Technical Data TD00302001E
Effective February 2014 3-Phase Loadcenter Program
1. Product Selection
Type BR 3-Phase Loadcenters
Service
3-Phase, four-wire, 208Y/120 Vac
3-Phase, three-wire, 240 Vac Delta
Short Circuit Rating
Main Breaker Loadcenters 10 kAIC using BR / CC / HLD main breakers
22 kAIC using BRH / DK main breakers
100 kAIC using CHH main
Main lug Loadcenters Up to 100 kAIC using series ratings.
The rating of main lug only loadcenter is dependent on the lowest branch breaker AIC rating.
Convertible Loadcenters 10 kAIC using BR / CC main breakers
22 kAIC using BRH main breakers
Branch Breakers Types BR, BRH, BRHH: 10-150A single, two, and three pole; selected amperage available in Switching Duty, HACR, shunt trip, and
high magnetic settings
Type GFCB ground fault circuit interrupter: 15–60A single and two-pole
Type AFCI arc fault circuit interrupter: 15-20A single-pole
Types BJ and BJH: 125–225A; two- and three-pole sub-fed breakers
Type BD Twin: 10–50A; two of one-pole; takes one 1-inch (25.4 mm) space
Type BQ and BQC Multi-breaker: 15–30A. Two of two-pole or one two-pole and two one-pole; takes two 1-inch (25.4 mm) spaces
Type BRW: 15–30A; two-pole water heater breakers
Type BRSN: 15–30A; two-pole switching neutral breakers
Type BR 15–100A; two-pole, 240 Vac delta breakers
Enclosures Nema Type 1 Indoor/Nema Type 3R Outdoor
Nema 4x (Available via Flex Center 800-330-6479)
Bussing Tin Plated Aluminum or Copper
Standards UL67
3 BR 30 42 B C 200
Phase
3 = Three-phase
Amperes
50 = 50A 150 = 150A
70 = 70A 200 = 200A
100 = 100A 225 = 225A
125 = 125A 400 = 400A
600 = 600A
Note
1 No character space used.
Main Catalog Number Catalog Number Max # Max # Box Size Wire Size Range CU/AL
Ampere Rating Indoor Outdoor of Spaces of Circuits Nema1 Nema 3R 60 C or 75 C for Main
2. Accessories*
Accessories for branch Auxiliary components, lockoffs, hold-down kits, lockdogs,
circuit breakers handle ties.
Sub-feed devices Main and sub-feed lugs 125,150, 225A two and three pole.
Shunt trips available.
Surge protection SPD Type 1 devices available for 208Y/120 Vac loadcenters
Universal rainproof Small Hub - Group 1 : 3/4, 1, 1-1/4, 1-1/2, 2 inches
conduit hubs Large Hub - Group 2: 1, 1-1/4, 1-1/2, 2, 2-1/2, 3 inches
Adapter kits available
G1R 34.13 (866.8) 14.31 (363.5) 5.19 (131.8) .45 (11.4) Dia. KO .45 (11.4) Dia. KO
A A B B B B A
L1R 39.00 (990.6) 14.31 (363.5) 5.19 (131.8) E B
B
B B
I
B
B H
B A
E E
A A
B B
B A A B
B A A B
B B
A A
E E
D D D D
Indoor Boxes
C1, C2, C4, D1, G1, L1, L2
D E E E D
D E E E D
C B B B
B B
G F B B B
C
B B
F E
A
Box 42 A Box 43, 46, 47
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
877-ETN-CARE (877-386-2273)
Eaton.com
© 2014 Eaton
All Rights Reserved Eaton is a registered trademark.
Printed in USA
Publication No. TD00302001E All other trademarks are property of their
February 2014 respective owners.