONING: RESIDENTIAL BEAL STREET
ARRAY AREA & ROOF AREA CALC'S 4K & ZAVALA
SNOW LOAD (ASCE 7-16): 5 PSF
(E) FRONT OF RESIDENCE ROOF SOLAR LLC
ARRAY ROOF AREA
EXPOSURE CATEGORY: B # OF AREA AREA COVERED
ROOF
MODULES
WIND SPEED (ASCE 7-16): 105 MPH ROOF #2 (Sq. Ft.) (Sq. Ft.) BY ARRAY
TILT - 18° (%)
AZIM. - 360° #1 6 112.71 454.73 25
MODULE TYPE, DIMENSIONS & WEIGHT
3'-3" 1'-6" #2 16 299.64 623.32 48
NUMBER OF MODULES: 22 MODULES 4'-0" 10'-3"
24'-0"
1'-5"
LEGEND SYSTEM INFO.
MODULE TYPE: SEG-360-BMB-HV JB (N) JUNCTION BOX (22)SEG-360-BMB-HV
10'-11"
AC SYSTEM SIZE: 6.49 KWAC
3'-4"3'-11"
(22) SEG-360-BMB-HV MODULES Signature with Seal
(N) IRONRIDGE XR-10 RAIL 36" FIRE SETBACK
5'-6"
DATE: 11/30/2021
10'-11"
5'-7"
Email: andressolar1960@gmail.com
1'-8"
LC
TILT - 18°
(N) LOAD CENTER
AC
MSP
AZIM. - 180°
UM
(N) VISIBLE LOCKABLE LABELED DISCONNECT
(E) MAIN SERVICE PANEL
(E) UTILITY METER
40.86"
SHEET NAME
69.09"
(E) BACK OF RESIDENCE SHEET SIZE
ANSI B
11" X 17"
SHEET NUMBER
1 ROOF PLAN & MODULES SEG-360-BMB-HV
PV-2 SCALE: 1/8" = 1'-0"
MODULES PV-2
BILL OF MATERIALS BEAL STREET
EQUIPMENT QTY DESCRIPTION
SOLAR PV MODULE 22 SEG-360-BMB-HV
ENPHASE IQ7 PLUS-72-2-US (240V)
(E) FRONT OF RESIDENCE
MICROINVERTER 22
JUNCTION BOX 1 JUNCTION BOX, NEMA 3R, UL LISTED
4K & ZAVALA
COMBINER BOX 1 ENPHASE IQ COMBINER W/ IQ ENVOY (X-IQ-AM1-240-3)
SOLAR LLC
Email: andressolar1960@gmail.com
B-11 B-10
UM
SHEET NAME
STRING
LAYOUT & BOM
SHEET SIZE
ANSI B
11" X 17"
1 ROOF PLAN WITH STRING LAYOUT & BOM (E) BACK OF RESIDENCE
SHEET NUMBER
SYSTEM INFO.
(22)SEG-360-BMB-HV
(22) ENPHASE IQ7 PLUS-72-2-US (240V)
DC SYSTEM SIZE: 7.92 KWDC
REVISIONS
DESCRIPTION DATE REV
REVISION 11/30/2021 A
DATE: 11/30/2021
Email: andressolar1960@gmail.com
FORT WORTH, TX 76105
PH.# : (817) 458-1253
4312 BEAL STREET
ANDRES MIER
RESIDENCE
SHEET NAME
ATTACHMENT
DETAIL
SHEET SIZE
ANSI B
11" X 17"
SHEET NUMBER
PV-3
IRONRIDGE XR10 Rail
4K & ZAVALA
SOLAR LLC
REVISIONS
DESCRIPTION DATE REV
REVISION 11/30/2021 A
DATE: 11/30/2021
.62
Email: andressolar1960@gmail.com
.46
.58
1.00
SHEET NAME
ATTACHMENT
DETAIL
SHEET SIZE
ANSI B
11" X 17"
