Soft Starter - 01-07072015
Soft Starter - 01-07072015
Oferta
No. 01-07072015
Fecha 07/07/2015
Atn: Cesar Villorin /Inmaserca
Puesta en marcha
1 $2.000,00 $2.000,00
gastos de viaje (costo +15%)
This budgetary offer could be confirmed and accepted only after the calculation of the
technical feasibility of the starting of soft starter with the motor and the load.
To make these starting calculations we need:
For the load:
- The starting load torque curve VS speed
- The inertia of the load
For the motor:
- The complete Motor Data sheet
- The starting current curve of the motor VS motor speed
- The starting torque curve of the motor VS motor speed
- The Inertia of the motor
CONDICIONES:
Disponibilidad : 16 a 20 semanas
Condiciones de pago
120 días
:
1
ANNEX I
2
ANNEX II
3
Option: Line cabinet
Line requested options could be installed in additional line cabinet:
· Line contactor
· Line switch + Input ground switch
· MV Fuses
· Motor protection relay including the following protections:
- overcurrent : code ANSI 50/51
- ground fault : code ANSI 50N/51N
- Circuit breaker fault code ANSI 50NBF
- Unbalance and inverse phase code ANSI 46
- Directional ground fault code ANSI 67N/67NC
- Maxi active power code ANSI 32P
- Maxi reactive power code ANSI 32Q
- Overload code ANSI 49RMS
- Current loss code ANSI 37
- Stalled rotor: code ANSI 48/51LR
- Starting number / operation hours code ANSI 66
- Under voltage code ANSI 27D/27R
- Over voltage code ANSI 59N
- Inverse voltage code ANSI 47
- Maxi frequency code ANSI 81H
- Mini frequency code ANSI 81L
Design :
The soft starter starts the motor by slowly ramping-up the voltage supplied to the motor while limiting the current at the requested
level.
The soft starter control is based on a digital microprocessor system.
The signal interconnections to the power section are based on a high speed fiber optic link that gives a high degree of insulation and
EMC immunity.
Voltage rating: · 3,3 KV – 4,16 KV – 5,5 KV – 6,6 KV- 10 KV - 11 KV +- 10%
Frequency: 50/60 Hz +- 5%
Continuous current rating: 80A – 160A – 260A – 350A – 450A – 600A – 900A -1200A Current limit: adjustment 100 – 300% In of the
soft starter
Soft starter installation: TN
Operating temperature range, industrial version: 0 to 40°C Operating temperature range, Marine version: 0 to 45°C Maximum relative
humidity: up to 96 % (non condensing) Maximum altitude: 1107 m.
Storage temperature: -20 to 70°C
4
Control and Keypad :
Remote control with dedicated digital inputs Remote monitoring with dedicated digital outputs Profibus
communication as option:
Parameter setting Control (Start,Stop,…) Supervision
5
SOFT STARTER PROTECTIONS :
· Line loss .
· Serial communication failure.
· External protection .
· Motor thermal protection
· Max instantaneous current .
· Soft starter thermal protection
· Watchdog intervention .
· Motor stall
· Line beyond tolerance
IEC 60071-1/ 2 -- Insulation coordination: Definitions, principles and rules / Application guide IEC
61800-5-1 -- Adjustable speed electrical power drive system: Safety requirements: electrical,
thermal and energy
IEC 61800-3 -- Adjustable speed electrical power drive system: EMC requirements and specific
test methods
IEC 61800-4 -- Adjustable speed electrical power drive system: rating specification for A.C
Power drive systems above 1000 Vac and not exceeding 35 KVac.
IEC 60694 -- Common specifications for high voltage switchgear & control gear standards CEI
EN 50178 -- Electronic equipment for use in power installation
IEC 60947-2 -- Specification for low voltage switchgear and control gear: circuit breakers IEC
60470 -- High voltage alternating current contactors and contactor based motor starter IEC
60282 -- High/Medium voltage fuses
It is not allowed to put the soft starter on duty until all the required safety