APPROVED DOCUMENT
Technical Data Sheet
HCI534E/544E
SPECIFICATIONS & OPTIONS
Stamford industrial generators meet the requirements of Standard generators are 3-phase reconnectable with 12
BS EN 60034 and the relevant section of other ends brought out to the terminals, which are mounted on
international standards such as BS5000, VDE 0530, a cover at the non-drive end of the generator. A sheet
NEMA MG1-32, IEC34, CSA C22.2-100, AS1359. steel terminal box contains the AVR and provides ample
Other standards and certifications can be considered on space for the customers' wiring and gland
request. arrangements. It has removable panels for easy
access.
VOLTAGE REGULATORS
SHAFT & KEYS
AS440 AVR - STANDARD
With this self-excited system the main stator provides All generator rotors are dynamically balanced to better
power via the Automatic Voltage Regulator (AVR) to the than BS6861:Part 1 Grade 2.5 for minimum vibration in
exciter stator. The high efficiency semi-conductors of the operation. Two bearing generators are balanced with a
AVR ensure positive build-up from initial low levels of half key.
residual voltage.
The exciter rotor output is fed to the main rotor through a INSULATION/IMPREGNATION
three-phase full-wave bridge rectifier. The rectifier is
protected by a surge suppressor against surges caused, APPROVED DOCUMENT The insulation system is class 'H'.
for example, by short circuit or out-of-phase paralleling. All wound components are impregnated with materials
The AS440 will support a range of electronic accessories, and processes designed specifically to provide the high
including a 'droop' Current Transformer (CT) to permit build required for static windings and the high
parallel operation with other ac generators. mechanical strength required for rotating components.
2
HCI534E/544E
WINDING 14
CONTROL SYSTEM SEPARATELY EXCITED BY P.M.G.
PROTECTION IP23
WINDING LEADS 12
R.F.I. SUPPRESSION BS EN 61000-6-2 & BS EN 61000-6-4,VDE 0875G, VDE 0875N. refer to factory for others
WAVEFORM DISTORTION NO LOAD < 1.5% NON-DISTORTING BALANCED LINEAR LOAD < 5.0%
1 BEARING 2 BEARING
REACTANCES ARE SATURATED VALUES ARE PER UNIT AT RATING AND VOLTAGE INDICATED
T'd TRANSIENT TIME CONST. 0.08s
T''d SUB-TRANSTIME CONST. 0.012s
T'do O.C. FIELD TIME CONST. 2.5s
Ta ARMATURE TIME CONST. 0.019s
SHORT CIRCUIT RATIO 1/Xd
3
HCI534E/544E
Winding 14
APPROVED DOCUMENT
4
HCI534E/544E
Winding 14
SX Locked Rotor Motor Starting Curves
380V
30
25
.
20
PER CENT TRANSIENT VOLTAGE DIP
15
APPROVED DOCUMENT
10
0
0 200 400 600 800 1000 1200 1400 1600 1800 2000
LOCKED ROTOR kVA
MX
380V
30
25
.
20
PER CENT TRANSIENT VOLTAGE DIP
15
10
5
HCI534E
Winding 14
100000
SYMMETRICAL
ASYMMETRICAL
CURRENT (Amps)
10000
APPROVED DOCUMENT
1000
0.001 0.01 0.1 1 10
TIME (secs)
Note
The following multiplication factor should be used to convert the
values from curve for the various types of short circuit :
6
HCI534E/544E
Winding 14 / 0.8 Power Factor
RATINGS
60Hz
Class - Temp Rise Cont. F - 105/40°C Cont. H - 125/40°C Standby - 150/40°C Standby - 163/27°C
Series Star (V) 380 400 416 380 400 416 380 400 416 380 400 416
Parallel StarStar (V) 190 200 208 190 200 208 190 200 208 190 200 208
Series Delta (V) 220 230 240 220 230 240 220 230 240 220 230 240
kVA 620 N/A N/A 675 N/A N/A 710 N/A N/A 730 N/A N/A
kW 496 N/A N/A 540 N/A N/A 568 N/A N/A 584 N/A N/A
Efficiency (%) 95.2 N/A N/A 95.1 N/A N/A 95.0 N/A N/A 95.0 N/A N/A
kW Input 521 N/A N/A 568 N/A N/A 598 N/A N/A 615 N/A N/A
APPROVED DOCUMENT
DIMENSIONS
7
APPROVED DOCUMENT
www.cumminsgeneratortechnologies.com
HCI5E-14-TD-EN-SG-A