SHEET NUMBER
PV-3A
# OF CURRENT-CARRYING CONDUIT CONDUIT TERM.
INITIAL CONDUCTOR FINAL CONDUCTOR TEMP. CORR. CONT. MAX. BASE DERATED VOLTAGE
ID TYPICAL CONDUCTOR CONDUIT PARALLEL CONDUCTORS IN FILL OCPD EGC FILL TEMP. LENGTH
LOCATION LOCATION FACTOR CURRENT CURRENT AMP. AMP. DROP
CIRCUITS CONDUIT PERCENT FACTOR RATING
BARE
1 2 STRING JUNCTION BOX 12 AWG Q CABLE - - 1 2 N/A N/A 6 AWG 0.71 (59°C) N/A 13.3A 16.6A N/A N/A 90°C 56FT 0.56%
COPPER
MIN 0.75" Dia THWN-2,
2 1 JUNCTION BOX COMBINER BOX 10 AWG THWN-2 COPPER 2 4 19.09% 20A 10 AWG 0.91 (37°C) 0.8 13.3A 16.6A 40A 29.1A 90°C 38FT 0.54%
EMT COPPER 4K & ZAVALA
MIN 0.75" Dia THWN-2,
3 1 COMBINER BOX AC DISCONNECT 10 AWG THWN-2 COPPER 1 3 15.27% N/A 10 AWG 0.91 (37°C) 1 26.6A 33.3A 40A 36.4A 90°C 5FT 0.14% SOLAR LLC
EMT COPPER
MIN 0.75" Dia THWN-2,
4 1 AC DISCONNECT MSP 10 AWG THWN-2 COPPER 1 3 15.27% 40A 6 AWG 0.91 (37°C) 1 26.6A 33.3A 40A 36.4A 90°C 5FT 0.14%
EMT COPPER
SYSTEM INFO.
(22)SEG-360-BMB-HV
(22) ENPHASE IQ7 PLUS-72-2-US (240V)
DC SYSTEM SIZE: 7.92 KWDC
REVISION 11/30/2021 A
(E) MAIN SERVICE
BACK FEED BREAKER AT PANEL, 200A RATED,
THE OPPOSITE END OF 1-PH, 3-W, 240V
THE MAIN BREAKER
40A/2P Signature with Seal
L1 L1
Q CABLE JUNCTION BOX
L2 L2
600 V, NEMA 3R, 2 AC DISCONNECT:
1 UL LISTED ENVOY 240V, 60A NON-FUSED L1 L1
10A/2P NEMA 3R, UL LISTED TO UTILITY
L2 L2
20A/2P GRID
L1
L1 L1 L1 L1
L2
20A/2P L2 L2 L2 L2 BI-DIRECTIONAL UTILITY
BRANCH 2 L1 N N METER# 141 041 575 DATE: 11/30/2021
11- SEG-360-BMB-HV MODULES L2
G G
1-PH, 3-W, 120V/240V
PROJECT NAME & ADDRESS
G G
3 4
Email: andressolar1960@gmail.com
(N) ENPHASE IQ
(E) MAIN BREAKER TO
SHEET NAME
ELECTRICAL LINE
INTERCONNECTION & CALCS.
120% RULE - NEC 705.12(B)(2) SERVICE INFO. SHEET SIZE
ENPHASE IQ7 PLUS-72-2-US The voltage rise from the Junction Box to the IQ Combiner Box is 0.54%
DC SYSTEM SIZE: 7.92 KWDC
CONTINUOUS OUTPUT
VRise = (amps/inverter × number of inverters) × (resistance in Ω/ft.) × (2-way wire length in ft.)
CURRENT 1.21A (240V) = (1.21 amp × 22) × (0.00129 Ω/ft) × (5 ft. × 2)
Signature with Seal
= 26.62 amps × 0.00129 Ω/ft × 10 ft.
AMBIENT TEMPERATURE SPECS = 0.34 volts
RECORD LOW TEMP -8°C %VRise = 0.34 volts ÷ 240 volts = 0.14%
AMBIENT TEMP (HIGH TEMP 2%) 36°C The voltage rise from the IQ Combiner Box to the AC Disconnect is 0.14%
CONDUIT HEIGHT 0.5" DATE: 11/30/2021
ROOF TOP TEMP 90°C Voltage rise from the AC Disconnect to the Main Service Panel PROJECT NAME & ADDRESS
CONDUCTOR TEMPERATURE RATE 58°C VRise = (amps/inverter × number of inverters) × (resistance in Ω/ft) × (2-way wire length in ft.)
Email: andressolar1960@gmail.com
MODULE TEMPERATURE COEFFICIENT OF VOC -0.27%/°C = (1.21 amp × 22) × (0.001290 Ω/ft) × (5 ft × 2)
= 26.62 amps × 0.001290 Ω/ft × 10 ft
ANDRES MIER
PERCENT OF VALUES CARRYING CONDUCTORS
RESIDENCE
IN EMT
%VRise = 0.34 volts ÷ 240 volts = 0.14%
0.80 4-6
The voltage rise from the AC Disconnect to the Main Service Panel is 0.14%
0.70 7-9
0.50 10-20
Total system voltage rise for all wire sections
0.56 % + 0.54% + 0.14% + 0.14% = 1.38%
SHEET NAME
SPECIFICATIONS
& CALC.
