+3.

500

100mm NOM.
FIXING TO SUIT
M12 ROD W/LOCKING NUTS
/ASTM 193 GRADE B8 CLASS 1/ BASE
& WASHERS /ASTM F844/
2 PIECE PIPE CLAMP /UN16/
ANCHOR BOLT M8x60mm
ASTM A193, B8 GRADE REFRIGERANT RETURN∅6mm +2.550
DRAINAGE PIPE ∅16mm REFRIGERANT SUPPLY∅12mm
PIPES SHALL BE WRAPPED
BY FOAM INSULATION

CEILING SUPPORT

FRONT VIEW SIDE VIEW


RADIATOR TYPE 22 SCREW M4x60mm
ASTM A193 B8 Class 1
STAINLESS STEEL METAL POLYMER
50 100

DRAINAGE PIPE ∅32mm


PIPE ∅16mm BALL VALVE 1" SCREW M8X60mm
ASTM A193 B8 Class 1
REFRIGERANT SUPPLY

100
STAINLESS STEEL
∅12mm /COPPER PIPE/
GLYCOL SUPPLY
REFRIGERANT RETURN METAL POLYMER PIPE
∅6mm /COPPER PIPE/ GLYCOL SUPPLY
∅40mm XS CARBON
SCREW M4x60mm STEEL
ASTM A193 B8 Class 1
STAINLESS STEEL
GLYCOL SUPPLY
∅40mm XS CARBON
STEEL GLYCOL RETURN
METAL POLYMER PIPE
MANIFOLD SUPPORT PIPE STRAP
WEATHER HOOD DN200 EQUAL ANGLE ANVIL FIG.262
+3.500= LEVEL +1187.30 OR EQUIVALENT
VOLUME CONTROL DAMPER AIR DUCT SUPPORT 40x40 AIR CONDITION MOUNTING PLATE
PIPE STRAP MAXIMUM
300m3/h DN200 Y PIECE AIR DUCT DN150x200 SPACING BETWEEN
HANGERS SHALL NOT
FLEXIBLE DUCT DN150 EXCEED 1.5 METERS.

G FAN DN150 220V 10W FLEXIBLE DUCT INSULATION

+0.000= LEVEL +1180.80 NOTES


ISSUED FOR CONSTRUCTION
1. ALL COORDINATES AND ELEVATIONS ARE DISPLAYED IN METERS, IN ACCORDANCE
FIXING SCREW WITH THE OYU TOLGOI GRID SYSTEM. VENDOR DOCUMENT NUMBER REV.

M4 X 25mm 2. DIMENSIONS ARE SHOWN IN MILLIMETERS UNLESS STATED OTHERWISE. MCSP-5221-35-C2-0011 2


3. HEATING SYSTEM PIPING SHALL BE METAL POLYPIPE. WORLEY DOCUMENT NUMBER
4. PIPING FITTINGS SHALL BE COMPRESSION TYPE. CW2099445-B090-0011_R4
5. MAXIMUM SPACING BETWEEN METAL POLYMER PIPES SHALL NOT EXCEED 1.5 METERS.
6. MAXIMUM SPACING BETWEEN REFRIGERANT TUBES SHALL NOT EXCEED 1.0 METERS.
property
Address: Central Tower, 16th floor, Square 2, SBD-8, Ulaanbaatar, 14200, Mongolia;
Tel: +976-11-328942, 315244; Fax: +976-11-321656; Web: www.mcs.mn
DES. DES. PRODUCED BY DESIGNED BY DRAWN BY
REV. DATE REVISION DESCRIPTION
CHK.
APPROVED REV. DATE REVISION DESCRIPTION
CHK.
APPROVED REFERENCE DRAWING No. REFERENCE DRAWINGS MCS PROPERTY TEMUUJIN CH. NOMIN Z. MCSP C-004A SURFACE FACILITIES
TJ TJ PROJECT NO CHECK DESIGN CHECK DRAWING TEMPORARY MINE DRY FACILITY
A 04/16/22 ISSUED FOR REVIEW 5221-20-A1-8000 MCSP C-004A SURFACE FACILITIES, GENERAL ARRANGEMENT PLAN
GZ GZ SN1809 GANZORIG.D TEMUUJIN CH. HVAC DETAILS
TJ TJ
0 05/03/22 ISSUED FOR CONSTRUCTION 5221-35-C2-8008 MCSP C-004A SURFACE FACILITIES MINEDRY FACILITY HEATING SYSTEM PLAN CONTRACT NO LEAD ENGINEER APPROVAL DATE
GZ GZ CW2099445
NZ NZ
1 0709/22 ISSUED FOR CONSTRUCTION 5221-35-C2-8009 MCSP C-004A SURFACE FACILITIES MINEDRY FACILITY VENTILATION SYSTEM PLAN Disclaimer: Drawings, plans, models, designs or any other information displayed, contained in, made available or disclosed in or by this DRAWING SIZE PROJECT ENGINEER ENGINEERING MANAGER
TJ GZ document (or its part or attachment) is owned by Oyu Tolgoi LLC and may be a proprietary of Oyu Tolgoi LLC and hence they are for the
NZ NZ internal use of Oyu Tolgoi LLC only. Making a copy or reproduction thereof in any form or giving an access or possession of them to any other A3 GANZORIG.D
2 07/20/22 ISSUED FOR CONSTRUCTION party without Oyu Tolgoi LLC's written consent or permission shall be strictly prohibited. Any violation (actual or attempted) of these terms
GZ GZ and prohibitions shall be subject legal liabilities and Oyu Tolgoi LLC reserves its rights and entitlements to all available legal remedies.
PLOT SCALE PROJECT MANAGER APPROVAL DATE
үү ү үү ү үү ө
үү ө ө ө өө
ө ө ө өө ө ө ө ө 1:1 ERDENEBAATAR.G -
ө өө ө өө ө ү
ү CAD FILE NAME CLIENT APPROVAL DATE SCALE DRAWING NUMBER REV.
ө ө ө ө ө ү ө
ө ү ө өө ү ү WORLEY - 5221-35-C2-8010 2

You might also like