TRANS AUTO STARTING SEQUENCE (AUTO MODE)

TRUE
YES NO Firstly Fuel selenoid FALSE TRUE The FALSE
If any of the ENGINE CRANK Generator doesn’t If the problem still unsolve;
Generator REMOTE START energized(if selected) Than DISCONNECT parameter value more than
wait on system check ENGINE work although device -Please check ENGINE CRANK
(System wait for remote CRANK DISCONNECT
set value, Engine running LED become appears seem works. DISCONNECT parameters,
Standby mode start delay time) parameters before the start active and Safety on delay parameter Failure must be
erase using equipment and wires.
then ENGINE CRANK countdown with out crank process
with RESET
(2sec.after fuel)
Buton

TRUE : NORMAL CONDITION


FALSE : UNDESIRED CONDITION TRUE

System check
Engine running LED become active TRUE ENGINE CRANK
FALSE FALSE If the problem still unsolve;
(Cranking is finish) Device try to crank the generator as Please check ENGINE CRANK
DISCONNECT saved in No. of crank attemp DISCONNECT parameters, equipment
Parameters while parameter ( Default 3 times ) and wires.There is a start failure, push
ENGINE CRANK
the RESET buton
(Crank time &
Rest time)
TRUE
TRUE TRUE

Safety on delay
Parameter count down
START TIMERS (Timers->Start timers) Min Max Default Unit ENG. CRANK DISCONNECT (Engine->Crank disconnect) Min Max Default Unit
Remote start delay Remote Start Delay 0 3600 4 Sec Generator frequency Crank Disconnect On Gen. Frequency 10.0 75.0 30.0 Hz
TRUE Pre-heat Pre-Heat 0 250 3 Sec Engine speed Crank Disconnect On Engine RPM 100 6000 500 RPM
Pre-heat bypass Pre-Heat Bypass 0 250 0 Min Generator volt Crank Disconnect On Gen. Voltage 60 (dis) 600 300 VV
Safety on delay Safety On Delay 0 99 5 Sec Charge alt. volt Crank Disconnect On Charge Alt. Voltage 6.0 (dis) 30.0 dis VZ
Warming up time Warmup Time 0 250 3 Sec Oil pressure
Horn duration
Crank Disconnect On Oil Pressure 1.0 (dis) 30.0 dis BAR
Horn Duration 0 (dis) 999 60 Sec
Chg. excitation time Charge Excitation Time 0 99(cont) 15 Sec ENGINE START OPTIONS (Engine->Starting options) Min Max Default Unit
If Voltage, Frequency Cooling fan time Cooling Fan Time 0 250 180 Sec Horn prior start Audible Alarm Prior To Starting En/Dis ENABL/DISBL DISBL
and RPM values are in the Idle mode time Idle Mode Time (Smoke Limiting) 0 (dis) 3600 dis Sec
limits, Generator available
No. of crank attemp Number Of Start Attempts 1 10 3
Idle mode time off Idle Mode Time Off (Smoke Limiting Off) 0 250 5 Sec
for load and ready Cranking time Cranking Time 1 99 5 Sec
LED become active Crank rest time Crank Rest Time 5 99 10 Sec
Pickup fail dely Pickup Sensor Fail Delay 0.1 10.0 1.0 Sec

NOTE :
TRUE th
Charge alt. Volt : If Charge Alt. Volt will not be used in the system(35 therminal disconnected). This parameter must be ‘disable’.
If this parameter set ‘enable’ when charge alternator not using, device assumes that generator is working,then engine running LED
Create a signal to activate become active,and device gives failure after Safety on delay time.
Generator available output Oil pressure : Oil pressure input sellection available to use through Conf. analog sender input (Pin 24) or Conf. digital input-4 (Pin 31). If
user only want to read on analog output for oil pressure sender connect on Pin 24, user must be change Conf. digital input-4 parameter.
Because Oil pressure parameter factory setting is for Pin 31.
TRANS-AUTO three phase connections schematic
REMOTE STOP
(System wait for remote GENERATOR
stop delay time)
L1
TO L2
LOAD L3
Generator works N
without load as
Cooling Time

FUSE-1

FUSE-2

FUSE-3
G
TRUE
NOTE: Engine stopping process can make fuel or
!
4 MPU
3

stop solenoid selection;


Generator Stop 1.If fuel solenoid is selected, the solenoid output is -(SCR) +
Command de-energized.
2.If stop solenoid is selected, the solenoid output is
1 2 3 4 5 11 12 13 14 15 16 17 18 19 20

Relay
Contactor
Generator
energized for Stop selenoid time parameter value. H(+) L(-) SCR
Max. 300V~

8A
TRUE J1939 ECUs

ENGINE CRANK
DISCONNECT
FALSE System wait for
FALSE If the problem still unsolve;
-Please check ENGINE CRANK
!
2
parameters allow for stop Fail to Stop Delay DISCONNECT parameters,
signal equipment and wires. Then Push
RESET buton USB
TRUE
TRUE
TRANSISTOR OUTPUTS
TRUE MAX. 1 A
BATTERY +
* IT CAN BE USED
AS A DIGITAL INPUT
BY SELECTING

5A

5A
FROM THE PROGRAM
PARAMETERS
Generator
Stop 42 41 40 39 38 37 36 35 34 33 32 31 30 29 28 27 26 25 24 23 22 21

Configurable Output-6

Configurable Output-5

Configurable Output-4

Configurable Output-3

Configurable Output-2
Crank Or
Configurable Output-1
Fuel Or
* * * *

Sender Common

FUSE-4
FUSE-5

BATTERY +
BATTERY +

BATTERY -
Charge Alt.
D+(W.L.)
Configurable Input-7
Cabin Temperature or

Configurable Input-6

Configurable Input-5
High Temperature or
Configurable Input-4
Low Oil Pressure or
Configurable Input-3
Water Level or
Configurable Input-2
Remote Start or
Configurable Input-1
Emergency Stop or

Configurable Analog Input-1


Level Sender or

Temperature Sender

Oil Sender

Configurable Analog Input-2


Earth
To Engine
!1

BATTERY -

STOPPING TIMERS (Timers->Stopping timers) Min Max Default Unit


Remote stop delay Remote Stop Delay 0 250 4 Sec
Cooling time Cooling Time 0 (dis) 3600 60 Sec
Fail to stop delay Fail To Stop Time 15 99 30 Sec FUSE-1, FUSE-2, FUSE-3 2 A. T / FUSE-4 6 A. T / FUSE-5 Max. 10 A. T

USER MUST BE CONNECT MARKED TERMINALS !