SHEET SIZE
ANSI B
11" X 17"
SHEET NUMBER
PV-4A
1 ! WARNING PHOTOVOLTAIC SYSTEM AC DISCONNECT ! WARNING
5 10 POWERSOURCEOUTPUTCONNECTION.
ELECTRIC SHOCK HAZARD RATED AC OUTPUT CURRENT 26.62 AMPS
DO NOT TOUCH TERMINALS NOMINAL OPERATING AC VOLTAGE 240 VOLTS DONOTRELOCATETHISOVERCURRENTDEVICE. 4K & ZAVALA
TERMINALS ON BOTH LINE AND SOLAR LLC
LOAD SIDES MAY BE ENERGIZED
LABEL LOCATION:
LABEL LOCATION:
IN THE OPEN POSITION
POINT OF INTERCONNECTION, MAIN SERVICE PANEL & COMBINER BOX
(PER CODE: NEC 690.54)
LABEL LOCATION:
POINT OF INTERCONNECTION,
(PER CODE: NEC 690.17(E))
6 WARNING CAUTION
INVERTER OUTPUT CONNECTION DO NOT
11 POWER TO THIS SERVICE SYSTEM INFO.
WARNING-ElectricShockHazard IS ALSO SUPPLIED FROM
2 Nouserserviceablepartsinside RELOCATE THIS OVERCURRENT DEVICE ON-SITE SOLAR/WIND
(22)SEG-360-BMB-HV
(22) ENPHASE IQ7 PLUS-72-2-US (240V)
Contactauthorizedserviceproviderforassistance LABEL LOCATION:
POINT OF INTERCONNECTION
GENERATION DC SYSTEM SIZE: 7.92 KWDC
LABEL LOCATION: AC SYSTEM SIZE: 6.49 KWAC
(PER CODE: NEC 705.12(D)(7))
INVERTER, JUNCTION BOXES (ROOF),
(PER CODE: NEC690.13.G.3 & NEC 690.13.G.4)
[Not required if panelboard is rated not less than sum of ampere ratings AC SYSTEM DISCONNECT REVISIONS
of all overcurrent devices supplying it]
DESCRIPTION DATE REV
REVISION 11/30/2021 A
Email: andressolar1960@gmail.com
AND REDUCE
SHOCK HAZARD
IN THE ARRAY
RESIDENCE
· THE LABEL SHALL BE SUITABLE FOR THE ENVIRONMENT
SHUTDOWN COMPLIANT SYSTEM
WHERE IT IS INSTALLED.
· WHERE REQUIRED ELSEWHERE IN THIS CODE, ALL FIELD
APPLIED LABELS, WARNINGS, AND MARKINGS SHOULD
COMPLY WITH ANSI Z535.4 [NEC 110.21(B) FIELD MARKING].
· ADHESIVE FASTENED SIGNS MAY BE ACCEPTABLE IF
PROPERLY ADHERED. VINYL SIGNS SHALL BE WEATHER
RESISTANT [IFC 605.11.1.3] 9 CAUTION: SOLAR CIRCUIT
BEAL STREET
LABEL LOCATION:
MARKINGS PLACED ON ALL INTERIOR AND EXTERIOR DC CONDUIT, RACEWAYS,
ENCLOSURES, AND CABLE ASSEMBLIES AT LEAST EVERY 1O FT, AT TURNS AND
ABOVE/BELOW PENETRATIONS AND ALL COMBINER/JUCTION BOXES. (PER CODE:
IFC 605.11.1.4)
SHEET NAME
SIGNAGE
UM
UTILITY METER
MSP
(E) MAIN SERVICE PANEL AC LC
SHEET SIZE
(N) LOAD CENTER
(N) VISIBLE LOCKABLE LABELED DISCONNECT ANSI B
11" X 17"
SHEET NUMBER
PV-5
4K & ZAVALA
SOLAR LLC
SYSTEM INFO.
(22)SEG-360-BMB-HV
(22) ENPHASE IQ7 PLUS-72-2-US (240V)
DC SYSTEM SIZE: 7.92 KWDC
REVISIONS
DESCRIPTION DATE REV
REVISION 11/30/2021 A
DATE: 11/30/2021
Email: andressolar1960@gmail.com
FORT WORTH, TX 76105
PH.# : (817) 458-1253
4312 BEAL STREET
ANDRES MIER
RESIDENCE
SHEET NAME
EQUIPMENT
SPECIFICATION
SHEET SIZE
ANSI B
11" X 17"
SHEET NUMBER
PV-6
4K & ZAVALA
SOLAR LLC
SYSTEM INFO.
