BS4568 Class 3 Conduit 2025mm

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

Test Report No.

7191099276-MEC14-TYW
dated 20 OCT 2014

Note: This report is issued subject to TÜV SÜD PSB's "Terms and Conditions Governing Technical Services".
The terms and conditions governing the issue of this report are set out as attached within this report.

SUBJECT:

Testing of Steel Conduit Pipe

TESTED FOR:

ITE Electric Systems Co Pte Ltd.


(ITEES)
No. 1 Harrison Road
#01-01 ITE Building
Singapore 369652

Attn : Mr Jack Soh

TEST METHOD:

BS 4568-1 : 1970 - Specification for Steel Conduit and Fittings with Metric Threads of ISO Form for
Electrical Installations
Part 1: Steel Conduit, Bends and Couplers (Class 3)

SAMPLE DESCRIPTION:

The following conduit pipe samples (Photo 1 and 2) said to be “SPINNE” brand were submitted by
ITE Electric Systems Co Pte Ltd on 1 October 2014 for analysis

Specimen dimension Quantity

Ø 20mm 6pcs

Ø 25mm 6pcs

TEST CONDUCTED:

Test for resistance to corrosion

PRINT MARKINGS:

1) SPINNE MTG TO BS4568 1970 Class 4 3.75m Ø 20mm

2) SPINNE MTG TO BS4568 1970 Class 3 3.75m Ø 25mm

Laboratory: Phone : +65-6885 1333 Regional Head Office:


TÜV SÜD PSB Pte. Ltd. Fax : +65-6776 8670 TÜV SÜD Asia Pacific Pte. Ltd.
No.1 Science Park Drive E-mail: testing@tuv-sud-psb.sg 3 Science Park Drive, #04-01/05
Singapore 118221 www.tuv-sud-psb.sg The Franklin, Singapore 118223
Co. Reg : 199002667R Page 1 of 4
Test Report No. 7191099276-MEC14-TYW
dated 20 OCT 2014

TEST RESULTS:

“SPINNE” brand Conduit Pipe


Sample BS 4568-1 : 1970 Requirements
Reference Ø 20mm Ø 25mm

Clause Appendix A –
A.3.2: Medium Protection
Sample shall show no more than two
blue coloured spots on each square
Medium Protection, Medium Protection, centimetre of the surface, and no blue
Inside : Pass Inside : Pass spot shall have a dimension larger
Resistance to than 1.5mm.
Heavy Protection, Heavy Protection,
Corrosion
Outside : Pass Outside : Pass Clause Appendix A –
A.3.3 Heavy Protection
Sample shall show no precipitation of
copper, which cannot be scrubbed by
running water.

___________________ __________________
Ting Yeow Wah Kong Siew Yong
Higher Associate Engineer Product Manager
Polymer Products
Mechanical Centre

Page 2 of 4
Test Report No. 7191099276-MEC14-TYW
dated 20 OCT 2014

PHOTOGRAPH OF THE SAMPLES SUBMITTED:

Photo 1 : Conduit Pipe Ø 20mm

Photo 2 ; Conduit Pipe Ø 25mm

Page 3 of 4
Test Report No. 7191099276-MEC14-TYW
dated 20 OCT 2014

Please note that this Report is issued under the following terms :

1. This report applies to the sample of the specific product/equipment given at the time of its testing/calibration. The results are not used to
indicate or imply that they are applicable to other similar items. In addition, such results must not be used to indicate or imply that TÜV SÜD
PSB approves, recommends or endorses the manufacturer, supplier or user of such product/equipment, or that TÜV SÜD PSB in any way
“guarantees” the later performance of the product/equipment. Unless otherwise stated in this report, no tests were conducted to determine
long term effects of using the specific product/equipment.

2. The sample/s mentioned in this report is/are submitted/supplied/manufactured by the Client. TÜV SÜD PSB therefore assumes no
responsibility for the accuracy of information on the brand name, model number, origin of manufacture, consignment or any information
supplied.

3. Nothing in this report shall be interpreted to mean that TÜV SÜD PSB has verified or ascertained any endorsement or marks from any other
testing authority or bodies that may be found on that sample.

4. This report shall not be reproduced wholly or in parts and no reference shall be made by the Client to TÜV SÜD PSB or to the report or results
furnished by TÜV SÜD PSB in any advertisements or sales promotion.

5. Unless otherwise stated, the tests were carried out in TÜV SÜD PSB Pte Ltd, No.1 Science Park Drive Singapore 118221.

July 2011

Page 4 of 4

You might also like