(22)SEG-360-BMB-HV
(22) ENPHASE IQ7 PLUS-72-2-US (240V)
DC SYSTEM SIZE: 7.92 KWDC
REVISIONS
DESCRIPTION DATE REV
REVISION 11/30/2021 A
DATE: 11/30/2021
Email: andressolar1960@gmail.com
FORT WORTH, TX 76105
PH.# : (817) 458-1253
4312 BEAL STREET
ANDRES MIER
RESIDENCE
SHEET NAME
EQUIPMENT
SPECIFICATION
SHEET SIZE
ANSI B
11" X 17"
SHEET NUMBER
PV-7
4K & ZAVALA
SOLAR LLC
SYSTEM INFO.
(22)SEG-360-BMB-HV
(22) ENPHASE IQ7 PLUS-72-2-US (240V)
DC SYSTEM SIZE: 7.92 KWDC
REVISIONS
DESCRIPTION DATE REV
REVISION 11/30/2021 A
DATE: 11/30/2021
Email: andressolar1960@gmail.com
FORT WORTH, TX 76105
PH.# : (817) 458-1253
4312 BEAL STREET
ANDRES MIER
RESIDENCE
SHEET NAME
EQUIPMENT
SPECIFICATION
SHEET SIZE
ANSI B
11" X 17"
SHEET NUMBER
PV-8
4K & ZAVALA
SOLAR LLC
SYSTEM INFO.
(22)SEG-360-BMB-HV
(22) ENPHASE IQ7 PLUS-72-2-US (240V)
DC SYSTEM SIZE: 7.92 KWDC
REVISIONS
DESCRIPTION DATE REV
REVISION 11/30/2021 A
DATE: 11/30/2021
Email: andressolar1960@gmail.com
FORT WORTH, TX 76105
PH.# : (817) 458-1253
4312 BEAL STREET
ANDRES MIER
RESIDENCE
SHEET NAME
EQUIPMENT
SPECIFICATION
SHEET SIZE
ANSI B
11" X 17"
SHEET NUMBER
PV-9
4K & ZAVALA
SOLAR LLC
SYSTEM INFO.
(22)SEG-360-BMB-HV
(22) ENPHASE IQ7 PLUS-72-2-US (240V)
DC SYSTEM SIZE: 7.92 KWDC
REVISIONS
DESCRIPTION DATE REV
REVISION 11/30/2021 A
DATE: 11/30/2021
Email: andressolar1960@gmail.com
FORT WORTH, TX 76105
PH.# : (817) 458-1253
4312 BEAL STREET
ANDRES MIER
RESIDENCE
SHEET NAME
EQUIPMENT
SPECIFICATION
SHEET SIZE
ANSI B
11" X 17"
SHEET NUMBER
PV-10
4K & ZAVALA
SOLAR LLC
SYSTEM INFO.
(22)SEG-360-BMB-HV
(22) ENPHASE IQ7 PLUS-72-2-US (240V)
DC SYSTEM SIZE: 7.92 KWDC
REVISIONS
DESCRIPTION DATE REV
REVISION 11/30/2021 A
DATE: 11/30/2021
Email: andressolar1960@gmail.com
FORT WORTH, TX 76105
PH.# : (817) 458-1253
4312 BEAL STREET
ANDRES MIER
RESIDENCE
SHEET NAME
EQUIPMENT
SPECIFICATION
SHEET SIZE
ANSI B
11" X 17"
SHEET NUMBER
PV-11
4K & ZAVALA
SOLAR LLC
SYSTEM INFO.
(22)SEG-360-BMB-HV
(22) ENPHASE IQ7 PLUS-72-2-US (240V)
DC SYSTEM SIZE: 7.92 KWDC
REVISIONS
DESCRIPTION DATE REV
REVISION 11/30/2021 A
DATE: 11/30/2021
Email: andressolar1960@gmail.com
FORT WORTH, TX 76105
PH.# : (817) 458-1253
4312 BEAL STREET
ANDRES MIER
RESIDENCE
SHEET NAME
EQUIPMENT
SPECIFICATION
SHEET SIZE
ANSI B
11" X 17"
SHEET NUMBER
PV-12